YASKAWA VS mini CIMR-J7B0P7 Instruction manual
विज्ञापन
विज्ञापन
VS mini J7 Series
Instruction Manual
COMPACT GENERAL-PURPOSE INVERTER
(VOLTAGE VECTOR CONTROL)
2
PREFACE
YASKAWA’s VS mini J7 is a compact and simple inverter that is as easy to use as a contactor. This instruction manual describes installation, maintenance, inspection, troubleshooting, and specifications of the
VS mini J7. Read this instruction manual thoroughly before operation.
YASKAWA ELECTRIC CORPORATION
General Precautions
• Some drawings in this manual are shown with the protective covers and shields removed, in order to illustrate detail with more clarity. Make sure all covers and shields are replaced before operating this product.
• This manual may be modified when necessary to reflect improvements to the product, or changes in specifications.
Such modifications are denoted by a revised manual No.
• To order a copy of this manual, contact your YASKAWA representative.
• YASKAWA is not responsible for any modification of the product made by the user. Any modifications will void the warranty.
CONTENTS
NOTES FOR SAFE OPERATION. . . . . . . . . . . . . . . . . . . . . 5
1. RECEIVING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
• Checking the Name Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2. IDENTIFYING THE PARTS . . . . . . . . . . . . . . . . . . . . . . 13
3. SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
• Standard Specifications (200V Class) . . . . . . . . . . . . . . . . . . 15
• Standard Specifications (400V Class) . . . . . . . . . . . . . . . . . . 18
• Standard Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
• Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
• Parameters List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4. MOUNTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
• Choosing a Location to Mount the Inverter . . . . . . . . . . . . . . 35
• Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
• Mounting/Removing Components . . . . . . . . . . . . . . . . . . . . . 37
5. WIRING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
• Wiring Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
• Wire and Terminal Screw Sizes . . . . . . . . . . . . . . . . . . . . . . 39
• Wiring the Main Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
• Recommended Peripheral Devices . . . . . . . . . . . . . . . . . . . . 43
• Wiring the Control Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
• Wiring Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
6. OPERATING THE INVERTER . . . . . . . . . . . . . . . . . . . . 47
• Test Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
• Operating the Digital Operator. . . . . . . . . . . . . . . . . . . . . . . . 49
• LED Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
• Simple Data Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
3
7. PROGRAMMING FEATURES . . . . . . . . . . . . . . . . . . . . 57
• Parameter Set-up and Initialization . . . . . . . . . . . . . . . . . . . . 57
• Setting V/f pattern . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
• Switching LOCAL/REMOTE Modes . . . . . . . . . . . . . . . . . . . 61
• Selecting Run/Stop Commands. . . . . . . . . . . . . . . . . . . . . . . 62
• Selecting Frequency Reference . . . . . . . . . . . . . . . . . . . . . . 63
• Setting Operation Condition . . . . . . . . . . . . . . . . . . . . . . . . . 65
• Selecting Stopping Method . . . . . . . . . . . . . . . . . . . . . . . . . . 82
• Building Interface Circuits with External Devices. . . . . . . . . . 84
• Setting Frequency by Current Reference Input . . . . . . . . . . . 89
• Decreasing Motor Speed Fluctuation . . . . . . . . . . . . . . . . . . 93
• Motor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
• Selecting Cooling Fan Operation. . . . . . . . . . . . . . . . . . . . . . 96
• Using MEMOBUS (MODBUS) Communications
(when option card is installed). . . . . . . . . . . . . . . . . . . . . . . 96
8. MAINTENANCE AND INSPECTION . . . . . . . . . . . . . . . 99
• Periodical Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
• Part Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
9. FAULT DIAGNOSIS AND CORRECTIVE ACTIONS. . 103
APPENDIX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
• CE Conformance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
4
NOTES FOR SAFE OPERATION
Read this instruction manual thoroughly before installation, operation, maintenance or inspection of the VS mini. In this manual, NOTES FOR SAFE OPERATION are classified as “WARNING” or “CAUTION”.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury to personnel.
CAUTION
Indicates a potentially hazardous situation which, may result in minor or moderate injury to personnel, and possible damage to equipment if not avoided. It may also be used to alert against unsafe practices.
Items described in CAUTION may also result in a vital accident in some situations. In either case, follow these important notes.
These are steps to be taken to ensure proper operation.
RECEIVING
CAUTION
(Ref. page)
• Do not install or operate any inverter which is damaged or has missing parts.
Failure to observe this caution may result in personal injury or equipment damage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5
6
MOUNTING
CAUTION
(Ref. page)
• Lift the inverter by the cooling fin. When moving the unit, never lift by the plastic case or the terminal covers.
Failure to observe this caution may cause the unit to be dropped resulting in damage to the unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
• Mount the inverter on nonflammable material (i.e., metal).
Failure to observe this caution can result in a fire. . . . . . . . . . . . . . . . . . . . . . . 13
• When mounting open chassis in an enclosure, install a fan or other cooling device to keep the intake air temperature below 122
°
F (50
°
C).
Overheating may cause a fire or damage to the unit. . . . . . . . . . . . . . . . . . . . . 35
• The VS mini J7 generates heat. For effective cooling, mount it vertically.
Refer to the figure in “Mounting Dimensions” on page 16.
WIRING
WARNING
(Ref. page)
• Start wiring only after verifying that the power supply is turned OFF for at least one minute, and all LED’s and change LED’s are extinguished.
Failure to observe this warning can result in electric shock or fire. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
• Wiring should be performed only by qualified personnel.
Failure to observe this warning can result in electric shock or fire. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
• When wiring the emergency stop circuit, check the wiring thoroughly before operation.
Failure to observe this warning can result in personal injury. . . . . . . . . . . . . . 39
WARNING
(Ref. page)
• For 400V class, make sure to ground the supply neutral.
• Make sure to ground the ground terminal according to the local ground code.
Failure to observe this warning can result in electric shock or fire. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
CAUTION
(Ref. page)
• Verify that the inverter rated voltage coincides with the
AC power supply voltage.
Failure to observe this caution can result in personal injury or fire.
• Do not perform a withstand voltage test of the inverter.
It may cause semi-conductor elements to be damaged.
• Make sure to tighten terminal screws of the main circuit and the control circuit.
Failure to observe this caution can result in a malfunction, damage or a fire. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
• Never connect the AC main circuit power supply to output terminals U, V and W.
The inverter will be damaged and void the warranty. . . . . . . . . . . . . . . . . . . . 42
• Do not connect or disconnect wires or connectors while power is applied to the circuit.
Failure to observe this caution can result in personal injury.
• Do not change signal/control wiring during operation.
The machine or the inverter may be damaged.
7
8
OPERATION
WARNING
(Ref. page)
• Only turn ON the input power supply after replacing the digital operator or optional blank cover.
Do not remove the digital operator or the covers while current is flowing.
Failure to observe this warning can result in electric shock.
• Never operate the digital operator or dip switches when your hand is wet.
Failure to observe this warning can result in electric shock.
• Never touch the terminals while current is flowing, even when the inverter is stopped.
Failure to observe this warning can result in electric shock.
• When the fault retry function is selected, stand clear of the inverter or the load. It may restart unexpectedly after being stopped.
(Construct machine system, so as to assure safety for personnel, even if the inverter should restart.) Failure to observe this warning can result in personal injury.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
• When continuous operation after power recovery is selected, stand clear of the inverter or the load. It may restart unexpectedly after being stopped.
(Construct machine system, so as to assure safety for personnel, even if the inverter should restart.) Failure to observe this warning can result in personal injury.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
• Since the digital operator stop button can be disabled by a parameter setting, install a separate external emergency stop switch.
Failure to observe this warning can result in personal injury.
• If an alarm is reset with the operation signal ON, the inverter restarts automatically. Only reset the alarm after verifying that the operation signal is OFF.
Failure to observe this warning can result in personal injury. . . . . . . . . . . . . . 46
CAUTION
(Ref. page)
• Never touch the heatsink or braking resistor, the temperature is very high.
Failure to observe this caution can result in harmful burns to the body.
• Since it is easy to change operation speed from low to high speed, verify the safe working range of the motor and machine before operation.
Failure to observe this caution can result in personal injury and machine damage.
• Install a holding brake separately if necessary.
Failure to observe this caution can result in personal injury.
• Do not change signals during operation.
The machine or the inverter may be damaged.
• All the parameters of the inverter have been preset at the factory. Do not change the settings unnecessarily.
The inverter may be damaged. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
MAINTENANCE AND INSPECTION
WARNING
(Ref. page)
• Never touch high-voltage terminals in the inverter.
Failure to observe this warning can result in an electrical shock. . . . . . . . . . . 99
• Disconnect all power before performing maintenance or inspection. Then wait at least one minute after the power supply is disconnected and all LEDs and CHARGE LED are extinguished.
The capacitors discharge slowly, and may be dangerous. . . . . . . . . . . . . . . . . 99
9
WARNING
(Ref. page)
• Do not perform a voltage withstand test on any part of the VS mini J7.
This electronic equipment uses semiconductors and it is vulnerable to high voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
• Only authorized personnel should perform maintenance, inspections or parts replacement.
[Remove all metal objects (watches, bracelets, etc.) before operation.]
(Use tools which are insulated against electrical shock.)
Failure to observe this warning can result in an electrical shock. . . . . . . . . . . 99
CAUTION
(Ref. page)
• The control PC board employs CMOS ICs.
Do not touch the CMOS elements.
They are easily damaged by static electricity.
• Do not connect or disconnect wires, digital operator, connectors, or cooling fan while power is applied to the circuit.
Failure to observe this caution can result in personal injury. . . . . . . . . . . . . . . 99
Others
WARNING
• Never modify the product.
Failure to observe this warning can result in an electrical shock or personal injury and will void the warranty.
(Ref. page)
10
WARNING LABEL
A warning label is displayed on the front cover of the inverter, as shown below. Follow these instructions when handling the inverter.
PLASTIC ENCLOSURE
NAME-
PLATE
STATUS
INDICATOR
LAMP
WARNING
LABEL
Warning Label
•
•
•
Read manual before installing.
disconnecting power supply.
To conform to CE requirements make sure to ground the supply neutral for 400V class.
11
1. RECEIVING
After unpacking the VS mini J7, check the following:
• Verify that the part numbers match your purchase order or packing slip.
• Check the unit for physical damage that may have occurred during shipping.
If any part of VS mini J7 is missing or damaged, call for service immediately.
• Checking the Nameplate
U.S. and Canadian Safety Standards for Types of 3-phase, 200VAC,
0.13HP (0.1kW)
Example of 3-phase, 220VAC, 0.13 (0.1kW)
12
2. IDENTIFYING THE PARTS
13
Notes
14
3. Specifications
• Standard Specifications (200V Class)
Model
Voltage Class
CIMR-J7AU!!!!
3-phase
Single-phase
Max. Applicable Motor Output HP (kW)†
200V single- / 3-phase
20P1 20P2 20P4 20P7 21P5 22P2
B0P1 B0P2 B0P4 B0P7 B1P5
0.13
(0.1)
0.3
0.25
(0.2)
0.6
0.5
(0.4)
1.1
1
(0.75)
1.9
2
(1.5)
3.0
-
3
(2.2)
4.2
23P7
-
5
(3.7)
6.7
Inverter Capacity (kVA)
Rated Output Current (A)
Max. Output Voltage (V)
(3-phase output only)
0.8
1.6
3 5 8 11 17.5
3-phase models, 200 to 230V (proportional to input voltage)
Single-phase models, 200 to 240V (proportional to input voltage)
Max. Output Frequency (Hz) 400 Hz (Programmable)
Rated Input Voltage and
Frequency
3-phase, 200 to 230V, 50/60Hz
Single-phase, 200 to 240V, 50/60Hz
Allowable Voltage Fluctuation -15 to +10%
Allowable Frequency Fluctuation
±
5%
Control Method Sine wave PWM (V/f control)
Frequency Control Range
Frequency Accuracy
(Temperature Change)
Frequency Setting Resolution
0.1 to 400Hz
Digital reference:
±
0.01% (-10 to +50
°
C)
Analog reference:
±
0.5% (25
±
10
°
C)
Digital reference: 0.1Hz (less than 100Hz) / 1Hz (100Hz or more)
Analog reference: 1 / 1000 of max. output frequency
Output Frequency Resolution 0.01Hz
Overload Capacity
Frequency Reference Signal
150% rated output current for one minute
0 to 10VDC (20k
Ω
), 4 to 20mA (250
Ω
), 0 to 20mA (250
Ω
)
Frequency setting volume (Selectable)
Accel/Decel Time
Braking Torque
V/f Characteristics
0.1 to 999sec.
(accel/decel time are independently programmed)
Short-term average deceleration torque‡
0.13HP, 0.25HP (0.1, 0.25kW): 150%
0.5HP, 1HP (0.55, 1.1kW): 100%
2HP (1.5kW): 50%
3HP (2.2kW) or more: 20%
Continuous regenerative torque: Approx. 20%
Possible to program any V/f pattern
† Based on a standard 4-pole motor for max. applicable motor output.
‡ Shows deceleration torque for uncoupled motor decelerating from 60Hz with the shortest possible deceleration time.
15
Model
Voltage Class
3-phase
CIMR-J7AU!!!!
Single-phase
Motor Overload Protection
Instantaneous Overcurrent
Overload
Overvoltage
Undervoltage
Momentary Power Loss
Cooling Fin Overheat
Stall Prevention Level
Cooling Fan Fault
Ground Fault
Power Charge Indication
Multi-function Input
Multi-function Output
Standard Functions
200V single- / 3-phase
20P1 20P2 20P4 20P7 21P5 22P2
B0P1 B0P2 B0P4 B0P7 B1P5 -
23P7
-
Electronic thermal overload relay
Motor coasts to a stop at approx. 200% of inverter rated current
Motor coasts to a stop after 1 minute at 150% of inverter rated output current
Motor coasts to a stop if DC bus voltage exceed 410V
Stops when DC bus voltage is approx. 200V or less (approx.
160V or less for single-phase series)
Following items are selectable: Not provided (stops if power loss is 15ms or longer), continuous operation if power loss is approx. 0.5s or shorter, continuous operation
Protected by electronic circuit
Individual levels during accel/running, enable/disable provided during deceleration
Protected by electronic circuit (fan stalling detection)
Protected by electronic circuit (rated output current level)
RUN lamp stays ON or digital operator LED stays ON.
(Charge LED is provided for 400V)
ON until the DC bus voltage becomes 50V or less.
Four of the following input signals are selectable: Reverse run
(3-wire sequence), fault reset, external fault (NO/NC contact input), multi-step speed operation, Jog command, accel/decel time select, external baseblock (NO/NC contact input), speed search command, accel/decel hold command, LOCAL/
REMOTE selection, communication/control circuit terminal selection, emergency stop fault emergency stop alarm
Following output signals are selectable (1 NO/NC contact output):
Fault, running, zero speed, at frequency, frequency detection
(output frequency
≤
or
≥
set value), during over torque detection, minor error, during baseblock, operation mode, inverter run ready, during fault retry, during UV, during speed search, during speed search, data output through communication
Full-range automatic torque boost, slip compensation, DC injection braking current/time at start/stop frequency reference bias/gain, [MEMOBUS communications (RS-485/422, max.
19.2K bps).]
