AAON SS1016 VCM Controller Technical Guide
Reklama
Reklama
FACTORY CONTROLS SYSTEM
VCM - Controller
Technical Guide
VCM Controller Code: SS1016
Requires System Manager Code: SS1010 Version 3.0 and up
Requires Service Tool Code: SS1009 Version 3.0 and up
Table Of Contents
Controller Overview ........................................................................................................................................ 4
Features ...................................................................................................................................................................................... 4
Applications ................................................................................................................................................................................ 4
Controller Installation & Wiring ...................................................................................................................... 8
General ..................................................................................................................................................................................... 10
Controller Mounting .................................................................................................................................................................. 10
Important Wiring Considerations .............................................................................................................................................. 10
Expansion Board Installation & Wiring ........................................................................................................ 11
Jumper Settings ......................................................................................................................................................................... 11
Wiring Considerations .............................................................................................................................................................. 12
Input/Output Wiring Details........................................................................................................................... 14
Space Temperature Sensor ...................................................................................................................................................... 14
Remote SAT Reset Signal ........................................................................................................................................................ 14
Supply & Return Temperature Sensor ...................................................................................................................................... 15
Outdoor Air Temperature Sensor .............................................................................................................................................. 17
Economizer Damper Actuator ................................................................................................................................................... 18
Suction Pressure Transducer ................................................................................................................................................... 19
Supply Fan VFD Signal Or Zoning Bypass Damper Actuator .................................................................................................. 21
Binary Inputs Wiring ................................................................................................................................................................. 22
Outdoor Air Humidity Sensor .................................................................................................................................................... 23
Indoor Wall Mounted Humidity Sensor ..................................................................................................................................... 24
Return Air Mounted Humidity Sensor ....................................................................................................................................... 25
Building Pressure Sensor Wiring .............................................................................................................................................. 26
Building Pressure Control
Output Wiring ............................................................................................................................................................................ 27
CO2 Sensor Wiring ................................................................................................................................................................... 28
Modulating Heating Device Wiring ........................................................................................................................................... 29
Modulating Cooling Device Wiring ........................................................................................................................................... 30
Return Air Bypass Wiring .......................................................................................................................................................... 31
Start-up & Commissioning ............................................................................................................................ 32
Controller Addressing ............................................................................................................................................................... 32
Power Wiring ............................................................................................................................................................................ 32
Initialization: .............................................................................................................................................................................. 33
Operating Summary .................................................................................................................................................................. 33
Programming The Controller .................................................................................................................................................... 33
Inputs & Outputs ........................................................................................................................................... 34
VCM Controller ......................................................................................................................................................................... 34
OE354 (4) Analog Input
(1) Analog Output Expansion Board ......................................................................................................................................... 35
OE355 (4) Analog Output
Expansion Board ...................................................................................................................................................................... 35
OE357 (4) Relay Expansion Boards ......................................................................................................................................... 35
OE356 Binary Expansion Board #1 .......................................................................................................................................... 36
OE356 Binary Expansion Board #2 .......................................................................................................................................... 36
FACTORY CONTROLS SYSTEM
WattMaster Controls Inc.
8500 NW River Park Drive · Parkville , MO 64152
Toll Free Phone: 866-918-1100
PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: [email protected]
Visit our web site at www.orioncontrols.com
Form: AO-VCM-TGD-01A Copyright 2005 WattMaster Controls, Inc.
AAON
®
is a registered trademark of AAON, Inc., Tulsa, OK.
WattMaster Controls, Inc. assumes no responsibility for errors, or omissions.
This document is subject to change without notice.
Technical Guide
Sequence Of Operations ............................................................................................................................... 37
Occupied/Unoccupied
Mode of Operation .................................................................................................................................................................... 37
HVAC Modes of Operation ....................................................................................................................................................... 37
Vent Mode Operation ................................................................................................................................................................ 37
Cooling Mode Operation ........................................................................................................................................................... 37
Dehumidification Mode ............................................................................................................................................................. 39
Remote Forced Dehumidification ............................................................................................................................................. 40
Return Air Bypass Damper Control .......................................................................................................................................... 40
Heating Mode Operation .......................................................................................................................................................... 40
Warm-up Mode Operation ........................................................................................................................................................ 42
Off Mode ................................................................................................................................................................................... 42
Remote Control of HVAC Mode ................................................................................................................................................ 42
Supply Air Temperature
Setpoint Reset .......................................................................................................................................................................... 42
Supply Fan Control ................................................................................................................................................................... 43
Duct Static Pressure Control .................................................................................................................................................... 43
Building Pressure Control ......................................................................................................................................................... 43
IAQ (CO2) Operation ................................................................................................................................................................ 44
Pre-heater Operation ................................................................................................................................................................ 44
Outdoor Air Lockouts ................................................................................................................................................................ 44
Supply Air Cutoffs ..................................................................................................................................................................... 44
Scheduling ................................................................................................................................................................................ 44
Internal Trend Logging .............................................................................................................................................................. 45
Force Modes or Overrides ........................................................................................................................................................ 45
VAV/Zone Box Compatibility ..................................................................................................................................................... 46
VAV/Zone System ..................................................................................................................................................................... 46
Zoning System .......................................................................................................................................................................... 46
Troubleshooting ............................................................................................................................................ 47
Using LEDs To Verify Operation ............................................................................................................................................... 47
Appendix ........................................................................................................................................................ 48
Diagnostic LEDs Operation ...................................................................................................................................................... 48
System Configuration Options .................................................................................................................................................. 49
10 kOhm Type III Temperature Sensor Testing ........................................................................................................................ 53
OE265 RH Sensor Testing ....................................................................................................................................................... 54
OE271 Pressure Sensor Testing .............................................................................................................................................. 55
OE258 Pressure Sensor Testing .............................................................................................................................................. 55
OE275 Suction Pressure Transducer Testing ........................................................................................................................... 56
Notes: ............................................................................................................................................................ 57
VCM Controller
3
Technical Guide
Controller Overview
Features
The VCM Controller Board is designed with 7 analog inputs, 2 analog outputs and 5 relay outputs. The controllers input and output capabilities can be expanded by use of either 2 slot or 4 slot expansion boards that plug into the VCM Controller by means of a modular cable. The
VCM Controller can be configured for control of VAV Units (with or without VAV/Zone Controllers), Constant Volume Units and Make-up
Air Units. Features include the following:
•
Up to a Combined Total of 20 Stages of Heating & Cooling
•
Modulating Cooling Output (Digital Compressor or Chilled
Water Valve Control)
•
Modulating Heating Output (Hot Water Valve, Steam Valve,
SCR Electric Heat Control)
•
Full Integration with the AAON
®
MODGAS II Modulating Natural Gas Controller
•
Full Integration with the AAON
®
MHGRV II Modulating
Hot Gas Reheat Controller
•
Configurable for Air to Air Heat Pump Applications
•
Advanced Dehumidification Capabilities
•
Primary/Secondary Heating Control
•
Automatic Supply Air Reset
•
Selectable Control Sensor
•
Fan Proving Interlock
•
Dirty Filter Alarm
•
Smoke Detector Input
•
Drybulb/Wetbulb Control of Economizer Operation
•
Building Pressure Control
•
Remote Override Capabilities
•
I.A.Q. Economizer Reset
•
7 Day, 2 Event per Day Scheduling
•
14 Holiday Event Scheduling
•
Optimal Start Scheduling
•
Trend Logging Capability
•
Static Pressure Control For Filter Loading Applications
•
Accepts Remote HVAC Mode Selection Via Contact
Closure On Expansion Input Board
•
Configurable for PAC and DPAC Applications
Most common HVAC unit control applications can be configured using only the VCM Controller board. If the application requires more inputs and/or outputs, optional expansion boards are available to provide for additional analog, binary or digital inputs and outputs as required. These expansion boards are installed on either a 2 slot or 4 slot expansion base board that connects to the VCM Controller board via a modular cable connection.
The available expansion board configurations allow for (8) additional binary inputs, 4 additional analog inputs, 1 additional analog output, and up to 16 additional binary (relay) outputs. The various expansion boards connect to the 2 slot or 4 slot expansion base boards. Jumpers located on the base boards near each expansion board socket must be set according to the board type installed on that socket.
Applications
Variable Air Volume Unit
The VCM can be configured to control a VFD Supply Fan for Duct
Static Pressure control. If the unit is not equipped with a VFD, but Duct
Static Pressure control is needed, a modulating Zoning Bypass Damper can be controlled by the VCM.
VAV units are typically designed for occupied Cooling with Morning
Warm-up Heating. This option is available with the VCM. The VCM can also be used for a Zoning System that needs Duct Static Pressure control and Occupied Cooling and Heating. The VCM also has the ability to be configured for Duct Static Pressure Control by controlling the
Supply Fan VFD for the purpose of maintaining proper Duct Static
Pressure in response to varying filter loading conditions.
The VCM allows Dehumidification Priority on a VAV unit. This could be useful on a building with very low internal sensible load, but has a high internal and/or external latent load. During VAV Dehumidification the VCM activates Cooling based on the Evaporator Coil Temperature and activates Modulating Hot Gas Reheat to warm the Supply Air Temperature to the Active Supply Air Temperature Setpoint.
Constant Air Volume Unit
The VCM can be configured to activate a Constant Volume Supply
Fan. In most cases, this is a very basic unit with Space Temperature control. The VCM can be used for kitchen, restaurant or lab environments that are 100% Outdoor Air part of the time and return air part of the time. The Hood On input allows the VCM to know when to switch to 100% Outdoor Air control based on an exhaust hood activating. The
VCM requires Outdoor and Indoor Air Temperature Sensors to accomplish this application.
Make-up Air Unit
The VCM can be configured for 100% Outdoor Air control for Makeup Air. All HVAC Modes are determined from the Outdoor Air Sensors.
The Outdoor Air Volume must always be at least 50% or higher to be configured for Outdoor Air control.
4
VCM Controller
Technical Guide
Air to Air Heat Pump Unit
The VCM can be configured to control an Air to Air Heat Pump. The compressors are used for both Heating and Cooling. With the VCM controller the Reversing Valve is activated during Heating operation as the default because AAON units are typically built to fail to Cooling operation. The Reversing Valve can be configured to activate during
Cooling operation for equipment that is built to fail to Heating operation.
Auxiliary Heating Stages are configured as Heat Relays and are used to supplement the Compressor Heating Stages. If the unit is not equipped with Auxiliary Heating Stages, Heating Relays do not need to be configured in order for the unit to provide Heating. Auxiliary Heating can also be Modulating heat in the form of SCR Electric, Hot Water or
Steam.
For PAC configured units, the Return Air Bypass Damper is only used during the Dehumidification Mode. When the VCM controller is in Dehumidification Mode, the Return Air Bypass Damper will modulate open as the Space Temperature falls below the Cooling Setpoint. Modulation of the Return Air Bypass Damper is controlled using a proportional range from 0% (when the Space Temperature is equal to the Cooling Setpoint), up to 100% (when the Space Temperature falls to the halfway point between the Cooling and Heating Setpoints). A separate,
Return Air Damper Actuator will modulate the Return Air Damper slightly further towards its closed position as the Return Air Bypass
Damper opens. This is to ensure that enough Return Air is bypassed around the Evaporator Coil through the Return Air Bypass Damper to raise its temperature. The rate which the Return Air Damper closes while the Return Air Bypass Damper is open is user adjustable.
DPAC – Digital Precision Air Control
This control scheme can only be used on Constant Volume HVAC units that are equipped with a Return Air Bypass Damper, a Digital Compressor and use a Space Temperature Sensor as the Controlling Sensor.
The Cooling and Dehumidification Modes operate in the same manner as described under the Cooling and Dehumidification titled sections of this manual. In the Heating Mode, the VCM activates the Reversing
Valve and stages compressors to provide Heating if the Outdoor Air
Temperature is above the OAT Cooling Lockout Setpoint. The compressor heating stages are activated as needed to achieve the Active
Supply Air Setpoint. Staged or Modulating Auxiliary Heat can be activated to supplement Compressor Heating in order to achieve the Active
Supply Air Setpoint if the Outdoor Air Temperature is below the OAT
Heating Lockout Setpoint. If the Outdoor Air Temperature is below the
OAT Cooling Lockout Setpoint, only Auxiliary Heating will occur. If the Outdoor Air Temperature is above the OAT Heating Lockout, only
Compressor Heating will occur.
PAC (Precision Air Control)
This control scheme can only be used on Constant Volume HVAC units that are equipped with a Return Air Bypass Damper and use a
Space Temperature Sensor as the Controlling Sensor.
The DPAC control scheme provides improved moisture removal capabilities over the PAC control scheme and provides for tighter temperature control by combining a Digital Compressor with the Return Air
Bypass Damper. See the Cooling Mode section of this manual for detailed Digital Compressor operation. See the PAC Control previously described in this section for detailed Return Air Bypass Damper operation.
The Digital Compressor is used during both Cooling and Dehumidification Modes. The Return Air Bypass Damper is used only during the
Dehumidification Mode.
PAC Control provides improved moisture removal capabilities while utilizing internal space loads for reheat by redirecting the Return Air path from the upstream side of the DX Evaporator Coil to the downstream side of the coil.
VCM Controller
5
Technical Guide
Controller Overview
.20 Dia.
Typ. of 4
7.3”
6.2“
U3
1
RN1
CX1
U1
U2
CX2
TB1
COMM
T
SHLD
R
CX5
LD6
TB3
COMM
LD7
PWR
+VDC
AIN1
AIN2
AIN3
AIN4
1
RN5
U5
RS-485
COMM
AIN5
GND
C10
GND
AOUT1
C12
AOUT2
AIN7
GND
PJ1
C17
D15
HH
U13
RAM
CX13
U15
R15
C14
R19
U14
U12
CX14
C15
R22
R24
R25
EPROM
TUC-5R PLUS
(1 MEG)
YS101816 REV. 2
LD8
LED1
RV1
VREF ADJ
C1
R1
LD9
LED2
U7
P1
+VREF
5.11V
TEST POINT
EWDOG
R28
INPUTS
U6
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
ADDRESS
SW1
ADD
1
2
4
8
16
32
TOKEN
NETWORK
U10
JP1
X2
CX10
CX6
CX12
C20
CX15
U4
CX4
1
U9
PAL
C7
1
D12
R13
SC1
D19
PRESSURE
SENSOR
R26
EXPANSION T'STAT
VR1
L1
VR2
6.7”
V1
V2
V3
COM1-3
R1
R2
R3
R4
R5
COM4-5
TB2
V4
V5
U8
R6
C9
C13
C16
TB4
GND
24VAC
Figure 1: VCM Controller Dimensions
6.6”
6
VCM Controller
Technical Guide
4.00
2.12
4.24
0.28
D3
R14
PWR LD1
D3
R20
PWR LD1
4.73
LM358N
I/O
YS101780
TMODULAR LO 2S
R5
R6
R4
R2
R1
R3
5.40
5.96
9.52
LM358N
R13
R14
D2
D1
P82B715P
R1
R2
R3
8.29
8.96
4.00
OE352 2 Slot Expansion Base Board
R10
R11
R12
0.28
2.12
4.24
OE353 4 Slot Expansion Base Board
Figure 2: Expansion Base Boards Dimensions
1.67”
1.67”
1.67”
1.67”
TB1
TB1
TB1
TB1
V4
V1
Q1
U2
K4
K1
P2506-2 P2506-2 P2506-2
4.00”
CX2
PCF8591P
P1
OE354
4 Analog Input 1 Analog
Output Expansion Board
4.24”
4.00”
C4 C3
LM358 LM358
C1 C2
R1
TDA8444P
PHILIPS
AN ID ID
RV1
P1
OE355
4 Analog Output
Expansion Board
4.24”
4.00”
C4
C3
PCF8574P
74HC14N
C2
C1
P1
OE356
4 Binary Input
Expansion Board
4.24”
4.00”
K3
K2
U3 CX2
CX1
P1
OE357
4 Relay Output
Expansion Board
4.24”
Figure 3: Expansion Boards Dimensions
VCM Controller
7
Technical Guide
Controller Installation & Wiring
RS-485
Communications
Loop Connection
RS-485
Communications
Driver Chip
Comm
LED
Power
LED
Diagnostic
Blink Code
LEDs
Pull-up Resistors
For Analog Inputs
Analog Input
And Output
Modular Service
Tool - Mini Din
Connector
Terminal Block
Duct Static Pressure Sensor
(AIN6 Modular Connection)
Typical
Pin 1
Indicator
RAM
Chip
EPROM
Chip
U3
CX1
1
RN1 U2
CX2
CX4
U1
U4
TB1
COMM
T
SHLD
R
CX5
U5
LD6
COMM
LD7
PWR
1
RS-485
COMM
HH
LD8
LED1
RV1
VREF ADJ
C1
R1
LD9
LED2
U7
P1
+VREF
5.11V
TEST POINT
EWDOG
R28
INPUTS
ADDRESS
TB3
+VDC
RN5
AIN1
AIN2
AIN3
AIN4
AIN5
GND
C10
GND
AOUT1
C12
AOUT2
AIN7
GND
PJ1
C17
D15
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
U13
SW1
CX13
U15
U6
C20
RAM
CX15
C15
R22
R24
R25
EPROM
TUC-5R PLUS
(1 MEG)
YS101816 REV. 2
ADD
1
2
4
8
16
32
TOKEN
NETWORK
U10
JP1
X2
CX10
R15
C14
R19
U14
U12
CX14
CX6
CX12
1
U9
PAL
C7
1
D12
R13
SC1
D19
L1
R26
PRESSURE
SENSOR
EXPANSION
T'STAT
VR1
VR2
PAL
Chip
V1
V2
V3
COM1-3
R1
R2
R3
R4
R5
COM4-5
TB2
V4
V5
U8
R6
C9
C13
C16
TB4
GND
24VAC
Expansion Board
(Modular Connection)
Real Time
Clock Chip
DigiSensor
(Modular Connection)
Mounting Hole
Typ of 4
Mounting
Backplate
Relay Output
Terminal Block
Address Switch
EEPROM
24 VAC
Power Input
Figure 4: VCM Controller Component Locations
8
VCM Controller
Technical Guide
D1
RLY1
D2
CX3
RLY2
D3
RLY3
D4
RN2
RLY4
D5
RLY5
X1
C2
C3
RN4
CX8
NE5090NPB3192 0PS
D10
R7
R10
D13
R11
C11
U11
PHILIPS
VDC
0-5
0-1
VDC
RN3
C21
D17
D18
C18
C19
R27
V6
D16
POWER
PJ2
PJ3
VCM Controller
9
Technical Guide
Controller Installation & Wiring
General
Correct wiring of the VCM controller is the most important factor in the overall success of the controller installation process. In general most
VCM controllers are factory installed and wired at the AAON
® factory.
It is also possible to purchase these controllers directly from WattMaster
Controls for installation in the field. Some of the following information pertains to field wiring and may not apply to your installation since it was pre-wired at the factory. However, in the unlikely event that troubleshooting of the controller is required, it is a good idea to be familiar with the system wiring, no matter if it was factory or field wired.
Controller Mounting
When the controller is to be field mounted, it is important to mount the controller in a location that is free from extreme high or low temperatures, moisture dust and dirt. See Table 1 for a list of the required operating conditions for the VCM Controller and associated expansion boards.
Warning: When using a single transformer to power more than one controller or expansion board, the correct polarity must always be maintained between the boards. Failure to observe correct polarity will result in damage to the VCM controller and expansion boards.
Please carefully read and apply the following information when wiring the VCM controller or the VCM Expansion Boards. See Figure 5 for
VCM controller wiring diagram. See Figures 6, 7 and 8 for Expansion
Board Wiring.
1.
All wiring is to be in accordance with local and national electrical codes and specifications.
2.
Minimum wire size for 24 VAC wiring should be 18 gauge.
3.
Minimum wire size for all sensors should be 24 gauge.
Some sensors require 2 conductor wire and some require 3 or 4 conductor wire.
Be careful not to damage the electronic components when mounting the controller. Remove the controller from its backplate. Mark the control enclosure base using the backplate as a template. Drill pilot holes in the enclosure base and secure the backplate to it using sheet metal screws.
Do not allow metal shavings to fall onto the circuit board. Reattach the controller to the backplate.
Important Wiring Considerations
The VCM controller and expansion boards must be connected to a 24
VAC power source of the proper size for the calculated VA load requirements. All transformer sizing should be based on the VA rating listed in Table 1.
4.
Be sure that all wiring connections are properly inserted and tightened into the terminal blocks. Do not allow wire strands to stick out and touch adjoining terminals which could potentially cause a short circuit.
Control
Device
5.
When communication wiring is to be used to interconnect
VCM controllers together or to connect to other communication devices, all wiring must be plenum rated, minimum 18 gauge, 2 conductor, twisted pair with shield.
WattMaster can supply communication wire that meets this specification and is color coded for the network or local loop. Please consult your WattMaster distributor for information. If desired, Belden #82760 or equivalent wire may also be used.
VCM Controller
Board
2 Slot Expansion
Base Board
4 Slot Expansion
Base Board
24VAC
60Hz
24VAC
60Hz
24VAC
60Hz
8
10
°
F to 149
°
F
90% RH
*N.C.
10
10
°
F to 149
°
F
90% RH
*N.C.
20
10
°
F to 149
°
F
90% RH
*N.C.
6.
Before applying power to the VCM controller, be sure to recheck all wiring connections and terminations
thoroughly.
* Non-Condensing
Table 1: Voltage and Environment Requirements
10
VCM Controller
Technical Guide
Expansion Board Installation & Wiring
Jumper Settings
OE354 4 Analog Input 1 Analog Output Expansion Board
(1 per VCM Controller)
Several different Expansion Boards are available for use with the VCM
Controller to provide additional inputs and outputs beyond those found on the VCM Controller board. These Expansion Boards are mounted to either the OE352, 2 slot Expansion Base Board(s) or the OE353, 4 slot
Expansion Base Board(s) depending on the total number of expansion boards to be used with your particular application.
OE355 4 Analog Output Expansion Board
(1 per VCM Controller)
OE356 4 Binary Input Expansion Board
(Up to 2 boards per VCM Controller)
OE357 4 Relay Output Expansion Board
(Up to 4 boards per VCM Controller)
The OE352 2 Slot Expansion Base board or the OE353 4 Slot Expansion Base boards are connected to the VCM Controller and to each other with modular cables. A maximum of (2) Expansion Base Boards total, (4 slot, 2 slot or a combination of both) can be connected to the
VCM controller.
The VCM controller uses the following expansion boards. The maximum quantities of each expansion board that can be used for each VCM controller are also listed.
The various Expansion Boards can be mounted on the Expansion Base
Board in any order, however, the address jumpers located near each
Expansion Board plug-in socket must be set correctly for the Expansion Board that is connected to that socket. In addition the OE354, 4
Analog Input 1 Analog Output Expansion Board also has Voltage Jumpers (J01, J02, J03 & J04) and Pullup Resistors (PU1, PU2, PU3, &
PU4) that must be correctly configured for proper Expansion Board operation. See Figure 6 for the correct address jumper, voltage jumper and Pullup resistor settings for the VCM application.
R5
OPTO1
BIN 1
R6
BIN 2
BIN 3
R8
OPTO2
BIN 4
R10
COM
R12
4 DIG. IN MOD. I/O BD.
YS101788
R1
R2
R3
R4
CX2
U2
CX1
U1
OE356 4 Binary Input Expansion Board #1
Address Jumpers
Jumpers
Under
Expansion
Board To Be
Set As Shown
For Proper Operation Pullup Resitors PU1, PU2,
PU3 & PU4 Must Be Removed As Shown
AIN1
AIN2
R5
R6
AIN3
AIN4
R7
GND
R8
R9
AOUT1
D5
R10
PU1
C2
PU2
C3
PU3
C4
PU4
C5
C1
LM358
JO1
JO2
JO3
JO4
Jumper Must Be Off For AIN1, 2 & 4
Jumper Must Be ON For AIN3
Jumper On = 0-10VDC Input Setting
Jumper Off = 0-5 VDC Input Setting
D2
R3
D3
R4
D4
R1
D1
R2
CX1
T L
PHILIPS
I D
U1
4 ANALOG IN MOD. I/O BD.
YS101784
Address Jumpers
Jumpers
Under
Expansion
Board To Be
Set As Shown
OE354 4 Analog Input - 1 Analog Output Expansion Board
R5
OPTO1
BIN 1
BIN 2
BIN 3
BIN 4
COM
R6
R8
R10
OPTO2
R12
4 DIG. IN MOD. I/O BD.
YS101788
R1
R2
R3
R4
CX2
U2
CX1
U1
Address Jumpers
OE356 4 Binary Input Expansion Board #2
Jumpers
Under
Expansion
Board To Be
Set As Shown
Q1
CX2
R7
D3
R8
D4
R9
D1
R6
D2
U2
AOUT1
AOUT2
AOUT3
AOUT4
GND
Q2
R2
Q3
R3
Q4
R4
CX3
U3
CX1
U1
4 AOUT MOD. I/O BD.
R5
YS101786
OE355 4 Analog Output Expansion Board
Address Jumpers
Jumpers
Under
Expansion
Board To Be
Set As Shown
AC
:
-PS
UL5A250V
CONTACT
24VDC
G5L-114P
OMRON
AC
:
-PS
24VDC
UL5A250V
CONTACT
G5L-114P
OMRON
K1
ULN2803A/
PHILIPS T L
HA
AN
U1
K2 74HC04N
AC
:
-PS
24VDC
CONTACT
OMRON
G5L-114P
UL5A250V AC
:
-PS
24VDC
CONTACT
OMRON
G5L-114P
UL5A250V
K3
RN1
PCF8574P
U2
4RLY IO BD.
YS101790
K4
Address Jumpers
Relays 6-9 Relays 10-13
Relays 14-17 Relays 18-21
Jumpers
Under
Expansion
Board To Be
Set As Shown
OE357 4 Relay Output Expansion Board
Figure 6: Expansion Board Jumper and Pullup Resistor Settings
VCM Controller
11
Technical Guide
Expansion Board Installation & Wiring
Wiring Considerations
The expansion base boards must be connected to 24 VAC as shown in the wiring diagram below. Please see Table #1 for correct VA requirements to use when sizing the transformer(s) used for powering the expansion base boards.
Also please note that when wiring the OE356 - 4 Binary Input Expansion Board(s), its contacts must be wired as wet contacts (connected to
24 VAC) not dry contacts as used with the OE357 - 4 Relay Expansion
Boards . See Figures 7 and 8 for complete wiring details.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
10 VA Minimum Power Required For
Each OE352 - 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each OE353 - 4 Slot Expansion Base Board
Modular Cable
Connect To VCM Controller
Modular Cable
Connect To Next Expansion Board
(When Used)
Building Pressure
Relief FAN VFD
+
COM
Orion - OE258 Building Pressure
Transducer
EXC
OUT
COM
Hood On - N.O. Contact
Dirty Filter - N.O. Contact
Proof Of Flow - N.O. Contact
Remote Forced Occupied - N.O. Contact
BIN1
BIN2
BIN3
BIN4
COM
Plastic Tubing To Building
Pressure Sensing Locations
Orion - OE255 Room Mounted CO2 Sensor
Or
Orion - OE256 Return Air Mounted CO2 Sensor
AC+/DC+
AC/GND
0-10V OUTPUT
SIGNAL GROUND
Orion - OE265-13 Outdoor Air
Humidity Sensor
VAC OR DC
GND
0-5V
Orion OE265-11 Indoor Air
Humidity Sensor
VIN
GND
VOUT (0-5V)
Modulating Heating
(0 to 10 VDC Input)
+
COM
Modulating Cooling
Or Digital Scroll Compressor
(1.5 to 5, 0 to 10 or 2 to 10 VDC Input)
+
COM
When Copeland Scroll Compressor Is
Used Wire Per Copeland Digital Scroll
Wiring Detail
Return Air
Damper Actuator
(0-10 VDC)
Remote Forced Heating - N.O. Contact
Remote Forced Cooling - N.O. Contact
Smoke Detector - N.C. Contact
Remote Forced Dehumidification
N.O. Contact
BIN1
BIN2
BIN3
BIN4
COM
COM 1
+ 2
Y1 3
AIN1
AIN2
AIN3
AIN4
GND
AOUT1
AOUT1
AOUT2
AOUT3
AOUT4
GND
D3
R20
PWR LD1
R5
R1
OPTO1
BIN 1
BIN 2
BIN 3
BIN 4
COM
R6
R8
R10
OPTO2
R2
R3
R4
R12
4 DIG. IN MOD. I/O BD.
YS101788
R5
OPTO1
BIN 1
R6
BIN 2
BIN 3
R8
OPTO2
BIN 4
R10
COM
AIN1
AIN2
AIN3
AIN4
GND
R8
R9
AOUT1
D5
R12
4 DIG. IN MOD. I/O BD.
YS101788
R5
R6
R7
PU1
C2
PU2
PU3
C3
C4
PU4
C5
C1
LM358
R10
R1
R2
R3
R4
JO1
JO2
JO3
JO4
Q1
AOUT1
D1
R6
D2
Q2
R2
AOUT2
AOUT3
AOUT4
R7
D3
R8
Q3
R3
Q4
R4
GND
D4
R9
4 AOUT MOD. I/O BD.
R5
YS101786
CX3
CX2
U2
U3
U2
CX2
U2
R1
D1
R2
D2
R3
D3
R4
D4
CX1
U1
4 ANALOG IN MOD. I/O BD.
YS101784
CX2
CX1
CX1
U1
CX1
U1
U1
OE352 2 Slot Or OE353 - 4 Slot Expansion Board
Belimo Actuator Wiring
Shown. Consult Factory For
Other Manufacturers Wiring
Instructions
As Required - OE353 Is Shown
Return Air Bypass
Damper Actuator
(0-10 VDC)
COM 1
+ 2
Y1 3
Figure 7: Expansion Board Wiring Details For Binary Input, Analog Input and Analog Output Boards
12
VCM Controller
Technical Guide
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
10 VA Minimum Power Required For
Each OE352 - 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each OE353 - 4 Slot Expansion Base Board
Modular Cable
Connect To VCM Controller
Modular Cable Connect To
Next Expansion Base Board
(When Used)
Configurable Relay Output # 6
Configurable Relay Output # 7
Configurable Relay Output # 8
Configurable Relay Output # 9
Configurable Relay Output # 10
Configurable Relay Output # 11
Configurable Relay Output # 12
Configurable Relay Output # 13
Configurable Relay Output # 14
Configurable Relay Output # 15
Configurable Relay Output # 16
Configurable Relay Output # 17
Configurable Relay Output # 18
Configurable Relay Output # 19
Configurable Relay Output # 20
Configurable Relay Output # 21
D3
R20
PWR LD1
AC
:
-PS
AC
:
-PS
4RLY IO BD.
OMRON
CONTACT
UL5A250V
G5L-114P
24VDC
AC
:
-PS
OMRON
CONTACT
UL5A250V
G5L-114P
24VDC
AC
:
-PS
4RLY IO BD.
OMRON
CONTACT
UL5A250V
G5L-114P
24VDC
AC
:
-PS
OMRON
CONTACT
UL5A250V
G5L-114P
24VDC
AC
:
-PS
OMRON
CONTACT
UL5A250V
G5L-114P
24VDC
4RLY IO BD.
AC
:
-PS
OMRON
CONTACT
UL5A250V
G5L-114P
24VDC
AC
:
-PS
OMRON
CONTACT
UL5A250V
G5L-114P
24VDC
4RLY IO BD.
OMRON
CONTACT
UL5A250V
G5L-114P
24VDC
AC
:
-PS
AC
:
-PS
YS101790
AC
:
-PS
OMRON
CONTACT
UL5A250V
G5L-114P
24VDC
AC
:
-PS
OMRON
CONTACT
UL5A250V
G5L-114P
24VDC
YS101790
AC
:
-PS
OMRON
OMRON
CONTACT
UL5A250V
G5L-114P
CONTACT
UL5A250V
G5L-114P
24VDC
24VDC
AC
:
-PS
OMRON
CONTACT
UL5A250V
G5L-114P
24VDC
YS101790
AC
:
-PS
OMRON
CONTACT
UL5A250V
G5L-114P
24VDC
AC
:
-PS
OMRON
CONTACT
UL5A250V
G5L-114P
24VDC
YS101790
OMRON
CONTACT
UL5A250V
G5L-114P
24VDC
K1
K2
K3
RN1
K4
K1
K2
K3
RN1
K4
K1
K2
K3
RN1
K4
K1
K2
K3
RN1
K4
74HC04N
74HC04N
74HC04N
74HC04N
ULN2803A/
ULN2803A/
ULN2803A/
ULN2803A/
PCF8574P
PCF8574P
PCF8574P
PCF8574P
Note:
All Relay Outputs Are
Normally Open And Rated
For 24 VAC Power Only.
2 Amp Maximum Load.
OE352 2 Slot Or OE353 - 4 Slot Expansion Board
As Required - OE353 Is Shown
Figure 8: Expansion Board Wiring Details For Relay Expansion Boards
VCM Controller
U1
U2
U1
U2
U1
U2
U1
U2
13
Technical Guide
Input/Output Wiring Details
Space Temperature Sensor
The Space Temperature Sensor is typically used for constant volume
HVAC unit applications controlling one zone. The Space Temperature
Sensor is a 10K Type III thermistor sensor. The Space Temperature
Sensor should be mounted approximately 5 ft. above the floor in the space that is to be controlled. The Space Temperature Sensor is available in a sensor only, sensor with override button, sensor with slide adjust and sensor with slide adjust and override configurations.
Remote SAT Reset Signal
A Remote Supply Air Temperature Reset Signal can be connected to
AIN 7 for applications requiring remote reset of the Supply Air Temperature Setpoint.
When the Slide Offset option on the Room Sensor is used, the Remote
Supply Air Temperature Reset Signal cannot be used. Only one of these options may be used on the VCM controller.
When the Remote Supply Air Temperature Reset Signal option is needed the Slide Offset option on the Room Sensor cannot be used. Only one of these options may be used on the VCM controller.
The VCM controller can accept either a 0-5 VDC signal or a 0-10 VDC signal on this input. When a 0-10 VDC signal is to be used, a resistor must be installed. See Figure 10 for complete Remote Supply Air Temperature Reset Signal wiring details.
See Figure 9 for complete Space Temperature Sensor wiring details.
OE210,OE211, OE212 or OE213
Space Temperature Sensor
TEMP
GND
AUX
AIN1
GND
Note:
Either The Slide Offset Option For The Space
Temperature Sensor Or The Remote Supply Air
Temperature Reset Signal Option (by Others) May Be
Connected To AIN7 On The VCM Controller. Only
One Option Is Allowed, Not Both.
Optional Slide Offset
Wiring Connection For
OE212 or OE213
Sensor Only
AIN7
Figure 9: Space Temperature Sensor Wiring
Note:
When Using 0-10 VDC For The Remote Signal
Source Must Have (2) 10kOhm Resistors Wired As
Shown. When Using 0-5 VDC For The Remote
Signal These Resistors are Not Required And The
Signal Can Be Wired Directly To AIN7 and GND,
Remote Supply Air
Temperature Reset Signal
(By Others)
0-5 VDC or 0-10 VDC Signal
GND
10 kOhm Resistors
Used With 0-10 VDC
Signal Only
AIN7
GND
Note:
Either The Slide Offset Option For The Space
Temperature Sensor Or The Remote Supply Air
Temperature Reset Signal Option (by Others) May Be
Connected To AIN7 On The VCM Controller. Only
One Option Is Allowed, Not Both.
Pullup Resistor PU7 Must Be
Removed When Using The
Remote Supply Air Temperature
Reset Signal Input
Figure 10: Remote Supply Air Temperature Reset Signal Wiring
14
VCM Controller
Technical Guide
Supply & Return Temperature Sensor
For applications that do not use either the AAON
®
MODGAS II or
MHGRV II boards, the Supply Air & Return Air Temperature Sensors must be wired as shown in the Figure 11 for proper operation. The
Supply Air & Return Air Temperature Sensors are 10K Type III thermistor sensors. The Supply Air Temperature Sensor should be mounted in the unit discharge plenum or in the supply air duct. The Return Air
Temperature Sensor should be mounted in the return air duct. If the system has a Zoning Bypass Damper installed, be sure the return air sensor is located upstream of the bypass duct connection.
Note: If your AAON
®
HVAC unit uses the MODGAS II
Controller and/or the MHGRV II Controller, the
Supply Air Sensor must be wired to one of these controllers and not to the VCM Controller.
