Allen-Bradley Rockwell Automation 1734-AENT User manual
Below you will find brief information for Adapter Module 1734-AENT. This manual provides installation, configuration, and maintenance instructions for the EtherNet/IP adapter. It explains how to communicate with POINT I/O modules, detailing both direct and rack-optimized connections, and includes example applications to guide setup. You'll learn about essential features like the Common Industrial Protocol(CIP), the producer/consumer model, and how to set the Requested Packet Interval (RPI).
Advertisement
Advertisement
POINT I/O EtherNet/IP Adapter Module
Catalog Number 1734-AENT
User Manual
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application,
Installation and Maintenance of Solid State Controls (publication SGI-1.1
available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com
) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
ATTENTION
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to: personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD
Labels may be on or inside the equipment, such as a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD
Labels may be on or inside the equipment, such as a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Allen-Bradley, Rockwell Automation, POINT I/O, RSLinx, RSLogix 5000 and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Preface
What This Preface Contains
This preface describes how to use this manual. See the table for a list of where to find specific information within this chapter.
Topic
Common Techniques Used in This Manual
About the Example Applications
Where to Find More Information
Page
Who Should Use This
Manual
This manual is intended for control engineers and technicians who are installing, configuring, and maintaining an EtherNet/IP control system that communicates with POINT I/O modules through a 1734-AENT adapter. We assume you have a good understanding of Ethernet networks and the TCP/IP protocol.
ATTENTION
You must use series C POINT I/O modules with the 1734-AENT adapter. Series A or B POINT I/O modules will not work with this adapter.
Common Techniques Used in This Manual
We use the following conventions throughout this manual:
• Numbered lists provide sequential steps.
• Bulleted lists provide information, not procedural steps.
The screen captures shown in this manual are pictures of the software’s actual screens.
iii
TIP
This symbol identifies helpful tips.
Publication 1734-UM011D-EN-P - January 2011
iv Preface
How to Use This Manual
This manual contains an overview of the 1734-AENT adapter. It describes how to install and configure the adapter and provides examples showing how to use the adapter to communicate with POINT I/O modules over an
EtherNet/IP network.
About the Example Applications
This manual presents two example applications that demonstrate the procedures for configuring and communicating with POINT I/O modules using the 1734-AENT adapter. We intend the example applications as building blocks to help you get your own system up and running. We recommend that you set up and run the example applications and use them as guides.
Here is the type of system you’ll be setting up.
1734-AENT
10.88.70.2
POINT I/O
Slot 0 1 2 3
Local chassis
Data
Logix5555 controller (slot 1)
1756-ENBT
10.88.70.4 (slot 3)
Switch
10.88.70.26
Programming terminal
Slot 0 1 2 3 4
31393-M
Publication 1734-UM011D-EN-P - May 2011
Preface v
System Components
We used the following components for the example applications. You need the same or similar components to set up your own control system using
POINT I/O modules on an EtherNet/IP network.
Quantity Product Name
Hardware
1
1
POINT I/O EtherNet/IP adapter
POINT I/O 24V DC sink output module
1
1
1
1
1
1
1
1
1
1
1
POINT I/O relay output module
DIN rail
ControlLogix chassis
Catalog Number
1734-AENT
1734-OV4E/C
1734-OW2/C
199-DR1 or equivalent
1756-A4 (or 1756-A7,
1756-A13,1756-A17)
1756-PA72 (or 1756-PB72) ControlLogix power supply
Logix5555 controller
ControlLogix EtherNet/IP bridge module
Personal computer that supports
RSLogix 5000 software
Ethernet switch
1756-L55
1756-ENBT
Any appropriate model running Windows
NT 4.0, Service Pack 6A or higher
Refer to manufacturer’s specifications
24V DC power supply 1734-EP24DC
Associated media and connectors as needed
Software
9355-WAB, 9355-WABOEM, 9355-WABC RSLinx communications software, version 2.31.00 or later
RSLogix 5000 programming software, version 11.11 or later
9324-RLD300ENE
Publication 1734-UM011D-EN-P - May 2011
vi Preface
Where to Find More
Information
Refer to the following Rockwell publications as needed for additional help when setting up and using your EtherNet/IP network.
