S&C AT-2, AT-3, AT-12 Source-Transfer Control Instruction sheet
Pubblicità
Pubblicità
S8C Type AT Source-Transfer Controls
I
Field Replacement
INSTRUCTIONS
I
TABLE OF CONTENTS
I
Section
INTRODUCTION
Page
Number
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
Section Page
Number
REI’LACING TYPE AT-2 SOURCE-TRANSFER CONTROL IN
REPLACING TYPE AT-2
OR TYPE AT-3 SOURCE-TRANSFER
CONTROL IN METALENCLOSED SWITCHGEAR
.
.
. . . . .
.2
WEATHERPROOF ENCLOSURE APPLICATION
. . . . .
REI’LACING TYPE AT-12 SOURCE-TRANSFER CONTROL
.
. .
.7
. . .
I
INTRODUCTION
I
The equipment covered by this publication must be selected
for
a specific application and it must be operated and maintained by qualified persons who are thoroughly trained and who understand any hazards that may be involved. This publication is written only for such qualified persons and is not intended to be a substitute for adequate training and experience i n safety procedures
for
this type
of
equipment.
This
publication provides instructions for replacing an
%!kc
Transfer Control, when such replacement is indicated i n 1
Instruction Sheet 514-520, “S&C Type AT Source-
Transfer Controls: Troubleshooting Guide.”
S&C ELECTRIC CANADA
S&C ELECTRIC COMPANY
New Publlcatlon @1993
Chicago
LTD.
0
Toronto January
INSTRUCTION SHEET
5
1
Page
1
of
24
31,1994
Sac
Type
AT Source-Transfer Controls
I
Field Replacement
I
REPLACING TYPE AT-2
OR TYPE AT-3 SOURCE-TRANSFER CONTROL
IN METAL-ENCLOSED SWITCHGEAR
step 1
on
the Type
AT
control faceplate in the “MANLJAL” position. See Figure
1. step 3
control
AT from
the switchgear-bay stile, until the latch at the rear of the control locks. See Figure 2.
step 2
Decouple t h e Type
MS-2
or
Type AS-30 Switch
Operators. Refer to the instruction sheet furnished for the switch operators.
Page 2 24 S&C ELECTRIC COMPANY
51
INSTRUCTION
SHEET
of
January 31,1994 S&C ELECTRIC CANADA
Chicago
LTD. Toronto
I
REPLACING TYPE AT-2 OR TYPE AT-3 SOURCE-TRANSFER CONTROL
IN METAL-ENCLOSED SWITCHGEAR - Continued
I
Manual/automatic operation selector switch
Overcurrent-lockout indicating lamp and reset liushbutton
(furnished when overcurrent-lockout feature-Catalog Number
Suffix “-K”-is included)
\
.
- Automatic-transfer .-
“ready” indicating lamp
Type AT-3 Control
Type AT-2 Control
Figure 1. Front-panel features of S&C Type AT-2 and Type AT-3 Source-Transfer Controls.
q
s&C ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
INSTRUCTION SHEET
5
1 d-525
Page 3 of 24
January 31,1994
S&C Type AT Source-Transfer Controls
1
IN METAL-ENCLOSED SWITCHGEAR - Continued
Field Replacement
I
REPLACING TYPE AT-2 OR TYPE AT-3 SOURCE-TRANSFER CONTROL step 4
Remove the input plug from the input receptacle located on the programming panel at the rear of the control and immediately transfer it to the shorting receptacle. See Figure 3.
1
step 10
Connect the ground wire to the underside of the replacement Type AT control enclosure. See Figure 4.
Step 11
Set the timer adjustment dials and operating-mode selector switches on the programming panel of the replacement Type AT control in accordance with the settings of the replaced control, as noted in Step 6.
Failure to immediately place the input plug on the shorting receptacle may result in damage to the voltage sensors and voltage limiters that will render the automatic-transfer scheme inoperative.
step 12
Place the manual/automatic operation selector switch on the replacement Type AT control faceplate in the
“MANUAL” position. See Figure 1.
This procedure short-circuits and isolates the secondaries of the voltage sensors, if furnished, and isolates the voltage transformers.
Step 5
Remove the left-hand entrance bay plug and the righthand entrance bay plug from their receptacles on the programming panel. See Figure 3. On Type AT-2 controls, make note of which source is the “preferred” and which is the “alternate,” so that the replacement control can be set accordingly. If thecontrol isfurnished
with optional remote-indication feature (Catalog
Number Suffix “-Al ‘I): Also remove the remoteindication output plug from its associated receptacle on the programming panel.
step 13
Connect the left-hand entrance bay plug and the righthand entrance bay plug to their receptacles on the programming panel of the replacement Type AT control. See Figure 3. On Type AT-2 controls, make sure that the “preferred” and “alternate” settings are in accordance with the designations noted in Step 5. If
the control is furnished with optional remote-
indicationfeature (Catalog NumberSuflix “-Al ‘): Also
connect the remote-indication output plug to its associated receptacle on the programming panel of the replacement Type AT control.
Step 6
Make note of the tuner-adjustment dial settings on the programming panel, as well as the settings of the operating-mode selector switches on the programming panel, so that the replacement control can be set accordingly. See Figure 3.
Step 7
Discpnnect the ground wire from the underside of the
Type AT control enclosure. See Figure 4.
Step 8
Remove and retain the four W-20X W hex-head stainless-steel cap screws and lo&washers at the top and bottom of the Type AT control enclosure, which secure the control to the telescoping support rails. See
Figure 2. Then remove the Type AT control.
Step 9
Set the replacement Type AT control into place and secure it to the telescoping support rails using the
W-20X W’ hex-head stainless-steel cap screws and lockwashers retained from Step 8. See Figure 2.