Please see Figure 12 for Supply Air Temperature Sensor Wiring when using the MODGAS II controller and/or the MHGRV II controller. The
Return Air Temperature Sensor always connects to the VCM controller as shown in Figure 11
OE231
Supply Air Temperature Sensor
Mount In HVAC
Unit Supply
Air Duct
OE231
Return Air Temperature Sensor
Mount In HVAC
Unit Return
Air Duct
INPUTS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
AOUT2
AIN7
GND
OE331-21-VCM
VCM Controller Board
Figure 11: Supply Air and Return Air Temperature Sensor Wiring- Units Without MODGAS II or MHGRV II
VCM Controller
15
Technical Guide
Input/Output Wiring Details
VALV
GAS
SER.#
U3
CX3
U4
CX4
U5
CX5
V3 V2 V1
EPROM
AUX LOSPD
RAM
128
64
32
16
ADD
128
64
32
16
ADD
U2
SETPOINT
DISCHARGE
LIMIT
RESET
C1
YS101818
BOARD
552PROCESSOR
C2
P1
C4
C3
PHILIPS
CX1
PHILIPS
R2 WDOG
U1
U6
CX6
R15
T
R
SHLD
TB2
R26
R26
R25
C6
J01
C2 C1
24VAC
GND
D8
V4
TB3
POWER
GND
P1
RV1
OARD
SAT
YS101826PREV1
GASB
MODULATING
PJ1
O
F
F
C15
SW2
TB5
O
F
F
E VALV
AUX
COM
COMP
FAN
SW1
V4
V2
V1
V3
TUS STA
POWER
U3
U5
K4
COMP
K1
E
K2
K3
VALV
AUX
FAN
STEP
EPROM
CX3
U4
CX4
U5
CX5
C4
0-10V
C2
THERM
4-20MA
SETUP
AUXIN
RAM
U2
C1
BOARD
552PROCESSOR
YS101818
X1
P1
C2
C4
C3 CX1
RV1
COMM
R2
WDOG
COUT
U1
U6
CX6
D1
C13
U2
N CI
C3
D1
V5
L2
C1
L1
C8
PJ1
D1
D2
COM1-3
D3
RN2
D4
COM4-5
D5
X1
C2
C3
RN4
CX8
D10
R7
R10
D13
R11
U11
VDC
0-5
0-1
VDC
C11
RN3
D17
D18
C18
C19
D16
R27
V6
POWER
PJ2
PJ3
C15
O
TB5
O
F
F
E VALV
AUX
COMP
FAN
COM
SW1
V4
V2
V1
V3
SW2
TUS STA
POWER
U3
U5
K1
K4
AUX
K3
E
K2
VALV
COMP
FAN
STEP
EPROM
CX3
U4
CX4
U5
CX5
C4
0-10V
C2
4-20MA
THERM
SETUP
AUXIN
RAM
U2
GND
SAT
C1
BOARD
552PROCESSOR
YS101818
X1
P1
C2
C4
C3 CX1
RV1
COMM
R2
WDOG
UT CO
U1
U6
CX6
D1
C13
U2
N CI
C3
D1
V5
L2
C1
L1
C8
PJ1
D1 D2
COM1-3
D3
RN2
D4
COM4-5
D5
X1
C2
C3
RN4
CX8
D10
R7
R10
D13
U11
R11
VDC
0-1
VDC
0-5
C11
RN3
D17
D18
C18
C19
R27
V6
POWER
D16
PJ2
PJ3
16
D1 D2
COM1-3
D3
RN2
D4
COM4-5
D5
X1
C2
C3
RN4
CX8
D10
R7
R10
D13
R11
U11
VDC
0-5
0-1
VDC
C11
RN3
AIN2
GND
D17
D18
C18
C19
D16
R27
V6
POWER
PJ2
PJ3
PJ1
VALV
GAS
SER.#
U3
CX3
U4
CX4
U5
CX5
V3 V2 V1
EPROM
AUX LOSPD
RAM
32
64
16
128
ADD
32
64
16
128
ADD
U2
SETPOINT
DISCHARGE
LIMIT
RESET
C1
YS101818
BOARD
552PROCESSOR
C1
C2
P1
C4
P1
RV1
OARD
ING
YS101826PREV1
GASB
MODULAT
PJ1
24VAC
GND
D8
V4
TB3
POWER
C3
PHILIPS
CX1
PHILIPS
R2 WDOG
U1
U6
CX6
R15
R
SHLD
T
R26
R25
R26
C6
TB2
J01
C2
GND
SAT
D1 D2
COM1-3
D3
RN2
D4
COM4-5
D5
X1
C2
C3
RN4
CX8
D10
R7
R10
D13
U11
R11
VDC
0-5
VDC
0-1
C11
RN3
D17
D18
C18
C19
R27
V6
POWER
D16
PJ2
PJ3
PJ1
VCM Controller
Technical Guide
Outdoor Air Temperature Sensor
The Outdoor Air Sensor must be wired as shown in the illustration below for proper operation of the VCM controller. The Outdoor Air Temperature Sensor is a 10K Type III thermistor sensor. The sensor should be mounted in the upright position as shown, in an area that is protected from the elements and direct sunlight. Be sure to make the wiring splices inside of the Outdoor Air Temperature Sensor weather-tight enclosure.
See Figure 13 for detailed wiring.
Caution:
Be sure to mount the Outdoor Air Sensor in an area that is not exposed to direct sunlight. The shaded area under the HVAC unit rain hood is normally a good location. Unused conduit opening(s) must have closure plugs installed and must be coated with sealing compound to provide a rain tight seal. Water can damage the sensor.
OE250
Outdoor Air
Temperature Sensor
Make Splice Connections
Inside Sensor Enclosure
As Shown. Seal All
Conduit Fittings With
Silicone Sealant.
Mount Sensor Outdoors
In Shaded Protected
Area & In Upright
Position As Shown
INPUTS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
AOUT2
AIN7
GND
OE331-21-VCM
VCM Controller Board
Figure 13: Outdoor Air Temperature Sensor Wiring
VCM Controller
17
Technical Guide
Input/Output Wiring Details
Economizer Damper Actuator
The Economizer Damper Actuator Signal voltage output is a 2-10 VDC output. This signal output is used by the VCM controller to modulate the Economizer Damper Actuator in order to control the amount of
Outdoor Air delivered to the HVAC unit for Free Cooling and/or Indoor
Air Quality requirements. See Figure 14 for detailed wiring.
Warning: It is very important to be certain that all wiring is correct as shown in the wiring diagram below.
Failure to observe the correct polarity will result in damage to the actuator or VCM controller.
Economizer Damper Actuator
(Belimo Actuator Shown)
COM 1
Belimo Actuator Wiring
Shown. Consult Factory For
Other Manufacturers Wiring
Instructions
24 VAC Power Source
Sized For Actuator VA Load
E
R
EC1
AAON
Unit
Terminals
2-10 VDC
Output
INPUTS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
AOUT2
AIN7
GND
OE331-21-VCM
VCM Controller Board
Figure 14: Economizer Damper Actuator Wiring
18
VCM Controller
Technical Guide
Suction Pressure Transducer
The Suction Pressure Transducer is required for any VCM application with DX Cooling that requires Dehumidification. It is also required for any application which utilizes a digital scroll compressor.
has 3 color coded stripped wires on the other end. The stripped wire ends can be spliced to other wires to extend the wiring length when required.
The Suction Pressure Transducer is used to measure suction pressure at the HVAC units DX evaporator coil suction line. This suction line pressure is converted to saturated refrigerant temperature by the VCM controller. This temperature is used by the VCM controller to accurately control the compressors and reheat cycle components to provide optimum performance from the system during Dehumidification operation.
When used in dehumidification applications on HVAC units without digital scroll compressors the Suction Pressure Transducer wires to the
VCM controller board as shown in Figure 15. In this application the
Suction Pressure Transducer connects to the VCM board through a cable with a built-in signal conditioner. The cable is supplied with a 3 pin
Packard mating connector for attachment to the sensor on one end and
For applications that use a Digital Scroll Compressor, the Suction Pressure Transducer wires directly to the Digital Scroll Compressor Controller supplied by the compressor manufacturer. See Figure 16 for wiring details.
In this application the Suction Pressure Transducer connects to the digital scroll compressor with a prefabricated cable similar to the one used in the previous application but without the signal conditioner built in. The signal conditioning is controlled by the Digital Compressor controller.
This cable also has a 3 pin Packard mating connector for attachment to the sensor on one end and has 3 color coded stripped wires on the other end. The stripped wire ends can be spliced to other wires to extend the wiring when required to connect the Digital Compressor controller.
OE275-01-NDC
Suction Pressure
Transducer
With Signal Conditioner
(250 PSIG)
Transducer Cable
With Built-In Signal
Conditioner
WH
BK
RD
+VDC
AIN5
GND
Pullup Resistor PU5
Must Be Removed
OE331-21-VCM
VCM Controller Board
Figure 15: Suction Pressure Transducer Wiring (Units Without Digital Compressors)
VCM Controller
19
Technical Guide
Input/Output Wiring Details
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
10 VA Minimum Power Required For
Each 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each 4 Slot Expansion Base Board
Connect To VCM Controller
Connect To
Next Expansion Base Board
(When Used)
D3
R20
PWR LD1
AOUT2
1.5 to 5 VDC
GND
OE275-01-NDC
Suction Pressure
Transducer
(250 PSIG)
RD
WH
BK
P4 SHLD
EXC P3
P2
P1
OUT
COM
Copeland Digital
Compressor Controller
P5
P6
C1
C2
OE352 or OE353 Expansion Base Board
INPUTS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
AOUT2
AIN7
GND
OE331-21-VCM
VCM Controller Board
Figure 16: Suction Pressure Transducer Wiring (Units With Digital Compressors)
20
VCM Controller
Technical Guide
Supply Fan VFD Signal Or Zoning Bypass Damper Actuator
The Supply Fan VFD or Zoning Bypass Damper Actuator Signal is a 0-
10 VDC output. This signal output can be connected to the Supply Fan Variable
Frequency Drive to modulate the Supply Fan speed and control Duct
Static Pressure utilizing the Duct Static Pressure Sensor connected to the VCM controller board. Alternatively it can be connected to a Zoning Bypass Damper Actuator which will modulate the Zoning Bypass
Damper Actuator to control Duct Static Pressure utilizing the Duct Static
Pressure Sensor connected to the VCM controller board. A Duct Static
Pressure Sensor must be connected in order for the VFD or Zoning
Bypass Damper Actuator to operate. See Figure 17 and Figure 18 for detailed wiring.
Caution:
Variable Frequency Drive units can cause large transient noise spikes which can cause interference to be propagated on other electronic equipment. Use shielded wire wherever possible and route all sensor and controller wiring away from the Variable
Frequency Drive and the HVAC Unit electrical
Caution:
The VFD Unit Must Be Configured For 0-10 VDC Input.
The Input Resistance At The VFD Must Not Be Less
Than 1000 Ohms When Measured At The VFD
Terminals With All Input Wires Removed.
+
VFD 0-10VDC Input
_
GND
Supply Fan Variable Frequency Drive
(By Others)
INPUTS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
AOUT2
AIN7
GND
OE331-21-VCM
VCM Controller Board
Figure 17: Supply Fan VFD Signal Wiring
24 VAC Power Source
Sized For Actuator VA Load
Bypass Damper Actuator
(Belimo Actuator Shown)
COM 1
GND
24 VAC
0-10 VDC
Belimo Actuator Wiring
Shown. Consult Factory For
Other Manufacturers Wiring
Instructions
Figure 18: Zoning Bypass Damper Signal Wiring
VCM Controller
INPUTS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
AOUT2
AIN7
GND
OE331-21-VCM
VCM Controller Board
21
Technical Guide
Input/Output Wiring Details
Binary Inputs Wiring
All Binary Inputs are to be wired as 24 VAC wet contact closures. Only
24 VAC power must be supplied to the OE356 Binary Input Board through a Normally Open Contact closure in order for the signal to be recognized by the controller. If a Dry Contact closure is used , it will not work. See Figure 19 for detailed wiring.
Warning: Do not apply any voltage greater than 24 VAC to the Binary Input Expansion boards. Higher voltages will damage the expansion Board and possibly other components on the system.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
Connect To VCM Controller
10 VA Minimum Power Required For
Each 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each 4 Slot Expansion Base Board Connect To Next Expansion Base Board
(When Used)
Exhaust Hood On - N.O. Contact
Dirty Filter - N.O. Contact
Proof Of Flow - N.O. Contact
Remote Forced Occupied - N.O. Contact
Remote Forced Heating - N.O. Contact
Remote Forced Cooling - N.O. Contact
Smoke Detector - N.C. Contact
Remote Forced Dehumidification - N.O. Contact
BIN1
BIN2
BIN3
BIN4
COM
BIN1
BIN2
BIN3
BIN4
COM
D3
R20
PWR LD1
R5
OPTO1
BIN 1
BIN 2
R6
BIN 3
BIN 4
R8
OPTO2
R10
COM
R12
4 DIG. IN MOD. I/O BD.
YS101788
R5
OPTO1
BIN 1
BIN 2
BIN 3
R6
R8
OPTO2
BIN 4
R10
COM
R12
4 DIG. IN MOD. I/O BD.
YS101788
R1
R2
R3
R4
R1
R2
R3
R4
CX2 CX1
U2
U1
CX2 CX1
U2
U1
OE352 or OE353 Expansion Base Board
Figure 19: Binary Inputs Wiring
22
VCM Controller
Technical Guide
Outdoor Air Humidity Sensor
When used with the VCM controller, the Outdoor Air Humidity Sensor is connected to the system by wiring it to the AIN1 input on the OE354,
4 Analog Input 1 Analog Output Expansion board. It must be wired as shown in Figure 20 for proper controller operation.
Warning: It is very important to be certain that all wiring is correct as shown in the wiring diagram below.
Failure to observe the correct polarity will result in damage to the OA Humidity Sensor or controller.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-
GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion
Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
OE265-13
OA Humidity Sensor
10 VA Minimum Power Required For
Each 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each 4 Slot Expansion Base Board
Connect To VCM Controller
Connect To Next Expansion Base Board
(When Used)
Span
Zero
4 3 2 1
ON
6 5 4 3 2 1
ON
AIN1
0-5 VDC Input
GND
Pullup Resistor PU1 Must
Be Removed As Shown
D3
R20
PWR LD1
AIN1
R5
AIN2
R6
AIN3
AIN4
R7
GND
R8
R9
AOUT1
D5
R10
PU1
C2
PU2
C3
PU3
C4
PU4
C5
C1
LM358
JO1
JO2
JO3
JO4
D2
R3
D3
R4
D4
R1
D1
R2
CX1
U1
4 ANALOG IN MOD. I/O BD.
YS101784
Jumper J01 Must
Be Removed As Shown
OE352 or OE353 Expansion Base Board
4 3 2 1
ON
Jumpers Must Be Set as
Shown For Correct
O-5 VDC Operation
1 & 3 Are Off
2 & 4 Are On
6 5 4 3 2 1
ON
Jumpers Must Be Set as
Shown For Normal
Operation Of Sensor
1, 2, 4, 5 & 6 Are Off
3 Is On
Figure 20: Outdoor Air Humidity Sensor Wiring
VCM Controller
23
Technical Guide
Input/Output Wiring Details
Indoor Wall Mounted Humidity Sensor
When used with the VCM controller, the Indoor Wall Mounted Humidity Sensor is connected to the system by wiring it to the AIN2 input on the OE354, 4 Analog Input, 1 Analog Output Expansion board. It must be wired as shown in Figure 21 for proper controller operation.
Warning: It is very important to be certain that all wiring is correct as shown in the wiring diagram below.
Failure to observe the correct polarity will result in damage to the Space Humidity Sensor or controller.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-
GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion
Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
10 VA Minimum Power Required For
Each 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each 4 Slot Expansion Base Board
Connect To VCM Controller
Connect To Next Expansion Base Board
(When Used)
OE265-11
Space Humidity Sensor
Zero
Span
4 3 2 1
ON
6 5 4 3 2 1
ON
6 5 4 3 2 1
ON
AIN2
0-5 VDC Input
GND
Pullup Resistor PU2 Must
Be Removed As Shown
4 3 2 1
ON
Jumpers Must Be Set as
Shown For Correct
O-5 VDC Operation
1 & 3 Are Off
2 & 4 Are On
Jumpers Must Be Set as
Shown For Normal
Operation Of Sensor
1, 2, 4, 5 & 6 Are Off
3 Is On
Figure 21: Indoor Wall Mounted Humidity Sensor Wiring
D3
R20
PWR LD1
AIN1
R5
AIN2
AIN3
AIN4
R6
R7
GND
R8
R9
AOUT1
D5
R10
PU1
C2
PU2
C3
PU3
PU4
C4
C5
C1
LM358
JO1
JO2
JO3
JO4
R1
D1
R2
D2
R3
D3
R4
D4
CX1
U1
4 ANALOG IN MOD. I/O BD.
YS101784
Jumper J02 Must
Be Removed As Shown
OE352 or OE353 Expansion Base Board
24
VCM Controller
Technical Guide
Return Air Mounted Humidity Sensor
When used with the VCM controller, the Return Air Mounted Humidity Sensor is connected to the system by wiring it to the AIN2 input on the OE354, 4 Analog Input, 1 Analog Output Expansion board. It must be wired as shown in Figure 221 for proper controller operation.
Warning: It is very important to be certain that all wiring is correct as shown in the wiring diagram below.
Failure to observe the correct polarity will result in damage to the RA Humidity Sensor or controller.
4 3 2 1
ON
WARNING!!
Observe Polarity! All boards must be wired with GND-to-
GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion
Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
Jumpers Must Be Set as
Shown For Correct
O-5 VDC Operation
1 & 3 Are Off
2 & 4 Are On
10 VA Minimum Power Required For
Each 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each 4 Slot Expansion Base Board
OE265-14
RA Humidity Sensor
Connect To VCM Controller
Connect To Next Expansion Base Board
(When Used)
Span
Zero
4 3 2 1
ON
6 5 4 3 2 1
ON
AIN2
0-5 VDC Input
GND
Pullup Resistor PU2 Must
Be Removed As Shown
D3
R20
PWR LD1
AIN1
R5
AIN2
AIN3
AIN4
R6
R7
GND
R8
R9
AOUT1
D5
R10
PU1
C2
PU2
C3
PU3
PU4
C4
C5
C1
LM358
JO1
JO2
JO3
JO4
R1
D1
R2
D2
R3
D3
R4
D4
CX1
U1
4 ANALOG IN MOD. I/O BD.
YS101784
Jumper J02 Must
Be Removed As Shown
OE352 or OE353 Expansion Base Board
6 5 4 3 2 1
ON
Jumpers Must Be Set as
Shown For Normal
Operation Of Sensor
1, 2, 4, 5 & 6 Are Off
3 Is On
Figure 22: Indoor Return Air Mounted Humidity Sensor Wiring
VCM Controller
25
Technical Guide
Input/Output Wiring Details
Building Pressure Sensor Wiring
The OE258 Building Pressure Sensor must be wired as shown in the illustration below for proper operation. There are 3 terminal connections on the OE258 Building Pressure Sensor. Connect the power side of the 24 VAC power source to the terminal labeled “+ EXC” . Connect the GND side of the 24 VAC power source to the terminal labeled “-
COM”. Connect the remaining terminal labeled “OUT” to AIN4 on the
OE354, 4 Analog Output 1 Analog Input Expansion Board terminal block. See Figure 23 below for detailed wiring. The pullup resistor P4 on the expansion board must be removed and the voltage jumper J04 must also be removed as shown in the wiring diagram for the OE258
Building Pressure Sensor to operate correctly.
Warning: It is very important to be certain that all wiring is correct as shown in the wiring diagram below.
Failure to observe the correct polarity will result in damage to the HVAC Unit Controller, Building
Pressure Sensor and the Expansion Board.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-
GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion
Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
10 VA Minimum Power Required For
Each 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each 4 Slot Expansion Base Board
Connect To VCM Controller
Connect To Next Expansion Base Board
(When Used)
OE258
Building Pressure Sensor
+
-
EXC
OUT
COM
Tubing To Building
Pressure Sensing Location
Tubing To Atmospheric
Pressure Sensing Location
0-5 VDC Input
AIN4
GND
Pullup Resistor PU4 Must
Be Removed As Shown
D3
R20
AIN1
AIN2
AIN3
AIN4
R5
R6
R7
GND
R8
R9
AOUT1
D5
R10
PWR LD1
PU1
C2
PU2
C3
PU3
C4
PU4
C5
C1
LM358
JO1
JO2
JO3
JO4
R1
D1
R2
D2
R3
D3
R4
D4
CX1
T L
AN
I D
U1
4 ANALOG IN MOD. I/O BD.
YS101784
Jumper J04 Must
Be Removed As Shown
OE352 or OE353 Expansion Base Board
Figure 23: Building Pressure Sensor Wiring
26
VCM Controller
Technical Guide
Building Pressure Control
Output Wiring
The Building Pressure Control Output is a 0-10 VDC or 2-10 VDC signal sent from the OE354, 4 Analog Input 1 Analog Output Expansion Board. When using the output for Direct Building Pressure control
(output signal rises on a rise in building pressure), the output signal can be connected to either a Variable Frequency Drive controlling an exhaust fan or to a damper actuator controlling an exhaust damper. When used in this manner the output signal must be configured for Direct
Acting operation.
When using this output for Reverse Building Pressure Control (output signal rises on a fall in building pressure), a damper actuator controlling an OA Damper would be used. When using the OA damper for
Reverse Building Pressure Control, the output signal must be configured for Reverse Acting operation. A Building Pressure Sensor connected to AIN4 on the OE354 Expansion board is used to sense and control the signal to the Building Pressure Output. The OE258 Building Pressure Sensor must be connected in order for the Building Pressure Output to operate correctly.