For Information About See This Publication
Using EtherNet/IP for industrial control EtherNet/IP Performance and Application Guide
Publication Number
ENET-AP001
Ethernet communication interface modules
ControlLogix chassis
ControlLogix power supplies
Logix5555 programmable controllers
Ethernet Communication Interface Module Installation
Instructions
Ethernet Communication Interface Module User Manual
ControlLogix Chassis Installation Instructions
ControlLogix Power Supplies Installation Instructions
Logix5555 Controller User Manual
1756-IN053
1756-UM051
1756-IN080 (series B)
1756-IN613 (PA72/PB72)
1756-UM523
SoftLogix5800 controller SoftLogix5800 User Manual 1789-UM002 (L10, L30, L60)
ControlLogix EtherNet/IP bridge module with firmware revision 2.3 or later
ControlLogix EtherNet/IP Bridge Module Installation Instructions 1756-IN019
RSLogix 5000 programming software
1734-AENT adapter
POINT I/O digital and analog modules and PointBLOCK I/O modules
POINT I/O interface modules
Getting Results with RSLogix 5000, version 3.2.1 or later
POINT I/O EtherNet/IP Adapter Installation Instructions
POINT I/O Digital and Analog Modules and PointBLOCK I/O
Modules User Manual
POINT I/O RS-232 ASCII Module User Manual
POINT I/O RS-232 ASCII Module Installation Instructions
POINT I/O expansion power supply POINT I/O 24V DC Expansion Power Supply Installation
Instructions
POINT I/O Field Potential Distributor Installation Instructions POINT I/O field potential distributor
POINT I/O input modules POINT I/O 120V AC Input Module Installation Instructions
POINT I/O Input Module Installation Instructions
POINT I/O encoders/counter modules POINT I/O Encoders/Counter Module User Manual
POINT I/O Encoders/Counter Module Installation Instructions
9399-RLD300GR
1734-IN590
1734-UM001
1734-UM009
1734-IN588
1734-IN058
1734-IN059
1734-IN010
1734-IN051
POINT I/O 22V AC input module
POINT I/O RTD and isolated thermocouple input module
POINT I/O 220V AC Input Module Installation Instructions
POINT I/O RTD and Isolated Thermocouple Input Module
Installation Instructions
POINT I/O thermocouple and RTD input module
Thermocouple and RTD Input Module User Manual
POINT I/O IV2 and IV4 input module POINT I/O Input Module Installation Instructions
1734-UM006
1734-IN005
1734-IN008
1734-IN011
1734-UM004
POINT I/O Protected Output Module Installation Instructions
(OB2EP)
1734-IN052
POINT I/O 120/220V AC output module POINT I/O 120/220V AC Output Module Installation Instructions 1734-IN009
POINT I/O protected output module POINT I/O Protected Output Module Installation Instructions 1734-IN056
1734-IN586
POINT I/O voltage output analog module
POINT I/O 2 Voltage Output Analog Module Installation
Instructions
1734-IN002
POINT I/O protected sink output module POINT I/O Protected Sink Output Module Installation Instructions 1734-IN585
Publication 1734-UM011D-EN-P - May 2011
Preface vii
For Information About See This Publication Publication Number
POINT I/O 2 relay output module
POINT I/O synchronous serial interface absolute encoder module
POINT I/O 2 Relay Output Module Installation Instructions (OX2) 1734-IN587
POINT I/O 2 Relay Output Module Installation Instructions (OW2) 1734-IN055
POINT I/O Synchronous Serial Interface Absolute Encoder
Module Installation Instructions
1734-UM007
1734-IN583 POINT I/O cold junction compensation wiring base assembly
POINT I/O wiring base assembly
Very high-speed counter module
POINT I/O Cold Junction Compensation Wiring Base Assembly
Installation Instructions
POINT I/O Wiring Base Assembly Installation Instructions
POINT I/O Very High-speed Counter Module Installation
Instructions
1734-IN013
1734-IN003
RSLinx
Very High-speed Counter Module User Manual
RSLinx Enterprise Getting Results Guide
1734-UM003
LNXENT-GR001
TIP
Many of these publications are available online from: http://literature.rockwellautomation.com/
TIP
Rockwell Software products contain extensive tutorials and help screens. We recommend that you use the tutorials and help screens to learn about these products.