Telescoping support raiir
‘Ii’-20 x ‘12” hex-head stainless-steel cap screws and lockwashers
Figure 2. Type AT control in drawout position.
5
14-525 INSTRUCTION SHEET
Page 4 of 24
Janbarv 31.1994
S&C ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto •
i
I
REPLACING TYPE AT-2 OR TYPE AT-3 SOURCE-TRANSFER CONTROL
IN METAL-ENCLOSED SWITCHGEAR - Continued
Voltage-sensor signal adjustments and measurements
7
Input plug (signal-voltage, control-voltage, and currentsensing input circuits)
\
Voltage-sensor signaladjustment screws and test jacks
II
II
Timer-adjustment dials on Type AT-3
Controls Catalog -
Numbers 38891 and 38893
Timer-adjustment dials
Shorting receptacle,
Input receptacle
Fuseholders for voltage-transformer secondary fuses
\
\
Pushbutton test switches
to simulate loss of source voltage and, when the optional overcurrent-lockout feature
(Catalog Number Suffix “-K”) is included, an overcurrent condition
Operating-mode
L selector switches
for return transfer
I
. Selector switch included with optional open-phase detection feature (Catalog
Number Suffix “-Ll,”
“-L3,” or “-L4”)
Voltage-t1
Fuseholders for voltage-transfer
grounding circuit (contain solid slugs)
V
Rehote-indication
receptacle provided with optional remoteindication feature (Catalog
Number Suffix “-Al”)
Left-hand entrance bay and right-hand entrance bay plugs
Fuseholder and test jack arrangement
\ on Type AT-2 Control Catalog
Number 38881 and Type AT-3 Control
Catalog Number 38891, for use with three voltage transformers per source
- --.
.^.. -. .~
igure 3. Adjustment, testing, and programming features at rear of Type AT-Z Source-Transter Gonrrol r;aralog Numoer
38883, for use with two S&C Indoor Voltage Sensors and one voltage transformer per source. Insets show construction differences on other models.
INSTRUCTION SHEET 5 141525
Page 5 of 24
January 31,1994 m s&c ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
S&C Type AT Source-Transfer Controls
1
Field Replacement
REPLACING TYPE AT-2 OR TYPE AT-3 SOURCE-TRANSFER CONTROL
IN METAL-ENCLOSED SWITCHGEAR - Continued step 14
Remove the input plug from the shorting receptacle and immediately transfer it to the input receptacle.
See Figure 3.
step 15
Refer to Instruction Sheet 514-501, “S&C Source-
Transfer Controls-Type AT-2: For Two-Way Transfer,
Catalog Numbers 38881 and 38883” or Instruction
Sheet 514-506, “S&C Source-Transfer Controls-Type
AT-3: For Two-Way Transfer with Bus-Tie Switch,
Catalog Numbers 38891 and 38893” and perform the procedures described therein in the “ADJUSTMENTS
AND PROGRAMMING” section. Then perform the procedures described therein in the “OPERATIONAL
TESTING (EXERCISING)” section.
Step 16
After operational testing has been completed, again place the manual/automatic operation selector switch on the replacement Type AT control faceplate in the
“MANUAL” position. See Figure 1.
step 17
Unlock the latch at the rear of the replacement Type
AT control and slou& push the control into the switchgear-bay stile. Secure the control in the stile by tightening the screw fastener. See Figure 2.
step 18
Couple the Type MS-2 or Type AS-30 Switch Operators.
Refer to the S&C instruction sheet furnished for the switch operators.
step 19
Place the manual/automatic operation selector switch on the replacement Type AT control faceplate in the
“AUTOMATIC” position and confirm that the automatic-transfer “ready” indicating lamp is illuminated.
Ground wire 2
Figure 4. Disconnecting ground wire from underside of Type AT control.
5
14-525 INSTRUCTION SHEET
Page 6 of 24
January 31,1994
S&C ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
I
REPLACING TYPE AT-2 SOURCE-TRANSFER C6NTROL IN WEATHERPROOF
I
ENCLOSURE APPLICATION
Step 1
on the Type AT-2 control in the “ M A N U A L ” position.
See Figure 5.
Step 2
Decouple the Type AS-1A or Type
AS-10
Switch
S&C
instruction sheet furnished for the switch operators.
Step 3
Remove the voltage-transformer secondary fuses and grounding circuit slugs. See Figure 5.
Step
4
Remove the source 1 plug and the source 2 plug from their receptacles. See Figure
5.
Make note of which source is the “preferred and which is the “alternate,”
so
that the
If
the control is furnished with optional remote- indication feature ’T):Also
remove the remote-indication output plug from its associated receptacle.
step 5 as
well
as
switches,
so
that the
See Figure
5.
Step 6
llisconnect the ground wire from the underside of the
Type AT-2 control. See Figure
5.
Step 7
Remove and retain the four %“-2OX%” hex-head stainless-steel cap screws and lockwashers at the top and bottom of the Type AT-2 control, which secure
5.
Then remove the Type AT-2 control.
Step 8
Set the replacement Type AT-2 control into place and secure it to the weatherproof enclosure using the
Vi””20
X
%” hex-head stainless-steel cap screws and lockwashers retained from Step 7. See Figure
5.
I
I
S&C ELECTRIC CANADA LTD.
S&C ELECTRIC COMPANY
Toronto January
Chicago Page
INSTRUCTION SHEET
5
1
7 of 24
31,1994
SBC Type AT Source-Transfer Controls
I
Field
Replacement
I
REPLACING TYPE AT-2 SOURCE-TRANSFER CONTROL IN WEATHERPROOF
ENCLOSURE APPLICATION
-
step 9
Connect the ground wire to the underside of the replacement Type AT-2 control enclosure. See Figure 5.
Step 10
Set the timer adjustment dials and operating-mode
step 14
Refer to Instruction Sheet 514-510, “S&C Source-
Transfer Controls--Type AT-2: In Weatherproof
Enclosures” and perform the procedures described therein in the “ADJUSTMENTS AND PROGRAMMING” section. Then perform the procedures described therein in the “OPERATIONAL TESTING
“ section. in accordance with the settings of the replaced control,
as
noted in Step 5.
Step 15
After operational testing has been completed, again
Step 11
Place the manual/automatic operation selector switch
“ M A N U A L ” position. See Figure 5. on the replacement Type AT-2 control in the “MANUAL“ position. See Figure 5.
Step 12
Connect the source 1 plug and the source 2 plug to
Step 16
AS-10
Switch Operators.
Refer to the S&C instruction sheet furnished for the switch operators.
See Figure
5.
Make sure that the “preferred” and
“alternate” source settings are in accordance with the designations noted in Step 4.
If the control isfumzished
with optional remote-indication feature (Catalog
Number Suffix “-A1
’9:
Also
connect the remote- indication output plug to its associated receptacle on the replacement Type AT control.
Step 17
Place the manual/automatic operation selector switch on the replacement Type AT-2 control in the “AUTO-
MATIC” position and confirm that the automatic- transfer ‘‘ready” indicating lamp is illuminated.
Step 13
Replace the voltage-transformer secondary fuses and grounding circuit slugs. See Figure 5.
5
1
INSTRUCTION SHEET
Page 8 of 24 S&C ELECTRIC COMPANY
January 31,1994 S&C ELECTRIC CANADA LTD.
Chicago
Toronto
I
REPLACING TYPE AT-2 SOURCE-TRANSFER CONTROL IN WEATHERPROOF
ENCLOSURE APPLICATION - Continued
Time range selector switch
Voltage-transformer signalvoltage test jacks
Voltage-transformer secondary fuses and grounding slugs stainless-steel
Overcurrent-lockout pickup
level switch (furnished when overcurrent-lockout feature-
Catalog Number Suffix
“-Kl”-is included)
Pushbutton test switches to simulate loss of source voltage and (when overcurrent-lockout feature-Catalog Number Suffix
“-Kl” or “-K2”-is included) an o v e r c u r r e n t c o n d i t i o n
Operating-mode selector
switches for return transfer
Manual/automatic operation selector switch
Overcurrent-lockout indicating lamp and reset pushbutton
(furnished when overcurrentlockout feature-Catalog
Number Suffix “-Kl” or
“-K2”-is included)
Source-voltage indicating lamps
B’
Automatic-transfer “ready” indicating lamp
Fuseholders for signal-voltage and grounding circuits
\
Selector switch (furnished when open-phase detection feature-
Catalog Number Suffix “-Ll”-is included)
\
Ground wire
Control-voltage-seeking relay
Source 1 and source 2 plugs
Terminal strips for external connections
Remote-indication receptacle
(furnished when remoteindication feature-Catalog
Number Suffix “-Al”-is included)
Figure 5. Adjustment, testing, and programming features of Type AT-2 Source-Transter control In wearnerproor enclosure.
m s&c ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
INSTRUCTION SHEET 5 141525
Page g of 24
January 3l,lgg4
I
S&C Type AT Source-Transfer Controls
I
Field Replacement
I
REPLACING TYPE AT-I2 SOURCE-TRANSFER CONTROL
the pad-mounted gear, which is stamped on the nameplate affixed to the enclosure door. Note the
“ R supplement to the catalog number
. . . some of the steps which follow vary according to this
“R”
step 5
Remove the input plug from the input receptacle located below the programming panel and
immediately
9.
I step
1
Failure to immediately place the input plug on the shorting receptacle may result in damage to the voltage sensors and w render
step 2
Place the manual/automatic operation selector switch on the Type AT-12 control faceplate in the
“ M A N U A L ” position. See Figure 6.
step 3
For pad-mounted gear models having an
“Rl,
’’
or “R3”
supplement to the catalog number and furnished with optimal decoupling feature (Catalog
Number Suffix
“C8’J):
Decouple each stored-energy operator using the utility tool furnished. See Figure 7. labeled “Decoupling Socket.” Insert the utility tool
all the way into the soclcet
to depress the spring-loaded locking pin. While maintaining the locking pin depressed, turn the utility tool
counterclockwise
5 to
7 complete turns, until firm resistance is felt and the
“DECOUF’LED target is
centered
in the indicator port.
Remove the tool. Proceed to Step
4.
For
pad-mounted gear models having an
“R4”
supplement
to
the catalog number:
Decouple each stored-energy operator by grasping the associated decoupler and turning it
counterclockwise
5 to
6
complete turns, until firm resistance is felt and the
“DECOUPLED” target
is
centered
in the indicator port.
See Figure 8.
Step 4
Remove the bolted cover labeled “Source-Transfer
Control Switches and Timers” to gain access to the programming panel of the Type AT-12 control. See
Figure 9.
This procedure short-circuits and isolates the secon- daries of the voltage sensors and also isolates the current sensors utilized with the optional overcurrent- lockout feature (Catalog Number S u f f i
“-Y2”
if furnished.
Step
6
Remove the left-hand switch compartment plug and right-hand switch compartment plug from the preferred-source receptacle and alternate-source receptacle on the programming panel. See Figure 9.