16
Model
Voltage Class
3-phase
CIMR-J7AU!!!!
Single-phase
Cooling Method
Ambient Temperature
Humidity
Storage Temperature†
Location
Elevation
200V single- / 3-phase
20P1 20P2 20P4 20P7 21P5 22P2
B0P1 B0P2 B0P4 B0P7 B1P5 -
23P7
-
Status Indicator LED RUN and ALARM provided as standard LED’s
Digital Operator
(JVOP-140)
Available to monitor frequency reference, output frequency, output current. 3 character, 7 segment LED Display.
Terminals
Main circuit: screw terminals
Control circuit: plug-in screw terminal
Wiring Distance between
Inverter and Motor
Enclosure
328ft (100m) or less‡
Open chassis
Cooling fan is provided for 200V, 0.75kW (3-phase), 400V,
1.5kW (single-phase), others are self-cooling
Open chassis: -10 to +50
°
C (14 to 122
°
F)
(not frozen)
95% RH or less (non-condensing)
-4 to 140
°
F (-20 to +60
°
C)
Indoor (free from corrosive gases or dust)
3280ft (1000m) or less
Vibration
Up to 9.8m / S
2
(1G) at less than 20Hz, up to 2m / S
2
(0.2G) at less than 20 to 50Hz
†Temperature during shipping (for short period)
‡ If the wiring distance between inverter and motor is long, reduce the inverter carrier frequency.
For details, refer to “Reducing motor noise or leakage current (n46)”on page 79.
17
• Standard Specifications (400V Class)
Voltage Class
Model
CIMR-J7A!!!!
3-phase
400V 3-phase
40P2 40P4 40P7 41P5 42P2 43P7
Max. Applicable Motor Output HP (kW)*
Inverter Capacity (kVA)
Rated Output Current (A)
Max. Output Voltage (V)
Max. Output
Frequency (Hz)
Rated Input Voltage and Frequency
Allowable Voltage
Fluctuation
Allowable Frequency
Fluctuation
Control Method
Frequency Control Range
0.25
(0.2)
0.5
(0.4)
1
(0.75)
2
(1.5)
3
(2.2)
5
(3.7)
0.9
1.2
1.4
1.8
2.6
3.4
3.7
4.8
4.2
5.5
6.5
8.6
3-phase, 380 to 460V (proportional to input voltage)
400 Hz (Programmable)
3-phase, 380 to 460V, 50/60Hz
-15 to +10%
±
5%
Frequency Accuracy
(Temperature Change)
Frequency Setting Resolution
Sine wave PWM (V/f control)
0.1 to 400Hz
Digital reference:
±
0.01%, 14 to 122
°
F (-10 to
+50
°
C)
Analog reference:
±
0.5%, 59 to 95
°
F (25
±
10
°
C)
Digital reference: 0.1Hz (less than 100Hz) / 1Hz
(100Hz or more)
Analog reference: 1 / 1000 of max. output frequency
Output Frequency
Resolution
Overload Capacity
Frequency Reference
Signal
Accel/Decel Time
Braking Torque
V/f Characteristics
0.01Hz
150% rated output current for one minute
0 to 10VDC (20k
Ω
), 4 to 20mA (250
Ω
), 0 to 20mA
(250
Ω
) Frequency setting volume (Selectable)
0.1 to 999 sec. (accel/decel time are independently programmed)
Short-term average deceleration torque†
0.2kW: 150%
0.75kW: 100%
2HP (1.5kW): 50%
3HP (2.2kW) or more: 20%
Continuous regenerative torque: Approx. 20%
Possible to program any V / f pattern
* Based on a standard 4-pole motor for max. applicable motor output.
† Shows deceleration torque for uncoupled motor decelerating from 60Hz with the shortest possible deceleration time.
18
Model
Voltage Class
CIMR-J7A!!!!
3-phase
Motor Overload Protection
Instantaneous Over Current
Overload
Over Voltage
Under Voltage
Momentary Power Loss
Cooling Fin Overheat
Stall Prevention Level
Cooling Fan Fault
Ground Fault
Power Charge Indication
Multi-function Input
Multi-function Output
Standard Functions
40P2 40P4
400V 3-phase
40P7 41P5 42P2 43P7
Electronic thermal overload relay
Motor coasts to a stop at approx. 200% of inverter rated current
Motor coasts to a stop after 1 minute at 150% of inverter rated output current
Motor coasts to a stop if DC bus voltage exceed
820V
Stops when DC bus voltage is approx. 400V or less
Following items are selectable: Not provided (stops if power loss is 15ms or longer), continuous operation if power loss is approx. 0.5s or shorter, continuous operation
Protected by electronic circuit
Individual levels during accel/running, enable/disable provided during deceleration.
Protected by electronic circuit (fan stalling detection)
Protected by electronic circuit (rated output current level)
Charge LED is provided
On until the DC bus voltage becomes 50V or less.
Four of the following input signals are selectable:
Reverse run (3-wire sequence), fault reset, external fault (NO/NC contact input), multi-step speed operation, Jog command, accel/decel time select, external baseblock (NO/NC contact input), speed search command, accel/decel hold command,
LOCAL/REMOTE selection, communication/control circuit terminal selection, emergency stop fault, emergency stop alarm
Following output signals are selectable (1 NO/NC contact output,):
Fault, running, zero speed, at frequency, frequency detection (output frequency
≤
or
≥
set value), during over torque detection, during under voltage detection, minor error, during baseblock, operation mode, inverter run ready, during fault retry, during
UV, during speed search, data output through communication
Full-range automatic torque boost, slip compensation, DC injection braking current/time at start/stop frequency reference bias/gain, frequency reference with built-in volume, [MEMOBUS communications (RS-485/422, max. 19.2K).]
19
Voltage Class
Model
CIMR-J7A!!!!
3-phase 40P2 40P4
400V 3-phase
40P7 41P5 42P2 43P7
Status Indicator LED RUN and ALARM provided as standard LEDs
Digital Operator
Terminals
Available to monitor frequency reference, output frequency, output current. 3 character, 7 segment
LED display.
Main circuit: screw terminals
Control circuit: plug-in screw terminal
Wiring Distance between
Inverter and Motor
328ft (100m) or less†
Enclosure
Cooling Method
Ambient Temperature
Humidity
Storage Temperature*
Location
Elevation
Vibration
Open chassis or enclosed wall-mounted
Cooling fan is provided for 200V, 0.75kW (3-/single phase), 200V, 0.75kW (1.5HP), others are selfcooling
Open chassis: -10 to +50
°
C (14 to 122
°
F)
(not frozen)
95% RH or less (non-condensing)
-20 to 60
°
F (-4 to +140
°
C)
Indoor (free from corrosive gases or dust)
3280ft (1000m) or less
Up to 9.8m / S
2
(1G) at less than 20Hz, up to 2m / S
2
(0.2G) at less than 20 to 50Hz
* Temperature during shipping (for short period)
† If the wiring distance between inverter and motor is long, reduce the inverter carrier
frequency.
For details, refer to “Reducing motor noise or leakage current (n46)” on page 79.
20
• Standard Wiring
21
Terminal Description
Type Terminal Name Function (Signal Level)
R/L1,
S/L2,
T/L3
AC power supply input
Use main circuit power input (for single-phase inverter,
R/L1, S/L2).
Even thought T/L3 is available, do not use the terminal for other purposes such as relay terminal.
U/T1,
V/T2,
W/T3
Inverter output Inverter output
+2, +1
+1, (–)
DC reactor connection
DC power supply input
Grounding
When connecting optional DC reactor, remove the main circuit short-circuit bar between +2 and +1.
DC power supply input (+1: positive, –: negative)
*
Grounding 200V: grounding to 100
Ω
or less
400V: grounding to 10
Ω
or less
S1 Forward run input
S2 Multi-function input selection 2
S3
S4
Multi-function input selection 3
Multi-function input selection 4
Closed: FWD run
Factory setting closed: REV run
Factory setting: Fault reset
Factory setting: External fault (N.O. contact)
Photocoupler insulation
24VDC,
8mA.
S5 Multi-function input selection 5
Factory setting: Multi-step speed reference 1
SC Multi-function input selection common Control signal common
FS Power for frequency setting +12V (permissible current 20mA max.)
FR Master speed frequency reference 0 to +10DC (20k
Ω
) or 4 to 20mA (250
Ω
) or 20mA (250
Ω
) (1/1000 resolution)
FC Frequency reference common 0V
MA NO contact output
MB
MC
NC contact output
Contact output common
Form C contact
Factory setting: running
Contact capability
250VAC 1A or less,
30VDC 1A or less
AM
AC
Analog monitor output
Analog monitor common
Factory setting:
Output frequency 0 to +10VDC
0V
* DC power supply input terminal is not available on CE/UL standards.
0 to+10VDC, 2mA or less,
8-bit resolution
22
• Dimensions
23
Dimensions in inches (mm)/mass in lb (kg)
Voltage class
200V
3-phase
200V singlephase
400V
3-phase
Capacity
HP (kW)
W H D W1 H1 H2
0.13 (0.1) 2.68 (68) 5.04 (128) 2.76 (70) 2.20 (56) 4.65 (118) 0.20 (5)
Mass
0.25 (0.2) 2.68 (68) 5.04 (128) 2.76 (70) 2.20 (56) 4.65 (118) 0.20 (5)
0.5 (0.4) 2.68 (68) 5.04 (128) 4.02(102) 2.20 (56) 4.65 (118) 0.20 (5)
1 (0.75) 2.68 (68) 5.04 (128) 4.80(122) 2.20 (56) 4.65 (118) 0.20 (5)
2 (1.5) 4.25 (108) 5.04 (128) 5.08 (129) 3.78 (96) 4.65 (118) 0.20 (5)
3 (2.2) 4.25 (108) 5.04 (128) 6.06 (154) 3.78 (96) 4.65 (118) 0.20 (5)
M 4
M 4
M 4
M 4
M 4
1.32 (0.6)
1.98 (0.9)
2.43 (1.1)
3.09 (1.4)
3.31 (1.5)
5 (3.7) 5.51 (140) 5.04 (128) 6.34 (161) 5.04(128) 4.65 (118) 0.20 (5)
0.13 (0.1) 2.68 (68) 5.04 (128) 2.76 (70) 2.20 (56) 4.65 (118) 0.20 (5)
0.25 (0.2) 2.68 (68) 5.04 (128) 2.76 (70) 2.20 (56) 4.65 (118) 0.20 (5)
0.5 (0.4) 2.68 (68) 5.04 (128) 4.41 (112) 2.20 (56) 4.65 (118) 0.20 (5)
1 (0.75) 4.25 (108) 5.04 (128) 5.08 (129) 3.78 (96) 4.65 (118) 0.20 (5)
2 (1.5) 4.25 (108) 5.04 (128) 6.06 (154) 3.78 (96) 4.65 (118) 0.20 (5)
0.25 (0.2) 4.25 (108) 5.04 (128) 3.19 (81) 3.78 (96) 4.65 (118) 0.20 (5)
0.5 (0.4) 4.25 (108) 5.04 (128) 3.90 (99) 3.78 (96) 4.65 (118) 0.20 (5)
1 (0.75) 4.25 (108) 5.04 (128) 5.08 (129) 3.78 (96) 4.65 (118) 0.20 (5)
2 (1.5) 4.25 (108) 5.04 (128) 6.06 (154) 3.78 (96) 4.65 (118) 0.20 (5)
3 (2.2) 4.25 (108) 5.04 (128) 6.06 (154) 3.78 (96) 4.65 (118) 0.20 (5)
5 (3.7) 5.51 (140) 5.04 (128) 6.34 (161) 5.04(128) 4.65 (118) 0.20 (5) d
M 4 1.32 (0.6)
M 4
M 4
M 4
M 4
M 4
M 4
M 4
M 4
M 4
M 4
M 4
M 4
4.63 (2.1)
1.32 (0.6)
1.54 (0.7)
2.20 (1.0)
3.31 (1.5)
3.31 (1.5)
2.20 (1.0)
2.43 (1.1)
3.31 (1.5)
3.31 (1.5)
3.31 (1.5)
4.63 (2.1)
Fig.
2
2
2
2
1
2
2
2
2
2
1
1
1
2
2
1
1
1
24
• Parameters List
First Functions (Parameters n001 to n049)
No.
Register
No. for
Transmission
Name Description
01
02
03
04
05
06
07
08
0101H
0102H
0103H
0104H
0105H
0106H
0107H
0108H
Parameter write-in prohibit / initialize
Operation reference selection
Frequency reference selection
Stopping method selection
REV run prohibit
Operation stop key selection
0: Parameter n001 set / read and parameter n02 ~ n79 can be read.
(FREF of the operator can be set.)
1: Functions (parameters n01 ~ n79) can be set / read.
6: Clear fault history
8: 2 wire initialize
(Japanese Specification)
9: 3 wire initialize
(Japanese Specification)
10: 2 wire initialize
(American Specification)
11: 3 wire initialize
(American Specification)
0: Operator
1: Control circuit terminal
2: Communication
0: Volume
1: Frequency reference 1 (n21)
2: Control circuit terminal
(voltage 0 ~ 10V)
3: Control circuit terminal
(current 4 - 20 mA)
4: Control circuit terminal
(current 0 - 20 mA)
5: Not used (setting error)
6: Communication
(register number 0002H)
0: Decel to stop
1: Coast to stop
0: Reverse run enabled
1: Reverser run disabled
0: Stop key enabled
1: Stop key is enabled only when run command is selected to the operator.
Frequency reference selection in local mode
0: Volume
1: Frequency reference selection (n21)
0: Frequency reference setting by the operator is enabled with the ENTER key input Setting method selection for frequency reference 1: Frequency reference setting by the operator is not required the ENTER key input.
Initial
Setting
1
1
2
0
0
0
0 (Note4)
0
*User
Setting
Ref.
Page
57
62
63
82
65
81
63
63
25
No.
Register
No. for
Transmission
Name Description
Initial
Setting
09 0109H
Maximum output frequency
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 50.0 ~ 400Hz
Setting unit: 1V
Setting range: 1 ~ 255V
60.0Hz
230V (Note 1) 10 010AH Maximum voltage
11
12
010BH
010CH
Maximum voltage output frequency
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.2 ~ 400Hz
Mid. output frequency
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.1 ~ 399Hz
13
14
15
16
010DH
010EH
010FH
0110H
Mid. output frequency
Minimum output frequency
Mid. output frequency voltage
Acceleration time 1
Setting unit: 1V
Setting range: 1 - 255V
Setting unit: 0.1Hz
Setting range: 0.1 ~ 10.0Hz
Setting unit: 1V
Setting range: 1 ~ 50V
Setting unit: 0.1s (less than 100s) / 1s
(100s or greater)
Setting range: 0.0 ~ 999s
17
18
0111H
0112H
Deceleration time 1
Acceleration time 2
Setting unit: 0.1s (less than 100s) / 1s
(100s or greater)
Setting range: 0.0 ~ 999s
Setting unit: 0.1s (less than 100s) / 1s
(100s or greater)
Setting range: 0.0 ~ 999s
19
20
0113H
0114H
Deceleration time 2
S-curve accel / decel selection
Setting unit: 0.1s (less than 100s) / 1s
(100s or greater)
Setting range: 0.0 ~ 999s
0: No S-curves
1: 0.2s
2: 0.5s
3: 1.0s
21
22
0115H
0116H
Frequency reference 1
(Master speed frequency reference)
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.0 ~ 400Hz
Frequency reference 2
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.0 ~ 400Hz
23 0117H Frequency reference 3
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.0 ~ 400Hz
60.0Hz
1.5Hz
12V (Note1)
1.5Hz
12V (Note1)
10.0s
10.0s
10.0s
10.0s
0
0.0Hz
0.0Hz
0.0Hz
*User
Setting
Ref.