For more information about Rockwell Software products, visit the Rockwell Software internet site: http://www.software.rockwell.com
Terminology
Refer to the table for the meaning of common terms.
Term
BootP
Bridge
CIP
Connection
Consumer
Definition
BootP (Bootstrap Protocol) is a low-level protocol that provides configurations to other nodes on a TCP/IP network. BootP configuration files let you automatically assign IP addresses to an
Ethernet module. You can also obtain subnet masks and gateway addresses from BootP.
A node between two similar communication subnets where protocol translation is minimal.
Control and information protocol, the EtherNet/IP application layer uses the producer/consumer networking model. In this model one producer broadcasts (multicasts) the data once to all the consumers.
All consumers see the data simultaneously and may choose whether to consume (receive) the data or not. Delivery time is consistent, no matter how many consumers there are.
The communication mechanism from the controller to another module in the control system, usually used to exchange I/O data.
A destination device in the CIP networking model. See CIP.
Publication 1734-UM011D-EN-P - May 2011
viii Preface
Publication 1734-UM011D-EN-P - May 2011
Term
CSMA/CD
Determinism
DHCP
Definition
Carrier sense multiple access/collision detection is the access method used in Ethernet. When a device wants to gain access to the network, it checks to see if the network is quiet (senses the carrier).
If it is not, it waits a random amount of time before retrying. If the network is quiet and two devices access the line at exactly the same time, their signals collide. When the collision is detected, they both back off and each waits a random amount of time before retrying.
The ability to predict when information will be delivered. Important in time-critical applications.
The dynamic host configuration protocol is an Internet protocol, similar to BootP, for automating the configuration of computers that use TCP/IP. DHCP can be used to automatically assign IP addresses, to deliver IP stack configuration parameters, such as the subnet mask and default router, and to provide other configuration information, such as the addresses for printer, time, and news servers.
DNS
The 1734-AENT factory default is DHCP enabled. When you apply power, the module sends a message containing its hardware address to any DHCP server on the network. The server(s) replies by sending a message with an appropriate IP address for the adapter. The adapter responds by acknowledging to a server that it will use the offered IP address.
The domain name system is a hierarchical, distributed method of organizing the name space of the Internet. The DNS administratively groups hosts into a hierarchy of authority that allows addressing and other information to be widely distributed and maintained. A big advantage to the DNS is that using it eliminates dependence on a centrally-maintained file that maps host names to addresses.
Ethernet
EtherNet/IP
A physical layer standard using carrier sense multiple access with collision detection (CSMA/CD) methods.
Ethernet industrial protocol applies a common application layer (CIP) over Ethernet by encapsulating messages in TCP/UDP/IP.
Ethernet network A local area network designed for the high-speed exchange of information between computers and related devices.
Explicit messaging Non-time critical messaging used for device configuration and data collection, such as downloading programs or peer-to-peer messaging between two PLC units.
Full duplex
Fully qualified domain name
Gateway
A mode of communication that allows a device to send and receive information at the same time, effectively doubling the bandwidth.
A fully qualified domain name (FQDN) is a domain name that includes all higher level domains relevant to the entity named. If you think of the DNS as a tree-structure with each node having its own label, a fully qualified domain name for a specific node would be its label followed by the labels of all the other nodes between it and the root of the tree. For example, for a host, a FQDN would include the string that identifies the particular host, plus all domains of which the host is a part, up to and including the top-level domain (the root domain is always null). For example, PARIS.NISC.SRI.COM is a fully qualified domain name for the host at 192.33.33.109.
A module or set of modules that allows communications between nodes on dissimilar networks.
Preface ix
Term
Hardware address Each Ethernet device has a unique hardware address (sometimes called a MAC address) that is 48 bits. The address appears as six digits separated by colons (such as, xx:xx:xx:xx:xx:xx). Each digit has a value between 0 and 255 (0x00 to 0xFF). This address is assigned in the hardware and cannot be changed. The hardware address is required to identify the device if you are using a BOOTP utility.
Host name
Definition
The host name is the unique name for a computer within its domain.
It's always the first element of a full name, and, with its domain and top-level domain suffix, creates the unique name of that computer on the Internet. For example, let's say a trading website is www.trading.com. The host name is www, which is not unique on the web, but is unique within the trading domain.
Hub
Implicit messaging Real-time messaging of I/O data.
IP Internet protocol that provides the routing mechanism for messages.
All messages contain not only the address of the destination station, but the address of a destination network, which allows messages to be sent to multiple networks within an organization or around the world.
IP address A 32-bit identification number for each node on an Internet Protocol network. These addresses are represented as four sets of 8-bit numbers (numbers from 0 to 255), with decimals between them. Each node on the network must have a unique IP address.
Latency
The host name can also refer to the fully qualified domain name
(FQDN), or in this example, www.trading.com. Both naming methods seem to be used interchangeably in various documents. For the purposes of this document, the host name will refer to the FQDN, or as in this example, www.trading.com.
A central connecting device that joins devices together in a star configuration. Hubs are generally not suitable for use in I/O control systems, since they are time-critical applications that cannot tolerate lost packets.
Multicast
Producer
Rack-optimized
Subnet mask
The time between initiating a request for data and the beginning of the actual data transfer.
In the CIP producer/consumer model, one producer multicasts
(broadcasts) the data once to all the consumers.
The source of information in the CIP networking model. See CIP.
A physical and logical collection of application modules.
Switch
TCP
An extension of the IP address that allows a site to use a single net
ID for multiple networks.
A network device that cross connects devices or network segments.
A switch provides each sender/receiver the full network bandwidth
(2x in full duplex mode), reduces collisions, and increases determinism.
The transport control protocol is a more reliable but slower transport protocol than UDP. It is used for explicit (not time critical) messaging in EtherNet/IP.
Publication 1734-UM011D-EN-P - May 2011
x Preface
Term
TCP/IP
Transaction
UDP
Definition
The transmission control protocol/internet protocol is a transport-layer protocol (TCP) and a network-layer protocol (IP) commonly used for communication within networks and across internetworks.
An exchange of request and data and response and data.
The user datagram protocol (UDP) is a transport protocol that provides a very simple but fast capability to send datagrams between two devices. It is used for I/O (implicit) messaging in EtherNet/IP.
Publication 1734-UM011D-EN-P - May 2011
xi
Preface
Summary of Changes
About the Adapter
Install the Adapter
Configure the Adapter for Your
EtherNet/IP Network
Table of Contents
Important User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
What This Preface Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
Who Should Use This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
Common Techniques Used in This Manual . . . . . . . . . . . . . . . . . . . . . .iii
How To Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iv
About the Example Applications . . . . . . . . . . . . . . . . . . . . . . . . . . .iv
System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v
Where to Find More Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .vi
New and Revised Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . xv
Change Bars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xv
Chapter 1
What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Important Adapter Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Set the Chassis Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Adapter Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Empty Slots and RIUP Situations. . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Cycle Power To a System For the First Time . . . . . . . . . . . . . . . . . 4
Hardware/Software Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
What the Adapter Does . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Use of the Common Industrial Protocol (CIP) . . . . . . . . . . . . . . . . . . . 5
Understand the Producer/Consumer Model . . . . . . . . . . . . . . . . . . . . . 6
Specify the Requested Packet Interval (RPI) . . . . . . . . . . . . . . . . . . . . . 6
Support of Rack-optimized and Direct Connections. . . . . . . . . . . . . . . 7
Mix Rack-optimized and Direct Connections . . . . . . . . . . . . . . . . . 7
Determine Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Understand Messaging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Establish I/O Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Configure Autobaud . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Chapter 2
What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Identify Adapter Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Mount the Adapter on a DIN Rail Before Installing Modules . . . . . . 10
Mount (or Replace) the Adapter to an Existing System. . . . . . . . . . . . 11
Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Chapter 3
What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Gateway Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Subnet Mask. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Set the Network Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Use the Rockwell BootP/DHCP Utility . . . . . . . . . . . . . . . . . . . . . . . . 20
Save the Relation List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Use DHCP Software to Configure Your Adapter . . . . . . . . . . . . . . . . 23
Publication 1734-UM011D-EN-P - May 2011
xii
Configure the Adapter for
Direct Connection in RSLogix
5000 Software
Configure the Adapter for
Direct Connection and Rack
Optimization in RSLogix 5000
Software
LED Status Indicators
Adapter Web Pages
Chapter 4
What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Set Up the Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Create the Example Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Add the Local EtherNet/IP Bridge to the I/O Configuration. . . 28
Add the POINT I/O Adapter to the I/O Configuration . . . . . . . 30
Add the POINT I/O Modules to the I/O Configuration . . . . . . 33
Edit the Controller Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Create the Ladder Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Download the Program to the Controller. . . . . . . . . . . . . . . . . . . . . . . 39
Verify the Module Chassis Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Configure the Adapter with Fixed IP Address . . . . . . . . . . . . . . . . . . . 43
Recover From an Overloaded Adapter. . . . . . . . . . . . . . . . . . . . . . . . . 44
Chapter 5
What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Create the Example Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Configure the I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Add the Local EtherNet/IP Bridge to the I/O Configuration. . . 48
Add the POINT I/O Adapter to the I/O Configuration . . . . . . . 50
Add the POINT I/O Module and Configure for Direction
Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Add the POINT I/O Module and Configure For
Rack Optimization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Download the Program to the Controller. . . . . . . . . . . . . . . . . . . . . . . 58
Verify the Module Chassis Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Access Module Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Chapter 6
What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Interpret the Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Appendix A
What This Appendix Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Work with the Home Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Work with the Diagnostics Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Use the Diagnostic Overview Page. . . . . . . . . . . . . . . . . . . . . . . . . 70
Use the Network Settings Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Use the Ethernet Statistics Page . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Use the I/O Connections Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Use the Diagnostic Messaging Page . . . . . . . . . . . . . . . . . . . . . . . . 75
Work with the Configuration Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Use the Identity Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Use the Network Configuration Page. . . . . . . . . . . . . . . . . . . . . . . 78
Use the Services Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Work with the Browse Chassis Page . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Appendix B
Publication 1734-UM011D-EN-P - May 2011
xiii
Configure the RSLinx Ethernet
Communication Driver
1734 POINT I/O
Module/RSLogix 5000
Controller Tag Reference
Quick Start
Index
What This Appendix Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Install the RSLinx Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Configure the AB_ETH/IP Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Appendix C
What This Appendix Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
1734 POINT I/O Catalog Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Valid Number Ranges for RSLogix 5000 Data Types . . . . . . . . . . . . . 92
Digital 2 POINT Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Digital 2 POINT Output – With Over Load and
Open Load Diagnostic Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Digital 2 POINT Output – With Over
Load Diagnostic Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Digital 4 POINT Output – With Over
Load and Open Load Diagnostic Status . . . . . . . . . . . . . . . . . . . . . . . . 98
Digital 4 POINT Output – With Over
Load Diagnostic Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Analog 2 Channel Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Appendix D
What This Appendix Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Necessary Prerequisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Configure the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Enter Adapter Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Add Another Module Under the Adapter . . . . . . . . . . . . . . . . . . 134
Configure 1734 POINT I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . 135
Configure an Ethernet Driver in RSLinx Software . . . . . . . . . . . . . . 138
Launch RSLinx Software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Publication 1734-UM011D-EN-P - May 2011
xiv
Notes:
Publication 1734-UM011D-EN-P - May 2011
Summary of Changes
This publication contains new and revised information not in the last release.
New and Revised Information
See the table for a summary of the major changes in this manual.