See Figure 24 for detailed wiring of the Building Pressure Control
Output Signal.
Caution:
Variable Frequency Drive units can cause large transient noise spikes which can cause interference to be propagated on other electronic equipment. Use shielded wire wherever possible and route all sensor and controller wiring away from the Variable
Frequency Drive and the HVAC unit electrical wiring.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-
GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion
Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
10 VA Minimum Power Required For
Each 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each 4 Slot Expansion Base Board
Connect To VCM Controller
Connect To Next Expansion Base Board
(When Used)
Wiring When Using Damper Actuator
For Building Pressure Control
Belimo Actuator Wiring
Shown. Consult Factory For
Other Manufacturers Wiring
Instructions
Building Pressure Control
Damper Actuator
(By Others - Belimo Actuator Shown)
COM 1
GND
24 VAC
D3
R20
PWR LD1
Both Types Of Building Pressure Control
Devices Are Shown
Only One Type Of Building Pressure Control
Device May Be Used On Each HVAC Unit
Building Pressure Control
Exhaust Fan Variable Frequency Drive
(By Others)
+
_
GND
The VFD Unit Must Be Configured For 0-10vdc Input. The
Input Resistance At The VFD Must Not Be Less Than 1000
Ohms When Measured At The VFD Terminals With All
Input Wires Removed.
GND
AOUT1
AIN1
R5
AIN2
AIN3
AIN4
R6
R7
GND
R8
R9
AOUT1
D5
R10
PU1
PU2
C2
C3
PU3
C4
PU4
C5
C1
LM358
JO1
JO2
JO3
JO4
R1
D1
R2
D2
R3
D3
R4
D4
CX1
T L
AN
U1
4 ANALOG IN MOD. I/O BD.
YS101784
0-10VDC or 2-10 VDC
(Configurable)
OE352 or OE353 Expansion Base Board
Wiring When Using Exhaust Fan VFD
For Building Pressure Control
Figure 24: Building Pressure Control Output Wiring
VCM Controller
27
Technical Guide
Input/Output Wiring Details
CO
2
Sensor Wiring
The OE255 or OE256 CO
2
Sensors are used to sense the current CO
2 level in the conditioned space. The pullup resistor PU3 must be removed and the voltage jumper J03 must be in position (0-10 VDC position ) on the OE354, 4 Analog Input 1 Analog Output Expansion Board for proper operation of the CO
2
Sensor. See Figure 25 for detailed wiring.
Warning: It is extremely important to be certain that the
CO
2
Sensors “AC/GND” terminal is connected to the GND terminal on the OE354 expansion board and to the 24 VAC expansion base board power source GND connection. The “AC+/DC+ ” terminal on the CO
2
Sensor must be connected to the 24 VAC power side of the 24 VAC power source supplying power to the expansion base board terminal as shown. Failure to observe the correct polarity will result in damage to the HVAC
Unit Controller, CO
2
Sensor and the Expansion
Board.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-
GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion
Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
10 VA Minimum Power Required For
Each 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each 4 Slot Expansion Base Board
Connect To VCM Controller
Connect To Next Expansion Base Board
(When Used)
OE255 or OE256
(0-10VDC Signal)
AIN3
0-10 VDC Input
GND
Pullup Resistor PU3 Must
Be Removed As Shown
D3
R20
PWR LD1
AIN1
R5
AIN2
R6
AIN3
AIN4
R7
GND
R8
R9
AOUT1
D5
R10
PU1
PU2
C2
C3
PU3
C4
PU4
C5
C1
LM358
JO1
JO2
JO3
JO4
D2
R3
D3
R4
D4
R1
D1
R2
CX1
U1
4 ANALOG IN MOD. I/O BD.
YS101784
Jumper J03 Must
Be In Place As Shown
OE352 or OE353 Expansion Base Board
Figure 25: CO
2
Sensor Wiring
28
VCM Controller
Technical Guide
Modulating Heating Device Wiring
The Modulating Heating Device signal can be configured for either a
0-10 VDC or 2-10 VDC output signal. The output signal can be configured for either Direct Acting or Reverse Acting operation as required.
The Output signal is normally used to control a Modulating Hot Water
Valve, Modulating Steam Valve or for SCR Control of an Electric Heating Coil.
See Figure 26 for detailed wiring of the Modulating Heating Device.
Warning: It is very important to be certain that all wiring is correct as shown in the wiring diagram below.
Failure to observe the correct polarity could result in damage to the Modulating Heating Device or the Analog Output expansion board.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-
GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion
Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
10 VA Minimum Power Required For
Each 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each 4 Slot Expansion Base Board
Connect To VCM Controller
Connect To Next Expansion Board
(When Used)
The Modulating Heating Device Used Must Be Designed To
Accept Either a 0-10 Or a 2-10 VDC Input. The AOUT1
Output Voltage Is User Configurable For Either Voltage. The
Heating Device Used Can Be A Modulating Hot Water Valve,
Steam Valve Or SCR Controlled Electric Heating Coil.
+
0-10 VDC or 2-10 VDC
(Configurable)
_
GND
Modulating Heating Device
(By Others)
AOUT1
GND
D3
R20
PWR LD1
AOUT1
AOUT2
AOUT3
AOUT4
GND
4 AOUT MOD. I/O BD.
R7
D3
R8
D4
R9
D1
R6
D2
Q1
Q2
R2
Q3
R3
Q4
R4
R5
YS101786
CX2
CX3
U2
U3
CX1
U1
OE352 or OE353 Expansion Base Board
Figure 26: Modulating Heating Device Wiring
VCM Controller
29
Technical Guide
Input/Output Wiring Details
Modulating Cooling Device Wiring
The Modulating Cooling Device signal can be configured for either a
0-10 VDC, 2-10 VDC or 1.5-5.0 VDC output signal. The output signal can also be configured for either Direct Acting or Reverse Acting operation as required by your application. This signal output would normally be connected to a Modulating Chilled Water Valve or Digital
Compressor Controller.
to the Digital Compressor Controller instead of the VCM board and the
Modulating Cooling Output signal must be configured for a 1.5 to 5.0
VDC output signal. For Digital Compressor wiring details see Figure 16.
Warning: It is very important to be certain that all wiring is correct as shown in the wiring diagram below. Failure to observe the correct polarity could result in damage to the Modulating Cooling Device.
See Figure 27 for detailed wiring of the Modulating Cooling Device when using a Chilled Water Valve. When this output is used with a
Digital Compressor, the Suction Line Pressure Transducer must be wired
WARNING!!
Observe Polarity! All boards must be wired with GND-to-
GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion
Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
10 VA Minimum Power Required For
Each 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each 4 Slot Expansion Base Board
Connect To VCM Controller
Connect To Next Expansion Board
(When Used)
The Modulating Cooling Device Used Must Be Designed
To Accept Either A 0-10 VDC, 2-10 VDC Or 1.5-5.0 VDC
Input. The AOUT1 Output Voltage Is User Configurable
For These Voltages. The Cooling Device Used Can Be A
Modulating Chilled Water Valve or A Digital Scroll
Compressor. If Using A Digital Scroll Compressor
Please See Digital Scroll Detailed Wiring Information In
This Manual.
+
_
0-10 VDC, 2-10 VDC or 1.5-5.0 VDC
(Configurable)
GND
AOUT2
GND
Modulating Cooling Device
(By Others)
D3
R20
PWR LD1
AOUT1
AOUT2
AOUT3
AOUT4
GND
4 AOUT MOD. I/O BD.
R7
D3
R8
D4
R9
D1
R6
D2
Q1
Q2
R2
Q3
R3
Q4
R4
R5
YS101786
CX2
CX3
U2
U3
CX1
U1
OE352 or OE353 Expansion Base Board
Figure 27: Modulating Cooling Device Wiring
30
VCM Controller
Technical Guide
Return Air Bypass Wiring
The VCM controller can be configured for PAC or DPAC control schemes. Both PAC and DPAC control schemes provide improved moisture removal capabilities while utilizing internal space loads for reheat by redirecting the Return Air around the Evaporator Coil instead of through the coil. See the PAC and DPAC applications section of this manual for complete operation details.
The DPAC control scheme provides improved moisture removal capabilities and tighter temperature control than the PAC controls scheme by combining Digital Compressor control in addition to Return Air
Bypass control.
See Figure 28 for detailed wiring of the Return Air Bypass and Return
Air Damper Actuators.
See Figure 16 for detailed wiring of the Digital Compressor.
The PAC & DPAC control schemes both utilize a Return Air Bypass
Damper Actuator and a Return Air Damper Actuator to modulate the
Return Air and Return Air Bypass Dampers to control the amount of air that is redirected around the Evaporator Coil.
Warning: It is very important to be certain that all wiring is correct as shown in the wiring diagram below.
Failure to observe the correct polarity could result in damage to the Damper Actuators or the
Analog Output expansion board.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-
GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion
Boards must be wired in such a way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
10 VA Minimum Power Required For
Each 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each 4 Slot Expansion Base Board
Connect To VCM Controller
Connect To Next Expansion Board
(When Used)
GND
Return Air
Damper Actuator
(0-10 VDC)
COM 1
+ 2
Y1 3
0-10 VDC
0-10 VDC
Return Air Bypass
Damper Actuator
(0-10 VDC)
COM 1
+ 2
Y1 3
Belimo Actuator Wiring
Shown. Consult Factory For
Other Manufacturers Wiring
Instructions
Figure 28: Return Air Bypass Wiring
VCM Controller
AOUT3
AOUT4
GND
D3
R20
PWR LD1
AOUT1
AOUT2
AOUT3
AOUT4
GND
4 AOUT MOD. I/O BD.
R7
D3
R8
D4
R9
D1
R6
D2
Q1
Q2
R2
Q3
R3
Q4
R4
R5
YS101786
CX2
CX3
U2
U3
CX1
U1
OE352 or OE353 Expansion Base Board
31
Technical Guide
Start-up & Commissioning
In order to have a trouble free start-up it is important to follow a few simple procedures. Before applying power for the first time it is very important to correctly address the controller and run through a few simple checks.
Controller Addressing
All VCM controllers are equipped with address switches. If the VCM controller is to operate as a stand alone system (not connected to any other HVAC unit or VAV/Zone controllers) the controller address switch should be set for address 1. When using the Modular Service Tool or
System Manager to program and configure the VCM controller you would enter this address to communicate with the controller. When the system is to be connected to other HVAC unit controllers on a communication loop, each controllers address switch must be set with a unique address between 1 and 59. When the VCM controller will be used with
VAV/Zone controllers the VCM controller’s address switch must be set as address 59, no exception. See Figure 29 for address switch setting information. For detailed information regarding communication wiring and connection for interconnected and networked systems, please see the Orion System Installation & Troubleshooting Guide.
Power Wiring
One of the most important checks to make before powering up the system for the first time, is to confirm proper voltage and transformer sizing for the controller. Each VCM controller requires 8 VA of power delivered to it at 24 VAC. Each 2 slot expansion board requires 10 VA at 24 VAC and each 4 slot expansion board requires 20 VA at 24 VAC.
You may use separate transformers for each device (preferred) or power several devices from a common transformer. If several devices are to be powered from a single transformer correct polarity must be followed.
Warning: Observe Polarity! All boards must be wired with
GND-to-GND and 24 VAC-to-24 VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Boards must be wired in such a way that the Expansion Boards and the VCM Controller are always powered together.
Loss of power to the Expansion Board will cause it to become inoperative until power is restored to the Expansion Board.
Check all wiring leads at the terminal block for tightness. Be sure that wire strands do not stick out and touch adjacent terminals. Confirm that all sensors required for your system are mounted in the appropriate location and wired into the correct terminals on the VCM controller. Be sure any Expansion Boards connected to the VCM controller are also correctly wired just as you did for the VCM controller.
After all the above wiring checks are complete, apply power to the
VCM controller and all expansion boards connected to it.
This Switch Should Be
In The OFF Position
As Shown
ADDRESS
ADDRESS
ADD
1
2
4
8
16
32
TOKEN
NETWORK
ADDRESS
ADD
ADD
Controller
Address Switch Shown Is
Address Switch
Address Switch Shown Is
Set For Address 1
Set For Address 13
The Address For Each Controller
Must Be Unique To The Other Controllers
On The Local Loop And Be Between 1 and 59
Note:
The Power To The Controller Must Be Removed And
Reconnected After Changing The Address Switch Settings
Caution
Disconnect All Communication Loop Wiring From The
Controller Before Removing Power From The Controller.
Reconnect Power And Then Reconnect Communication Loop
Wiring.
INPUTS
TB3
+VDC
RN5
AIN1
AIN2
AIN3
AIN4
AIN5
GND
C10
GND
AOUT1 C12
AOUT2
AIN7
GND
PJ1
C17
D15
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
ADDRESS
SW1
ADD
1
2
4
8
16
32
TOKEN
NETWORK
U10
JP1
X2
U13
CX13
U15
CX10
R15
C14
R19
U14
U12
CX14
C15
R22
R24
R25
C20
CX15
CX12
R26
PRESSURE
SENSOR
EXPANSION
VR1
C7
D12
R13
SC1
D19
L1
VR2
R6
C9
C13
C16
TB4
GND
24VAC
Figure 29: VCM Controller Address Switch Setting
32
VCM Controller
Technical Guide
Initialization:
On system power up a 30 second startup delay is performed where all default setpoints are initialized, LED’s are initialized and all outputs are turned off.
When power is first applied, LED 1 and LED2 will flash out the controller address. LED1 will flash to represent Tens. LED2 will flash to represent Ones. After the controller address is complete, there will be a short pause and then 60 fast flashes to represent controller initialization. There will be no controller operation or communications during initialization. After initialization, LED1 & LED2 will continuously flash the status code.
Programming The Controller
The next step is programming the controller for your specific requirements. In order to configure and program the VCM controller you must use an operator interface. Four different operator interfaces are available for programming and monitoring of the VCM controller. These are:
•
Modular Service Tool
•
Modular System Manager
•
Tactio SI Touch Screen Interface
•
Notebook or Desktop Computer With
Prism II Computer Front End Software Installed
Example of a controller address of 59:
LED1 will flash 5 times. LED2 will flash 9 times.
See Table 2 in the Troubleshooting Section of this manual for detailed diagnostic blink code information.
Operating Summary
There is a standard set of operating instructions that are continuously repeated during normal operations. They are listed below.
1.) Read Analog Inputs for Temperatures, Pressures and Binary
Contact Closures
2.) Calculate Occupied / Unoccupied Mode of Operation
3.) Calculate HVAC Mode of Operation
4.) Set all outputs to match calculations for Heating or Cooling or vent Mode
5.) Broadcast information to other controllers if configured.
6.) Log all temperatures and output conditions
7.) Repeat steps 1 through 6 continuously
Any of these devices or a combination of them can be used to access the status, configuration and setpoints of any controller on your communications loop. See the Operator Interfaces Technical Guide for complete
VCM controller programming instructions if you are going to be using the Modular Service Tool or Modular System Manager with your system.
If you are going to be using a Notebook or Desktop computer and the
Prism II Computer Front End Software, please see the Orion Prism II
Computer Front End Technical Guide. If you will be using the Tactio SI
Interface please see the Tactio SI Touch Screen Technical Guide. No matter which operator interface you use, it is recommended that you proceed with the programming and setup of the VCM controller in the order that follows:
1.) Configure The Controller For Your Application
2.) Program The Controller Setpoints.
3.) Program The Controller Operation Schedules.
4.) Set The Controller Current Time And Date.
5.) Review Controller Status Screens To Verify System
Operation And Correct Controller Configuration
Mode
Selection
STATUS PREV
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE - TEST
ON
1
4
7
DEC
UP
ESC
DOWN
CLEAR
ENTER
2
5
8
0
3
6
9
NEXT
System Manager
1
4
7
DEC
2
5
8
0
UP
3
6
-
9
MINUS
PREV
ESC
DOWN
CLEAR
ENTER
NEXT
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
Figure 30: Modular Service Tool & Modular System Manager Operator Interfaces
VCM Controller
33
Technical Guide
Inputs & Outputs
VCM Controller
AIN1 - Space Temperature Sensor Input
If you want to generate Occupied or Unoccupied Heating and Cooling demands based on Space Temperature, select this Sensor for the HVAC
Mode enable. The Space Temperature Sensor can be used for Night
Setback control regardless of the HVAC Mode Sensor selected. If the
Space Temperature Sensor used is equipped with the optional Pushbutton Override Feature, this input will detect user overrides from Unoccupied back to Occupied operation for a user adjustable amount of time. This Sensor is not required for Cooling Only HVAC units configured for Supply Air Temperature control as the HVAC Mode Enable
Sensor, unless Night Setback operation is required. The Space Temperature can also be configured to reset the Supply Air Temperature
Setpoint. The Space Temperature Sensor is the only Sensor that can be used for Night Setback operation during the Unoccupied Mode.
AIN2 - Supply Air Temperature Sensor Input
The Supply Air Temperature Sensor is the default HVAC Mode Enable
Sensor. For typical VAV units that are Cooling Only with Morning Warmup, this Sensor should be configured as the HVAC Mode Enable Sensor. Heating will only occur during Morning Warm-up. After Morning
Warm-up expires, the Supply Air Temperature will be maintained at the
Supply Air Temperature Cooling Setpoint. The HVAC unit must always have a Supply Air Temperature Sensor installed.
AIN3 - Return Air Temperature Sensor Input
If you want to generate occupied Heating and Cooling demands based on Return Air Temperature, select this Sensor as the HVAC Mode Enable Sensor. The Return Air Temperature Sensor is also used to initiate or cancel the Morning Warm-up Period. This temperature must be at least 5°F above the Outdoor Air Temperature to allow Economizer-
Cooling operation.
AIN4 - Outdoor Air Temperature Sensor Input
The Outdoor Air Temperature is used to lockout Heating or Cooling to conserve energy at whatever temperature the user deems appropriate for each Mode of operation. The Outdoor Air Temperature Sensor can also be used to provide Low Ambient Temperature Protection in the building. If the Outdoor Air Temperature is below the Low Ambient
Temperature Setpoint, the Preheat Relay Output will be maintained during Occupied operation and will not be allowed to stage off unless the
Supply Fan is turned off. When using 100% (MUA Units) Outdoor Air applications, the Outdoor Air Temperature Sensor should be configured as the HVAC Mode Enable Sensor. The Outdoor Air Temperature
Sensor is also used in combination with the Outdoor Air Humidity Sensor for Dewpoint calculations.
AIN5 – Suction Pressure Sensor Input
A Suction Pressure Sensor can be connected to this input. This Sensor is required when using Dehumidification with DX Cooling units. The
VCM controller converts the Suction Pressure reading to Suction Temperature. This calculated Evaporator Coil Temperature, is considered to be the Saturation Vapor Pressure of the refrigerant leaving the evaporator coil. In most cases, the Supply Air Temperature leaving the Evaporator coil will be 10°F to 15°F higher than the calculated Evaporator
Coil Temperature.
Note: All temperature Sensors must be Thermistor Type III which provide 77.0°F @ 10 K Ohms Resistance.
AIN6 - Duct Static Pressure Sensor Input
This special phone jack style input connection accepts a Duct Static
Pressure Sensor input modular cable. The Duct Static Pressure Sensor reading is used to determine current Duct Static Pressure. This Static
Pressure reading is used to control the output signal supplied to the
Supply Fan VFD or Zoning Bypass Damper Actuator. If you have configured the HVAC unit for Constant Volume operation, this Sensor is optional. If it is installed on a Constant Volume unit, it will not affect operation, it will be used as a status only reading.
AIN7 – Space Temp. Sensor Slide Adjust or
Remote SAT Reset Signal Input
AIN 7 on the VCM controller is a dual purpose input. It can be used for the Space Sensor Slide Adjust option or for connection of the Remote
Supply Air Setpoint Reset Signal option. Only one or the other can be used not both.
Space Temperature Sensor Slide Adjust
If the Space Temperature Sensor being used has the optional Slide Adjust feature, its AUX output is connected to this input. The Slide Adjust control is used to vary the HVAC Mode Heating and Cooling Setpoints by a user configured maximum amount. The Slide Adjustment adjusts whichever Temperature Sensor that has been configured as the HVAC
Mode Enable Sensor even if that Sensor is not the installed Space Temperature Sensor.
If Space Temperature is configured as the SAT/Reset Source, the Slide
Adjustment adjusts both the HVAC Mode Enable Heating and Cooling setpoints and the SAT/Reset Source Heating and Cooling setpoints simultaneously by a user configurable maximum amount.
Remote Supply Air Temperature Reset Signal
When a 0-5 VDC Remote Supply Air Temperature Reset Signal is to be used, the controller must be configured for it and the Room Sensor
Slide Offset setpoint must be set to zero for this option. If the slide offset is not set to zero, the Supply Air Temperature Reset will not function.
The Remote Supply Air Temperature Reset signal must be configured so its setpoint will be at the coldest Supply Air Temperature at 0 VDC and its setpoint will be at the warmest Supply Air Temperature at 5
VDC.
If a 0-10 VDC reset signal is used, a resistor network will need to be installed on AIN 7. See the VCM wiring diagram for details.
AOUT1 - Economizer Control Signal
This voltage signal (2-10 VDC) is used to position the Outdoor Air
Damper during Economizer Control. It is also used to maintain the
Outdoor Air Damper at its Minimum Position during the Occupied Mode when the Outdoor Air Temperature and/or Outdoor Humidity is not suitable for Economizer Cooling purposes.
34
VCM Controller
Technical Guide
AOUT2 - Duct Static Pressure Control Signal
This voltage signal (0-10 VDC) can be connected to a Supply Fan VFD or to Proportional Inlet Vanes to control the Duct Static Pressure. This signal can also be connected to a 0-10 VDC Modulating Zoning Bypass
Damper Actuator to control Duct Static Pressure. When this signal is used to control a Zoning Bypass Damper Actuator, the Zoning Bypass
Damper Actuator needs to be mechanically configured to close the Zoning Bypass Damper on an increase of the 0-10 VDC output signal. This is necessary because the signal is Direct Acting and is not configurable as a Reverse Acting Signal on the VCM controller.
R1 - Supply Fan (Enable)
This is a non-configurable output.
R2 Thru 5 - User Configurable Relays
These relays are configurable by the user. For all the available configuration options see the OE357 4 Relay Output Expansion Board section of this manual.
OE354 (4) Analog Input
(1) Analog Output Expansion Board
AIN1 - Outdoor Air Humidity Sensor Input
This input is used to connect an Outdoor Air Humidity Sensor that, combined with the Outdoor Air Temperature Sensor reading, is used to calculate a Dewpoint and/or Wetbulb Temperature. Outdoor Air
Dewpoint Temperature is used to activate the Dehumidification Mode on MUA and CAV configured units which utilize the Dual Damper
Mode (Hood On/Off) control feature. The Wetbulb Temperature is used for Economizer enthalpy control.
AIN2 – Indoor Air Humidity Sensor Input
The Indoor Air Humidity Sensor is used to activate Dehumidification
Mode on a VAV or CAV unit. The Sensor can be either a Wall Mounted
Space Humidity Sensor or a Return Air Duct Mounted Humidity Sensor.
AIN3 - CO
2
Sensor Input
This Sensor is required if you need to monitor Indoor Air Quality and modify the Economizer operation based on levels of CO
2 or building you are monitoring. The CO
2
in the space
Sensor can be either a Wall
Mounted CO
2
Sensor or and Return Air Mounted CO
2
Sensor as required by your specific application.
AIN4 - Building Pressure Sensor Input
This Sensor is only required if you wish to configure the VCM Controller for Building Pressure Control. Building Pressure Control can be accomplished by using one of two main control methods. One control method uses the 0-10 VDC signal to control an Exhaust Fan VFD or an
Exhaust Damper Actuator for Direct Acting Pressure Control applications. In addition, for Reverse Acting Pressure Control applications it can control an Outdoor Air Damper Actuator. The other available control method is to configure one of the Output Relays as an Exhaust Fan output which will activate the Exhaust Fan anytime the Building Pressure is above the Building Pressure Setpoint.
AOUT1 - Building Pressure Control Signal
This voltage signal (0-10 VDC) is used to provide an output signal to a
Building Pressure Control device. The output signal can be connected to either an Exhaust Fan VFD or an Exhaust Damper Actuator when
Direct Acting Building Pressure Control is required. When Reverse
Acting Building Pressure Control is required, the output signal would be connected to an Outdoor Air Damper Actuator. When used in this application the output signal must be configured for Reverse Acting
Operation.
OE355 (4) Analog Output
Expansion Board
AOUT1 – Modulating Heating Signal
This output signal can be configured for either 0–10 VDC or a 2-10
VDC output signal. This signal can be configured for either Direct Acting or Reverse Acting operation. This output signal is used to operate a
Modulating Heating Device to maintain the Heating Supply Air Temperature Setpoint.
AOUT2 – Modulating Cooling Signal
This output signal can be configured for either 0–10 VDC, 2-10 VDC or 1.5-5.0 VDC output signals. This signal can be configured for either
Direct Acting or Reverse Acting operation. This output signal is used to operate a Modulating Cooling Device to maintain the Cooling Supply
Air Temperature Setpoint. If your unit uses a Digital Compressor this must be configured for a 1.5-5.0 VDC output signal.
AOUT3 – Return Air Damper Signal
This output signal is a Direct Acting 0–10 VDC output signal that is used to modulate a Return Air Damper Actuator in concert with a Return Air Bypass Damper Actuator for PAC or DPAC control schemes.
AOUT4 – Return Air Bypass Damper Signal
This output signal is a Direct Acting 0–10 VDC output signal that is used to modulate a Return Air Bypass Damper Actuator in concert with a Return Air Damper Actuator for PAC or DPAC control schemes.
OE357 (4) Relay Expansion Boards
R6 – R21 User Configurable Relay Outputs
Relays can be configured in any order but we recommend that they be configured in the following order:
1.
Cooling stages
2.
Heating stages
3.
Warm–up Mode Command (for VAV Boxes)
4.
Reversing Valve (for Air to Air Heat Pumps)
5.
Reheat
6.
Exhaust Fan
7.
Pre-Heater (for Low Ambient Protection)
8.
Alarm
9.
Override
10. Occupied
11. Economizer
VCM Controller
35
Technical Guide
Inputs & Outputs
By using all (4) of the available 4 Relay Expansion Boards and the 4 relay outputs available on the VCM controller, you have the ability to configure up to a combined total of 20, Heating Stages, Cooling Stages, and options 3 through 11 listed above.
OE356 Binary Expansion Board #1
BIN2 - Remote Forced Cooling Mode Input
This wet contact input is used to provide a means for another BAS or control device (by others) to force the unit into Cooling Mode when it closes. See the Note regarding Remote Force Mode Setting that follows at the end of this section.
Note: The Binary Inputs require wet contacts (24 VAC only) to recognize an active input. If you provide dry contacts, the contact closure will not be recognized
BIN1 – Exhaust Hood On Input
When this wet contact input closes the VCM controller switches from
Indoor Air Control to Outdoor Air Control. This is typically used on
CAV applications requiring Dual Damper (Hood On/Off) Modes.
BIN2 - Dirty Filter Contact Closure Input
This wet contact input is required for Filter Status Indication and requires a Differential Pressure Switch to initiate “Dirty Filter” indication.
BIN3 – Proof of Flow Input
A Proof of Flow Switch that provides a wet contact closure whenever the HVAC unit Supply Fan is operating can be connected to this input.
If the Proof of Flow Switch contact opens while the Supply Fan is operating, all Heating and Cooling is suspended or disabled. The Proof Of
Flow Switch is an optional input. This means the VCM controller must be configured by the user to recognize this input signal.
BIN4 – Remote Forced Occupied Mode Input
When this wet contact input closes, it will force the VCM controller into the Occupied Mode. When the Remote Forced Occupied Signal is removed, the controller will revert to the Unoccupied Mode of operation if no internal or external schedule has been configured or is in effect when this occurs.
OE356 Binary Expansion Board #2
BIN1 – Remote Forced Heating Mode Input
This wet contact input is used to provide a means for another BAS or control device (by others) to force the unit into Heating Mode when it closes. See the Note regarding Remote Force Mode Setting that follows at the end of this section.
Note: Remote Forced Heating or Cooling Modes require that the user enter zero values for both the Heating and
Cooling Setpoints for the HVAC Mode Enable. The
VCM Controller will then look for wet contact closures on the Remote Forced Cooling Mode and
Remote Forced Heating Mode inputs to enable the
HVAC Modes. If both the Remote Forced Heating and
Remote Forced Cooling Modes are active, the unit will operate in Vent Mode. The unit may also be operated in Vent Mode by providing a wet contact closure signal to the Remote Occupied Input.
BIN3 – Smoke Detector Input
This wet contact input is used to initiate shutdown of the HVAC unit when a Smoke Detector (by others) contact closure occurs. The controller remains active and can initiate alarm relays.
BIN4 – Remote Forced Dehumidification
This wet contact input is used to provide a means for another BAS or control device (by others) to force the VCM controller into Dehumidification Mode.
Note: When using the Remote Forced Dehumidification function the user must set the Dehumidification Spt
Indoor RH to 100% for the Remote Forced
Dehumidification feature to function.
36
VCM Controller
Technical Guide
Sequence Of Operations
Occupied/Unoccupied
Mode of Operation
The VCM controller can utilize several methods for determining the
Occupied Mode of Operation. These are:
Forced Schedule
Remote Forced Occupied Signal
Internal Schedule
Push Button Override Signal
Forced Schedule
The VCM controller can be forced into the Occupied Mode by inputting a Forced Schedule from any operator interface.
Remote Forced Occupied Signal
When this wet contact input closes, it will force the VCM controller into the Occupied Mode. When the Remote Forced Occupied Signal is removed, the controller will revert to the Unoccupied Mode of operation if no Internal or External Schedule has been configured or is in effect when this occurs.
You can still use the Space Temperature Sensor input for an Override
Command even when a Space Temperature Sensor is not connected.
Simply provide a Momentary Push-Button connected between AIN1 and the Ground Terminal on the same terminal block. Follow the above procedure for initiating Overrides, even on Supply Air Temperature Controlled Cooling only HVAC units.
HVAC Modes of Operation
There are 6 possible HVAC Modes of Operation. They are:
Vent Mode
Cooling Mode
Dehumidification
Heating Mode
Warm-Up Mode
Off Mode
Vent Mode Operation
This Mode only applies to the Occupied Mode of Operation. The Vent
Mode is defined as the Supply Fan running with no Heating, Cooling or
Dehumidification demand.
Note: If the Remote Forced Occupied Mode is to be used, it is necessary to set all the Internal Week Schedules to
‘0’ so that the Internal Schedule always commands the
Unoccupied Mode.
Vent Mode can occur during the Occupied Mode if the Space, Return or
Outdoor Air Temperature Sensors are selected as the HVAC Mode Enable Sensor. Vent Mode can also occur if the Supply Air Temperature
Sensor is the HVAC Mode Enable Sensor and the VCM has been configured for Remote Forced Heating and Cooling. See the Remote Con-
trol of HVAC Mode section in this manual for complete details.
Internal Week Schedule
An Internal Week Schedule, which supports up to two start/stop events per day, is available for determining Occupied and Unoccupied Schedules. If you are using the Internal Schedule, an Optimal Start calculation is also available. See the Scheduling Section of this manual for more information on the Optimal Start Feature.
Push Button Override Signal
During Unoccupied hours, the user can force the VCM controller back to Occupied operation by pressing the Override Button on the Space
Temperature Sensors for a period of less than 3 seconds. This initiates the Override or resets the Override Timer back to zero during Unoccupied hours of operation.
Note: During Vent Mode, all Cooling and Heating Stages are deactivated and the Economizer Damper is maintained at a Minimum Position to provide fresh air into the building. The Static Pressure is still maintained by the
Supply Fan VFD or Zoning Bypass Damper Signal since the Supply Fan is still operating in this Mode.
Cooling Mode Operation
Occupied Cooling Mode occurs whenever the HVAC Mode Enable Temperature is above the HVAC Mode Enable Cooling Setpoint. Unoccupied Cooling Mode only occurs if a Space Temperature Sensor is connected to the VCM, or a broadcast of Space Temperature is being received from an Averaging Broadcast Controller and only then if the
Space Temperature is above the Cooling Setpoint.
During Override operations, the user can cancel the Override by pressing the Override Button for a period of time between 3 seconds and 10 seconds. This restores the VCM controller to Normal Unoccupied Operation.
If the Override Button is held for more than 10 seconds, it causes a
Space Sensor Failure Alarm. This is due to the fact that the Override
Button actually shorts the Space Temperature Sensor input to ground. If this input is shorted to ground or left floating with no Space Temperature Sensor detected for more than 10 seconds, it is considered a Space
Temperature Sensor failure.
The Mechanical Cooling will be disabled if the Outdoor Air Temperature is below the Cooling Lockout Setpoint by 1°F. This gives a 2°F hysteresis around the Cooling Lockout Setpoint to prevent unwanted cycling in and out of Mechanical Cooling Mode. If the Outdoor Air
Temperature disables the Mechanical Cooling while it is currently operating, the Mechanical Cooling will stage off if all staging and run times are satisfied.
If the Economizer has been enabled for operation, it is used as the first stage of Cooling and the Mechanical Cooling will be activated if necessary. See the Economizer Operation section for a more detailed operating sequence.
VCM Controller
37
Technical Guide
Sequence Of Operations
No matter which Sensor is configured for the HVAC Mode Enable or if the Remote BAS sets the Mode through Remote Forced Cooling, the
Supply Air Temperature is always controlled to the Active Supply Air
Temperature Setpoint while in the Cooling Mode..
Stage Control Window
The Cooling Stage Control Window Setpoint determines when the compressors start to stage up and stage down. In the Cooling Mode, as the
Supply Air Temperature rises above the Active Supply Air Temperature
Setpoint, the Cooling Stages will begin to stage on based on the Cooling Stage Up Delay setting. The Cooling Stages will continue to run until the Supply Air Temperature drops below the Active Supply Air
Temperature Setpoint minus the Cooling Stage Control Window. For example if the Supply Air Temperature Setpoint is 55° and the Cooling
Stage Control Window is 5°, as the Supply Air Temperature drops below 50°, the Cooling Stages will begin to stage off based on the Cooling Stage Down Delay setting.
A Digital Compressor is a Variable Capacity Compressor that has a 10 to 1 turn down ratio. The VCM is capable of handling a single stage
Cooling unit with a Digital Compressor as its only stage. It is also capable of handling multistage Cooling units with a Digital Compressor.
The Digital Compressor is always the first stage of Cooling. On multistage Cooling units with a Digital Compressor, Fixed Capacity Compressors will stage up while the Digital Compressor modulates to achieve the Active Supply Air Temperature Setpoint. A three compressor Cooling unit with a Digital Compressor is the only special staging arrangement.
On three compressor Cooling units with a Digital Compressor, the first stage of Cooling is the Digital Compressor. The second stage of Cooling is a Fixed Capacity Compressor, equal to the maximum capacity of the Digital Compressor. The third stage of Cooling is a Fixed Capacity
Compressor with double the capacity of the second compressor. When the third stage of Cooling activates, the second stage (compressor) of
Cooling deactivates. The fourth stage of Cooling is when the second stage (compressor) of Cooling is reactivated. In this way, a three compressor Cooling unit with a Digital Compressor becomes four stages of
Cooling.
Cooling Staging Delay
Minimum Off Time
A Cooling Stage cannot be activated unless it has been off for this amount of time.
Minimum Run Time
After a Cooling Stage has been activated, it must remain on for this amount of time.
Staging Up Delay
After the first Cooling Stage has been activated, this delay prevents additional stages from activating too quickly before they are needed to achieve the Active Supply Air Temperature
Setpoint.
Staging Down Delay
After a Cooling Stage has met its Minimum Run Time and is not needed, this delay prevents additional stages from deactivating too quickly in case they are needed to maintain the Active
Supply Air Temperature Setpoint Temperature.
If the Supply Air Temperature rises above the Active Supply Air Temperature Setpoint, the Digital Compressor signal will modulate as needed up to 100%. When the Digital Compressor signal reaches 100% the
Cooling Stage Up Delay begins. If the Digital Compressor signal remains at 100% and the Cooling Stage Up Delay expires, an additional
Fixed Capacity Compressor will activate if equipped.
If the Supply Air Temperature falls below the Active Supply Air Temperature Setpoint, the Digital Compressor signal will modulate as needed down to 0%. When the Digital Compressor signal reaches 0% the Cooling Stage Down Delay begins. If the Digital Compressor signal remains at 0% and the Cooling Stage Down Delay expires, the Digital Compressor, or a Fixed Capacity Compressor will be deactivated. The Digital Compressor is always the last compressor to be deactivated.
Economizer Operation
This section assumes you have configured your HVAC unit to control the Outdoor Air Dampers in an Economizer Mode of operation.
Modulating Cooling
The Modulating Cooling Proportional Window is used to determine the signal to the Modulating Cooling Source and is user adjustable.
The Modulating Cooling signal is calculated based on the differential between the Supply Air Temperature and the Active Supply Air Temperature Setpoint based on the Modulating Cooling Proportional Window. The Maximum Signal Adjustment per Time Period is 10% and is not user adjustable. The Minimum Signal Adjustment per Time Period is based on the Modulating Cooling Proportional Window. The larger the Modulating Cooling Proportional Window, the smaller the signal adjustment will be per Time Period. The Time Period is the delay between another increase or decrease in the Modulating Cooling Source
Signal and is user adjustable. For example, if the Modulating Cooling
Proportional Window is 5
°
F, the signal would be adjusted 2% per
°
F each Time Period above or below the Active Supply Air Temperature
Setpoint. When the Supply Air Temperature is above or below the
Active Supply Air Temperature Setpoint by 5
°
F or more, the signal would adjust 10% each Time Period.
The VCM can control one of two Modulating Cooling sources, such as a Chilled Water Valve or a Digital Compressor. Whichever source is used, the VCM will control the Modulating Cooling source to maintain the Active Supply Air Temperature Setpoint.
The Economizer is used as the first stage of Cooling if the Outdoor Air or Wetbulb Temperature is below the Economizer Enable Setpoint. For
Wetbulb control of the Economizer, an Outdoor Air Humidity Sensor must be installed. If the unit is equipped with a Return Air Temperature
Sensor, the Outdoor Air or Wetbulb temperature must be at least 5°F colder than the Return Air Temperature to allow the Economizer to modulate. The same is true if the unit is only equipped with a Space Temperature Sensor. By using the Return Air and/or Space Temperature reference, it allows the VCM to calculate whether the Outdoor Air Temperature will assist in Free Cooling.