Make note of which source is the “preferred” and which is the “alternate,” that the replacement control can be set accordingly.
is
optimal remote-indicatim feature (Catalog Number
Suffix
“-A1
’7:
Also
remove the remote-indication output plug from its associated receptacle on the programming panel.
Step 7
Make note of the timer-adjustment dial settings on the programming panel,
as
well
as
the settings
of
the panel,
so
that the replacement control can accordingly. See Figure 9. be set
5
1
INSTRUCTION SHEET
Page 10 of 24
January 31,1994 S&C
S&C ELECTRIC COMPANY Chicago
ELECTRIC CANADA LTD. Toronto
REPLACING TYPE AT-12 SOURCE-TRANSFER CONTROL - Continued
Manual/automatic operation selector switch
Overcurrent-lockout reset pushbutton and indicating
lamp (furnished when overcurrent-lockout feature-
Catalog Number Suffix “-Y2” or “-Y3”-is included)
Source-voltage indicating lamps
. putomatic-transfer “ready”
Indicating lamp
Figure 6. S&C Type AT-12 Source-Transfer Control taceplare.
q
s&c ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
INSTRUCTION SHEET 5 l&525
Page 11 of 24
January 3l,lgg4
S&C Type AT Source-Transfer Controls
1
Field Replacement
REPLACING TYPE AT-12 SOURCE-TRANSFER CONTROL - Continued
Decoupling socket
Decoupling indicator
‘l4”-20 x %” round-head
‘stainless-steel screws (2)
Utility tool
- r o t a t e counterclockwise to decouple switch from switch operator
Hinged cover
Figure 7. Decoupling stored-energy operator. Applicable
to pad-mounted gear models having an “Rl,” “R2,” or “R3”
suppfement to the catalog number and furnished with
optional decoupling feature (Catalog Number Suffix “-C6”).
Figure 6. Decoupling stored-energy operator. Applicable to pad-mounted gear models having an “R4” supplement to the catalog number.
514m525
INSTRUCTION SHEET
Page 12 of 24
January 31,19Q4
S&C ELECTRIC COMPANY
l
Chicago s&C ELECTRIC CANADA LTD.‘* Toronto
REPLACING TYPE AT-12 SOURCE-TRANSFER CONTROL - Continued
Voltage-sensor signal adjust-
ments and measurements for preferred and alternate sources
Voltage-sensor signaladjustment screws and test jacks
Selector switch included
/ with the optional open-phase detection feature (Catalog
Number Suffix “-Yl” or “-Y3”)
Input plug (signal-voltage, control-voltage, and currentsensing input circuits)
Timer-adjustment dials
Remote-indication receptacle
(not visible) provided with optional remote-indication feature (Catalog Number
Suffix “-Y4”)
Pushbutton test switches to
simulate loss of source voltage and, when the optional overcurrent-lockout feature
(Catalog Number Suffix “-Y2” or “-Y3”) is included, an overcurrent condition
Operating-mode selector
switches for return transfer
Preferred-source and alternate-source connector
plugs-interchangeable, to allow selection of either source as preferred
. Shorting receptacle
Figure 9.
Type AT-12 Source-Transfer Control programming panel with bolted cover removed, showing adjustment, measurement, testing, and programming features of the control.
I lm
S&C ELECTRlC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
INSTRUCTION SHEET
5 1 a-525
Page 13 of 24
January 31,1994
S&C Type AT Source-Transfer Controls
1 Field Replacement
1 REPLACING TYPE AT-12 SOURCE-TRANSFER CONTROL - Continued step 8
For pad-mounted gear moo!.& hating an ‘Rl, ” “R2, ” or “R3” supplement to the catalog number and furnished with optional decoupling feature (Catalog
Number Suffix “T8’3: Discharge each stored-energy operator quick-make, quick-break
mechanism using
the utility tool furnished. See Figure 10. For each storedenergy operator, open the emergency trip access cover and insert the utility tool into the socket on the shaft.
Turn the utility tool in the direction indicated to either
trip open or trip closed, as appropriate. Remove the tool. Or, on earlier models, turn the associated manual trip lever to the trip open. or trip closed position, as appropriate. For pad-mounted gear models having an
“Rl” or “R2” supplement to the catalog number, proceed to Step 9. For pad-mounted gear models having an “R3” supplement to the catalog number and horizontally split access panels as shown in Figure 14, proceed to
Step 10. For pad-mounted gear models having an “R3” supplement to the catalog number and vertically split access panels as shown in Figure 15, proceed to Step 11.
For pad-mounted gear models having an “‘R4”
supplement to the catalog number: Discharge each stored-energy operator quick-make, quick-break dual-purpose manual handle mechanism using the furnished. See Figure 11. For each stored-energy operator, open the emergency trip access cover and insert the keyed end of the dual-purpose manual handle into the groove of the tripping shaft. Turn the manual handle in the direction indicated to either trip gpen or trip closed, as appropriate. Proceed to Step 12.
I
Utility tool-
turn to trip open
or trip closed
position
Emergency trip access cover
igure 10. Discharging stored-energy operator quick-make,
quick-break mechanism. Applicable to pad-mounted gear models having an “Rl, ” “R2,” or “R3” supplement to the catalog number and furnished with optional decoupling feature (Catalog Number Suffix “-CS”).
J
Figure 11. Discharging stored-energy operator qurcK-maKe, quick-break mechanism. Applicable to pad-mounted gear models having an “R4” supplement to the catalog number.
5 l&525 INSTRUCTION SHEET
Page 14 of 24
January 31,1994
S&C ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
•
* i
REPLACING TYPE AT-I2 SOURCE-TRANSFER CONTROL
-
Step
9
models
having an ”or
“R2” suppkm#at to the catalog number:
Remove the switch operator access panels from both the left-hand and right-hand sides of the low-voltage control compart- ment, using the following procedure. plate
on
its associated bottom switch operator access panel, to facilitate reassembly. See Figure 7.