Chapter
Appendix B - Configure the RSLinx
Revised to include
Removal of Ethernet device installation instructions
Change Bars
Change bars (as shown with this paragraph) show the areas in this manual that are different from previous editions and indicate the addition of new or revised information.
xv Publication 1734-UM011D-EN-P - May 2011
xvi Summary of Changes
Notes:
Publication 1734-UM011D-EN-P - May 2011
1
Chapter
1
About the Adapter
What This Chapter Contains
This chapter provides an overview of the 1734-AENT POINT I/O
EtherNet/IP adapter, its primary features, and how to use it. You need to understand the concepts discussed in this chapter to configure your adapter and use it in an EtherNet/IP control system. See the table for a list of where to find specific information in this chapter.
Topic
Important Adapter Considerations
Empty Slots and RIUP Situations
Cycle Power To a System For the First Time
Hardware/Software Compatibility
Use of the Common Industrial Protocol (CIP)
Understand the Producer/Consumer Model
Specify the Requested Packet Interval (RPI)
Support of Rack-optimized and Direct Connections
Mix Rack-optimized and Direct Connections
Page
ATTENTION
You must use series C POINT I/O modules with the
1734-AENT adapter. Series A or B POINT I/O modules will not work with this adapter.
Important Adapter
Considerations
Before you begin using your adapter, note the following important considerations.
Set the Chassis Size
The 1734-AENT POINT I/O adapter for EtherNet/IP requires configuration of its chassis size before you can make any I/O connections.
Publication 1734-UM011D-EN-P - May 2011
2 About the Adapter
The default setting for the chassis size is 1 slot, which represents the adapter by itself.
Set the chassis size as the sum of the slot of the adapter plus the slots of each
I/O module in the adapter backplane. For example, the adapter plus 4 I/O modules uses a chassis size of 5. The adapter stores this chassis size setting in non-volatile storage.
When the adapter’s non-volatile chassis size does not match the actual number of modules present on its backplane, the adapter does not make any I/O connections and an error occurs, as shown in the Module Properties dialog.
Publication 1734-UM011D-EN-P - May 2011
Adapter Replacement
It is important to note that during a connection request from the controller, the chassis size setting for a 1734-AENT adapter is not communicated to the adapter. You must always set this chassis size using a separate operation. This includes situations when you are replacing an adapter. The adapter does not make any I/O connections until it is configured with the appropriate chassis size.
Empty Slots and RIUP Situations
The POINT I/O system does not have the ability to detect an empty terminal base. Because of this, there are numerous situations in which you can potentially configure a system that is unusable or one that exercises unintended control.
In an attempt to address these situations, you must observe the following rules for POINT I/O system construction and the removal and reinsertion of modules:
About the Adapter 3
• A correct POINT I/O system does not have any empty terminal bases.
• After you cycle power, the adapter does not run any I/O until the number of modules comprising the chassis equals the stored chassis size.
– Because the adapter cannot detect empty terminal bases, it cannot assume any safe operation until there is a match between the number of modules indicating their presence in the chassis and what the adapter has saved in non-volatile memory.
– Actual module identification (such as, electronic keying) is done when connection establishment requests are received from the controller or controllers.
• A module removed under power does not disrupt operation of the other
I/O modules.
– When you remove a module, the adapter determines what changed.
– Whenever you remove a module with an active connection from the
POINT I/O system, the adapter indicates this by flashing the
POINTBus Status LED red and reports a minor recoverable fault.
• If more than one contiguous module is removed under power, connections to all modules in the contiguous missing module set are disallowed until all modules are replaced. Because the adapter cannot detect an empty base, it does not know the physical positioning of the modules until all the missing modules are replaced.
• If a module separating two sets of contiguous missing modules is removed, the two sets merge into a single set. All the modules must be replaced before connections are permitted to any module in the set.
• If modules of different types are removed and returned to the wrong locations, attempts to connect to these modules fail during verification of the electronic ID (providing that keying has not been disabled).