The VCM Controller can monitor an Outdoor Air Humidity Sensor and combine that reading with the Outdoor Air Temperature reading to calculate a Wetbulb Temperature. If this Wetbulb Temperature is not available, just the Outdoor Air Temperature will be used. Whichever temperature is available, it must be below the Economizer Enable Setpoint by 1°F to enable the Economizer during the Cooling Mode of operation. When the temperature rises 1°F above the Economizer Enable
Setpoint, the Economizer will be disabled and return to Minimum Position.
38
VCM Controller
Technical Guide
As soon as the Cooling Mode is started, the Economizer will calculate a starting damper position based on the Outdoor Air Temperature and the differential between the Supply Air Temperature and the Active
Supply Air Temperature Setpoint. After it moves to this initial Setpoint, further adjustments will be made in small increments to fine tune the damper position to maintain the Active Supply Air Temperature Setpoint.
If the Economizer reaches 100% open and the Supply Air Temperature is still too warm, the Mechanical Cooling will be enabled to operate to provide additional stages of Cooling. Once a Mechanical Cooling Stage has been activated, the Economizer will remain full open until the Mechanical Cooling Stages are off or the Outdoor Air Temperature or
Wetbulb Temperature causes the Economizer to be disabled.
For DX Cooling Stages, the VCM activates the Cooling Stages based on the actual Evaporator Coil Temperature compared to the Evaporator
Coil Temperature Setpoint. The Evaporator Coil Temperature is calculated by using the Suction Pressure Sensor and converting the pressure to temperature. For Digital Compressor units, the VCM will modulate the Digital Compressor to maintain the Evaporator Coil Temperature
Setpoint and activate Fixed Capacity Compressors as necessary.
For Chilled Water units the VCM opens the Chilled Water Valve to a fixed 100% position to provide full moisture removal capabilities.
If the Economizer is not enabled to provide Cooling during the Occupied Mode, it will still maintain the Minimum Position programmed by the user to provide minimum fresh air into the building. During the
Unoccupied Mode, the Economizer will be closed. If during the Unoccupied Mode there is a call for Cooling and the Economizer is enabled by Outdoor Air Drybulb or Wetbulb temperature, it will modulate between full closed and full open to provide Free Cooling.
If you configured your VCM Controller for Dehumidification control, you need to install a Humidity Sensor on the optional Analog Input
Expansion Board. If the VCM is configured as a MUA unit, use an
Outdoor Air Humidity Sensor. If the VCM is configured as a VAV or
CAV unit, use an Indoor Air Humidity Sensor such as a Wall Mounted or Duct Mounted Sensor. If the VCM is to be used for Dual Damper
Modes during Occupied hours, use both Indoor and Outdoor Air Humidity Sensors. As an example this could be used in a kitchen application when you have a CAV unit using both Outdoor Air and Return Air.
This unit could be configured to operate using Return Air when the
Exhaust Hood is off or 100% Outdoor Air when the Exhaust Hood is on.
The Supply Air Temperature must be above the Supply Air Temperature Setpoint before the Mechanical Cooling can be activated.
Dehumidification Mode
During the Dehumidification Mode the VCM activates Cooling to extract moisture from the Supply Air and utilizes either Modulating Hot
Gas Reheat, On/Off Hot Gas Reheat or Heating to warm the Supply Air before entering the building. Hot Gas Reheat is the standard form of
Reheat. The HVAC unit’s Heat Source or a Heat Source located in the
Supply Air Duct can be used for Reheat if the unit is not equipped with
Hot Gas Reheat. Please see the warning note that follows regarding applications operating Heating and Cooling simultaneously
If the unit is equipped with a Modulating Hot Gas Reheat board
(MHGRV II), it is automatically detected by the VCM controller. In
Dehumidification Mode, as the Cooling causes the Supply Air Temperature to drop, the MHGRV II will bypass Hot Gas to the Hot Gas
Reheat Coil, raising the Supply Air Temperature back up to the Active
Supply Air Temperature Setpoint.
If the unit is equipped with an On/Off Hot Gas Valve, then one of the relays will be configured for Reheat. The Reheat Relay will be activated if the Supply Air Temperature is less than the HVAC Mode Enable Heating Setpoint. The Hot Gas Reheat Relay will remain on during the Dehumidification Mode regardless of the Supply Air Temperature. This is to insure a steady Supply Air Temperature.
Warning: Simultaneous Heating and Cooling cannot be approved unless the HVAC unit has been specifically designed for this purpose. A Special
Price Authorization (SPA) must be obtained from the AAON
®
factory for these applications to avoid warranty and/or rating problems. WattMaster
Controls Inc. assumes no liability for any
Simultaneous Heating and Cooling application if a
SPA is not obtained from the AAON
®
Factory at the time the HVAC unit is ordered.
On 100% Outdoor Air applications the Outdoor Air Dewpoint initiates the Dehumidification Mode when the Outdoor Air Dewpoint rises above the Outdoor Air Dewpoint Setpoint during the occupied Mode of operation. The Outdoor Air Dewpoint is calculated by using an Outdoor
Air Temperature Sensor and an Outdoor Air Humidity Sensor.
On VAV or CAV applications the Indoor Air Humidity initiates Dehumidification when the Indoor Air Humidity rises above the Indoor Air
Humidity Setpoint during the occupied Mode of operation.
When Heating is used for Reheat instead of Hot Gas Reheat, the VCM can activate the Heat Source(s) discussed in the Heating Mode section.
Heating can also be used in conjunction with Hot Gas Reheat to add additional Reheat for applications that require a higher Supply Air
Drybulb Temperature than what Hot Gas Reheat can provide. When
Heating is used in conjunction with Reheat, the VCM restricts the Heating to one form of Modulating Heat, or one stage of Gas or Electric
Heat.
The Dehumidification Mode can be configured to have Dehumidification Priority. If configured, the VCM will enter the Dehumidification
Mode when the Dewpoint or Humidity is above the Setpoint regardless of the current Heating or Cooling demands. The Reheat is always controlled to the Active Supply Air Temperature Setpoint. The Active Supply Air Temperature Setpoint will change during Heating, Cooling or
Vent Modes. During the Vent Mode, the Supply Air Temperature Setpoint will be a Calculated Setpoint that is halfway between the HVAC Mode
Setpoints.
Note: MODGAS II cannot be used in conjunction with Hot
Gas Reheat to add additional Reheat.
VCM Controller
39
Technical Guide
Sequence Of Operations
If Dehumidification Priority has not been configured, the VCM will only enter the Dehumidification Mode and use Reheat during the Vent
Mode. The Reheat will be controlled to a Calculated Supply Air Temperature Setpoint that is halfway between the HVAC Mode Setpoints.
Night Dehumidification can also be configured and is used primarily for CAV units that require an Unoccupied Mode of Dehumidification.
Night Dehumidification is only activated when the Indoor Air Humidity is above the Indoor Air Humidity Setpoint during the Unoccupied
Mode.
Remote Forced Dehumidification
Dehumidifcation Mode is normally controlled by using a Humidity Sensor connected to the (4) Analog Input (1) Analog Output Expansion
Board input AIN1 or AIN2. If desired Dehumidification Mode can also be determined by using a remote BAS or other user supplied remote device. The VCM controller will check Binary Input Expansion Board
#2 for a 24 VAC signal on BIN4. If the signal is present it will force the
VCM controller into Dehumidifcation Mode regardless of the mode it is currently operating in if Dehumidification Priority Mode has been configured. If Dehumidification Priority Mode has not been configured, the unit will only be forced into Dehumidification Mode if it is operating in the Vent Mode during the time the remote signal is being supplied to input BIN4.
Note: When using the Remote Forced Dehumidification function the user must set the Dehumidification Spt
Indoor RH to 100% for the Remote Forced
Dehumidification feature to function.
Return Air Bypass Damper Control
The return air bypass (RAB) damper is only used on constant air volume units with space temperature configured as the HVAC Mode Enable sensor. The RAB damper is only active during the dehumidification mode and is used as the first form of reheat. If the HVAC unit is equipped with modulating hot gas reheat, the RAB damper needs to be at 100% before the modulating hot gas reheat can be used. The RAB damper modulates from 0-100% as the space temperature falls below the cooling setpoint. When the space temperature is equal to the cooling setpoint, the RAB damper will be at 0%. When the space temperature falls to halfway between the cooling and heating setpoints, the RAB damper will be at 100%.
If the HVAC unit is equipped with separate actuators for the outdoor air and return air dampers, the return air damper will proportionally close more as the RAB damper opens. The rate at which the return air damper closes is user adjustable. The purpose of closing the return air damper more as the RAB Damper opens, is to allow more air to bypass the evaporator coil through the RAB Damper. If you want more air to pass through the RAB Bypass Damper, enter a larger number in the Return
Air Damper Factor setpoint. If you want less air to pass through the
RAB Damper, enter a smaller number in the Return Air Damper Factor setpoint.
Heating Mode Operation
Occupied Heating Mode occurs whenever the HVAC Mode Enable
Temperature is below the HVAC Mode Enable Heating Setpoint. Unoccupied Heating Mode only occurs if a Space Temperature Sensor is connected to the VCM or a broadcast of Space Temperature is being received from an Averaging Broadcast Controller.
The Mechanical Heating will be disabled if the Outdoor Air Temperature is above the Heating Lockout Setpoint by 1°F. This gives a 2°F hysteresis around the Heating Lockout Setpoint to prevent unwanted cycling in and out of Mechanical Heating Mode. If the Outdoor Air
Temperature disables the Mechanical Heating while it is currently operating, the Mechanical Heating will stage off if all staging and run times are satisfied.
No matter which Sensor is configured for the HVAC Mode Enable or if the Remote BAS sets the Mode through Remote Forced Heating, the
Supply Air Temperature is always controlled to the Active Supply Air
Temperature Setpoint while in Heating Mode.
Stage Control Window
The Heating Stage Control Window Setpoint determines when the
Heating Stages begin to stage up and stage down. In the Heating Mode, as the Supply Air Temperature falls below the Active Supply Air Temperature Setpoint, the Heating Stages will begin to stage on based on the Heating Stage Up Delay. The Heating Stages will continue to run until the Supply Air Temperature rises above the Active Supply Air
Temperature Setpoint plus the Heating Stage Control Window. For example if the Supply Air Temperature Setpoint is 140°F and the Heating Stage Control Window is 5
°
F, as the Supply Air Temperature rises above 145
°
F, the Heating Stages will begin to stage off based on the
Heating Stage Down Delay.
Heating Staging Delay
Minimum Off Time
A Heating Stage cannot be activated unless it has been off for this amount of time.
Minimum Run Time
After a Heating Stage has been activated, it must remain on for this amount of time.
Staging Up Delay
After the first Heating Stage has been activated, this delay prevents additional stages from activating too quickly before they are needed to achieve the Active Supply Air Temperature
Setpoint.
Staging Down Delay
After a Heating Stage has met its Minimum Run Time and is not needed, this delay prevents additional stages from deactivating too quickly in case they are needed to maintain the Active
Supply Air Temperature Setpoint.
40
VCM Controller
Technical Guide
MODGAS II Controller
The MODGAS II Controller is treated as a single stage of gas Heating when connected to the VCM’s expansion port. The Supply Air Temperature is broadcast from the MODGAS II Controller to the VCM.
The Supply Air Temperature Setpoint is broadcast from the VCM to the
MODGAS II Controller. When the VCM enters the Heating Mode, it broadcasts a command to activate the MODGAS II Controller. The
MODGAS II Controller modulates the Natural Gas Valve to maintain the Supply Air Temperature Setpoint. See the MODGAS II Controller
Technical Guide for detailed operation information of the MODGAS II
Controller.
lating Heating Proportional Window. The larger the Modulating Heating Proportional Window, the smaller the signal adjustment will be per
Time Period. The Time Period is the delay between another increase or decrease in the Modulating Heating source signal and is user adjustable. For example, if the Modulating Heating Proportional Window is
5°F, the signal would be adjusted 2% per °F each Time Period above or below the Active Supply Air Temperature Setpoint. When the Supply
Air Temperature is above or below the Active Supply Air Temperature
Setpoint by 5°F or more, the signal would adjust 10% each Time Period.
MODGAS II Controller with Additional Stages of Heat
The VCM can activate the MODGAS II Controller and additional stages of heating if needed. If this configuration is needed, a heating relay must be configured on the VCM for the MODGAS II Controller, but it will not be connected to anything. The MODGAS II Controller will always be the first stage of heating in this configuration. Additional heating relays can be configured and connected to Staged Heating sources, such as Natural Gas or Electric Heat. In order for the additional stages to activate, the MODGAS II Controller must be at 100% and then the Stage Up Delay begins. Once the Stage Up Delay expires and the Gas Valve is still at 100%, another Fixed Stage of Heating will activate. This will be the VCM’s second stage of heat. The MODGAS
II Controller will modulate to achieve the Active Supply Air Temperature Setpoint. If the MODGAS II Controller modulates to 0% and the
Supply Air Temperature is above the Active Supply Air Setpoint plus the Heating Stage Control Window, the Stage Down Delay begins. Once the Stage Down Delay expires and the Supply Air Temperature has remained above the Active Supply Air Setpoint plus the Heating Stage
Control Window, the Fixed Stage of Heating will be deactivated. The
MODGAS II will remain active, even at the minimum valve position unless the Supply Air Temperature remains above the Active Supply
Air Setpoint plus the Heating Stage Control Window. The MODGAS II controller will be the last stage of heating to be deactivated.
Modulating Heating
The VCM supports various forms of Modulating Heat such as SCR
Electric Heat, Modulating Hot Water Heat and Modulating Steam Heat.
Whichever form of Modulating Heating is used, the VCM will modulate the Heat Source to achieve the Active Supply Air Temperature
Setpoint. Modulating Natural Gas is a form of Modulating Heat, but is controlled by the MODGAS II Controller. The VCM only activates the
MODGAS II as a stage of heat, therefore, the Modulating Heating Proportional Window does not apply when the VCM is connected to the
MODGAS II Controller and is the only form of Heating activated by the VCM.
The Modulating Heating Proportional Window is used to determine the signal to the Modulating Heating Source and is user adjustable. The
Modulating Heating Signal is calculated by the differential between the
Supply Air Temperature and the Active Supply Air Temperature Setpoint based on the Modulating Heating Proportional Window. The maximum signal adjustment per Time Period is 10% and is not user adjustable.
The minimum signal adjustment per Time Period is based on the Modu-
The VCM can activate two forms of Heating that are classified as Primary and Secondary Heat Sources. The Primary Heat Source used can be SCR Electric Heat, Modulating Hot Water Heat or Modulating Steam
Heat. The Secondary Heat Source used can be Modulating Natural Gas
(MODGAS II Controller), Staged Gas Heat or Staged Electric Heat.
Primary Modulating Heat and
Secondary Heat with MODGAS II Controller
The Modulating Heating Proportional Window is used to determine the signal to the Primary Heat Source and is user adjustable. The Heating
Stage Control Window is used to determine stage up and stage down of the Secondary Heat Source. In the Heating Mode, the Primary Heat
Source will modulate to achieve the Active Supply Air Temperature
Setpoint. When the Primary Heat Source reaches 100%, the Heating
Stage Up Delay begins. If the Primary Heat Source is still at 100% after the Heating Stage Up Delay expires, the Secondary Heat Source will activate, which is controlled by the MODGAS II Controller. The Primary Heat Source will then be forced to 0%, allowing the MODGAS II
Controller to modulate the gas valve to achieve the Active Supply Air
Temperature Setpoint. When the Secondary Heat Source reaches 100%, the Heating Stage Up Delay begins. If the Secondary Heat Source is still at 100% after the Heating Stage Up Delay expires, the Primary
Heat Source will be forced to 100%. The Primary Heat Source will remain at 100% to allow the Secondary Heat Source to modulate to achieve the Active Supply Air Temperature Setpoint. If the Supply Air
Temperature rises above the Active Supply Air Temperature Setpoint plus the Heating Stage Control Window, the Heating Stage Down Delay begins. If the Supply Air Temperature is still above the Active Supply Air Temperature Setpoint plus the Heating Stage Control Window and the Heating Stage Down Delay expires, the Primary Heat Source will forced to 0%. If the Secondary Heat Source modulates to 0%, the
Heating Stage Down Delay begins. If the Secondary Heat Source remains at 0% and the Heating Stage Down Delay expires, the Secondary
Heat Source will be deactivated, and the Primary Heat Source will modulate to achieve the Active Supply Air Temperature Setpoint. If the
Supply Air Temperature rises above the Active Supply Air Temperature
Setpoint plus the Heating Stage Control Window, the Primary Heat
Source modulates as needed to allow the Supply Air Temperature to cool off.
VCM Controller
41
Technical Guide
Sequence Of Operations
Primary Modulating Heat and Secondary Heat with
Staged Gas or Electric Heat
The Modulating Heating Proportional Window is used to determine the signal to the Primary Heat Source and is user adjustable. The Heating
Stage Control Window is used to determine stage up and stage down of the Secondary Heat Source. In the Heating Mode, the Primary Heat
Source will modulate to achieve the Active Supply Air Temperature
Setpoint. When the Primary Heat Source reaches 100%, the Heating
Stage Up Delay begins. If the Primary Heat Source is still at 100% after the Heating Stage Up Delay expires, the Secondary Heat Source will activate. The Primary Heat Source will then modulate to achieve the
Active Supply Air Temperature Setpoint. If the Secondary Heat Source is activated and the Primary Heat Source has modulated to 0%, the
Heating Stage Down Delay will begin. If the Primary Heat Source is still at 0% after the Heating Stage Down Delay expires, the Secondary
Heat Source will deactivate. If the Supply Air Temperature rises above the Active Supply Air Temperature Setpoint plus the Heating Stage
Control Window, the Primary Heat Source modulates to 0% to allow the Supply Air Temperature to cool off.
on both BIN1 and BIN2, the VCM will be in Remote Forced Venting
Mode. Remote Forced Venting Mode is considered to be Occupied Fan
Only operation. Once the Remote Forced Mode has been set, normal
Heating, Cooling or Venting Modes of operations will occur. All other user adjustable setpoints, such as the Heating and Cooling Supply Air
Temperature Setpoints are used in the actual control of the equipment.
During Dehumidification, if a Reset Source is not configured, the Supply Air Temperature Setpoint will be 70°F.
The Remote Occupied Input on the Binary Input Expansion Board #1,
BIN4 can also be used for Occupied Fan Only operation when the Remote Forced Heating or Cooling inputs are not activated.
Warm-up Mode Operation
When the VCM Controller switches to the Occupied Mode of Operation (Not Override Mode), the unit compares the Return Air Temperature to a Morning Warm-up Target Temperature. If the Return Air Temperature is below this Setpoint, the Warm-up Mode is initiated. This
Mode remains in effect until the Return Air Temperature rises above the Target Temperature or a user adjustable Time Period expires. Warmup Mode is not initiated by Push Button Overrides or Unoccupied Heating demands.
Supply Air Temperature
Setpoint Reset
The VCM incorporates a new automatic Supply Air Temperature Reset capability. During reset, the Supply Air Temperature Setpoints are always being calculated based on the Heating and Cooling demands of the reset source. Since the Supply Air Temperature Setpoints are not fixed during reset, we refer to them as the “Active Supply Air Temperature Setpoints”.
The Supply Air Temperature Setpoints can automatically be reset by configuring the Space Temperature or Return Air Temperature as the
SAT/Reset Source. The Supply Air Temperature Setpoints can also be reset by configuring the Fan VFD Signal or Remote SAT Reset as the
SAT Reset Source. The Fan VFD Signal and Remote SAT Reset options are not fully automatic and require the user to enter a Low and a
High Temperature Reset setpoint for both Heating and Cooling.