Remove the two ‘/4“-20X %” round-head stainless- steel screws that secure each hinge plate to its associated bottom switch operator access panel.
Retain the hardware.
I
(a) Remove the bolted cover labeled “Terminal Blocks“ on each side. See Figure
12.
(b)
If
the pad-mounted
gear
is
optional decoupling feature (Catalog NumberSuffKx
“-C8’3:
Open the hinged cover labeled “Decoupling Socket”
If the pad-mounted gear is
not furnished with optional o!6coupling feature:
Remove the two
‘h”“20X
%“ hex-head stainless-steel cap screws, lockwashers, and flat washers located near the center
of
each bottom switch operator access panel. See Figure
13.
Retain the hardware. plate on its associated bottom switch operator access panel, to facilitate reassembly. See Figure 7.
Remove the two W-20
X
M” round-head stainless- steel screws that secure each hinge plate to its associated bottom switch operator access panel.
Retain the hardware.
f l the pad-mounted gear
is
not furnished with optional decoupling feature:
Remove the two
%“-20X
M” hex-head stainless-steel cap screws, lockwashers, and flat washers located near the e) Detach the bottom switch operator access panel on each side by removing the three
or four
W-20
X%” hex-head stainless-steel cap screws, lockwashers, and flat washers that secure each panel. See Figure
14.
Retain the hardware.
f )
Proceed to Step 13.
See Figure
(c) Detach the bottom switch operator access panel on each side by removing the three or four
1/4“-20 X %“ hex-head stainless-steel cap screws, lockwashers, and flat washers that secure each panel. See Figure
12.
Retain the hardware.
(d) Proceed to Step
13.
step 10
For pad-mounted gear models having an “R3” suppkrrwnt to the catalog number
and horizontally
split access panels as s h o w n
in Rgure
switch operator access panels from both the left-hand and right-hand sides of the low-voltage control compartment, using the following procedure.
(a) Remove the bolted cover labeled ‘Terminal Blocks” on each side. See Figure
14.
(b) Mark the positions of the middle and bottom stationary door latches on the center channel to facilitate reassembly. See Figure
14.
( c )
Detach the middle and bottom stationary door latches by removing the
~/1sf‘-18 X
1“ hex-head zinc- plated cap screws and hex nuts that secure the latches in place. See Figure
14.
Retain the hardware.
(d)
If
the pad-mounted gear decoupling feature (Catalog Number
S u f l k
‘‘-C8’9:
step
11
For pad-mounted gear models having an “R3” supplement to the catalog number and vertically split
access
panels as
operator vertical access panels from both the left-hand and right-hand sides
of
t h e low-voltage control compartment, using the following procedure.
(a) Remove the bolted cover labeled ‘Terminal Blocks” on each side. See Figure
15.
(b)
If thepadimrvuntedgear isfumzished with optional
decouplingfeature (Catalog Number SuffKx
“-C8’3:
Open the hinged cover labeled “Decoupling Socket” on each side and mark the position of each hinge plate on its associated switch operator vertical
7.
Remove the two
%“-20X %” round-head stainless- steel screws that secure each hinge plate to its associated switch operator vertical access panel.
Retain the hardware.
If the pad-mounted gear
is
not furnished with optional decoupling feature:
Remove the two
%“-20 X
? h n
hex-head stainless-steel cap screws, lockwashers, and flat washers located near the center of each switch operator vertical access panel. See Figure
13.
Retain the hardware.
(c) The switch operator vertical access panel on each side is secured by five ‘/4””20X%” hex-head stainless-steel cap screws, lockwashers, and flat washers. See Figure
15.
Two wire leads are connected to the charging-shaft access port switch on the back of each panel. Remove the five screws and associated lockwashers and flat washers from on each side and mark the position of each hinge
S&C ELECTRIC
S&C ELECTRIC CANADA LTD.
COMPANY Chicago Page
Toronto January
INSTRUCTION SHEET
5
1
15 of 24
31,1994
S&C Type AT Source-Transfer Controls
I
1
Field ReDlacement
-r---
REPLACING TYPE AT-12 SOURCE-TRANSFER CONTROL - Continued
Operator target indicates whether stored-energy ooerator is in switch-ooen or switch-closed position and whether quick-make, quick-break mechanism is charged or discharged
\
Emergency-trip access cover
I
Charging shaft
Operation selector
Remote-control receptacle
(Catalog Number Suffix
Top switch operator access panel
%“-20 x J/4” hex-head stainless-steel cap screws, lockwashers, and flat washers
\
Bottom switch operator access panel target
I
Switch-position
I
Type AT-1 2
Source-Transfer Control
Termin~l-block compartment
\
Bolted cover provides access to the
AT-12 control’s programming panel
Hinged cover provides access to reverse-drive hub and, if decoupling feature (Catalog
Number Suffix “-C8”) is furnished, to decoupling sockets
Utility tool used for emergency manual tripping and, if optional decoupling feature is furnished, for decoupling stored-energy operator from interrupter switch
I
Decoupling indicator (furnished with optional decoupling feature)
lure 12. Low-voltage control compartment of pad-mounted gear models having an “Rl,, or --nz supplement
IO
me catalog
5 l&525 INSTRUCTION SHEET
Page 16 of 24
January 31,1994
S&C ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
q
*
REPLACING TYPE AT-12 SOURCE-TRANSFER CONTROL - Continued
each switch operator vertical access panel,
taking
care not to damage the wire leads or to bend the terminals of the access port switch. Retain the hardware. Mark the positions of the leads and disconnect them.
step 13
Disconnect the ground wire on the right side of the
Type AT-12 control enclosure. See Figure 17.
I
leads may result in improper reconnection that will render the pad-mounted gear inoperative.
Step 14
Remove the four WL20X 1” hex-head zinc-plated cap screws, lo&washers, and flat washers at the top and bottom of the Type AT-12 control enclosure, which secure the control to the upper mounting bracket and to the lower-left and lower-right mounting brackets.
See Figure 18. Retain the hardware.
(d) Remove the lower-center access panel surrounding the Type AT-12 control faceplate, which is secured at the bottom by a l/4”--20X3/4” hex-head stainlesssteel cap screw, lockwasher, and flat washer. See
Figure 15. Retain the hardware.
(e) Proceed to Step 13.
Step 12
For pad-mounted gear models having an “R4”
supplement to the catalog number: Remove the switch operator vertical access panels from both the left-hand and right-hand sides of the low-voltage control compartment, using the following procedure.
(a) Remove the bolted cover labeled “Terminal Blocks” on each side. See Figure 16.
(b) The switch operator vertical access panel on each side of the low-voltage control compartment is secured by live W-20X W hex-head stainless-steel cap screws, lo&washers, and flat washers. See
Figure 16. Two wire leads are connected to the charging-shaft access port switch on the back of each panel. Remove the five screws and associated lockwashers and flat washers from each switch operator vertical access panel, taking care not to damage the wire leads or to bend the terminals of the access port switch. Retain the hardware.
Mark the positions of the leads and disconnect them.
step 15
Remove the lope AT-12 control from the low-voltage control compartment by sliding it forward, to the right, and out from behind the center channel.
Step 16
Insert the replacement Type AT-12 control into the right-hand side of the low-voltage control compartment. Slide it in, then to the left, and behind the center channel.
Step 17
Loosely attach the replacement Type AT-12 control to the upper mounting bracket and to the lower-left and lower-right mounting brackets using the four
W-20X 1” hex-head zinc-plated cap screws, lockwashers, and flat washers retained from Step 14. See
Figure 18. Slide the control forward, toward the center channel, as far as possible. Then securely tighten the screws.
leads may result in improper reconnection that will render the pad-mounted gear inoperative.
(c) Remove the lower-center access panel surrounding the Type AT-12 control faceplate, which is secured at the bottom by a I/“--20X3/4” hex-head stainlesssteel cap screw, lo&washer, and flat washer. See
Figure 16. Retain the hardware.
Figure 13. Hardware to be removed near center of switch operator access panel on pad-mounted gear models not furnished with optional decoupling feature.
q
S&C ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
INSTRUCTION SHEET 5 14-525
Page 17 of 24
January 31,1994
S&C
Type AT Source-Transfer Controls
1
Field Replacement
1 REPLACING TYPE AT-12 SOURCE-TRANSFER CONTROL - Continued
Operator target indicates whether stored-energy operator is in switch-open or switch-closed position and whether quick-make, qui ck-break mechanism is charged or discharged
Remote-control receptacle
(Cataloa Number Suffix
‘;-cl I”)-
Open/close pushbuttons
\
Middle stationary door latch
\
%6”- 18X1” hex-head
zinc-plated cap screws and hex nuts
Upper stationary
Emergency-trip access cover
I
Charging shaft
Operation counter
/
Operation selector
I
Manual charging handle-
Switch-position * target
\
Vi’-20 x %” stainless-steel washers
Terminal-block compartment
/
/
Source-Transfer Control
Bottom stationary door latch
I
L p a n e l
Bottom switch operator access
Utility’tool used for emergency manual tripping and, if optional decoupling feature is furnished, for decoupling stored-energy operator from interrupter switch
Bolted cover provides access to the
AT-12 control’s programming panel
Decoupling indicator (furnished with optional decoupling feature)
Hinged cover provides access to reverse-drive hub and, if decoupling feature (Catalog
Number Suffix “XX”) is furnished, to decoupling sockets
Figure 14. Low-voltage control compartment of pad-mounted gear models having an “R3” supplement to the catalog
nUmDer
and horizontally split access panels.
5
14-525 INSTRUCTION SHEET
Page 18 of 24
January 31,1994
S&C ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
q
*
REPLACING TYPE AT-12 SOURCE-TRANSFER CONTROL - Continued
Operator target indicates whether stored-energy operator is in switch-open or switch-closed position and whether quick-make, quick-break mechanism is charged or discharged
\
a
bpenlclose pushbuttons
Emergency-trip access cover
/
I
/
I
%“-20x %” hex-head stainless-steel cap screws,
[ lockwashers, and flat washers
I
-Switch operator vertical access panel
I
Switch-position target
I
Terminal-block compartment
T/y pe AT-1 2
Source-Transfer Control
\
Bolted cover provides access to the
\ Lower-center access panel
AT-12 control’s programming panel
\
Decoupling indicator (furnished with optional decoupling feature)
Hinged cover provides access to reverse-drive hub and, if decoupling feature (Catalog
Number Suffix “-03”) is furnished, to decoupling sockets
\
Utility tool used for emergency manual tripping and, if optional decoupling feature is furnished, for decoupling stored-energy operator from interrupter switch
..- -.. _ . . . .
. .
igure 15. Low-voltage control compartment of pad-mounted gear models having an “R3” supplement to tne catalog numoer and vertically split access panels.
q
s&C ELECTRIC
COMPANY l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
INSTRUCTION SHEET 5 141525
Page 19 of 24
January 3l,lgg4
S&C Type AT Source-Transfer Controls
1 Field Replacement
1 REPLACING TYPE AT-12 SOURCE-TRANSFER CONTROL - Continued
Operator target indicates whether stored-energy operator is in switch-open or switch-closed position and whether quick-make, quick-break mechanism is charged or discharged
,
Open/close pushbuttons
\
-control receptacle
Number Suffix
anual handle
%“-20X J/s” hex-head stainless-steel cap screws, lockwashers, and flat washers
Operation counter
Emergency-trip access cover
Switch operator vertical access
~~
\ Decoupler indicator
Type AT-1 2
Source-Transfer Control
\
Lower-center access panel
T&minal-block compartment
\
Bolted cover provides access to the
AT-12 control’s programming panel
Figure 16. Low-voltage control compartment of pad-mounted gear models having an “R4” supplement to the catalog number.
5 141525 INSTRUCTION SHEET
Page 20 of 24
January 31,1994
S&C ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
I
REPLACING TYPE AT-12 SOURCE-TRANSFER CONTROL
-
Connect the ground wire to the right side
of
the replacement Type AT-12 control enclosure. See
Figure 17.
Step 18
For pad-mounted gear models having an "Rl" or
"R2" supplement to the catalog number, proceed to Step
19. For pad-mounted gear models having an "R3" supplement to the catalog number and horizontally split access panels
as
shown in Figure 14, proceed to
Step 20. For pad-mounted gear models having an "R3" supplement to the catalog number and vertically split access panels
as
shown in Figure 15, proceed to Step
21. For pad-mounted gear models having an "R4"
Step 19
models
hawing a n "R1 "or "R2"
supplement to the catalog number:
Replace the switch
I step
20
For pad-mounted gear models having an "R3" supplement to the catalog number and horizontally split
m e s s
panels as
shown
i n
Figure 14:
Replace the switch operator access panels on the left-hand and right-hand sides of the low-voltage control compart- ment, using the following procedure.
(at)
Reattach the bottom switch operator access panel on each side using the three or four '/4"-20X3/4" hex-head stainless-steel cap screws, lockwashers, and flat washers retained from Step 10. See
Figure 14. Be sure that the decoupling indicator and switch-position target are centered in their respective port openings.
(b)
lf the pad-mounted gear furnished with optimal decoupling feature (Catalog Number S u f f k V 8 ' 3 :
Reattach the hinged covers to the bottom switch following procedure.
(a) Reattach the bottom switch operator access panel on each side using the three
or
four 1Y4"-20X3/" hex-head stainless-steel cap screws, lockwashers, and flat washers retained from Step
9.
See
Figure 12. Be sure that the decoupling indicator and switch-position target are centered in their respective port openings.
Also
be sure to connect using the two W-20 X
W
round-head stainless- steel screws retained from Step 10. See Figure 7.
If the pad-mounted gear is not furnished with
optional &coupling feature:
Replace the two
W-20 X %" hex-head stainless-steel cap screws, lockwashers, and flat washers retained from Step
10, near the center of each bottom switch operator access panel. See Figure 13.
( e )
Loosely
reattacH the middle and bottom stationary door latches using the 5/16"-18X 1" hex-head zinc- utility tool
as
shown.
(b)
If
the pad-mounted gear
Reattach the hinged covers to the bottom switch
10. See Figure 14.
( d )
S h l y
close the right-hand door and observe the positions of the latching parts on the door relative to the stationary door latches. The 5/16-inch and
%inch clearances indicated
in
Figure 19 must be maintained. Readjust each stationary latch
as
using the two 1/i"-20 X %" round-head stainless- steel screws retained from Step 9. See Figure 7.
If
the pad-mounted gear
is
not furnished with optional decoupling feature:
Replace the two
~/4"-20X 'h" hex-head stainless-steel cap screws, lockwashers, and flat washers retained from Step
9,
near the center of each bottom switch operator access panel. See Figure 13.
(c) Replace the bolted cover labeled 'Terminal Blocks" on each side. See Figure 12.
(d)
Proceed to Step 23. torque the 5/16"-18X 1" hex-head zinc-plated cap screws to 24 to 28 foot-pounds.
( e )
Replace the bolted cover labeled "Terminal Blocks" on each side. See Figure 14.
( f) Proceed to Step 23.
S&C ELECTRIC COMPANY
S&C ELECTRIC CANADA LTD. Toronto January
Chicago Page 21
INSTRUCTION SHEET
of 24
31,1994
S&C Type AT Source-Transfer Controls
I
Field Replacement
REPLACING TYPE AT-12 SOURCE-TRANSFER CONTROL
-
Step 21
For
pad-mounted gear models having a n “R3” supplement to the catalog number and vertically split
access
panels as
operator vertical access panels on the left-hand and right-hand sides of the low-voltage control compart- ment, using the following procedure.
Replace the lower-center access panel surrounding t h e Type AT-12 control faceplate using the
W-20 X %“ hex-head stainless-steel cap screw,
(b) Reconnect the wire leads to the charging-shaft access port switch on the back of each switch operator access panel. Then reattach each access steel cap screws, lockwashers, and flat washers retained from Step 12. See Figure 16. Be sure that the emergency-trip shaft, operator target, switch- position target, and decoupler indicator are centered in their respective port openings.
Also
be sure to connect the chain for the dual-purpose manual handle as shown.
(e) Replace the bolted cover labeled ‘Terminal Blocks” on each side. See Figure 16.
I
See Figure 15.
Reconnect the wire leads to the charging-shaft access port switch on the back of each switch operator access panel. Then reattach each access panel using the five %-20 X
%‘‘
steel cap screws, lockwashers, and flat washers retained from Step 11. See Figure 15. Be sure that
Step 23
Set the timer adjustment dials and operating-mode selector switches on the programming panel
of
the replacement Type AT-12 control in accordance with the settings of the replaced control,
as
noted in Step 7. position target, and decoupling indicator are centered in their respective port openings.
Also
be
Step 24
on the replacement Type AT-12 control faceplate the “MANUAL” position. See Figure 6. in
decoupling feature
S u f l k ‘‘T8’1):
Reattach each hinged cover to the associated switch operator access panel by securing its hinge plate using the two ‘/4“-20X%“ round-head stainless-steel screws retained from Step 11. See
Figure 7.
If the p a d - m n t e d gear i s not furnished with optional decoupling feature:
Replace the two
‘/4”-20 X %” hex-head stainless-steel cap screws, lockwashers, and flat washers retained from Step
11, near the center access panel. See Figure 13.
Step 25
Connect the left-hand switch compartment plug and right-hand switch compartment plug to their recep- tacles on the programming panel of the replacement
Type AT-12 control. See Figure 9. Make sure that the
“preferred” and “alternate” settings are in accordance with the designations noted in
Step 6. If
the pad- mounted
gear
is furnished with optional remote-
’?:
Also connect the remote-indication output plug to its associated receptacle on the programming panel of the replacement Type AT-12 control.
Replace the bolted cover labeled ‘Terminal Blocks” on each side. See Figure 15.
Proceed to Step 23.
Step 26
Remove the input plug from the shorting receptacle and immediately transfer it to the input receptacle.
See Figure 9.
For
step 22
pad-mounted gear models having an
“R4”
supplement
to
the catalog number:
Replace the switch operator vertical access panels on the left-hand and right-hand sides
of
the low-voltage control compart- ment, using the following procedure. sensors and voltage limiters that w render the t h e Type AT-12 control faceplate using the
?4”-20 X
%” hex-head stainless-steel cap screw, lockwasher, and flat washer retained from Step
See Figure 16.
5
1
INSTRUCTION SHEET
January 31,1994
S&C ELECTRIC COMPANY
S&C ELECTRIC CANADA LTD.
Chicago
Toronto
REPLACING TYPE AT-12 SOURCE-TRANSFER CONTROL - Continued
Figure 17. Disconnecting
Source-Transfer Control.
ground wire on Type AT-12
I
‘Ii’-20 x 1” hex-head zinc-plated cao screws.
lodkwashers, and flat washers
Upper mounting bracket.
Ground wire’
Lower-left mounting bracket
Figure 18. Removing Type AT-12 Source-Tnrnsfer Control.
Pad-mounted gear model having an “R2” supptemeut to the catalog number is illustrated.
S&C ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
INSTRUCTION SHEET 5 141525
Page 23 of 24
January 3l,lgg4
x -
-
S&C Type AT Source-Transfer Controls
I
Step 27
Refer to Instruction Sheet 663-501 or 663-502, “S&C
Pad-Mounted Gear-Power-Operated
PMH
Models
(Operation and Adjustment)” or Instruction Sheet
667-551, “S&C Pad-Mounted Gear-Power-Operated
I
Field Replacement
REPLACING TYPE AT-I2 SOURCE-TRANSFER CONTROL
-
(b)
For each stored-energy operator, grasp the associated decoupler and turn it
clockwise
5
to
6 complete turns, until firm resistance is felt and the “COUPLED” target
is
centered in
the indicator port. See Figure 8.
I
the source-transfer control adjustment and program- ming procedures described therein. Then perform the
Step 31
Replace the bolted cover labeled “Source-Transfer
Control Switches and Timers.”
Step 28
After operational testing has been completed, again on the replacement Type AT-12 control faceplate in the “ M A N U A L ” position. See Figure
6.
Step 29
For
pad-mounted gear models having a n “Rl,
”
“R2,
’’
or “R3” supplement
to
the catalog number and furnished with optional decoupling feature (Catalog
Number Suffix “-C8’7:
Couple each stored-energy operator, using the following procedure.
(a)
Malce sure that the stored-energy operators are in the sume positions (open
or closed) as their associated Mini-Rupter Switches by observing the switch-position and operam-position targets.
If required, use the open/close pushbuttons (pro- vided control power is available) to reposition the operator(s).
(b) For each stored-energy operator, open the hinged tool furnished
the socket
to depress the spring-loaded locking pin. While maintaining the locking pin depressed, turn the utility tool
clockwise
5 to 7 complete turns, until firm resistance is felt and the “COUPLED” target
centered
in the indicator port.
is
7.
Remove the tool. Then close the hinged cover and secure it with the knurled screw.
(c) Proceed to Step 31.
Step
30
For
pad-mounted gear models having an
“R4” supplement
to
the catalog
number:
Couple each stored- energy operator, using the following procedure.
(a)
the same positions (open
or
closed)
as
their
associated Mini-Rupter Switches by observing the
switch-position and operator-position targets.
If required, use the open/close pushbuttons (pro- vided control power is available) to reposition the operator(s).
Step 32
Place the manual/automatic operation selector switch on the replacement Type AT-12 control in t h e
“AUTOMATIC” position and confirm that the automatic-transfer “ready” indicating lamp is lit.
step
33
compartment. Make sure that the doors to the high- voltage compartments are also closed and padlocked.
Bottom stationa
Figure 19. Clearances between latching parts on door and stationary door latches. Applicable to pad-mounted gear models having an “ R 3 supplement to the catalog number and horizontally split access panels.
5
1
INSTRUCTION SHEET
Page
24 of 24
January 31,1994
S&C ELECTRIC COMPANY
S&C
ELECTRIC CANADA LTD.
Chicago
Toronto