Page
58
58
58
58
58
58
58
69
69
69
69
72
65
65
65
26
No.
Register
No. for
Transmission
Name Description
24
25
26
27
28
0118H
0119H
011AH
011BH
011CH
Frequency reference 4
Frequency reference 5
Frequency reference 6
Frequency reference 7
Frequency reference 8
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.0 ~ 400Hz
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.0 ~ 400Hz
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.0 ~ 400Hz
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.0 ~ 400Hz
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.0 ~ 400Hz
29
30
31
011DH
011EH
011FH
Jog frequency reference
Frequency reference upper limit
Frequency reference lower limit
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.0 ~ 400Hz
Setting unit: 1%
Setting range: 0 ~ 110%
Setting unit: 1%
Setting range: 0 ~ 110%
32
33
0120H
0121H
Motor rated current
Setting unit: 0.1A
Setting range: 0 ~ 120% of inverter rated output current
Note: if set to 0%, then electronic thermal motor overload is disabled.
Electronic thermal motor protection
0: Standard motor application
1: Specialized motor application
2: No electronic motor overload protection
Initial
Setting
0.0Hz
0.0Hz
0.0Hz
0.0Hz
0.0Hz
6.00Hz
100%
0%
(Note 2)
0
*User
Setting
Ref.
Page
65
65
65
65
65
66
69
69
94
94
27
No.
Register
No. for
Transmission
34
35
36
37
38
39
0122H
0123H
0124H
0125H
0126H
0127H
Name Description
Parameter selection at electronic thermal motor protection
Cooling fan operation selection
Multi-function input selection 2
Multi-function input selection 3
Setting unit: 1min
Setting range: 1 ~ 60min
0: Controls the cooling fan OFF / ON
1: Operates when power is ON.
1: Not used
2: Reverse run reference (2 wire sequence)
3: External fault (N. O. contact input)
4: External fault (N. C. contact input)
5: Fault reset
6: Multi speed reference 1
8: Multi speed reference 2
7: Multi speed reference 3
9: Not used
10: Jog reference
11: Accel / decel time switching reference
12: External baseblock reference
(N. O. contact input)
13: External baseblock reference
(N. C. contact input)
14: Speed search command from Max. output frequency
15: Speed search command set frequency
16: Accel / decel hold
17: Local / remote switching
18: Communication / control circuit terminal switching
19: Emergency stop fault
(N. O. contact input)
20: Emergency stop alarm
(N. O. contact input)
21: Emergency stop fault
(N. C. contact input)
22: Emergency stop alarm
(N. C. contact input)
23~ 33: Unused
0: Forward / reverse command
(3 wire sequence)
Others are the same as parameter 36
Multi-function input selection 4
Same as parameter 36
Multi-function input selection 5
Same as parameter 36
34: Up/down reference
35: Self-test
(Note: valid power ON / OFF)
Initial
Setting
*User
Setting
Ref.
Page
8 min
0
2
5
3
6
94
96
82
84
84
84
28
No.
40 0128H
Multi-function output selection
41
Register
No. for
Transmission
0129H
42 012AH
43 012BH
Name
Analog frequency reference gain
Analog frequency reference bias
Analog frequency reference filter time parameter
Description
Initial
Setting
*User
Setting
Ref.
Page
0: Fault
1: During run
2: Frequency agree
3: During zero speed
4: Frequency detection
(detection level or greater)
5: Frequency detection
(detection level or less)
6: During over torque detection
(N. O. contact output)
7: During over torque detection
(N. C. contact output)
8: Not used
9: Not used
10: Minor fault (during warning display)
11: During baseblock
12: Run mode
13: Inverter ready
14: During fault retry
15: During UV
16: During reverse run
17: During speed search
18: Data output through communication
Setting unit: 1%
Setting range: 0 - 255%
Setting unit: 1%
Setting range: –99 ~ 99%
Setting unit: 0.01s
Setting range: 0.00 ~ 2.00s
(Note)
When 0.00s is set, there is no filter
1
100%
0%
0.10s
87
67
67
-
29
No.
Register
No. for
Transmission
Name
44
45
012CH
012DH
Monitor item selection
Monitor gain
0: Output frequency
1: Output current
Setting unit: 0.01
Setting range: 0.01 ~ 2.00
46
47
48
012EH
012FH
0130H
Carrier frequency
Fault reset
Set value: 1 ~ 4 carrier frequency = set value ¥ 2.5kHz
Set value: Synchronous type of 7 ~ 9 lower limit 1kHz and upper limit 2.5 kHz
Operation selection after momentary power loss
0: Operation does not continue.
1: Operation continues within momentary power ride through time
2: Operation always continues. (No
UV1 fault detection)
Setting unit: time
Setting range: 0 ~ 10 times
49
50
51
52
53
54
55
56
0131H
0132H
0133H
0134H
0135H
0136H
0137H
0138H
Jump frequency 1
Jump frequency 2
Jump frequency width
Stall prevention (current limit) during decel
Stall prevention (current limit) during accel
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.00 ~ 400Hz
(Note) If 0.0Hz is set, jump frequency 1 is enabled.
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.00 ~ 400Hz
(Note) If 0.0Hz is set, jump frequency 2 is disabled.
Setting unit: 0.1Hz
Setting range: 0.0 ~ 25.5Hz
(Note) If 0.0Hz is set, jump frequencies
1 ~ 2 are disabled.
DC injection braking current
Setting unit: 1%
Setting range: 0 ~ 100%
(note) If 0% is set, it becomes baseblock status.
DC injection braking time at stop
Setting unit: 0.1s
Setting range: 0.0 ~ 25.5s
(Note) If 0.0s is set, this function will no operate.
DC injection braking time at start
Setting unit: 0.1s
Setting range: 0.0 ~ 25.5s
(Note) If 0.0s is set, this function will not operate.
0: Stall prevention function is enabled during deceleration.
1: Stall prevention function is disabled during deceleration.
Setting unit: 1%
Setting range: 30 ~ 200%
(Note): If set at 200%, this function will not operate.
(Note): For rated output range, the operator level is automatically reduced.
Initial
Setting
0
1.00
4(Note 3)
0
0 time
0.0Hz
0.0Hz
0.0Hz
50%
0.0s
0.0s
0
170%
User
Setting
Ref.
Page
78
78
79
70
75
75
75
75
76
83
76
92
91
30
No.
Register
No. for
Transmission
Name
57
58
0139H
013AH
Stall prevention (current limit) during running
Frequency detection level
Setting unit: 1%
Setting range: 30 ~ 200%
(Note): If set at 200%, this function will not operate.
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.00 ~ 400Hz
59
60
61
013BH
013CH
013DH
Overtorque detection
Overtorque detection level
Overtorque detection time
0: Overtorque detection disabled.
1: Detects only at speed agree, operation continues after detection.
2: Detects only at speed agree, output is shut down after detection.
3: Detects during run, operation continued after detection.
4: Detects during run, output is shut down after detection.
Setting unit: 1%
Setting range: 30 ~ 200%
Setting unit: 0.1s
Setting range: 0.1 ~ 10.0s
62
63
64
013EH
013FH
0140H
Memory selection of hold output frequency
0: Hold output frequency is not stored.
1: Hold output frequency is stored.
Torque compensation gain
Motor rated slip
Setting unit: 0.1
Setting range: 0.0 ~ 2.5
Setting unit: 0.1Hz
Setting range: 0.0 ~ 20.0Hz
65
66
67
68
69
0141H
0142H
0143H
0144H
0145H
Motor no-load current
Slip compensation gain
Slip compensation primary delay time
Timeover detection selection
Setting unit selection of communications frequency reference/ frequency monitor
Setting unit: 1%
Setting range: 0 ~ 99%
Setting unit: 0.1
Setting range: 0.0 ~ 2.5
Setting unit: 0.1s
Setting range: 0.0 ~ 25.5s
0: Timeover detection enabled. (Coast to stop)
1: Timeover detection enabled.
(Deceleration stop by deceleration time 1)
2: Timeover detection enabled.
(Deceleration stop by deceleration time 2)
3: Timeover detection enabled.
(Operation continues, alarm displays)
4: Timeover detection disabled.
0: 0.1Hz / 1
1: 0.01Hz / 1
2: 100% / 30000
3: 0.1% / 1
Initial
Setting
160%
0.0Hz
0
160%
0.1s
0
1.0
(Note 2)
(Note 2)
1.0
2.0s
0
0
User
Setting
Ref.
Page
92
74
73
73
73
86
60
-
-
-
-
93
93
31
No.
Register
No. for
Transmission
Name
70 0146H Slave address
71 0147H Baud rate selection
72 0148H Parity selection
73 0149H Send waiting time
74 014AH RTS control
75
76
77
78 014EH Fault history
79 014FH Software No.
Initial
Setting
User
Setting
Ref.
Page
Setting unit: 1
Setting range: 0 ~ 32
0: 2400 bps
1: 4800 bps
2: 9600 bps
3: 19200 bps
0: Even parity
1: Odd parity
2: No parity
Setting unit: 1 = 1ms
Setting range: 10 ~ 65 ms
0: RTS control enabled.
1: RTS control disabled.
–
0: Execution completed / execution command receive condition
1: READ execute
2: COPY execute
3: VRFY execute
4: kVA display
5: Software No. display
0: READ prohibited.
1: READ allowed.
The 1 newest event is displayed
(Note) Setting is disabled.
Lower 3 digits of software numbers are displayed.
(Note): Setting is disabled.
0
2
0
10ms
0
-
-
-
-
-
-
-
-
54
1. Upper limit of setting range and initial setting are doubled at 400 class.
2. Changes depending on inverter capacity. Refer to the next page.
3. Initial setting of the model with digital operator (without volume) is 1.
Setting can be set to 0 by parameter initialization.
32
• KVA Dependant Parameter Default Settings
200V class 3-phase
No.
–
Name
Inverter capacity n32 Motor rated current n64 Motor rated slip n65
Motor no-load current
Unit kW
A
Hz
%
Factory setting
0.1kW
0.2kW
0.4kW 0.75kW 1.5kW
2.2kW
0.6
1.1
1.9
3.3
6.2
8.5
2.5
2.6
2.9
2.5
2.6
2.9
72 73 62 55 45 35
–
–
–
–
3.7kW
14.1
3.3
32
200V class single-phase
No.
n65
Name
– Inverter capacity n32 Motor rated current n64 Motor rated slip
Motor no-load current
Unit kW
A
Hz
%
Factory setting
0.1kW
0.2kW
0.4kW 0.75kW 1.5kW
2.2kW
0.6
1.1
1.9
3.3
6.2
8.5
2.5
2.6
2.9
2.5
2.6
2.9
72 73 62 55 45 35
–
–
–
–
3.7kW
14.1
3.3
32
400V class 3-phase
No.
–
Name
Inverter capacity n32 Motor rated current n64 Motor rated slip n65
Motor no-load current
Unit kW
A
Hz
%
–
–
–
–
Factory setting
0.2kW
0.4kW 0.75kW 1.5kW
2.2kW
0.6
2.5
1.0
2.7
1.6
2.6
3.1
2.5
4.2
3.0
73 63 52 45 35
–
7.0
3.2
33
3.7kW
7.0
3.2
33
33
Notes
34
4. MOUNTING
• Choosing a Location to Mount the Inverter
Be sure the inverter is protected from the following conditions:
• Extreme cold and heat. Use only within the ambient temperature range (for open chassis type): 14 to 122
°
F (-10 to +50
°
C)
• Rain, moisture.
• Oil sprays, splashes.
• Salt spray.
• Direct sunlight. (Avoid using outdoors).
• Corrosive gases (e.g. sulfurized gas) or liquids.
• Dust or metallic particles in the air.
• Physical shock, vibration.
• Magnetic noise. (Example: welding machines, power devices, etc.)
• High humidity.
• Radioactive substances.
• Combustibles: thinner, solvents, etc.
35
• Mounting Dimensions
Clearances as shown below are required when mounting the VS mini.
36
• Mounting/Removing Components
Removing and Mounting Digital Operator and Covers
• Removing front cover
Use a screwdriver to loosen the screw on the front cover surface to direction 1 to remove it. Then press the right and left sides to direction 2 and lift the front cover to direction 3.
• Mounting front cover
Insert the tab of the upper part of the front cover into the groove of the inverter. Press the lower part of front cover onto the plastic case until the cover snaps shut.
Tighten the screws.
• Removing option cover
After removing front cover, remove the option cover to direction 2 with section A as a supporting point.
• Mounting option cover
Mount the terminal cover in the reverse order of the above removal procedure.
• Removing upper/bottom covers
After removing front cover, lift the top and bottom covers to direction 1.
• Mounting upper/bottom covers
Mount the front cover in the reverse order of the above removal procedure.
37
Notes
38
5. WIRING
• Wiring Instructions
(1) Always connect the power supply via a molded-case circuit breaker (MCCB) to the power input terminals R/L1, S/L2, and T/L3 (R/L1, S/L2 for single-phase). Never connect the power supply to U/T1, V/T2, W/T3,-,+1 or +2.
The single-phase (200V class) inverter can be connected to a 200V 3-phase input.
However, when a single-phase supply is used, never use the terminal T/L3 for other purposes.
Inverter Power Supply Connection Terminals
200V 3-phase Input Power Supply
Specification Product
CIMR-J7!!2!!!
Connect to R/L1, S/L2, T/L3
200V Single Input Power Supply
Specification Product.
CIMR-J7!!B!!!
Connect to R/L1, S/L2
400V 3-phase Input Power Supply
Specification Product.
CIMR-J7!!4!!!
Connect to R/L1, S/L2, T/L3
(2) Connect the motor wiring to terminals U, V, and W on the main circuit output side
(bottom of the inverter).
(3) If the wiring distance between inverter and motor is long, reduce the inverter carrier frequency. For details, refer to “Reducing motor noise or leakage current
(n46)” on page 79.
(4) Control wiring must be less than 164ft(50m) in length and separate from the power wiring. Use twisted-pair shielded wire when inputting the frequency signal externally.
(5) Tighten the screws on the main circuit and control circuit terminals.
(6) Do not connect or disconnect wiring, or perform signal checks while the power supply is turned ON.
