VANLED INSTALLATION INSTRUCTIONS


Add to my manuals
2 Pages

advertisement

VANLED    INSTALLATION INSTRUCTIONS | Manualzz

Thank you for buying RAB lighting fixtures. Our goal is to design the best quality products to get the job done right. We’d like to hear your comments.

Call the Marketing Department at 888-RAB-1000 or email: [email protected]

VANLED - Drop Lens VANLED - Flat Lens

IMPORTANT

READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.

Fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON

FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.

WARNING: Make certain power is OFF before installing or maintaining fixture. No user serviceable parts inside.

CAUTION: For proper weatherproof function all gaskets must be seated properly and all screws inserted and tightened firmly. Apply weatherproof silicone sealant around the edge of the Ceiling Mounting Box and/or Junction Box. This is especially important with an uneven ceiling surface. Silicone all plugs and unused conduit entries.

CEILING MOUNTING

The fixture is suitable for outdoor applications in wet locations.

Ceiling Mounting Box

Plugs (4)

1. Remove Door by loosening (4) Captive Screws.

Access Plate

2. Remove Reflector/ LED Assembly by loosening (4)

Reflector/ LED Screws.

3. Hang Reflector/ LED Assembly by Tether Cable.

Screws (2)

Tether Cable 4. Knock out appropriate Slots as marked in Fig. 2, by loosening Screws (2) on Access Plate and secure to junction box (not supplied). Check gasket is fully sealed.

5. Mount Ceiling Mounting Box to ceiling by drilling out (4) Drill Locations as marked in Fig. 2. Use the appropriate mounting hardware for the mounting surface. Be sure gasket is properly seated.

Reflector/ LED

Assembly

Reflector/ LED

Screws (4)

Captive

Screws (4)

6. Feed fixture wires through the Access Plate or through one of the Plugs (4) to make electrical splices in junction box. Use appropriate UL approved wire connectors as required by code to complete wiring.

7. Re-assemble Reflector/ LED Assembly and Door. Be careful not to pinch wires.

Fig. 1

Door

8. Tighten all screws.

9. Use silicone or teflon tape on all Plugs and on the threads of all conduit entry points. If outdoor surface is irregular , use caulk to seal any gaps around Ceiling

Mounting Box.

Thank you for buying RAB lighting fixtures. Our goal is to design the best quality products to get the job done right. We’d like to hear your comments.

Call the Marketing Department at 888-RAB-1000 or email: [email protected]

DRILL LOCATION

2.37”

[60.2mm]

1.64”

[41.7mm]

12.04”

[305.9mm]

10.4”

[264.2mm]

ON-OFF WIRING

Universal voltage driver permits operation at 120V thru 277V,

50 or 60 Hz. Units ordered with (/480V) suffix are 480V, 50Hz or

60Hz. For Non-Dimming, follow the wiring directions in fig. 3.

1. Connect the black fixture lead to the (+) LINE supply lead.

2. Connect the white fixture lead to the (-) COMMON supply lead.

3. Connect the GROUND wire from fixture to supply ground.

10.34”

[262.7mm]

12.04”

[305.9mm]

(+)LINE BLACK

(-)COMMON WHITE

GROUND GROUND

LIGHT

FIXTURE

Fig. 3

2.27”

[57.7mm] Slot

9.27”

[235.5mm]

Fig. 2

Drill Location (4)

TROUBLESHOOTING

1. Check that the line voltage at the fixture is correct. Refer to wiring directions.

2. Be sure the fixture is grounded properly.

3. Is the photocell, if used, functioning properly?

0-10V DIMMABLE WIRING

Universal voltage driver permits operation at 120V thru 277V,

50 or 60 Hz. Units ordered with (/480V) suffix are 480V, 50Hz or 60Hz. For 0-10V Dimming, follow the wiring directions in fig. 4.

1. Connect the black fixture lead to the (+) LINE supply lead.

2. Connect the white fixture lead to the (-) COMMON supply lead.

3. Connect the GROUND wire from fixture to supply ground.

Do NOT connect the GROUND of the dimming fixture to the output.

4. Connect the purple fixture lead to the (V+) DIM lead.

5. Connect the gray fixture lead to the (V-) DIM lead.

6. Cap the yellow fixture lead, if present. Do NOT connect.

CLEANING & MAINTENANCE

CAUTION: Be sure fixture temperature is cool enough to touch. Do not clean or maintain while fixture is energized.

1. Clean polycarbonate lens with non-abrasive cleaning solution.

2. Do not open the fixture to clean the LEDs. Do not touch the LEDs.

Fig. 4

PATENT - US: pat. D722,194

Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation operation or maintenance.

Easy Installation & Product Help

©2015 RAB LIGHTING Inc.

Northvale, New Jersey 07647 USA

VANLED IN 0415

Tech Help Line

Call our experts 888 RAB-1000 rabweb.com

Visit our website for product info email

Answered promptly [email protected]

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement