2
1
Quick Reference Guide
Foundation™ Packaged
Rooftop Units
EDK
GDK
List of Options
This document and the information in it are the property of Trane, and may not
be used or reproduced in whole or in part without written permission. Trane
reserves the right to revise this publication at any time, and to make changes to
its content without obligation to notify any person of such revision or change.
Note: Most Factory Installed Options are available for downflow air discharge units only. Verify with ordering system for availability.
Table 1.
List of options
Factory Installed Options
Trademarks
Cooling and Gas/Electric
15 to 25 Tons
Model Numbers:
Copyright
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
All trademarks referenced in this document are the trademarks of their respective
owners.
Field Installed Options
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
2-in. MERV 13 Pleated Filters
Barometric Relief (a),(b)
Complete Coat™ Microchannel Condenser Coil
Condensate Overflow Switch
Economizer - Standard/Downflow(b)
Economizer - Low Leak/Downflow(b)
Electric Heaters
High Static Motor
Manual Outside Air Damper
Motorized Outside Air Damper
Multi-Speed Motor
Reference or Comparative Enthalpy Economizer
Single Zone VAV
Stainless Steel Heat Exchanger with 10 Year Warranty
Through-the-Base Electrical Access
Through-the-Base Gas Piping(b)
Unit Mounted Non-Fused Disconnect Switch(c)
Used With:
Cooling Only (Electric Heat Optional)
Gas Heat Unit
2-in. MERV 13 Pleated Filters
Barometric Relief(a)(b)
Condensate Overflow Switch
Condenser Coil Guard
Customer Connection Module
Demand controlled Ventilation
Differential Drybulb Economizer
Economizer - Standard/Downflow(b)
Economizer - Low Leak/Downflow(b)
Economizer - Standard/Horizontal
Economizer - Low Leak/Horizontal
Electric Heaters
Fresh Air Options Module
Hail Guard
High Altitude Kit
High and Low Static Drive Kit
Indoor Options Module
Low Ambient Control
LP Conversion Kit
Manual Outside Air Damper
Motorized Outside Air Damper
Power Exhaust
Reference or Comparative Enthalpy Economizer
Roof Curb
Thermostat
Through-the-Base Electrical Access
Through-the-Base Gas Piping(b)
Unit Mounted Non-Fused Disconnect Switch(c)
(a) Requires an economizer.
(b) Some field set up required.
(c) Must be ordered with Through-the-Base Electrical option.
RT-PRC127A-EN
September 2024
©2024
4
3
Table 2.
5
Table 4.
15 to 25 tons packaged rooftop performance data (gas or electric heat)
Nominal Size (Ton)
EDK180
Cooling Performance(a)
Gross Cooling Capacity
AHRI Net Cooling Capacity
Nominal Airflow CFM /
AHRI Rated CFM
EER
IEER (Multi -Speed Fan)
15
GDK180
EDK210
188,000
182,000
188,000
182,000
6000
6000
11
14.2
10.8
14
17.5
GDK210
EDK240
212,000
206,000
212,000
206,000
5600
5600
11
14.2
10.8
14
20
25
E/GDK
GDK240
EDK300
250,000
240,000
250,000
240,000
280,000
266,000
280,000
266,000
8000
8000
9000
9000
10
13.2
9.8
13
10
13.2
GDK300
9.8
13
Gas Heating Performance(b)
Low Heat (Input/Output) (MBh)
Medium Heat
(Input/Output) - (MBh)
–
240,000/194,000
–
240,000/194,000
–
240,000/194,000
–
240,000/194,000
–
320,000/259,000
–
320,000/259,000
–
320,000/259,000
–
320,000/259,000
High Heat (Input/Output) (MBh)
–
350,000/283,500
–
Other Information
Net Weight (Lbs) - Gas
Heat
Net Weight (Lbs) - Electric
Heat
Filters - Type Furnished(c)
Number and Size
Recommended
Table 3.
E/GDK
180
210
240
380,000 (Downflow),
350,000
(Horizontal)/307,800
(Downflow), 283,500
(Horizontal)(b)
–
380,000/308,000
–
380,000/307,800
300
–
2054
–
2069
–
2067
–
2103
1891
–
1896
–
1902
–
1938
–
Throwaway
Throwaway
Throwaway
Throwaway
Throwaway
Throwaway
Throwaway
Throwaway
(8) 20x24x2
(8) 20x24x2
(8) 20x24x2
(8) 20x24x2
(8) 20x24x2
(8) 20x24x2
(8) 20x24x2
(8) 20x24x2
(a) Units are AHRI Certified to AHRI Standard 340-360 (I-P). Rating conditions are 95°F outdoor air temperature, 80°F entering dry bulb, 67°F entering wet bulb with minimum external static pressure
as determined by rating standard.
(b) For 17.5T high heat option, input rate will de-rate from downflow to horizontal.
(c) Optional field-installed and factory MERV 13 filters available.
Unit MCA and MOP electrical data (standard indoor fan Motor cooling or gas heat)
Volts
Minimum Circuit
Ampacity(a)
Maximum Fuse Size or
Maximum Circuit Breaker
208-230
70
100
460
35
45
575
28
40
208-230
91
125
460
44
60
575
36
50
208-230
104
125
460
51
70
575
39
50
208-230
121
150
460
58
80
575
43
50
(a) Values does not include power exhaust values.
Table 4.
E/GDK
Unit indoor fan data
Volts
Standard HP - RPM
Oversized HP - RPM
3 - 1750
5 - 3450
5 - 3450
7.5 - 3450
5 - 3450
7.5 - 3450
208-230/3
180
460/3
575/3
208-230/3
210
460/3
575/3
208-230/3
240
460/3
575/3
Unit indoor fan data (continued)
Volts
Standard HP - RPM
Oversized HP - RPM
7.5 - 3450
10 - 1750
208-230/3
300
460/3
575/3
Table 5.
Unit dimensional data
Unit Length UL
Unit Width UW
Unit Height UH
Clearance C1
Clearance C2
Clearance C3
Clearance C4
Clearance C5
Curb Length CL
Curb Width CW
Supply Length SL(a)
Supply Width SW(a)
Return Length RL(a)
Return Width RW(a)
15 to 25 Tons
123 1/8
86 15/16
58 5/8
60
48
36
68
72
117 3/16
81
28 9/16
69 1/2
22 1/4
77
(a) Dimensions are for curb openings and not duct inserts. Reference the product
catalog for duct insert dimensions.
6
108
7
11
\
Table 6.
UH
Tons
Foundation
Model No.
Carrier
Model No.
15
G*K180
48TJD016, 48TJE016, 48TJF016, 48HJD017, 48HJF017,
48TMD016, 48TMF016, 48DP016, 48DR016
17.5
G*K210
48TJD020, 48TJF020, 48TMD020, 48TMF020, 48DP020
20
G*K240
48TJD024, 48TJE024, 48TJF024, 48TMD025, 48TMF025,
48HJD025, 48HJF025
25
G*K300
48TJD028, 48TJE028, 48TJF028, 48TMD028, 48TMF028
(a) Data is subject to change. Data pulled from publicly available data via competitive
websites.
Table 7.
UL
UW
RL
RW
SL
Curb compatibility matrix - gas heat(a)
Curb compatibility matrix - electric heat(a)
Tons
Foundation
Model No.
Carrier
Model No.
15
E*K180
50TJ016, 50TM016, 50DP016, 50HJ017
17.5
E*K210
50DP020, 50TJ020, 50TM020
20
E*K240
50TJ024, 50TM025, 50HJ025
25
E*K300
50TJ028, 50TM028
(a) Data is subject to change. Data pulled from publicly available data via competitive
websites.
SW
CL
12
CW
13
14
15
Trane and American Standard create comfortable, energy efficient indoor environments for commercial
and residential applications. For more information, please visit trane.com or americanstandardair.com.
Trane and American Standard have a policy of continuous product and product data improvement and reserve the
right to change design and specifications without notice. We are committed to using environmentally conscious print
practices.
RT-PRC127A-EN 15 Sep 2024
(NEW)
©2024
">