• Wire and Terminal Screw Sizes
1. Control Circuit
Model
Common to all models
Terminal Symbol
MA, MB, MC
S1 to
S5,SC,FS,FR,FC,AM,AC
Screw
M3
M2
Wire
Tightening
Torque lb • in (N • m)
Applicable size
4.44 to 5.33
(0.5 to 0.6)
1.94 to 2.21
(0.22 to 0.25) mm
2 twisted wire 0.5 to 1.25
single 0.5 to 1.25
twisted wire 0.5 to 0.75
single 0.5 to 1.25
AWG
20 to 16
20 to 16
20 to 18
20 to 16
Recommend size mm
2 AWG
Type
0.75
18 Shielded
0.75
18 wire or equivalent
39
2. Main Circuit
200V Class 3-phase Input Series
Model
CIMR-J7*U20P1
Terminal Symbol
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3
Screw
M3.5
Tightening
Torque lb • in
(N • m)
7.1 to 8.88
(0.8 to 1.0)
Applicable size mm
2
Recommended
AWG mm
2 size
AWG
0.75 to 2
18 to
14
2
Wire
14
CIMR-J7*U20P2
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3
M3.5
7.1 to 8.88
(0.8 to 1.0)
0.75 to 2
18 to
14
2
CIMR-J7*U20P4
CIMR-J7*U20P7
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3
M3.5
M3.5
7.1 to 8.88
(0.8 to 1.0)
7.1 to 8.88
(0.8 to 1.0)
0.75 to 2
0.75 to 2
18 to
14
18 to
14
2
2
CIMR-J7*U21P5
CIMR-J7*U22P2
R/L1,S/L2,-,+1,+2,U/T1,V/T2,W/T3
R/L1,S/L2,-,+1,+2,U/T1,V/T2,W/T3
M3.5
M3.5
7.1 to 8.88
(0.8 to 1.0)
7.1 to 8.88
(0.8 to 1.0)
2 to 5.5
2 to 5.5
14 to
10
14 to
10
2
3.5
CIMR-J7*U23P7
R/L1,S/L2,-,+1,+2,U/T1,V/T2,W/T3
M4
10.7 to 13.3
(1.2 to 1.5)
2 to 5.5
14 to
10
5.5
Note: The wire size indicated is for copper wires at 160
°
F (75
°
C)
14
14
14
14
14
10
Type
600V vinylsheathed wire or equivalent
200V Class Single-phase Input Series
Model Terminal Symbol Screw
Tightening
Torque lb • in
(N • m)
Wire
Applicable size mm
2
Recommended
AWG mm
2 size
AWG
Type
CIMR-J7*UB0P1
CIMR-J7*UB0P2
CIMR-J7*UB0P4
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3
M3.5
M3.5
M3.5
7.1 to 8.88
(0.8 to 1.0)
7.1 to 8.88
(0.8 to 1.0)
7.1 to 8.88
(0.8 to 1.0)
0.75 to 2
0.75 to 2
0.75 to 2
18 to
14
18 to
14
18 to
14
2
2
2
14
14
14
CIMR-J7*UB0P7
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3
M4
7.1 to 8.88
(0.8 to 1.0)
2 to 5.5
14 to10
3.5
2
12
14
CIMR-J7*UB1P5
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3
M4
7.1 to 8.88
(0.8 to 1.0)
2 to 5.5
14 to
10
5.5
2
Note: The wire size indicated is for copper wires at 160
°
F (75
°
C)
10
14
Note: Three-phase input is also acceptable for single-phase input series.
600V vinylsheathed wire or equivalent
40
400V Class 3-phase Input Series
Model
CIMR-J7*U40P2
Terminal Symbol
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3
Screw
M3.5
Tightening
Torque lb • in
(N • m)
7.1 to 8.88
(0.8 to 1.0)
Applicable size mm
2
Recommended
AWG mm
2 size
AWG
2 to 5.5
14 to
10
2
Wire
14
CIMR-J7*U40P4
CIMR-J7*U40P7
CIMR-J7*U41P5
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3
M3.5
M3.5
M3.5
7.1 to 8.88
(0.8 to 1.0)
7.1 to 8.88
(0.8 to 1.0)
7.1 to 8.88
(0.8 to 1.0)
2 to 5.5
2 to 5.5
2 to 5.5
14 to
10
14 to
10
14 to
10
2
2
2
CIMR-J7*U42P2
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3
M4
10.65 to 13.31
(1.2 to 1.5)
2 to 5.5
14 to
10
2
CIMR-J7*U43P0
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3
M4
10.65 to 13.31
(1.2 to 1.5)
2 to 5.5
14 to
10
2
3.5
CIMR-J7*U43P7
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3
M4
10.65 to 13.31
(1.2 to 1.5)
2 to 5.5
14 to
10
2
3.5
Note: The wire size indicated is for copper wires at 160
°
F (75
°
C)
14
14
14
14
14
12
14
12
Type
600V vinylsheathed wire or equivalent
41
• Wiring the Main Circuit
(Example of 3-phase,
200V class, 1.5kW
inverters)
• Main Circuit Input Power Supply
Connect the power supply wiring to input terminals L1 (R), L2(S) and L3(T) [L1(R),
L2(S) for single-phase inverters]. Never connect them to U/T1, V/T2, W/T3, -, +1, or +2. Otherwise the inverter may be damaged. Single-phase voltage may be connected to inverter but do not use terminal T/L3 for any other purposes.
When several VS mini J7 units are used side by side, ground each unit as shown in examples. Do not loop the ground wires.
On Single-phase models, terminal
T/L3 is connected internally within the inverter. Never use the terminal for other purposes.
• Grounding (Use ground terminal .)
Make sure to ground the ground terminal according to the local grounding code.
Never ground the VS mini J7 to welding machines, motors, or other electrical equipment.
• Wiring the Main Circuit Terminals
Pass the cables through wiring hole and connect. Be sure to mount the cover in its original position.
Connect with a Phillips (plus) screwdriver.
42
• Recommended Peripheral Devices
It is recommended that the following periheral devices be mounted between the AC main circuit power supply and VS mini J7 input terminals R/L1, S/L2, and T/L3.
• MCCB (Molded-case circuit breaker):
A circuit breaker should be connected for wiring protection.
• Magnetic contactor:
Mount a surge suppressor on the coil (refer to the table shown below).
To assure optimum inverter life when using a magnetic contactor to start and stop
the inverter, do not exceed one stop per hour.
Recommended MCCB and magnetic contactor
• 200V 3-Phase
VS mini J7 model J7 * *
20P1
Capacity (kVA) 0.3
0.8
Rated Output Current (A)
MCCB type NF30
(MITSUBISHI)
5A
Magnetic contactor type HI
(YASKAWA CONTROL)
HI-7E
J7 * *
20P2
0.6
1.6
5A
HI-7E
J7 * *
20P4
1.1
3
5A
HI-7E
J7 * *
20P7
1.9
5
10A
HI-7E
J7 * *
21P5
3.0
8
20A
HI-10-2E
J7 * *
22P2
4.2
11
20A
HI-10-2E
J7 * *
23P7
6.7
17.5
30A
HI-20E
• 200V single-Phase
VS mini J7 model
Capacity (kVA)
Rated Output Current (A)
MCCB type NF30, NF50
(MITSUBISHI)
Magnetic contactor type HI
(YASKAWA CONTROL)
J7 * *
B0P1
0.3
0.8
5A
HI-7E
J7 * *
B0P2
0.6
1.6
5A
HI-7E
J7 * *
B0P4
1.1
3
10A
HI-7E
J7 * *
B0P7
1.9
5
20A
HI-10-2E
J7 * *
B1P5
3.0
8
20A
HI-15E
• 400V 3-Phase
VS mini J7 model
Capacity (kVA)
Rated Output Current (A)
MCCB type NF30, NF50
(MITSUBISHI)
Magnetic contactor type HI
(YASKAWA CONTROL)
J7 * *
40P1
0.9
1.2
5A
HI-7E
J7 * *
40P2
1.4
1.8
5A
HI-7E
J7**
40P4
2.6
3.4
5A
J7 * *
41P5
3.7
4.8
10A
J7 * *
42P2
4.2
5.5
10A
J7 * *
43P7
7.0
9.2
20A
HI-7E HI-10-2E HI-10-2E HI-10-2E
43
Surge suppressors
Surge Suppressors Model
DCR2Coils and relays
Large size magnetic contactors
200V to
230V
Control relays
MY-2, -3 (OMRON)
HH-22, -23 (FUJI)
MM-2. -4 (OMRON)
50A22E
10A25C
Specifications
250VAC
0.5µF 200
Ω
250VAC
0.1µF 100
Ω
Code No.
C002417
C002482
• Ground fault interrupter:
Select a ground fault interrupter not affected by high frequencies. To prevent malfunctions, the leakage current sensitivity should be 200mA or more and the operating time 0.1 sec. or more.
Example: " NV series by Mitsubishi Electric Co., Ltd. (manufactured in 1988 and after).
" EGSG series by Fuji Electric Co., Ltd.(manufactured in 1984 and after).
• AC and DC reactor:
Install an AC reactor to connect to a power supply transformer of large capacity
(600kVA or more) or to improve power factor on the power supply side.
• Noise filter:
Use a noise filter exclusively for inverter if radio noise generated from the inverter causes other control devices to malfunction.
NOTE: (1) Never connect a general LC/RC noise filter to the inverter output circuit.
(2) Do not connect a phase advancing capacitor to the I/O sides and/or a surge suppressor to the output side.
(3) When a magnetic contactor is installed between the inverter and the motor, do not turn it ON/Off during operation.
For the details of the peripheral devices, refer to the catalog.
44
• Wiring the Control Circuit
Only basic insulation is provided for the control circuit terminals.
Additional insulation may be necessary in the end product.
• Control Circuit terminals
Pass the cable through wiring hole and connect. Be sure to mount all the covers in the original position.
* SW7 can be changed according to sequence input signal (S1 to S5) polarity.
0V common: NPN side (factory setting)
24 common: PNP side
Refer to pages 89 for SW8
Wiring the control circuit terminals
Screwdriver blade width
Insert the wire into the lower part of the terminal block and connect it tightly with a screwdriver.
Wire sheath strip length must be 0.22 in. (5.5mm).
45
Open the front cover and verify that the strip length is 0.22 in. (5.5mm)
• Wiring Inspection
After completing wiring, check the following:
• Wiring is properly connected.
• Wire clippings or screws are not left inside the unit.
• Screws are securely tightened.
• Bare wires in the terminal do not come in contact with other terminals.
If the FWD (REV) run command is given during the operation reference selection (n02=1) from the control circuit terminal, the motor will start automatically after the main circuit input power supply is turned ON.
46
6. OPERATING THE INVERTER
• Test Run
The inverter operates by setting the frequency (speed).
There are three types of operation modes for the VS mini J7:
1. Run command from the digital operator (local potentiometer/digital setting).
2. Run command from the control circuit terminal.
3. Run command from communications (MEMOBUS).
(Communication option card is required)
Prior to shipping, the drive is set up to receive run command and frequency reference from the control circuit terminal. Following are instructions for running the VS mini J7 using the digital operator (with volume). For instructions on operation, refer to page
47.
Operation reference or frequency reference parameters can be selected separately as shown below.
Name
Operation Reference
Selection
Frequency Reference
Selection
Parameter n02 = 0 --- Enables operator RUN, STOP/RESET
= 1 --- Enables control circuit terminal run/stop
= 2 --- Enables communications (MEMOBUS) n03 = 0 --- Enables operator volume
= 1 --- Enables frequency reference 1 (parameter 24)
= 2 --- Enables voltage reference (0 to 10V) of control circuit terminal
= 3 --- Enables current reference (4 to 20mA) of control circuit terminal
= 4 --- Enables current reference (0 to 20mA) of control circuit terminal
= 6 --- Enables communications (MEMOBUS)
47
Operation Steps
1. Turn the local pot (volume control) fully counter clockwise after turning the power ON.
Operator
Display
0.00
12-LED
Display
Status
Indicator LED
RUN
ALARM
2. Press DSPL 5 times to illuminate Lo/RE
Select Lo (local mode) using or key
Lo
Lo/RE
RUN
ALARM
3. F/R blinks.
Select FWD/REV run using keys
Never select REV when reverse run is prohibited.
For or
REV
RUN
ALARM
4. Press DSPL to illuminate FREF. Then press RUN.
0.00
RUN
ALARM
5. Operate the motor by turning the volume clockwise.
(Frequency reference corresponding to the volume position is displayed.)
If the volume is switched rapidly, the motor also accelerates or decelerates rapidly corresponding to the volume movement. Pay attention to load status and adjust the volume to the desired speed.
0.00 to 60.00
Minimum output frequency is
1.5Hz
Status indicator lamp
: ON : Blinking
Operation Check Points
• Motor rotates smoothly.
• Motor rotates in the correct direction.
• Motor does not have abnormal vibration or noise.
• Acceleration or deceleration is smooth.
• Current is appropriate for the load (No overload).
• Status indicator LED’s and digital operator display are correct.
: OFF
RUN
ALARM
48
• Operating the Digital Operator
All functions of the VS mini J7 are set by the digital operator. Below are descriptions of the display and keypad sections.
Digital Operator
49
Description of Status Indicator LED’s
There are two LED’s on the middle right section of the face of the VS mini. The inverter status is indicated by various combinations of the LED’s (ON, BLINKING and OFF). RUN indicator and status indicator of the functions.
RUN button have the same
For details on how the status indicator LED’s function at inverter faults, refer to
Section 8 “FAULT DIAGNOSIS AND CORRECTIVE ACTIONS” on page 103. If a fault occurs, the ALARM LED lights.
The fault can be reset by turning ON the fault reset signal (or pressing on the digital operator) when the operation signal is removed or by turning OFF the power supply. If the operation signal is ON, the fault cannot be reset by the fault reset signal.
STOP
RESET
key
50
• LED Description
By pressing selected.
on the digital operator, each of the function LED’s can be
The following flowchart describes each function LED.
51 and 52
51
Parameter
Parameter No. (Refer to page 57)
Return to
Multi-Function monitor
• Selecting monitor
Press key. When selecting monitor No.
is ON, data can be displayed by
[Example] Monitoring Output Voltage Reference
52
• Monitoring
Following items can be monitored by U-parameters
Parameter
No.
U-01
U-02
U-03
U-04
U-05
U-06
U-07
U-09
U-10
U-15
Name
Frequency reference
(FREF)
Output frequency
(FOUT)
Output current
(IOUT)
Output voltage
DC voltage
Input terminal status
Output terminal status
Fault history
Software No.
Data reception error
Description
Hz
Frequency reference can be monitored.
(Same as FREF)
Hz
AMP
Output frequency can be monitored.
(Same as FOUT)
Output current can be monitored.
(Same as IOUT)
V Output voltage can be monitored.
V Main circuit DC bus voltage can be monitored.
—
Input terminal status of control circuit terminals can be monitored.
—
Output terminal status of control circuit terminals can be monitored.
— Last four fault history is displayed.
— Software No. can be checked.
—
Contents of MEMOBUS communications data reception error can be checked. (contents of transmission register No. 003DH are the same)
53
Fault history display method
Fault description is displayed when U09 is selected.
(Example)
!!!: Fault description (“---” is displayed if there is no fault.)
(Refer to page 103 for details.)
• Clearing fault history
Set parameter n001 to 6 to clear fault history. Set data returns to its initial value after completion of 6 setting.
Note: Parameter initialize (n01 = 10, 11) also clears the fault history.
Setting and referring parameters
The following figure shows how to select and change parameters.
54
• Simple Data Setting
Volume setting (Refer to 5, OPERATING THE INVERTER) and digital setting are both available for simple accel/decel operation of the VS mini.
Frequency reference by analog voltage is set with initial setting (n03 = 2).