• If modules of the same type are removed and returned to the wrong locations, they accept connections from the controller or controllers and reconfigure with the correct data once they pass their electronic keying check.
• These removal and return conditions apply whether the system is under power or not. If the system is under power, the situation arises immediately. If the system is not under power, the situation arises in the next power cycle.
Publication 1734-UM011D-EN-P - May 2011
4 About the Adapter
Adapter Features
Cycle Power To a System for the First Time
When you cycle power to the POINT I/O for the first time, the adapter must assign addresses to every module in the backplane. POINT I/O modules all ship configured at the same address.
When you first apply power, we expect that all but one module on the backplane exhibits a solid red Module Status LED.
One by one the adapter resets these modules and addresses them appropriately. The amount of time that this operation takes is proportional to the size of your POINT I/O system.
The 1734-AENT adapter has the following features:
• EtherNet/IP messages encapsulated within standard TCP/UDP/IP protocol
• Common application layer with ControlNet and DeviceNet networks
• Interfacing via Category 5 rated twisted pair cable
• Half/full duplex 10 Mbit or 100 Mbit operation
• DIN rail mounting
• Communication to and from other POINT I/O modules on the same
DIN rail
• Communication supported by RSLinx software
• IP address assigned via standard BootP or DHCP tools
• I/O configuration via RSLogix 5000 software
• No network scheduling required
• No routing tables required
• Support of connections from multiple controllers simultaneously
Publication 1734-UM011D-EN-P - May 2011
Hardware/Software
Compatibility
About the Adapter 5
The 1734-AENT adapter and the applications described in this manual are compatible with the following firmware revisions and software releases.
Contact Rockwell Automation if you need software or firmware upgrades to use this equipment.
Product
1734-AENT adapter
1756-ENBT module
Logix 5555 controller
RSLogix 5000 software
RSLinx software
Firmware Revision/
Software Release
1.xx or later
2.3 or later
11 or later
11.11 or later
2.3.1 or later
What the Adapter Does
Use of the Common
Industrial Protocol (CIP)
The 1734-AENT adapter performs the following primary tasks:
5
5
L
5
5
• Control of real-time I/O data (also known as implicit messaging) – the
1734-AENT adapter serves as a bridge between POINT I/O modules and the network
B
T
E
N
EtherNet/IP Network
N
T
A
E
POINT
I/O B
T
E
N
ControlLogix
I/O
Other
Network
Devices
• Support of messaging data for configuration and programming information (also known as explicit messaging)
The 1734-AENT adapter uses the Common Industrial Protocol (CIP). CIP is the application layer protocol specified for EtherNet/IP, the Ethernet
Industrial Protocol, as well as for ControlNet and DeviceNet networks. It is a message-based protocol that implements a relative path to send a message from the producing device in a system to the consuming devices.
The producing device contains the path information that steers the message along the proper route to reach its consumers. Since the producing device holds this information, other devices along the path simply pass this information; they do not need to store it.
This has the following significant benefits:
• You do not need to configure routing tables in the bridging modules, which greatly simplifies maintenance and module replacement.
Publication 1734-UM011D-EN-P - May 2011
6 About the Adapter
Understand the
Producer/Consumer Model
The CIP producer/consumer networking model replaces the old source/destination (master/slave) model. The producer/consumer model reduces network traffic and increases speed of transmission. In traditional I/O systems, controllers poll input modules to obtain their input status. In the CIP system, input modules are not polled by a controller. Instead, they produce
(multicast) their data either upon a change of state (COS) or periodically.
The frequency of update depends upon the options chosen during configuration and where on the network the input module resides. The input module, therefore, is a producer of input data, and the controller is a consumer of the data.
The controller can also produce data for other controllers to consume. The produced and consumed data is accessible by multiple controllers and other devices over the EtherNet/IP network. This data exchange conforms to the producer/consumer model.
Specify the Requested
Packet Interval (RPI)
• You maintain full control over the route taken by each message, which enables you to select alternative paths for the same end device.
The RPI is the update rate specified for a particular piece of data on the network. The RPI can be specified for the adapter and include all of the I/O modules communicating through it (using a rack-optimized connection) or specified for a particular module (using direct connection).