Once the Warm-up Mode has been terminated, it cannot resume until the unit has been through a subsequent Unoccupied Mode. Only one
Warm-up Mode is allowed per Occupied cycle.
If you have stand alone VAV boxes that need to be forced wide open during the Warm-up Mode, you can configure one of the relay outputs to be used during this Mode. If the Warm-up Mode is active, the relay is activated. This relay then becomes the Force Open Command for all
VAV boxes to which it is wired.
Off Mode
If the schedule has set the Unoccupied Mode and no Heating, Cooling or Dehumidification demands exist, the VCM Controller enters the Off
Mode. During the Off Mode the Supply Fan is off and the Outdoor Air
Dampers are closed.
Remote Control of HVAC Mode
If Space Temperature or Return Air Temperature is configured as the
SAT/Reset Source, the user will need to enter the desired Heating and
Cooling Setpoints for the SAT/Reset Source. The VCM uses the HVAC
Mode Enable Setpoints to determine the mode of operation. Once the
HVAC Mode has been determined, the VCM calculates the Active Supply Air Temperature Setpoint based on the SAT/Reset Source Temperature in relation to the SAT/Reset Source Heating and Cooling Setpoints.
During the Dehumidification Priority Mode, the Active Supply Air Temperature Setpoint is calculated in the same way as the Heating or Cooling Modes. When the VCM is in the Venting Mode, the Supply Air
Temperature Setpoint will be calculated to be halfway between the
HVAC Mode Enable Setpoints. When the VCM is in Dehumidification
Priority and the HVAC Mode is the Vent Mode, the Supply Air Temperature Setpoint reset range will be + or - 10° F, above and below the calculated Vent Mode, Supply Air Temperature Setpoint.
Note: When using the Remote Control Of HVAC Mode both of the Heating and Cooling HVAC Mode Enable
Setpoints must be set to zero.
The Heating Mode, Cooling Mode and Vent Mode can be determined by a remote Building Automation System (BAS). The VCM will check the Binary Input Expansion Board #2 for a 24 VAC input signal on
BIN1 and BIN2. BIN1 is used for Remote Forced Heating Mode. BIN2 is used for Remote Forced Cooling Mode. If a 24 VAC signal is present
If the Fan VFD Signal is configured as the SAT/Reset Source, the SAT/
Reset Source Setpoints and Remote SAT Reset Setpoints create the range of Supply Air Temperature Reset from 0% to 100% Supply Fan VFD
Signal. When the Supply Fan VFD signal is at 0%, the SAT/Reset Source heating setpoint will be the lowest Supply Air Temperature setpoint for heating. When the Fan VFD signal is at 100% , the Remote SAT Reset heating setpoint will be the highest Supply Air Temperature setpoint for heating. When the supply fan VFD signal is at 0%, the Remote SAT
Reset cooling setpoint will be the highest Supply Air Temperature
42
VCM Controller
Technical Guide setpoint for cooling. When the supply fan VFD signal is at 100%, the
SAT/Reset Source cooling setpoint will the lowest Supply Air Temperature setpoint for cooling. During the dehumidification priority mode, the Active Supply Air Setpoint is calculated in the same way as the
Heating or Cooling Modes. When the VCM is in the Vent Mode, the
Supply Air Temperature Setpoint will be calculated to be halfway between the HVAC Mode Enable Setpoints.
Since the Duct Static Pressure Control Output Signal is a nonconfigurable Direct Acting Signal (0-10 VDC), when you are using a
Zoning Bypass Damper Actuator to control the Duct Static Pressure you must set up the Zoning Bypass Damper Actuator or the Zoning
Bypass Damper so that it is Reverse Acting in operation. The Output
Signal increases (closes Zoning Bypass Damper) if the Duct Static Pressure is below the Duct Static Pressure Setpoint by the Deadband amount and the Output Signal decreases (opens Zoning Bypass Damper) if the
Static Pressure is above the Setpoint by the Deadband amount.
If Remote SAT Reset is configured as the SAT/Reset Source, the SAT/
Reset Source Setpoints will be the lowest Supply Air Temperature
Setpoints for both Heating and Cooling when the Remote SAT Reset
Input is at 0 VDC. When the Remote SAT Reset Input is at 5 VDC, the
Remote SAT Reset Setpoints will be the highest Supply Air Temperature Setpoints for both Heating and Cooling. The supply air setpoint will proportional between the SAT/Reset Source Setpoints at 0 VDC and the Remote SAT Reset Setpoints at 5 VDC. During the Dehumidification Priority Mode, the Supply Air Temperature Setpoints will be the same as the Heating and Cooling Modes. When the VCM is in the
Vent Mode, the Supply Air Temperature Setpoint will be calculated to be halfway between the HVAC Mode Enable Setpoints.
Supply Fan Control
Anytime the Supply Fan is requested to start, a timer is checked to make sure the Supply Fan has been off for at least 1 minute. This 1 minute delay is to protect against rapid cycling of the Supply Fan. Once the 1 minute delay has been satisfied, the Supply Fan relay is activated and all other outputs are verified to be in the off condition for a period of 1 to 2 minutes. This short period of Supply Fan only Operation serves to purge the stagnant air from the duct before any Heating or
Cooling occurs.
If the Static Pressure ever rises 0.5” above the Duct Static Pressure
Setpoint, the Duct Static Pressure Control Output Signal will be cut in half every control period until the Static Pressure is brought under control. This is to prevent damage to the ductwork if all the VAV boxes are closed or some other blockage occurs in the ductwork.
Warning: The manufacturer does not assume responsibility for protecting the equipment from over pressurization! The user should always install mechanical high static protection cutoffs to protect their system!
When the Supply Fans starts, the Duct Static Pressure Control Output
Signal will go to the Minimum % for Heating. Anytime the Supply Fan is off the Duct Static Pressure Control Output Signal will remain at zero volts.
Normally the Supply Fan runs continuously during the Occupied Mode of operation. If the fan is only required to run in the Occupied Mode during Heating, Cooling or Dehumidification Modes, the VCM can be configured for Fan Cycle Mode.
Duct Static Pressure Control
The VCM Controller reads and controls Static Pressure in the duct system if the Supply Fan has been configured for Duct Static Pressure
Control. Anytime the Supply Fan is operating, the VCM Controller is controlling Duct Static Pressure. The Duct Static Pressure Setpoint and
Deadband limits are user adjustable along with a Control Interval. This
Control Interval is the amount of time that elapses between each adjustment to the Duct Static Pressure Control Output Signal. The default period is 10 seconds and should not be changed unless close observation reveals that the Supply Fan is hunting and not maintaining a stable pressure reading. The Static Pressure Control Output Signal can be used to control a Supply Fan VFD (Direct Acting Operation) or a Zoning
Bypass Damper Actuator (Reverse Acting Operation).
The Duct Static Pressure Control Output Signal is a non-configurable
Direct Acting Signal (0-10 VDC). This Output Signal can be used to directly connect to a Supply Fan VFD. The Output Signal increases
(Increases VFD Speed) if the Duct Static Pressure is below the Duct
Static Pressure Setpoint by the Deadband amount and the Output Signal decreases (Decreases VFD Speed) if the Static Pressure is above the
Setpoint by the Deadband amount.
If the Supply Fan control is not configured for Duct Static Pressure
Control, you can still monitor the Duct Static Pressure if the Duct Static
Pressure Sensor is installed, however no control will occur.
Building Pressure Control
The VCM can maintain Building Static Pressure anytime the Supply
Fan is operating by activating a Constant Volume Exhaust Fan, a VFD
Exhaust Fan, Modulating Exhaust Damper or by modulating the Outdoor Air Damper. A Building Pressure Transducer must be connected to the VCM’s Analog Input Expansion Board. For Constant Volume Exhaust Fan applications, only an Exhaust Fan Relay needs to be configured for on/off operation of the Exhaust Fan. VFD or Modulating Building Pressure control must be configured in order to operate. An Exhaust Fan Relay can also be configured along with Modulating Building Pressure control for an Enable output. Building Pressure can be maintained by either Direct or Reverse Acting control.
Direct Acting
If configured, a VFD Exhaust Fan or Modulating Exhaust Damper will be controlled by varying a 0-10 or 2-10 VDC control signal on the analog output of the optional Analog Input Expansion Board. If an enable output is required, an Exhaust Fan Relay can also be configured.
The Exhaust Fan Relay and the Modulating Signal will activate when the Building Static Pressure rises above the Building Static Pressure
Setpoint plus the Deadband. The Exhaust Fan Relay will remain active until the Building Static Pressure falls below the Building Static Pressure Setpoint minus the Deadband and the Modulating Signal falls to
0%.
VCM Controller
43
Technical Guide
Sequence Of Operations
On/Off Control
If you do not require a Modulating Control Signal, you can also configure one of the Relay Outputs as an Exhaust Fan Relay to activate whenever the Building Static Pressure is above the Building Static Pressure
Setpoint plus the Deadband. The Exhaust Fan Relay will deactivate when the Building Static Pressure falls below the Building Static Pressure Setpoint minus the Deadband. Only one Relay Output should be configured for this operation. There is no staging of additional Exhaust
Fan Relays.
When the Outdoor Air Temperature is below the Cooling Lockout
Setpoint, no Mechanical Cooling can operate. However, if the unit is equipped with an Economizer and the VCM is configured to use the
Economizer, it can be used to provide free Cooling when the Mechanical Cooling is locked out. For Air to Air Heat Pumps the Cooling lockout also applies to Compressor Heating, which means it usually will be a lower setting than on Cooling units that are not Air to Air Heat Pumps.
Reverse Acting
If configured, on a drop in building static pressure below the building pressure setpoint minus the deadband, the AOUT 1 terminal on the
Analog Input Expansion Board will modulate the 2-10 VDC signal to open the outside air damper. When this option is selected, no economizer free cooling or IAQ operation will be available.
IAQ (CO
2
) Operation
If you have configured the VCM Controller to monitor and control CO
2 levels, the Economizer operation will be modified as follows:
The Outdoor Air Heating Lockout operates so that when the Outdoor
Air Temperature is above the Outdoor Air Heating Lockout Setpoints, no Mechanical Heating can operate. This applies to any type of Heating except Compressor Heating as used on Air to Air Heat Pumps. The lockout for Compressor Heating is explained in the previous paragraph regarding Cooling Lockout Setpoints.
Supply Air Cutoffs
The Supply Air Temperature Cutoffs are designed to prevent extremely
High and Low temperature Supply Air from entering the building.
High Supply Air Temperature Cutoff
High Supply Air Temperature Cutoff is initiated when the Supply Air
Temperature rises above the HI SAT Cutoff Setpoint. When this occurs, Heating stages will be deactivated until the Supply Air Temperature falls 5 °F below the HI SAT Cutoff Setpoint.
1.
The Maximum Reset Position the Economizer can open to is determined by a user adjustable setpoint called the CO
2
Protection Limit Max. Level.
2.
The Minimum Position the Economizer can close down to is Reset higher as the level of CO
2
increases above the CO
Protection Limit Max Level programmed by the user. As
2 the CO
2
level increases above the adjustable CO
2
Setpoint, the Outdoor Air Damper will start opening beyond its
Minimum Position. At the CO
2
Protection Limit Reset
Range above Setpoint, the Economizer will be held to its
Maximum Reset Position and not allowed to open any further.
Pre-heater Operation
In colder climates where freezing temperatures are sometimes experienced, it is desirable to preheat the Outdoor Air being drawn into the
HVAC unit before it reaches the Water Coils to prevent freezing. The
Pre-heater control option is available by setting a Low Ambient Protection Setpoint and by configuring one of the relay outputs as a Pre-Heater.
Only one relay can be configured for this option and therefore staging of Pre-heater relays is not available.
The Pre-heater sequence operates so that anytime the Outdoor Air Temperature is below the Low Ambient Protection Setpoint and the Supply
Fan is running, the Pre-heater Relay will activate. It will remain on until the Outdoor Air Temperature rises 1°F above the Setpoint or the
Supply Fan shuts down. If the Proof Of Flow option is installed and configured, its signal must also be active for the Pre-Heater Relay to activate. This output will operate during any HVAC Mode that exists.
Outdoor Air Lockouts
The Outdoor Air Cooling and Heating Lockouts Setpoints are designed to prevent unwanted Mechanical Heating or Cooling operation during certain Outdoor Ambient Temperature conditions.
Low Supply Air Temperature Cutoff
Low Supply Air Temperature Cutoff is initiated when the Supply Air
Temperature falls below the LO SAT Cutoff Setpoint. If the VCM is in
Economizer Operation, Vent Mode or Heating Mode and the Supply
Air Temperature falls below the LO SAT Cutoff Setpoint for 10 minutes, it is assumed a Mechanical Failure has occurred and all Heating will be deactivated, the Supply Air Fan will shut off and the Outdoor
Air Dampers will close. If the VCM is in the Cooling or Dehumidification Mode and the Supply Air Temperature falls below the LO SAT
Cutoff Setpoint, the Cooling Signal or Cooling Stages will immediately begin deactivating. To restore normal operation, one of the following three things must occur:
1.
The Supply Air Temperature rises above the LO SAT
Cutoff Setpoint by 5 °F
2.
The VCM goes from Occupied to Unoccupied or
Unoccupied to Occupied Mode.
3.
The VCM’s power is cycled.
Scheduling
The VCM Controller has an internal power source for the Real Time
Clock (RTC) that allows the controller to keep the time and accurately control scheduling. It can also broadcast the time to the VAV/Zone Controllers if that option is configured.
The VCM Controller has an Internal 7 day Schedule with 2 Start/Stop
Events per day. You can also have 1 Holiday Schedule with 2 Start/Stop
Events per day. This Holiday Schedule can be used for 14 different
Holiday periods.
44
VCM Controller
Technical Guide
You can change the time on the VCM Controller through the Modular
Service Tool or the System Manager. You can also broadcast the time and date to all VCM controllers by using a Personal Computer and the
PRISM II Computer Front End Software.
The Internal Scheduling in the VCM Controller also includes a Self
Teaching Optimal Start Routine that can be activated by entering a value of 1.0 or greater for the Soak Multiplier Setpoint. The Optimal Start function can only be used if your VCM Controller has a Space Temperature Sensor installed and it is being used as the Controlling Sensor, or you are using WattMaster VAV/Zone controllers with the VCM controller. No adjustments other than the Soak Multiplier are required from the user because the VCM Controller monitors how long it takes to reach the Target Temperature each day and adjusts the Starting Time accordingly. That means the first day you operate your HVAC unit it will not be able to Optimally Start because it does not have a history of previous Starts and their results. After the first day, the VCM Controller will begin adjusting the Start Time, and after six Normally Scheduled
Starts have occurred, the Optimal Start Routine will have gathered enough data to provide an accurate Pre-start based on the learned conditions. This is an ongoing learning process of the six previous starts, so the unit automatically adjusts for the changing seasons. If you don’t need this feature but you are using the Space Temperature Sensor as the
Controlling Sensor, you can set the Soak Multiplier to zero to eliminate the Optimal Start Routines.
Internal Trend Logging
The VCM Controller continuously maintains an Internal Trend Log, which records a fixed set of values at an interval programmed by the user. These values can be retrieved only with the PRISM II Computer
Front End Software. If you do not have a computer with PRISM II
Software installed and connected to the system communications loop, you do not have access to these logs.
Outdoor Air Humidity
Indoor Air Humidity
Duct Static Pressure
Building Static Pressure
Economizer Signal Percentage
Supply Fan VFD/Zoning Bypass Damper Signal Percentage
Exhaust Fan VFD/Exhaust Damper Signal Percentage
Modulating Heat Signal Percentage
Modulating Cool Signal Percentage
On Board Relay Status (BIT Pattern )
Expansion Board Relay Status (BIT Pattern )
These items and values are explained in greater detail in the PRISM II
Computer Front End Software manual.
Force Modes or Overrides
The VCM Controller relay and analog outputs can be user overridden if the Modular Service Tool or the PRISM II Computer Front-end Program is used. The System Manager cannot be used for these Force
Modes. The Modes of operation for the relays are:
0 = Normal Operation
1 = Forced ON
2 = Forced OFF
The Analog Outputs are Forced if the user specifies a value between 0.0
and 10.0 VDC. To cancel the Force Mode, you must enter a value less than 0 such as -1.0 VDC.
There are 120 log positions available. Once the last (120th) position has been recorded, the log jumps back to the first position and begins overwriting the old data. This means the user is required to retrieve the logs at an interval that is shorter than the duration of the last 120 logs.
When the Analog Outputs are Forced, the display on the Modular Service Tool or Prism II program can be interpreted as the actual voltage.
During normal operation, the display indicates the percentage signal applied based on the user defined voltage limits. For example, if the user defines a 2.0 VDC to 10.0 VDC range, then 50% would be 6.0
VDC instead of the 5.0 VDC applied when the range is 0.0 VDC to
10.0 VDC.
Shown below are some log intervals and the duration of 120 logs.
1 Minute Interval = 2 Hours
12 Minute Interval = 24 Hours
15 Minute Interval = 30 Hours
30 Minute Interval = 60 Hours
60 Minute Interval = 120 Hours
The fixed items in the log are listed below:
As previously mentioned, Force Modes can only be activated when using either the Modular Service Tool or the PRISM II Computer Front
End Software. Furthermore, the Override condition can only remain in effect as long as one of these Operator Interface devices is connected and communicating with the VCM. That means that you cannot Force an Override condition and then walk away from the equipment with the
Override still active. The loss of communications, removal or shutdown of the Operator Interface will automatically terminate the Override within
10 minutes. This is to protect the equipment and to prevent an Override condition from remaining active indefinitely resulting in inefficient or dangerous operation of the equipment.
Date
Time
Space Temperature
Return Air Temperature
Outdoor Air Temperature
Active Cooling Setpoint
Active Heating Setpoint
Supply Air Temperature
Active Supply Air Temperature Setpoint
Warning: No equipment protection is available during the
Force Mode of operation. That means you could start a compressor without running the
Supply Fan or create other conditions that
WILL damage the equipment. WattMaster
Controls, Inc. assumes no responsibility or liability for the misuse of these user Overrides that cause damage to the equipment!
VCM Controller
45
Technical Guide
Sequence Of Operations
VAV/Zone Box Compatibility
The VCM Controller is designed to communicate with Orion VAV/Zone
Controllers. The VCM can be configured to broadcast its Internal Schedule, Time and Date, Fan and Heat Status and Supply Air Temperature.
The VCM can also broadcast Force to Max or Force to Fixed Position during Morning Warm-up. The Orion VAV/Zone Controllers broadcast
Push-Button Overrides from Unoccupied to Occupied. They can also generate Unoccupied Heating and Cooling calls to the VCM controller based on Setbacks.
If you are using another manufacturers VAV Box Controllers, the VCM
Controller can activate a relay to inform the VAV/Zone Controllers that the VCM controller is operating in Warm-up Mode. No other information can be passed between the VCM Controller and the other manufacturers VAV Box Controllers. This means that Overrides or Unoccupied
Heating and Cooling calls cannot activate the VCM Controller. If you need any of these capabilities you must use only Orion VAV/Zone controllers for controlling all your VAV Boxes.
VAV/Zone System
When the VCM goes into the Occupied Mode it initiates Morning Warmup if the Return Air Temperature is below the Morning Warm-up Target
Temperature Setpoint. During Morning Warm-up the VAV/Zone Controllers will modulate open if the Space Temperatures are too cold. They can also move to their Maximum Airflow or Fixed Airflow Position
Setpoint if they receive this broadcast from the VCM Controller. Once
Morning Warm-up has been satisfied, the VCM enters the Cooling Mode and the VAV/Zone Controllers will modulate to satisfy their Space Temperature Setpoints. If the Space Temperature falls below the Heating
Setpoint, staged or modulating Reheat can be activated to warm the space.