Following is an example in which the function LEDs are used to set frequency reference, acceleration time, deceleration time, and motor direction.
55
Notes
56
7. PROGRAMMING FEATURES
Factory settings of the parameters are shown as in the tables.
• Parameter Set-up and Initialization
Parameter selection/initialization (n01)
The following table describes the data which can be set or read when n01 is set.
Unused parameters among n01 to n79 are not displayed.
n001 Setting Parameter that can be set
0 n01
1 n01 to n79*
6
7
10
11
Fault history cleared
Not used
Initialize (2-wire sequence)
Initialize (3-wire sequence)=
Parameter that can be viewed n01 to n79 n01 to n79
* Excluding setting disabled parameters.
= Refer to page 85.
“ ” appears on the LED display for one second and the set data returns to its initial values in the following cases:
(1) The set values of input terminal function selection 2 to 5 (n36 to n39) are the same.
(2) The following conditions are not satisfied in the V/f pattern setting:
Max. output frequency (n09) > Max. voltage output frequency (n11)
> Mid. output frequency (n12)
> Min. output frequency (n14)
For details, refer to “Adjusting torque according to application” (V/f pattern setting) on page 56.
(3) If the following conditions are not satisfied in the Jump frequency setting:
Jump frequency 2 (n50) < Jump frequency 1 (n49)
(4) If Frequency reference lower limit (n31) > Frequency reference upper limit (n30)
(5) If motor rated current (n32) > 150% of inverter rated current
57
• Selecting V/f pattern
Adjusting torque according to application
Adjust motor torque by using “V/f pattern” and “full-range automatic torque boost”.
• V/f pattern setting
Set V/f pattern by parameters n09 to n15 as described below. Set each pattern when using a special motor (high-speed motor, etc.) or when requiring special torque adjustment of machine.
Be sure to satisfy the following conditions for the setting of n09 to n15.
n14 < n12 < n11 < n09
If n14 = n12, the set value of n13 is disabled.
Parameters
No.
n09
Name
Max. output frequency n10 Max. voltage n11 n12 n13 n14 n15
Max. voltage output frequency
(base frequency)
Mid. output frequency
Mid. output frequency voltage
Min. output frequency
Min. output frequency voltage
Unit
0.1Hz
1V
0.1Hz
0.1Hz
1V
0.1Hz
1V
Setting range
50.0 to 400Hz
1 to 255V
(0.1 to 510V)
0.2 to 400Hz
0.1 to 399Hz
0.1 to 255V
(0.1 to 510V)
0.1 to 10.0Hz
1 to 50V
(0.1 to 100V)
Initial Setting
60.0Hz
230V
(460V)
60.0Hz
1.5Hz
12V
(24V)
1.5Hz
12V
(24V)
58
• Typical setting of V/f pattern
Set the V/f pattern according to the application as described below. For 400V class, the voltage values (n10, n13, and n15) should be doubled. When running at a frequency exceeding 50Hz/60Hz, change the maximum output frequency (n09).
Note: Be sure to set the maximum output frequency according to the motor characteristics.
Increasing voltage of V/f pattern increases motor torque, but excessive increase may cause motor over excitation, motor overheat, or vibration.
59
When operating with frequency larger than 60Hz/50Hz, change only maximum output frequency (n09).
• Full-range automatic torque boost
Motor torque requirement changes according to load conditions. Full range automatic torque boost adjusts voltage of V/f pattern according to the requirement.
The VS mini J7 automatically adjusts the voltage during constant-speed operation as well as during acceleration.
The required torque is calculated by the inverter. This ensures tripless operation and energy-saving effects.
Output voltage ∝ Torque compensation gain (n63)
×
Required torque
Operation
Normally, no adjustment is necessary for torque compensation gain (n63 factory setting: 1.0). When wiring distance between the inverter and motor is long or when motor generates vibration, change the automatic torque compensation gain. In these cases, it may also be beneficial to adjust the V/f pattern (n09 to n15).
60
• Switching LOCAL/REMOTE Modes
The following functions can be selected by switching the LOCAL or REMOTE mode. To select RUN/STOP commands or frequency reference, change the mode in advance depending on the following applications.
• LOCAL Mode:
Enables the digital operator for RUN/STOP commands and
FWD/REV run commands. Frequency reference can be set by
volume or
• REMOTE Mode:
.
Run by the n02 setting (operation reference selection).
Frequency reference can be set by n03 (frequency reference selection) setting.
• How to select LOCAL/REMOTE modes
(When 17 is not set to any parameters n36 to n39)
(When 17 is set to any parameters n36 to n39)
61
• Selecting Run/Stop Commands
Refer to page 63 to select either the LOCAL mode or REMOTE mode.
Operation method (RUN / STOP commands, FWD / REV run commands) can be selected by the following method.
• LOCAL Mode
When Lo (local mode) is displayed on the digital operator (when is illuminated), or when the LOCAL / REMOTE changeover function is set as a multi-function input and the input terminal is turned ON, run operation is enabled by the or of the digital operator. FWD/REV is selected by illuminating and using or key to select FWD or REV.
• REMOTE mode
• Select remote mode
The following two methods are used to select remote mode:
1. Select rE (remote mode) for selection.
2. When the local / remote switching function is selected as multi-function input selection, turn OFF the input terminal to select remote mode.
• Select operation method by setting the parameter n02.
n02=0: Enables the digital operator (same with local mode)
=1: Enables the multi-function input terminal (see fig. below)
=2: Enables communications (refer to page 96)
• Example for using the multi-function input terminal as operation reference
(two-wire sequence) follows. For 3-wire sequencing, refer to page 85.
• Operating (RUN /STOP commands) by communications
(When option card is installed)
Setting parameter n02 to 2 in REMOTE mode can give RUN / STOP commands by communication (MEMOBUS). For details, refer to page 96.
62
• Selecting Frequency Reference
Frequency reference can be selected by the following methods.
• Setting by operator
Select REMOTE or LOCAL mode in advance. For the method of selecting the mode, refer to page 62.
LOCAL mode
Parameter n07 determines where the frequency reference is input from when in the local mode.
n07 =0: Enables the setting by volume on digital operator (initial setting)
Factory setting of the model with operator
(without volume) is n07=1.
=1: Enables the digital setting by digital operator, setting value is stored in parameter n21 (frequency reference 1).
• Digital setting by digital operator
Input frequency while FREF is illuminated (press ENTER after setting the desired frequency value).
Frequency reference setting is immediately effective when n08 = 1 The ENTER key does not have to be pressed to enter the reference.
n08 =0: Enables frequency reference acceptance by ENTER key.
=1: Disable frequency reference setting by ENTER key. It is not necessary to press the ENTER key to accept the reference.
REMOTE mode
Parameter n03 determines where the frequency reference is accepted from when in the REMOTE mode.
n03 =0: Enables frequency reference setting by volume on digital operator.
=1: Frequency reference 1 (parameter n21) is effective
=2: Voltage reference terminal “FR” is effective (0 to 10V)
(See the figure below)
=3: Current reference terminal “FR” is effective(4 to 20mA)
(Refer to page 90)*
=4: Current reference terminal “FR” is effective (0 to 20mA)
(Refer to page 90)*
=6: Communication (Refer to page 97)
63
64
*NOTE: SWB must be set to the “I” position when using terminal “FR” as a current reference input.
Example of frequency reference by voltage signal n03: 2 (factory setting)
SW8 is set to “V” position when using terminal “FR” as a voltage reference (default setting)
• Setting Operation Conditions
Reverse run prohibit (n06)
The “Reverse run disabled” setting will not accept a reverse run command from the control circuit terminal or digital operator. This setting is used for applications where a reverse run command is undesirable.
Setting
0
1
Description
Reverse run enabled
Reverse run disabled
Multi-step speed selection
Up to 8 preset references can be selected by using Multi-Function inputs.
Example: 8-step speed reference n02=1 (operation mode selection) n03=1 (Frequency reference selection) n21=25.0Hz (Frequency reference 1) n22=30.0Hz (Frequency reference 2) n23=35.0Hz (Frequency reference 3) n24=40.0Hz (Frequency reference 4) n25=45.0Hz (Frequency reference 5) n26=50.0Hz (Frequency reference 6) n27=55.0Hz (Frequency reference 7) n28=60.0Hz (Frequency reference 8)
When all multi-function reference inputs are OFF, frequency reference selected by parameter n03
(frequency reference selection) becomes effective.
n36=2 (Multi-function contact input terminal S2) n37=6 (Multi-function contact input terminal S3) n38=7 (Multi-function contact input terminal S4) n39=8 (Multi-function contact input terminal S5)
65
Operating at Jog frequency reference
By inputting a jog command and then a forward or (reverse) run command, operation is enabled at the jog frequency set in n29. When multi-step speed references 1, 2, 3 or 4 are input simultaneously with the jog command, the jog command has priority.
Name
Jog frequency reference
Jog command parameter No.
n29 n36 to n39
Setting
Factory setting: 6.00Hz
Set to “10” for any parameter.
66
• Adjusting speed setting signal
The relationship between the analog input signal and internal (terminal “FR”) frequency reference can be set by parameters n41 and n42.
FREQUENCY REFERENCE
(a) Frequency reference gain (n41)
The analog input voltage level for the maximum output frequency (n09) can be set in units of 1%. (maximum output frequency n09=100%)
∗ Factory setting : 100%
(b) Frequency reference bias (n42)
The frequency reference provided when the analog input is 0V (4mA or 0mA) can be set in units of 1%. (Maximum output frequency n09=100%)
∗ Factory setting : 0%
Example settings:
• To operate the inverter with frequency reference of 0% to 100% at 0 to 5V input
Gain n41 = 200%
Bias n42 = 0%
67
68
• To operate the inverter with frequency reference of 50% to 100% at 0 to
10V input
Gain n41 = 100%
Bias n42 = 50%
Adjusting frequency upper and lower limits
Frequency reference upper (n30) and lower
(n31) limits determines the range over which the inverter will operate.
• Frequency reference upper limit (n30)
Sets the upper limit of the frequency reference in units of 1%.
(n09: Maximum output frequency = 100%)
Factory setting: 100%
• Frequency reference lower limit (n31)
Sets the lower limit of the frequency reference in units of 1%.
(n09: Maximum output frequency = 100%)
When operating at frequency reference 0, operation is continued at the frequency reference lower limit.
However, when frequency reference lower limit is set to less than the minimum output frequency (n14), operation is not performed.
Factory setting: 0%
Using two accel/decel times
* When “deceleration to a stop” is selected (n04 = 0)
Two acceleration times and two deceleration times can be selected via a multi-function input. Programming any of terminals S2 through S5 (parameter n36 to n39) to “11”
“Accel/Decel time select”, provides the ability to switch between the 2 acceleration times (n16 and n18) and deceleration (n17 and n19) through a contact closure applied to the appropriate terminal (See timing diagram above).
69
At OFF: n16 (accel time 1) are used.
n17 (decel time 1)
At ON: n18 (accel time 2) are used.
n19 (decel time 2)
• Accel time
Set the time needed for output frequency to reach 100% from 0%.
• Decel time
Set the time needed for output frequency to reach 0% from 100%.
(Maximum output frequency n09 = 100%)
Automatic restart after momentary power loss (n47)
The inverter has the ability to ride thru momentary power outages provided the control logic power supplies are maintained.
When momentary power loss occurs, operation restarts automatically.
Setting.
0
1*
2*†
Description
Continuous operation after momentary power loss not provided.
Continuous operation after power recovery within momentary power loss ride thru time is provided.
Continuous operation after power recovery (Fault output not provided)
* Maintain the run command to continue operation after recovery from a momentary power loss.
† When 2 is selected, operation restarts if power supply voltage reaches its normal level while control power supply is held. No fault signal is output.
70
Soft-start characteristics (n020)
To prevent shock at machine start/stop, accel/decel can be performed in a S-curve pattern.
Setting
0
1
2
3
S-curve characteristic time
S-curve characteristic not provided
0.2 second
0.5 second
1.0 second
Note: The S-curve characteristics time from accel/decel rate 0 to a regular accel/decel rate determined by the set accel/decel time.
71
The following time chart shows FWD/REV run switching at deceleration to a stop.
Overtorque detection
If an excessive load is applied to the machine, output current increase can be detected to output alarm signals to multi-function output terminals MA and MB.
To output an overtorque detection signal, set output terminal function selection n40 to
“overtorque detection” [Setting:6 (NO contact) or 7 (NC contact)].
∗
Overtorque detection release width (hysterisis) is set at approx. 5% of inverter rated current.
72
• Overtorque detection function selection (n59)
Setting
0
1
2
3
4
Description
Overtorque detection not provided
Detected during speed agree, (alarm).
Operation continues after detection.
Detected during speed agree (fault). Operation stops during detection.
Detected during running, operation continues after detection. (alarm).
Detected during running, operation stops during detection. (fault).
(1) To detect overtorque at accel/decel, set to 3 or 4.
(2) To continue the operation after overtorque detection, set to 1 or 3.
During detection, the operator displays “ ” alarm (blinking).
(3) To halt inverter by a fault at overtorque detection, set to 2 or 4. At detection, the operator displays “ ” fault (ON).
• Overtorque detection level (n60)
Sets the overtorque detection current level in units of 1%. (Inverter rated current =
100%)
Factory setting: 160%
• Overtorque detection time (n61)
If the time when the motor current exceeds the overtorque detection level (n61), the overtorque detection function operates.
Factory setting: 0.1sec.
73
Frequency detection (n58)
Effective when the multi-function output terminal MA-MB-MC (parameter n40) is set to “frequency detection” (setting: 4 or 5). “Frequency detection” turns ON when output frequency is higher or lower than the frequency detection level (n58).
• Frequency detection 1 (Output frequency > Frequency detection level n58)
(Set n40 to “4”.)
• Frequency detection2 (Output frequency < Frequency detection level n58)
(Set n40 to “5”.)
74
Jump frequencies (n49 to n51)
This function allows the prohibit or “jumping” of critical frequencies so that the motor can operate without resonance caused by machine characteristics. This function is also used for dead band control. Setting the value to 0.00Hz disables this function.
Set prohibited frequency 1, 2 or as follows: n49 > n50
If this condition is not satisfied the inverter displays for one second and restores the data to original settings.
Continuous operation is prohibited within the jump frequency range.
However, during accel/decel the output frequency ramps through the jump frequency range (without jumping).
Continuing operation by automatic fault reset (n48)
Sets the inverter to restart and reset fault detection after a fault occurs.
The number of self-diagnosis and retry attempts can be set with n48 (0 thru 10 restarts).
The inverter will automatically restart after the following faults occur:
• OC (overcurrent)
• GF (ground fault)
• OV (over voltage)
The number of retry attempts are cleared to 0 during the following cases:
(1) If no other fault occurs within 10 minutes after retry
(2) When the fault reset signal is ON after the fault is detected
(3) Input power is turned OFF
75
Starting into a rotating motor - Tripless Operation
To start into a coasting motor without trip, use the speed search command or DC injection braking at start.
• Speed search command
Speed matches into a coasting motor upon starting without stopping the motor.
This function enables smooth switching between motor commercial power supply operation and inverter operation.
Set input terminal function selection (n36 to n39) to “14” (search command from maximum output frequency) or “15” (search command from set frequency).
Build a sequence so that FWD (REV) run command is input at the same time as the search command or after the search command. If the run command is input before the search command, the search command becomes disabled.
• Time chart at search command input
• DC injection braking at start (n52, n54)
When starting into a coasting motor, use DC injection to gradually brake the motor before beginning the acceleration ramp. Set the DC injection braking time at start in n54 in units of 0.1 second. Set DC injection braking current in n52 in units of 1%
(inverter rated current = 100%). When the setting of n54 is “0”, DC injection braking is not performed and acceleration starts from the minimum output frequency.
When n52 is set to 0, acceleration starts from the minimum output frequency after base blocking for n54 setting time.
76
Accel/Decel Hold
To hold acceleration or deceleration, use a multi-function input that is set to a value of
“16: Accel/Decel Hold. The output frequency is kept constant when the accel/decel hold command is input during acceleration or deceleration.
When the run command is removed during an accel/decel hold condition, accel/decel hold is internally released and operation ramps to stop.
Set multi-function input terminal selection (n36 to n39) to 16 (accel/decel hold command).
Note: When the FWD (REV) run command is input along with the accel/decel hold command, the motor does not operate. However, when frequency reference lower limit
(n31) is set greater than or equal to minimum output frequency (n14), the motor operates at frequency reference lower limit (n31).
77
Using a frequency meter or ammeter (n44)
Determines whether output frequency or output current is indicated on the analog output terminals, AM-AC, for monitoring.
Setting
0
1
Description
Output frequency
Output current
Initial setting-analog voltage of approx. 10V is output when output frequency (output current) is 100%.
Calibrating frequency meter or ammeter (n045)
Used to adjust analog output gain.
Scales the analog output voltage signal level at 100% of output frequency (output current).
Example: Frequency meter displays 0 to 60Hz with 0 to 3V.
10V x n45 setting (0.30V) = 3V (3V is output at 100% output frequency)
78
Reducing motor noise leakage current (n46)
Set inverter output transistor switching frequency (carrier frequency).
Setting Carrier Frequency (kHz)
Audible Noise from Motor
RFI Noise and
Current Leakage
7
8
9
1
2
3
4
12 fout
24 fout
36 fout
2.5
5.0
7.5
10.0
(Hz)
(Hz)
(Hz)
(kHz)
(kHz)
(kHz)
(kHz)
Higher
Not audible
Smaller
Larger
Setting values 7, 8, or 9 provides a synchronous carrier frequency that changes with output frequency as follows.
79
Carrier Frequency Varies According to Inverter Capacity (kVA).
Voltage Class
200V
Single-phase
3-phase
400V
3-phase
Capacity hp(kW)
0.13 (0.1)
0.25 (0.2)
0.5 (0.4)
1 (0.75)
2 (1.5)
3 (2.2)
5 (3.7)
0.25 (0.2)
0.5 (0.4)
1 (0.75)
2 (1.5)
3 (2.2)
4 (3.0)
5 (3.7)
Initial Setting
Setting
Carrier
Frequency
3
3
3
3
3
3
3
3
3
4
4
4
4
3
10kHz
10kHz
10kHz
10kHz
7.5kHz
7.5kHz
7.5kHz
7.5kHz
7.5kHz
7.5kHz
7.5kHz
7.5kHz
7.5kHz
7.5kHz
Maximum
Continuous
Output Current
(A)
0.8
1.6
3.0
5.0
8.0
11.0
17.5
1.2
1.8
3.4
4.8
5.5
7.2
9.2
Reduced
Current (A)
*1
–
7.0
10.0
16.5
1.0
1.6
3.0
4.0
4.8
6.3
7.6
(1) Reduce continuous output current by changing carrier frequency to a setting of 4 (10 kHz) for 200V class inverters (size > 1.5kW) and all 400V class inverters. Refer to the table above for the reduced current.
[Operation Condition]
•
• Input power supply voltage: 3-phase 200 to 230V (200V class)
Single-phase 200 to 240V (200V class)
Ambient temperature:
3-phase 380 to 460V (400V class)
14 to 122 o
F (-10 to +50 o
C)
(2) If the wiring distance is long (approx. 50 meters), reduce the inverter carrier frequency as described below.
Wiring Distance between
Inverter and Motor
Up to 50m Up to 100m More than 100m
Carrier frequency
(n46 setting)
10kHz or less
(n46=1, 2, 3, 4,
7, 8, 9)
5kHz or less
(n46=1, 2,
7, 8, 9)
2.5kHz or less
(n46=1, 7, 8, 9)
(3) Carrier frequency can be automatically reduced to 2.5 kHz when (n75) is set to 1 and the following conditions are satisfied.
Output frequency < 5Hz
Output frequency > 100%
Factory Setting (n75) is 0 (disabled)
80
Operator stop key selection (n06)
Selects whether the “STOP” key on the digital operator is effective when operating the inverter by an external source (input terminals or serial communications).
Setting
0
1
Description
STOP key effective when running either from multi-function input terminals or communications.
When STOP key is pressed, the inverter stops according to the setting of parameter n04. At this time, the digital operator displays “ ” alarm (blinking). This stop command is held in the inverter until both forward and reverse run commands are open, or until run command from communications becomes zero.
STOP key is ineffective when running either from multi-function input terminals or communications.
81
• Selecting Stopping Method
Selecting stopping method (n04)
Selects the stopping method when the run command is removed.
Setting
0
1
Description
Deceleration to stop
Coast to stop
• Deceleration to stop (n04 =0)
* When frequency reference is changed during running.
Upon removal of the FWD (REV) run command, the motor decelerates at the decel rate determined by the time set to decel time 1 (n17) and DC injection braking is applied immediately before stop. DC injection braking is also applied when the motor decelerates by setting the frequency reference lower than minimum output frequency while the(n14) with FWD (REV) run command remains ON.
If the decel time is short or the load inertia is large, an over voltage (OV) fault may occur during deceleration. In this case, increase the decel time.
82
• Coast to stop (n04=1)
* When frequency reference is changed during running.
Upon removal of the FWD (REV) run command, the motor starts coasting.
Applying DC injection braking
• DC injection braking current (n52)
Sets DC injection braking current level in units of 1%. (Inverter rated current=100%)
• DC injection braking time at stop (n53)
Sets the DC injection braking time at stopping in units of 0.1 second. When the setting of n53 is 0, DC injection braking is not performed but inverter output is shut
OFF at the timing of DC injection braking start.
When coast to a stop is selected as the stopping method selection (n04), DC injection braking at stop does not operate.
83
• Building Interface Circuits with External Devices
Using input signals
Multi-function input terminal S2 to S5 functions can be changed when necessary by setting parameters n36 thru n39 respectively. Parameters n36 thru n39 cannot be set to the same value.
Setting
0
6
7
8
10
11
12
2
3
4
5
13
Name
FWD/REV run command
(3 wire sequence selection)
Reverse run
(2 wire sequence selection)
External fault (NO contact input)
External fault (NC contact input)
Fault Reset
Multi-step speed reference 1
Multi-step speed reference 2
Multi-step speed reference 3
JOG command
Accel/Decel time select
External baseblock
(NO contact input)
External baseblock
(NC contact input)
Description
Setting enabled only for n37
Inverter stops by external fault signal input
Digital operator display is EF
!
*.
Resets the fault. Fault reset not effective with the run signal ON.
Motor coast to a stop by this signal input.
Digital operator display is
Ref.
85
65
65
65
66
69
–
65
–
–
75
–
14
15
16
17
18
19
20
21
22
34
35
Search command from maximum frequency
Search command from set frequency
Accel/decel hold command
LOCAL/REMOTE selection
Communication/control circuit terminal selection
Emergency stop fault
(NO contact input)
Emergency stop alarm
(NO contact input)
Emergency stop fault
(NC contact input)
Emergency stop alarm
(NC contact input)
UP/DOWN command
Self-test
Speed search reference signal
Inverter stops by emergency stop signal input according to stopping method selection (n04).
When frequency coasting to a stop (n04 is set to 1) method is selected, inverter coasts to a stop according to decel time setting 2 (n19).
Digital operator display is
Srp
(lit at fault, blinking at alarm).
Setting enabled only for n39 (terminal S5)
Setting enabled only for n39 (terminal S5)
* Numbers 2 to 5 is displayed in !corresponding to the terminal numbers S2 to S5 respectively.
76
76
77
61
87
–
–
–
–
86
_
Fault Reset
Fault reset is not effective with the run signal ON.
No.
n36 n37 n38 n39
Terminal
S2
S3
S4
S5
Initial Setting
2
5
3
6
84
Terminal function at 3-wire sequence selection
When 0 is set at the terminal S3 (n37), terminal S1 becomes run command, terminal S2 becomes stop command, and terminal S3 becomes FWD/REV run command.
• LOCAL/REMOTE select (setting: 17)
Select operation reference either by the digital operator or by the settings of operation method selection (n02) and frequency reference selection (n03). LOCAL/
REMOTE select is available only during stop.
Open: Run according to the setting of run command selection (n02) or frequency reference selection (n03)
Closed: Run by frequency reference and run command from the digital operator.
Example:Set n02 = 1, n03 = 2, n07 = 0.
Open: Run by frequency reference from multi-function input terminal FR and run command from multi-function input terminals S1 to S7.
Closed: Run by volume frequency reference and run command from the digital operator.
• UP/DOWN command (setting: 34)
With the FWD (REV) run command entered, accel/decel is initiated by inputting the UP or DOWN commands to multi-function input terminals S4 and S5. Closing the S4 input will cause the output frequency to increase. Closing the S5 input will cause the output frequency to decrease (as indicated in the following table. When
UP/DOWN commands are specified by n39, any function set to n38 becomes disabled; terminal S4 becomes an input terminal for the UP command and terminal
S5 for the DOWN command.
Multi-function Input Terminal
S4 (UP command)
Multi-function Input Terminal
S5 (DOWN command)
Operation Status
Closed
Open
Accel
Open
Closed
Decel
Open
Open
Hold
Closed
Closed
Hold
85
Time Chart at UP/DOWN Command Input
Notes:
(1) When UP/DOWN command is selected, the upper limit speed is set regardless of frequency reference.
Upper limit speed = Maximum output frequency (n09) x Frequency reference upper limit (n030)/100
(2) Lower limit value is either minimum output frequency (n14) or Maximum output frequency
(n09) x frequency reference lower limit (n31)/100% (whichever is greater).
(3) When the FWD (REV) run command is input, operation starts at the lower limit speed without an
UP/DOWN command.
(4) If the jog command is input while running by the UP/DOWN command, the jog command has priority.
(5) Multi-step speed reference 1 to 3 is not effective when UP/DOWN command is selected. Multistep speed reference is effective during running in hold status.
(6) When “1” is set for HOLD output frequency memory selection (n62), output frequency can be recorded during HOLD.
Setting
0
1
Description
Output frequency is not recorded during HOLD.
When HOLD status is continued for 5 seconds or longer, the output frequency during HOLD is recorded and the inverter restarts at the recorded frequency.
86
• Communication/multi-function input terminal selection input (setting: 18)
(This function is effective when option card is installed)
Operation can be changed from communication command, or from multi-function input terminal or digital operator command.
Run command and frequency reference from communication options are effective when multi-function input terminal for this setting is “closed.”
Run command and frequency reference in LOCAL/REMOTE mode are effective when “Open.”
Using output signals (n40)
Multi-function output terminal MA and MB functions can be changed when necessary by setting parameter n40.
• Terminal MA and MB functions: Set to n40
Setting
0 Fault
Name Ref page
–
1
2
3
4
5
6
7
10
11
Inverter Run
Agreed frequency
Zero speed
Frequency detection
Frequency detection
Overtorque detection
(NO contact output)
Overtorque detection
(NC contact output)
Minor Fault
Base blocked
Description
Closed when inverter fault occurs.
Closed when either FWD/REV command is input or voltage is output from the inverter.
Closed when setting frequency agrees with inverter output frequency.
Closed when inverter output frequency is less than minimum output frequency.
Output frequency
≥ frequency detection level (n58)
Output frequency
≤ frequency detection level (n58)
—
—
–
88
–
74
74
73
73
–
–
12
13
14
15
16
17
18
Operation mode
Inverter ready
Fault restart
In UV
In reverse run
In speed search
Data output from communication
Closed when the alarm is indicated.
Closed when the inverter output is shut off.
Closed when “LOCAL” is selected by LOCAL/REMOTE selection.
Closed when inverter fault is not detected, and operation is ready.
Closed during fault retry
Closed when undervoltage is detected.
Closed during reverse run.
Closed when inverter conducts speed search.
Operates multi-function output terminal independently from inverter operation (by MEMOBUS communication).
–
–
–
–
–
–
–
87
Initial setting of multi-function output terminal
No.
n40
Terminals
MA, MB
Initial Setting
1 (Inverter Run)
+ 2HZ
OUTPUT FREQUENCY
88
• Setting Frequency by Current Reference Input
When setting frequency by inputting current reference (4-20mA or 0-20mA) from the control circuit terminal FR, switch the DIP switch SW8 on the control circuit board to “I” side.
SW8 is accessed by removing the terminal cover.
SW8
Never input voltage reference to control circuit terminal FR when DIP switch SW8 is switched to “I” side. Damage to the inverter may result.
89
Current reference selection
After changing DIP switch (SW8) to the “I” side, PRESS PRGM on the digital operator, then set the following parameters.
4-20mA…n03 = 3
0-20mA…n03 = 4
Press the digital operator keys to run or stop the inverter. Switch run and stop direction by setting F/R LED.
Set frequency by the analog current signal
[0-100% (max frequency)/4-20mA or 0-
20mA] connected to the control circuit terminal.
Set run/stop and FWD/REV run with switching device connected to the control circuit terminal.
Multi-function input terminal S2 is set to
Reverse run/stop (n36 = 2).
Set frequency by the analog current signal
[0-100% (max. frequency)/4-20mA or 0-
20mA] connected to the control circuit terminal.
Frequency reference gain (n41)/bias (n42) can be set even when current reference input is selected. For details, refer to “Adjusting speed setting signal” on page 69.
90
• Preventing Motor from Stalling (Current Limit)
This function automatically limits the output current in response to load changes by adjusting the output frequency to prevent motor stalling.
• Stall prevention (current limit) level during acceleration (n56)
Sets the stall prevention (current limit) level during acceleration in units of 1%
(Inverter rated current = 100%).
Factory setting: 170%
A setting of 200% disables the stall prevention (current limit) during acceleration.
During acceleration, if the output current exceeds the value set for n56, acceleration stops and frequency is maintained. When the output current goes down to the value set for n56, acceleration continues.
* Stops the acceleration to prevent the motor from stalling.
† Release width (hysteresis) of stall prevention during accel is approx. 5% of inverter rated current.
*
In the constant horsepower area [output frequency > max. voltage output frequency
(n11)], following equation automatically decreases the stall prevention (current limit) level during acceleration.
*
*Note: The lower limit of the stall prevention level is 40% of the level set in n56.
91
• Stall prevention (current limit) level during running (n57)
Sets the stall prevention (current limit) level during running in units of 1% (Inverter current = 100%).
Factory setting: 160%
A setting of 200% disables the stall prevention (current limit) during running.
If the output current during speed agree exceeds the value set for n57 for longer than
100msec, deceleration starts.
As long as the output current exceeds the value set for n57 deceleration continues.
When the output current goes below the value set for n57, acceleration begins to the set frequency.
The accel/decel rates during stall prevention are determined by the accel time (n16 or n18) and decel time (n17 or n19) that is selected at the time of the stall prevention condition.
* Decreases frequency to prevent the motor from stalling.
† At acceleration start, output hysteresis is approx. 5% of inverter rated current.
• Stall prevention (current limit) function during deceleration (n55)
To prevent overvoltage during deceleration, the inverter automatically lengthen the deceleration time according to the value of main circuit DC voltage.
Setting
0
1
Stall prevention (current limit) during deceleration
Provided
Not Provided
92
• Decreasing Motor Speed Fluctuation
Slip compensation
As the load becomes larger, rotor speed is reduced as motor slip increases. The slip compensating function regulates the motor shaft speed as the load increases by increasing the output frequency.
When inverter output current is equal to the motor rated current (n32), the compensation frequency is added to the output frequency.
Compensation frequency = Motor rated slip (n64)
× Output current – Motor no-load current n65
--------------------------------------------------------------------------------------------------------------------------------------------
Electronic thermal reference current (n32)
– Motor no-load current (n65)
×
Slip compensation gain (n66)
Parameters
Parameters
No.
n032
Name
Motor rated current n64 n65
Motor rated slip
Motor no-load current
Unit Setting Range
0.1A 0 to 120% of inverter rated current
0.1Hz 0.0 to 20Hz
1% 0 to 99% (100% = Motor rated current n32)
Initial
Setting
*
*
* n66 Slip compensation gain 0.1
0.0 to 2.5
0.0
n67
Slip compensation primary delay time
0.1s
0.0 to 25.5s
When 0.0s is set, delay time becomes 2.0s
2.0s
* Differs depending on inverter capacity.
Notes:1. Slip compensation is not performed in the following condition:
Output frequency < minimum output frequency (n14).
2. Slip compensation is not performed during regeneration.
3. Slip compensation is not performed when motor rated current (n32) is set to 0.0A.
93
• Motor Protection
Motor overload detection
Built-in electronic thermal overload protection is provided to protect against motor overheating.
• Motor rated current (electronic thermal reference current, n32)
Set to the rated current value shown on the motor nameplate.
• Motor overload protection selection (n33, n34).
n33 Setting
0
1
2
Electronic Thermal Characteristics
Applied to general-purpose motor (limited speed range)
Applied to inverter duty motor (wide speed range)
Electronic thermal overload protection not provided
Parameters
No.
Name Unit Setting Range Initial Setting n34
Protection parameter selection
1min 1 to 60min 8min
The electronic thermal overload function calculates motor temperature, based on inverter output current and time, to protect the motor from overheating. When the electronic thermal overload relay is enabled and excessive current is flowing to the motor, an “ ” error occurs, shutting OFF the inverter output and preventing excessive overheating in the motor. When operating with one inverter connected to one motor, an external thermal relay is not needed. When operating several motors with one inverter, install a thermal relay on each motor and disable the electronic overload protection (n33=2).
94
• General-purpose motor and inverter motor
Induction motors are classified as general-purpose motors (limited speed range) or inverter motors (wide speed range), based on their cooling capabilities. Therefore, the motor overload function operates differently between these two motor types.
Cooling Effect
Effective when operated at 50/60Hz from commercial power supply
Example of 200V class motor
Torque Characteristics
Electronic Thermal overload
error (motor overload protection) occurs when continuously operated at
50/60Hz or less at 100% load.
Effective even when operated at low speed
(approx. 6Hz)
Base Frequency 60Hz
(V/f for 60Hz, 220V Input Voltage)
For low-speed operation, torque must be limited in order to stop motor temperature rise.
Electronic thermal overload protection not activated even when continuously operated at
50/60Hz or less at 100% load.
Base Frequency 60Hz
(V/f for 60Hz, 220V Input Voltage)
Use an inverter duty motor for continuous operation at low speed.
95
• Selecting Cooling Fan Operation
In order to increase fan life, the cooling fan can be set to operate when inverter is running or when power is supplied.
n35 = 0 (factory setting) : Operates only when inverter is running.
= 1
(Continues operation for 1 minute after inverter is stopped.)
: Operates while power is ON.
• Using MEMOBUS (MODBUS) Communications
Serial transmission is available with VS mini J7 using programmable controller
(MEMOCON series) and MEMOBUS. In order to perform serial communications, RS-
485/422 interface card (optional) must be installed.
• MEMOBUS (MODBUS) communications
MEMOBUS system is composed of a single master (PLC) and slaves (1 to 31
VS-mini units).
Transmission between master and slave (serial communication) is controlled according to the master program with the master initiating communication and the slave responding.
The master sends a signal to one slave at a time. Each slave has a pre-registered address No., and the master specifies the number and conducts signal communication. The slave receives the transmission to carry out designated functions and reply to the master.
VS mini J7 VS mini J7 VS mini J7
96
• Communications specifications
Interface RS-422, RS485
Synchronization Asynchronous (Start-stop synchronization)
Communication parameters
Baud rate: Selected from 2400/4800/9600/19200 bps
Data length: 8 bits fixed
Parity: Selected from even/odd/none
Stop bits: 1 bit fixed
Communication protocol
Max. number of inverters that can be connected
MEMOBUS (MODBUS) (RTU mode only)
31 units (When using RS-485)
97
Notes
98
8. Maintenance and Inspection
• Periodical Inspection
Periodically inspect the inverter as described in the following table to prevent accidents and to ensure high performance with high-reliability.
Location to Check
Terminal, unit mounting screws, etc.
Cooling fins
Printed circuit board
Check For
Connection hardware is properly seated and securely tightened.
Built up dust, dirt, and debris
Accumulation of conductive material or oil mist
Solution
Properly seat and tighten hardware.
Blow with dry compressed air:
39.2 X 10
4
to 58.8 X 10
4
Pa, 57 to 85 psi (4 to 6kg / cm
2
) pressure.
Blow with dry compressed air:
39.2 X 10
4
to 58.8 X 10
4
Pa, 57 to 85 psi (4 to 6kg / cm
2
) pressure.
If dust or oil cannot be removed, replace the inverter unit.
Replace the inverter unit.
Power elements and smoothing capacitor
Cooling fan
Abnormal odor or discoloration
Abnormal noise or vibration.
Cumulative operation time exceeding 20,000 hours.
Replace the cooling fan.
• Part Replacement
Inverter’s maintenance periods are noted below. Keep them as reference.
Part Replacement Guidelines
Part
Cooling fan
Smoothing capacitor
Breaker relays
Fuses
Electrolytic capacitors on
PCBs
Standard Replacement Period
2 to 3 years
5 years
—
10 years
5 years
Replacement Method
Replace with new part.
Replace with new part.
(Determine need by inspection).
Determine need by inspection.
Replace with new part.
Replace with new board. (Determine need by inspection).
Note: Usage conditions are as follows:
• Ambient temperature: Yearly average of 30°C.
• Load factor: 80% max.
• Operating rate: 12 hours max. per day.
99
Replacement of cooling fan
• Inverter having W-dimension (width) 2.68 inches (68mm)
1. Removal
(1) Press the right and left tabs of the fan cover inward (direction 1), and then pull them outward (direction 2) to remove the fan assembly from the inverter unit.
(2) Carefully pull the wiring in (direction 3) from the fan cover rear face, and remove the protective tube and connector.
(3) Open the left and right sides of the fan cover to remove the cooling fan from the cover.
2. Mounting
(1) Mount the cooling fan to the fan cover.
The arrow indicating the air flow direction of the cooling fan must be pointing away from the cover.
(2) Connect the connector and mount the protective tube firmly. Mount the connector joint section on the fan cover rear face.
(3) Mount the fan cover on the inverter. Be sure to snap-in the right and left tabs of the fan cover on the cooling fin.
AIR FLOW DIRECTION
100
• Inverter having W-dimension (width) 108mm (4.25 inches)
1. Removal
(1) Remove the front cover and terminal cover, and then remove the cooling fan connector (CN10).
(2) Press the right and left tabs of the fan cover inward (direction 1), and pull the fan cover downward (direction 2) to remove it from the inverter unit. Pull out the wiring from the cable lead-in hole at the bottom of the plastic case.
(3) Open the right and left sides of the fan cover to remove the cover from the cooling fan.
2. Mounting
(1) Mount the cooling fan to the fan cover.
The arrow mark indicating the air flow direction must point away from the cover.
(2) Mount the fan cover on the inverter. Be sure to snap-in the right and left tabs of the fan cover on the cooling fin. Lead in the wiring from the cable lead-in hole at the bottom of the plastic case to the inside of the inverter.
(3) Connect the wiring to the cooling fan connector (CN10) and mount the front cover and the terminal cover.
101
NOTES
102
9. Fault Diagnosis and Corrective Actions
This section describes the alarm and fault displays, explanations for fault conditions and corrective actions to be taken if the VS mini J7 malfunctions.
< Corrective Actions for models without digital operator >
1. Input fault reset or cycle the power supply OFF and ON.
2. When a fault cannot be corrected:
Turn the power supply OFF and check the wiring and control logic.
103
< Corrective Actions of Models with Digital Operator >
: ON : Blinking : OFF
Alarm Display
Digital
Operator
RUN ALARM
(Green) (Red)
Blinking
Alarm Display and Contents
Inverter
Status
Explanation
Causes and
Corrective Actions
UV (Main circuit low voltage)
Main circuit DC voltage drops below the low-voltage detection level while the inverter output is OFF.
200V: Main circuit DC voltage become lowered below approx. 200V (160V for single phase)
400V:Main circuit DC voltage become lowered below approx. 400V.
Check the following:
• Power supply voltage
• Main circuit power supply wiring is connected.
• Terminal screws are securely tightened.
Blinking
Blinking
Blinking
Warning
Fault contacts do not change state.
OV (Main circuit over voltage)
Main circuit DC voltage exceeds the over voltage detection level while the inverter output is OFF.
Detection level: approx. 410V or more (approx. 820V for
400V class).
Check the power supply voltage.
OH (Cooling fin overheat)
Intake air temperature rises while the inverter output is
OFF.
Check the intake air temperature.
CAL (MEMOBUS communications waiting)
Correct data has not been received from the PLC when the parameters n02
(operation command selection) is 2 or n03
(frequency reference selection) is 6, and power is turned ON.
Check communication devices and transmission signals.
104
Alarm Display
Digital
Operator
RUN ALARM
(Green) (Red)
Blinking
Blinking
Inverter
Status
Explanation
Causes and
Corrective Actions
Warning
Fault contacts do not change state.
OP! (parameters setting error when the parameters setting is performed through the MEMOBUS communications)
OP1: Two or more values are set for multi-function input selection.
(parameters n36 to n39)
OP2: Relationship among
V / f parameters is not correct.
(parameters n09, n11, n12, n14)
OP3: Setting value of motor rated current exceeds
120% of inverter rated current. (parameter n32)
OP4: Upper/lower limit of frequency reference is reversed. (parameters n30, n31)
OP5: Setting values of jump frequencies 1 and 2 are not appropriate.
(parameters n49 to n50)
OP9: Carrier frequency setting is incorrect.
(parameter n46)
Check the setting values.
OL 3 (Over torque detection)
Motor current exceeded the preset value in parameter n98.
Reduce the load and expand the accel/decel time.
Blinking
SER (Sequence error)
Inverter receives LOCAL/
REMOTE select command or communication/control circuit terminal changing signals from the multi-function terminal while the inverter is outputting.
Check the external circuit (sequence).
105
Alarm Display
Digital
Operator
RUN ALARM
(Green) (Red)
Blinking
Blinking
Blinking
Blinking or
Inverter
Status
Explanation
Causes and
Corrective Actions
Warning
Fault contacts do not change state.
BB (External base block)
Baseblock command at multifunction terminal is active.
The inverter output is shut
OFF (motor coasting).
Temporary condition is cleared when input command is removed.
Check the external circuit (sequence).
EF (Simultaneous FWD/REV run commands)
When FWD and REV run commands are simultaneously input for over
500ms, the inverter stops according to parameter n04.
Check the external circuit (sequence).
STP (Operator function stop)
STOP/RESET is pressed during running by the control circuit terminals FWD/REV command, or by the run command from communications. The inverter stops according to parameter n04.
STP (Emergency stop)
Inverter receives emergency stop alarm signal. Inverter stops according to parameter n04.
Open FWD/REV command of control circuit terminals.
Check the external circuit (sequence).
FAN (Cooling fan fault)
Cooling fan is locked.
Check the following:
• Cooling fan
• Cooling fan wiring is not connected.
Blinking
CE (MEMOBUS communications fault)
Check the communication devices or communication signals.
106
Alarm Display
Digital
Operator
RUN ALARM
(Green) (Red)
Inverter
Status
Explanation
Causes and
Corrective Actions
OC (Over current)
Inverter output current momentarily exceeds approx.
200% of rated current.
(Control power supply fault)
Voltage fault of control power supply is detected.
• Short circuit or grounding at inverter output side.
• Excessive load GD
2
• Extremely rapid accel/decel time
(parameters n19 to n22)
• Special motor used
Starting motor during coasting
• Motor of a capacity greater than the inverter rating has been started.
• Magnetic contactor open/closed at the inverter output side.
GF (Ground fault) Ground fault current at the inverter output exceeded inverter rated current.
• Check the motor insulation.
• Check that the connection between inverter and motor is not damaged.
Protective
Operation
Output is shut
OFF and motor coasts to a stop.
OV (Main circuit over voltage)
Main circuit DC voltage exceeds the overfatigue detection level because of excessive regenerative energy from the motor.
Detection level:
200V: Stops at main circuit
DC voltage below approx. 410V
400V: Stops at main circuit
DC voltage approx.
820V or more
• Insufficient decel time (parameters n20 and n22)
• Lowering of overhauling load
(elevator, etc.)
⇓
• Increase decel time.
UV1 (Main circuit low voltage)
Main circuit DC voltage drops below the low voltage detection level while the inverter output is ON.
200V: Stops at main circuit
DC voltage below approx. 200V (160V for single phase)
400V: Stops at main circuit
DC voltage approx.
400V or more
• Reduction of input power supply voltage
• Open phase of input supply
• Occurrence of momentary power loss
⇓
Check the following:
• Power supply voltage
• Main circuit power supply wiring is connected.
• Terminal screws are securely tightened.
107
Alarm Display
Digital
Operator
RUN ALARM
(Green) (Red)
Inverter
Status
Explanation
Causes and
Corrective Actions
Protective
Operation
OH (Cooling fin overheat)
Temperature rise because of inverter overload operation or intake air temperature rise.
• Excessive load
• Improper V/f pattern setting
• Insufficient axel time if the fault occurs during acceleration.
• Intake air temperature exceeding 122
°
F
(50
°
C)
• Calling fan stops
⇓
Check the following:
• Load size
• V/f pattern setting
(parameters n11 to n17)
• Intake air temperature
Output is shut
OFF and motor coasts to a stop.
OL1 (Motor overload)
Motor overload protection operates by built-in electronic thermal overload relay.
• Check the load size or V/f pattern setting
(parameters n09 to n15)
• Set the motor rated current shown on the nameplate by parameter n36.