Communications between the VCM and the VAV/Zone Controllers are handled by the MiniLink Polling Device. Alarm Polling and Tenant
Overrides are also monitored by the MiniLink Polling Device. Tenant
Overrides are overrides generated by the Space Temperature Sensor’s push button. The MiniLink Polling Device records the start and stop times and total run times of the overrides on a daily and monthly basis.
A computer running Prism II Computer Front End Software is required to retrieve all data acquired by the MiniLink Polling Device.
Zoning System
The VCM Controller automatically configures itself for Voting Control when the MiniLink Polling Device is installed and is configured as a
Voting System. The VCM controller sets the HVAC Mode Enable to the Return Air Temperature Sensor as soon as communication is acquired with the MiniLink Polling Device. If the VAV/Zone controllers are configured for Voting, the MiniLink Polling Device totals the Heating and Cooling demands and determines which HVAC Mode the VCM should be in. The MiniLink Polling Device broadcasts a forced Heating, Cooling or Vent Mode of operation to the VCM. Once the VCM receives the broadcast to set the HVAC Mode, it operates as previously described in the VCM Sequence of Operations. If communications are lost, the VCM returns to its own control and will maintain the HVAC
Mode Enable Setpoints by using the Return Air Temperature Sensor as the Controlling Sensor.
46
VCM Controller
Technical Guide
Troubleshooting
Using LEDs To Verify Operation
The VCM controller is equipped with 4 LEDs that can be used as very powerful troubleshooting tools. See Figure 29 for the LED locations.
The LEDs and their uses are as follows:
“COMM”
This LED will light up to indicate system communications.
“PWR”
This LED will light up to indicate that 24 VAC power has been applied to the controller.
“LED1”
This is the diagnostic blink code LED. It will light up and blink out diagnostic codes. LED1 also represents the tens column in the address blink code.
If the address switch setting is correct and the COMM LED still does not behave as indicated above, check to be sure the operators interface is connected correctly. If you are using the System Manager Operators Interface it must be connected to VCM controller as shown in
Figure 31, or anywhere on the local communications loop. If you are using the Modular Service Tool, verify that it is plugged in securely to the DIN connection on the VCM controller. See Figure 31 for DIN connector location.
“LED2”
This is the diagnostic blink code LED. It will light up and blink out diagnostic codes. LED2 also represents the ones column in the address blink code.
If the COMM LED still does not behave correctly, check the voltages at the communications terminal block. Be sure the board is powered up for this test. Unplug the communications terminal block from the board and check the DC voltage between T and SHLD and between R and
SHLD. Check the voltage with a digital multimeter set to DC volts.
The voltage should be between 2.4 to 2.5 VDC between SHLD and either T or R. If your voltage is not in this range, you probably have a damaged driver chip that must be replaced.
PWR LED Operations
When the VCM Controller is powered up the “PWR” LED should light up and stay on continuously. If it does not light up, check to be sure that you have 24 VAC connected to the board, that the wiring connections are tight and that they are wired for the correct polarity. The 24 VAC power must be connected so that all ground wires remain common. If after making all these checks the PWR LED does not light up, please contact WattMaster technical support for assistance.
For driver chip replacement instructions, please see the Orion Controls
System Installation & Troubleshooting Guide for more information or contact the factory for further assistance.
OE331-21-VCM
Controller Board
COMM LED Operations
When power is applied to the controller, the “COMM” LED will also light up. If this is a Stand Alone System (one controller only on the loop) or an Interconnected System (several VCM controllers tied together without a CommLink) the COMM LED will glow continuously.
The COMM LED will flicker when you are connected to the VCM controller and you are entering setpoints with the Modular Service Tool or the System Manager. It will also flicker if this is a Networked System. If this is a Networked System (the system has a CommLink installed) the COMM LED should flicker rapidly indicating that the system is communicating. A “flicker” is defined as a brief moment when the LED turns off then back on. It may be easier to see this “flicker” if you cup your hand around the LED.
Communications Terminals
System Manager Can Be
Connected Here With Pigtail
Cable
(COMM) Communications LED
(PWR) Power LED
(LED1) Diagnostic LED
COMM
T
SHLD
R
COMM
PWR
LED1
LED2
DIN Connector
For Modular
Service Tool
If the COMM LED does not operate as indicated above, first check the address switch setting. Verify the address switch as outlined in the
Diagnostic LEDs Operations section. See Figure: 29 for complete address switch setting instructions.
Note: LED1 represents the tens column and LED2 represents the ones column of the board address. If the address of the board is set to 59 with the address switch, then
LED1 will blink 5 times and then LED2 will blink 9 times.
(LED2) Diagnostic LED
Figure 31: LED Locations & Service Connections
VCM Controller
47
Technical Guide
Appendix
Diagnostic LEDs Operation
When power is first applied, both LEDs will be off for (1) second. At this time both LEDs will blink to indicate the setting of the address switch and then extinguish for 5 seconds. Verify that the address switch setting is correct by counting the number of blinks.
Note: LED1 represents the tens column and LED2 represents the ones column of the board address. If the address of the board is set to 59 with the address switch, then
LED1 will blink 5 times and then LED2 will blink 9 times.
Blink Code Description
Normal Operation
Supply Air Sensor Failure
Outdoor Air Sensor Failure
Space Sensor Failure
Mechanical Cooling Failure
Mechanical Heating Failure
Fan Proving Failure
Dirty Filter Alarm
Smoke Alarm
Low Supply Temperature Alarm
High Supply Temperature Alarm
Control Temp. Cooling Failure
Control Temp. Heating Failure
Push Button Override
Zone Override
Force Outputs Override
LED #1
Number
Of Blinks
3
4
1
2
5
1
2
2
3
0
1
1
2
3
4
0
LED #2
Number
Of Blinks
3
3
3
3
3
4
4
2
2
1
2
5
5
4
4
6
If the address switch is not correct, remove the communication loop terminal plug from the controller and then the power terminal plug. Set the address dip switches correctly. See Figure 29 for correct address switch setting instructions. After you are sure the address switch setting is correct, reconnect the power connection and then the communication loop connection to the board.
Note: Power to the Controller being addressed must always be cycled after changing address switch settings in order for the changes to take effect.
Reapply power to the controller and observe the blink code to verify the address is set correctly. If the LEDs now blink the correct address your board is addressed correctly. If they don’t light up at all, the board is not operating correctly and could be defective. Once the board is done blinking the address then LED2 will blink continuously for 30 seconds while the board calibrates. Once the board is done calibrating the Diagnostic
LEDs will blink a code every 10 seconds to indicate board status. See
Table 2 for a list of the various blink codes and their meaning.
If all of these tests are made and the controller still doesn’t operate, please contact WattMaster Controls Technical Support group. You can reach WattMaster Controls Technical Support at 866-918-1100.
Table 2: LED Blink Code Interpretation
48
VCM Controller
Technical Guide
System Configuration Options
The VCM controller can be used as a Stand Alone System (One VCM
Controller Only), connected together on a Interconnected System (Multiple VCM controllers Only), or connected together on a Network System (Multiple VCM Controllers, VAV/Zone Controllers, or Add -on
Controllers) to form a complete Orion Controls System that can be programmed and monitored with one or more of the available Orion Operator Interfaces.
Interconnected System
The Interconnected system is used when you have multiple VCM controllers on your job. With this system you simply connect the controllers together using WattMaster communications wire or 18 gauge 2 conductor twisted pair with shield wire (Belden #82760 or equivalent). This allows for all controllers that are connected on the communications loop to be programmed and monitored from one or more of the available Operator Interfaces connected on the communications loop.
For detailed information about the various Orion Controls Systems that are available and their related wiring requirements and options, please see the Orion Systems Technical Guide.
Operator Interfaces
The Orion Operator Interfaces are designed to provide for programming and monitoring of VCM controller(s) and/or any VAV/Zone or
Add-on Controller(s) connected to your Orion System. The Operators
Interfaces available for use with the Orion Systems are:
•
Modular Service Tool
•
Modular System Manager
•
Tactio SI - Touch Screen Interface
•
Personal Computer with Prism II Computer Front End
Software Installed
You can use any one of these interfaces or all of them on the same Orion
System.
Stand Alone System
The Stand Alone system is used when you have a single VCM controller only. Programming and status monitoring are accomplished by selecting and installing one or more of the Operator Interfaces.
See Figure 33 for a Typical Interconnected System Layout diagram.
Networked System
If you have 1 to 59 VCM controllers that require information sharing , simply connect the controllers together using WattMaster communications wire or 18 gauge 2 conductor twisted pair with shield wire (Belden
#82760 or equivalent). The Networked Single Loop system requires that either a MiniLink PD communication interface or a CommLink communication interface or both are purchased and wired into the communications loop in a similar manner to the VCM controllers.
The Networked Multiple Loop system is used when you have more than 59 VCM controllers and/or are using multiple VCM controllers that are connected to VAV/Zone controllers. These groups of controllers are broken up into multiple “Local Loops” which connect to each other via the “Network Loop”. Each individual MiniLink PD handles its specific local loop’s communications requirements. The CommLink communications interface handles all the communications between the individual MiniLink PDs to form the network loop. Up to 60 local loops can connected together with this configuration. This provides the capability for over 3500 controllers to be networked together.
See Figure 34 for a Typical Networked System Layout diagram.
See Figure 32 for a Typical Stand Alone System Layout diagram.
VCM Controller
49
Appendix
Technical Guide
Tactio
SI
Operator
Interfaces
Figure 32: Typical Stand Alone System Layout
50
VCM Controller
Technical Guide
Ta ct io
SI
VCM Controller
51
Appendix
Technical Guide
52
Ta ctio
SI
VCM Controller
Technical Guide
10 kOhm Type III Temperature Sensor
Testing
The following sensor voltage and resistance tables are provided to aid in checking sensors that appear to be operating incorrectly. Many system operating problems can be traced to incorrect sensor wiring. Be sure all sensors are wired per the wiring diagrams in this manual.
If the sensors still do not appear to be operating or reading correctly, check voltage and/or resistance to confirm that the sensor is operating correctly per the tables. Please follow the notes and instructions below each chart when checking sensors.
Temp
(
º
F)
35
40
45
20
25
30
50
52
54
56
58
-10
-5
0
5
10
15
Temperature – Resistance – Voltage For Type III 10 K Ohm Thermistor Sensors
Resistance
(Ohms)
Voltage @
Input (VDC)
Temp
(
º
F)
Resistance
(Ohms)
Voltage @
Input (VDC)
Temp
(
º
F)
Resistance
(Ohms)
93333
80531
69822
60552
52500
45902
40147
35165
30805
27140
23874
21094
18655
17799
16956
16164
15385
4.620
4.550
4.474
4.390
4.297
4.200
4.095
3.982
3.862
3.737
3.605
3.470
3.330
3.275
3.217
3.160
3.100
73
74
75
70
71
72
76
78
80
82
84
66
68
69
60
62
64
14681
14014
13382
12758
12191
11906
11652
11379
11136
10878
10625
10398
10158
9711
9302
8893
8514
3.042
2.985
2.927
2.867
2.810
2.780
2.752
2.722
2.695
2.665
2.635
2.607
2.577
2.520
2.465
2.407
2.352
110
115
120
125
130
135
86
88
90
95
100
105
140
145
150
4923
4449
4030
3656
3317
3015
8153
7805
7472
6716
6047
5453
2743
2502
2288
Voltage @
Input (VDC)
2.297
2.242
2.187
2.055
1.927
1.805
1.687
1.575
1.469
1.369
1.274
1.185
1.101
1.024
0.952
Thermistor Sensor Testing Instructions
Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).
nus) lead on GND terminal and the “+”(plus) lead on the sensor input terminal being investigated.
Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts. Place the “-”(mi-
If the voltage is above 5.08 VDC, then the sensor or wiring is “open.”
If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.
VCM Controller
53
Appendix
Technical Guide
OE265 RH Sensor Testing
The chart below is used to troubleshoot the OE265 Relative Humidity
Sensors.
Humidity
Percentage
(RH)
16%
18%
20%
22%
24%
0%
2%
4%
6%
8%
10%
12%
14%
OE265 Relative Humidity Transmitters – Humidity vs. Voltage For 0-5 VDC Sensors
Voltage
@
Input
(VDC)
Humidity
Percentage
(RH)
Voltage
@
Input
(VDC)
Humidity
Percentage
(RH)
Voltage
@
Input
(VDC)
Humidity
Percentage
(RH)
0.80
0.90
1.00
1.10
1.20
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
42%
44%
46%
48%
50%
26%
28%
30%
32%
34%
36%
38%
40%
2.10
2.20
2.30
2.40
2.50
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
68%
70%
72%
74%
76%
52%
54%
56%
58%
60%
62%
64%
66%
3.40
3.50
3.60
3.70
3.80
2.60
2.70
2.80
2.90
3.00
3.10
3.20
3.30
78%
80%
82%
84%
86%
88%
90%
92%
94%
96%
98%
100%
OE265-03 Relative Humidity Sensor
Testing Instructions:
Use the voltage column to check the Humidity Sensor while connected to a powered expansion board. Read voltage with meter set on DC volts.
Place the “-”(minus) lead on terminal labeled GND and the “+” lead on the AIN terminal that the Humidity sensor is connected to on the Analog Input/Output Expansion Board.
Voltage
@
Input
(VDC)
3.90
4.00
4.10
4.20
4.30
4.40
4.50
4.60
4.70
4.80
4.90
5.00
54
VCM Controller
Technical Guide
OE271 Pressure Sensor Testing
The table below is used to troubleshoot the OE271 Duct Static Pressure Sensors.
OE258 Pressure Sensor Testing
The table below is used to troubleshoot the OE258 Building Pressure
Sensors.
OE271 Duct Static Pressure Sensor
Pressure
@
Sensor
(“ W.C.)
0.90
1.00
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
2.10
2.20
2.30
2.40
2.50
Voltage
@
Input
(VDC)
0.25
0.33
0.41
0.49
0.57
0.65
0.73
0.81
0.89
0.97
1.05
1.13
1.21
1.29
1.37
1.45
1.53
1.61
1.69
1.77
1.85
1.93
2.01
2.09
2.17
2.25
Pressure
@
Sensor
(“ W.C.)
2.60
2.70
2.80
2.90
3.00
3.10
3.20
3.30
3.40
3.50
3.60
3.70
3.80
3.90
4.00
4.10
4.20
4.30
4.40
4.50
4.60
4.70
4.80
4.90
5.00
Voltage
@
Input
(VDC)
3.05
3.13
3.21
3.29
3.37
3.45
3.53
3.61
3.69
3.77
3.85
3.93
2.33
2.41
2.49
2.57
2.65
2.73
2.81
2.89
2.97
4.01
4.09
4.17
4.25
OE271 Pressure Sensor Testing Instructions
Use the voltage column to check the Duct Static Pressure Sensor while connected to powered controllers. Read voltage with meter set on DC volts. Place the “-”(minus) lead on GND terminal and the “+”(plus) lead on the 0-5 pin terminal on (JP1) with the jumper removed. Be sure to replace the jumper after checking.
OE258 Building Pressure Sensor
Pressure
@
Sensor
(“ W.C.)
-0.16
-0.15
-0.14
-0.13
-0.12
-0.11
-0.10
-0.09
-0.08
-0.07
-0.06
-0.05
-0.25
-0.24
-0.23
-0.22
-0.21
-0.20
-0.19
-0.18
-0.17
-0.04
-0.03
-0.02
-0.01
0.00
Voltage
@
Input
(VDC)
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
2.10
2.20
2.30
2.40
2.50
Pressure
@
Sensor
(“ W.C.)
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.15
0.16
0.17
0.18
0.19
0.20
0.21
0.22
0.23
0.24
0.25
Voltage
@
Input
(VDC)
3.50
3.60
3.70
3.80
3.90
4.00
4.10
4.20
4.30
4.40
4.50
4.60
2.60
2.70
2.80
2.90
3.00
3.10
3.20
3.30
3.40
4.70
4.80
4.90
5.00
OE258 Building Pressure Sensor Testing Instructions
Use the voltage column to check the Building Static Pressure Sensor while connected to a powered expansion board. Read voltage with meter set on DC volts. Place the “-”(minus) lead on terminal labeled GND and the “+” lead on terminal AIN4 on the Analog Input/Output Expansion Board.
VCM Controller
55
Technical Guide
Appendix
OE275 Suction Pressure Transducer
Testing
The Evaporator Coil Temperature is calculated by converting the Suction Pressure to Temperature. The Suction Pressure is obtained by using the OE275 Suction Pressure Transducer which is connected into the
Suction Line of the Compressor. See the OE275 Suction Pressure Transducer, Pressure, Temperature and Voltage Chart. The chart shows a tem-
OE275 Suction Pressure Transducer
Coil Pressure – Temperature – Voltage Chart
52.52
53.70
54.89
56.25
57.61
58.98
60.34
61.70
63.06
43.03
44.21
45.40
46.59
47.77
48.96
50.14
51.33
64.42
65.78
67.14
68.51
70.06
71.61
73.16
74.71
76.26
77.82
79.37
80.92
82.47
84.02
1.34
1.36
1.38
1.40
1.43
1.45
1.47
1.49
1.51
1.19
1.21
1.23
1.25
1.27
1.29
1.31
1.32
1.53
1.56
1.58
1.60
1.63
1.65
1.68
1.70
1.73
1.75
1.77
1.80
1.82
1.85
32
33
34
35
36
28
29
30
31
24
25
26
27
20
21
22
23
41
42
43
44
37
38
39
40
45
46
47
48
49
50
OE275 Suction Pressure Transducer Testing
Use the voltage column to check the Suction Pressure Transducer while connected to the VCM Controller. The VCM Controller must be powered for this test. Read voltage with a meter set on DC volts. Place the negative lead from the meter on a ground (GND) terminal located on the VCM’s 12-pin terminal block. Place the positive lead from the meter on the AIN5 terminal located on the VCM’s 12-pin terminal block.
63
64
65
66
67
59
60
61
62
55
56
57
58
51
52
53
54
72
73
74
75
68
69
70
71
76
77
78
79
80
99.86
101.62
103.60
105.58
107.56
109.54
111.52
113.50
115.48
85.79
87.54
89.30
91.06
92.82
94.58
96.34
98.10
117.46
119.44
121.43
123.65
125.87
128.09
130.31
132.53
134.75
136.97
139.19
141.41
143.63
2.10
2.13
2.16
2.20
2.23
2.26
2.29
2.32
2.35
1.88
1.91
1.93
1.96
1.99
2.02
2.05
2.08
2.39
2.42
2.45
2.49
2.52
2.56
2.59
2.63
2.66
2.70
2.74
2.77
2.81
56
VCM Controller
Notes:
Technical Guide
VCM Controller
57
Notes:
Technical Guide
58
VCM Controller
Notes:
Technical Guide
VCM Controller
59
AAON, Inc.
Form: AA-VCM-TGD-01A Printed in the USA November 2005
All rights reserved
WattMaster Controls Inc.
•
8500 NW River Park Drive
•
Copyright 2005
Parkville, Mo.
•
64152
Phone (816) 505-1100 www.orioncontrols.com
Fax (816) 505-1101
2425 So. Yukon Ave • Tulsa, OK 74107-2728
Ph: (918) 583-2266 • Fax: (918) 583-6094
AAON ® Part No. R38200
Atsisiųsti