OL2 (Inverter overload)
Inverter overload protection operates by built-in electronic thermal overload relay.
• Check the load size or V/f pattern setting
(parameters n09 to n15)
• Check the inverter capacity.
OL3 (Over torque detection)
Inverter output current exceeded the preset value in parameter n60.
Check the driven machine and correct the cause of the fault, or increase the value of
When over torque is detected, inverter performs operation parameter n60 up to the highest value according to the preset setting of parameter n59.
allowed for the machine.
108
Alarm Display
Digital
Operator
RUN ALARM
(Green) (Red)
Inverter
Status
Explanation
Causes and
Corrective Actions
EF!
(External fault)
Inverter receives an external fault input from control circuit terminal.
EF0: External fault reference through MEMOBUS communications
EF2: External fault input command from control circuit terminal S2
EF3: External fault input command from control circuit terminal S3
EF4: External fault input command from control circuit terminal S4
EF5: External fault input command from control circuit terminal S5
Check the external circuit (sequence).
Protective
Operation
Output is shut
OFF and motor coasts to a stop.
CPF-00
Initial memory fault is detected.
CPF-01
ROM error is detected.
Cycle power.
If the fault remains, replace the digital operator or inverter.
Cycle power. If the fault remains, replace the digital operator or inverter.
CPF-04
EEPROM fault of inverter control circuit is detected.
• Record all parameter data and initialize the parameters. (Refer to page 25 for parameter initialization)
• Cycle power.
If the fault remains, replace the inverter.
109
Alarm Display
Digital
Operator
RUN ALARM
(Green) (Red) or
Inverter
Status
Explanation
Causes and
Corrective Actions
CPF-05
AD converter fault is detected
Cycle power.
If the fault remains, replace the inverter.
Protective
Operation
CPF-06
• Option card connecting fault
Output is shut
OFF and motor coasts to a stop.
CPF-07
Operator control circuit
(EEPROM or AD converter) fault
Remove power to the inverter.
Check the connection
• A non-corresponding option card is connected.
of the digital operator.
Verify inverter software number (n179).
Cycle power. If the fault remains, replace the digital operator or inverter.
CE (MEMOBUS communications fault)
Normal reception of communication data is not possible.
Check the communication devices or communication signals.
STP (Emergency stop)
The inverter stops according to parameter n04 after receiving the emergency stop fault signal.
Check the external circuit (sequence).
—
(OFF)
Stops according to parameter.
• Insufficient power supply voltage
• Control power supply fault
• Hardware fault
For display/clear of fault history, refer to page 29.
Check the following:
• Power supply voltage.
• Main circuit power supply wiring is connected.
• Terminal screws are securely tightened.
• Control sequence.
Replace the inverter.
110
Appendix - CE Conformance
CE Conformance - Low Voltage Directive (LVD) Compliance
111
•
These circuits are hazardous and are separated from accessibility by protective separation.
‚
These circuits are not separated from hazardous circuits by protective separation, but only with basic insulation. These circuits cannot be accessed and must not be interconnected with any circuits which are accessible, unless they are isolated from accessible circuits by supplemental insulation. These circuits can be connected only to the following circuits:
30VDC or less (overvoltage category 2)
250 VAC or less (overvoltage category 2)
ƒ
These circuits are not separated from hazardous circuits by protective separation, but only with basic insulation. These circuits cannot be accessed and must not be interconnected with any circuits which are accessible, unless they are isolated from accessible circuits by supplemental insulation.
CE Conformance - Electro-Magnetic Compatibility (EMC)
Compliance
In order to conform to EMC standards, exclusive-use methods are required for line filter application, cable shielding and inverter installation. An outline of the methods follows.
The line filter and the inverter must be mounted on the same metal plate. The filter should be mounted as close to the inverter as practical. Keep cable as short as possible.
The metal plate should be securely grounded. The ground of the line filter and inverter must be bonded to the metal plate with as much area as possible.
For line power input cable, screened cable is recommended at least within the panel.
The screen of the cable should be connected to a solid ground. For the motor cable, screened cable (max. 20m) must be used and the screen of the motor cable is connected to ground at both ends by a short connection, using as large an area as practical.
For a more detailed explanation, please refer to Making YASKAWA Inverter Products
Conform with EMC Directive (G-TI#99012-V7).
The following table and figures show the line filter list for EMC standards and the installation/wiring of inverter and line filter.
Line Filter List for EMC Conformance
Recommended Line Filters for VS mini J7 made by Rasmi Electronics Ltd
(200V single phase)
VS mini J7 Model
CIMR-J7AUB0P1
CIMR-J7AUB0P2
CIMR-J7AUB0P4
CIMR-J7AUB0P7
CIMR-J7AUB1P5
CIMR-J7AUB2P2
CIMR-J7AUB3P7
RS 1010-J7
RS 1020-J7
RS 1030-J7
RS 1040-J7
Rated Voltage: AC 250V single phase
Ambient Temperature: 40
°
C (max.)
Current
(A)
10
20
30
40
Weight
(kg)
0.6
1.0
1.1
1.2
Dimension
W
×
D
×
H
71 x 45 x 169
111 x 50 x 169
144 x 50 x 174
174 x 50 x 174
112
Recommended Line Filters for VS mini J7 made by Rasmi Electronic Ltd
(200 V three phase)
VS mini J7 Model
CIMR-J7AU20P1
CIMR-J7AU20P2
CIMR-J7AU20P4
CIMR-J7AU20P7
CIMR-J7AU21P5
CIMR-J7AU22P2
CIMR-J7AU23P7
RS 2010-J7
RS 2020-J7
RS 2030-J7
Rated Voltage: AC 250V three phase
Ambient Temperature: 40
°
C (max.)
Current
(A)
10
16
26
Weight
(kg)
0.8
1.0
1.1
Recommended Line Filters for VS mini J7 made by Rasmi Electronic Ltd
(400 V three phase)
VS Mini J7
CIMR-J7AU40P2
CIMR-J7AU40P4
CIMR-J7AU40P7
CIMR-J7AU41P5
CIMR-J7AU42P2
CIMR-J7AU43P7
Model
RS 3005-J7
RS 3010-J7
RS 3020-J7
Rated Voltage: AC 480V three phase
Ambient Temperature: 40
°
C (max.)
Current
(A)
5
Weight
(kg)
1.0
10
20
1.0
1.1
Dimension
W
×
D
×
H
82 x 50 x 194
111 x 50 x 169
144 x 50 x 174
Dimension
W
×
D
×
H
111 x 45 x 169
111 x 45 x 169
144 x 50 x 174
113
Installation of Line Filter and Inverter VS mini J7 (CIMR-J7 ¨¨20P1 to 23 P7)
L1 L2 L3 P E
Shield
Cable
Control Panel
Rasmi
RFI
Filter
E
L1 L2 L3
R S T
VS mini
J7
Ground
Bonds
(remove any paint)
U V W
E
Shield
Cable
Ground Bonds
(remove any paint)
Max.20m
Motor Cable
1M
3-Ph
114
Installation of Line Filter and Inverter VS mini J7 (CIMR-J7 ¨¨B0P1 to B1P5)
L N P E
Shield
Cable
Control Panel
Rasmi
RFI
Filter
Metal
Mounting
Plate
L N
E
R S
VS mini
J7
Ground
Bonds
(remove any
paint)
U V W
E
Shield
Cable
Ground Bonds
(remove any paint)
Max.20m
Motor Cable
1M
3-Ph
115
Safety Warnings and Operating Information for Inverters
Introduction
Depending on their protection rating configuration, parts of inverters can have live, uninsulated and hot surfaces during operation. If housing components, the control unit or terminal covers are removed, incorrect installation and operation can lead to serious injuries and damage to other installations. It is thus absolutely essential to observe all the warnings and instructions in the operating manual. Installation, setup and maintenance should only be performed by properly qualified staff. IEC 364 / Cenelec HD 384 or DIN VDE 0100 and IEC 664 or DIN VDE. The applicable national safety and accident prevention regulations must also be observed.) For the purpose of observance of the safety requirement qualified staff are defined as individuals who are familiar with the installation, setup and operation of the converters and who have the proper qualifications for this work.
Proper use for intended purpose
Inverters are designed for installation in electrical systems or machines. A converter installed in a machine may only be activated if the machine conforms to the provisions of EU directive 89/392/
EEC (machine directives). EN 60204 must also be observed. The converter may also only be operated if the requirements of the EMC directive (89/336/EEC) are also satisfied. This frequency converter conforms to the requirements of the low voltage directive, 73/23/EEC. The harmonized standards of the prEN 50178/DIN VDE 0160 series have been applied, in combination with EN 660439-1 / VDE
06600 Part 500 and EN 60146 / VDE 0558. The specifications on the ratings plate and the specifications and connection requirements described in the documentation must be observed at all times.
Transportation and storage
All instructions for transport, storage and proper handling must be observed. Climatic and environmental conditions must conform to the requirements of prEN 50178.
Installation
The converters must be installed and cooled in compliance with the regulations outlines and referred to in the documentation. The cooling air flow direction is an important requirement that must be observed. This means that the unit may only be installed and operated in the specified orientation (e.g. upright). All distances specified must also be observed. The converters must be protected against excessive stresses. No components may be bent and no distances required for proper insulation may be changed. To prevent the risk of static electricity damage never touch electronic components or contacts.
Electrical connections
All national safety regulations (e.g. VBG 4) must be observed when working on live equipment. The electrical installation of the units must conform to the applicable regulations. For further information please refer to the documentation. In particular, please take care to observe all installation instructions regarding proper EMC immunity, e.g. for shielding, earthing, location of filters and cable routing.
This also applies for equipment with CE approvals. Compliance with the EMC legislation limits is the responsibility of the machine or system manufacturer.
RCCBs
For information on the use of RCCBs with inverters please contact your supplier or Yaskawa representative.
Operation
In some systems it may be necessary to install additional monitoring and protective facilities to comply with the applicable safety and accident prevention regulations. The only changes permitted are to the operator software of the inverters. Please note that the capacitors can remain charged for up to around 5 minutes after the frequency converter has been disconnected from the power supply. You should thus always wait for a short period before opening the unit and touching the electrical connections.
116
EU Manufacturer’s Declaration
Products
Static inverter, series VS mini J7
Scope
YASKAWA inverters are components (BDM*, defined by IEC 22g/21CDV) designed exclusively for installation in machines or systems (end products) by qualified re-users (e.g. mechanical engineering manufacturers).
Responsibility
As a component manufacturer we are responsible for the provision of installation instructions. These can be found in the installation guidelines publication G-TI#99012-V7 (a Yaskawa publication free upon request).
Our products have been tested by authorized bodies pursuant to the requirements of the standard listed below. The products conform to these standards listed below. The products conform to these standards listed below. The products conform to these standards, subject to due and proper observation of the installation instructions provided in section 10 of this manual:
Immunity - EMC resistance pursuant to EN50082-2 (1995)
ENV50204 (1995)
EN61000-4-2 (1996)
EN61000-4-4 (1995)
EN61000-4-6 (1996)
EN61000-4-8 (1994)
Emission - EMC interference emissions pursuant to EN500081-2 (1993)
EN55011 (1991) Class B Group 1
Up to 10m motor cable
Class A Group 1
Up to 20m motor cable
YASKAWA Electric Europe GmbH
Am Kronberger Hang 2
65824 Schwalbach am Taunus
Germany
Always observe all the safety instructions provided in this product documentation!
*AdÜ: Abkürzung bitte kontrollieren.
117
YASKAWA ELECTRIC AMERICA, INC.
Chicago-Corporate Headquarters
Phone: (847) 887-7000 Fax: (847) 887-7310 Internet: http://www.yaskawa.com
MOTOMAN INC.
805 Liberty Lane, West Carrollton, OH 45449, U.S.A.
Phone: (937) 847-6200 Fax: (937) 847-6277
YASKAWA ELECTRIC CORPORATION
New Pier Takeshiba South Tower, 1-16-1, Kaigan, Minatoku, Tokyo, 105-0022, Japan
Phone: 81-3-5402-4511 Fax: 81-3-5402-4580 Internet: http://www.yaskawa.co.jp
YASKAWA ELETRICO DO BRASIL COMERCIO LTDA.
Avenida Fagundes Filho, 620 Bairro Saude Sao Paolo-SP, Brasil CEP: 04304-000
Phone: 55-11-5071-2552 Fax: 55-11-5581-8795 E-mail: [email protected]
YASKAWA ELECTRIC EUROPE GmbH
Am Kronberger Hang 2, 65824 Schwalbach, Germany
Phone: 49-6196-569-300 Fax: 49-6196-888-301 Internet: http://www.yaskawa.de
MOTOMAN ROBOTICS AB
Box 504 S38525, Torsas, Sweden
Phone: 46-486-48800 Fax: 46-486-41410
MOTOMAN ROBOTEC GmbH
Kammerfeldstra β e 1, 85391 Allershausen, Germany
Phone: 49-8166-900 Fax: 49-8166-9039
YASKAWA ELECTRIC UK LTD.
1 Hunt Hill Orchardton Woods Cumbernauld, G68 9LF, Scotland, United Kingdom
Phone: 44-12-3673-5000 Fax: 44-12-3645-8182
YASKAWA ELECTRIC KOREA CORPORATION
Paik Nam Bldg. 901 188-3, 1-Ga Euljiro, Joong-Gu, Seoul, Korea
Phone: 82-2-776-7844 Fax: 82-2-753-2639
YASKAWA ELECTRIC (SINGAPORE) PTE. LTD.
Head Office: 151 Lorong Chuan, #04-01, New Tech Park Singapore 556741, SINGAPORE
Phone: 65-282-3003 Fax: 65-289-3003
TAIPEI OFFICE (AND YATEC ENGINEERING CORPORATION)
10F 146 Sung Chiang Road, Taipei, Taiwan
Phone: 886-2-2563-0010 Fax: 886-2-2567-4677
YASKAWA JASON (HK) COMPANY LIMITED
Rm. 2909-10, Hong Kong Plaza, 186-191 Connaught Road West, Hong Kong
Phone: 852-2803-2385 Fax: 852-2547-5773
BEIJING OFFICE
Room No. 301 Office Building of Beijing International Club,
21 Jianguomanwai Avenue, Beijing 100020, China
Phone: 86-10-6532-1850 Fax: 86-10-6532-1851
SHANGHAI OFFICE
27 Hui He Road Shanghai 200437 China
Phone: 86-21-6553-6600 Fax: 86-21-6531-4242
SHANGHAI YASKAWA-TONJI M & E CO., LTD.
27 Hui He Road Shanghai 200437 China
Phone: 86-21-6533-2828 Fax: 86-21-6553-6677
BEIJING YASKAWA BEIKE AUTOMATION ENGINEERING CO., LTD.
30 Xue Yuan Road, Haidian, Beijing 100083 China
Phone: 86-10-6232-9943 Fax: 86-10-6234-5002
SHOUGANG MOTOMAN ROBOT CO., LTD.
7, Yongchang-North Street, Beijing Economic & Technological Development Area,
Beijing 100076 China
Phone: 86-10-6788-0551 Fax: 86-10-6788-2878
Yaskawa Electric America, Inc., November 1999 YEA-TOA-S606-12 Printed In U.S.A.