When you add a module or an adapter to the I/O configuration of a controller, you must enter the RPI as a parameter. This value specifies how often to produce the data for that device. For example, if you specify an RPI of
50 ms, it means that every 50 ms the device should send its data to the controller or the controller should send its data to the device.
Use RPIs only for devices that exchange data. For example, a ControlLogix
EtherNet/IP bridge module in the same chassis as the controller does not require an RPI, because it is not a data-producing member of the system. Its use is only as a bridge to remote racks.
Publication 1734-UM011D-EN-P - May 2011
About the Adapter 7
Support of Rack-optimized and Direct Connections
The 1734-AENT adapter supports both direct and rack-optimized connections. A direct connection is a real-time data transfer link between the controller and whatever module occupies the slot that the configuration data references. Direct connection messaging occurs at a cyclic rate specified by the
RPI during configuration. A rack-optimized connection is a grouping of data from more than one I/O module into a single block of data sent over a single connection at the same data rate.
Rack-optimized connections reduce the total number of connections needed to transfer data when using many I/O modules in a system. The following example illustrates the benefit of rack-optimized connections.
Assume you set up a system that contains 8 digital I/O modules interfaced to a
1734-AENT adapter. If you use direct connections to transfer data to each of the these I/O modules, you need 8 connections to transfer all of the data, one to each of the 8 I/O modules. If you use a rack-optimized connection to transfer the data, you only need a single connection – the connection to the
1734-AENT adapter.
IMPORTANT
Although rack-optimized connections offer an efficient way to use resources, there are a few limitations on their use.
• You can use only rack-optimized connections to send data to and from digital I/O modules. Analog or speciality I/O requires direct connections.
• All data is sent at the same time as the RPI rate of the 1734-AENT adapter.
See the EtherNet/IP Performance and Application Guide, publication number ENET-AP001 , for more information on connections.
Mix Rack-optimized and Direct Connections
You can mix communication formats for different I/O modules communicating through the same adapter. I/O modules set up to use rack optimization communicate at the rate of the RPI configured for the
1734-AENT adapter. I/O modules configured for direct communication communicate at their own set RPIs and ignore the 1734-AENT adapter’s RPI.
Publication 1734-UM011D-EN-P - May 2011
8 About the Adapter
Before You Begin
To effectively use your adapter, note the following considerations.
Determine Compatibility
If using the adapter with a 1756-ENBT module or 1788-ENBT module, use the following required firmware revisions for these bridge modules:
• 1756-ENBT firmware revision 2.3 or later
• 1788-ENBT firmware revision 1.33 or later
If you use the BootP Utility to assign IP addresses to the adapter, use revision
2.3.2 or later.
Understand Messaging
Class 3 (Explicit Message) requests through the 1734-AENT adapter to a specific POINT I/O module may not always receive a response from the I/O modules. In the case where the I/O module does not reply to the request, the adapter responds with an error code indicating a timeout.
Establish I/O Connections
When you apply power to a POINT I/O system and establish I/O connections, the outputs transition to the idle state, applying idle state data before going to RUN mode. This occurs even when the controller making the connection is already in RUN mode.
Configure Autobaud
The adapter cannot reconfigure an I/O module that you previously configured to operate at a fixed communication rate. When you reuse a POINT I/O module from another POINT I/O system, configure the module to autobaud before using it with the adapter.
Publication 1734-UM011D-EN-P - May 2011
9
Chapter
2
Install the Adapter
What This Chapter Contains
This chapter describes how to physically install the adapter on the DIN rail and connect it to the EtherNet/IP network. The following table lists where to find specific information.
Topic
Mount the Adapter on a DIN Rail Before Installing
Mount or Replace the Adapter to an Existing System
Page
ATTENTION
You must use series C POINT I/O modules with the 1734-AENT adapter. Series A or B POINT I/O modules will not work with this adapter.
Identify Adapter
Components
Use the figure to identify the external features of the adapter.
Safety end cap
LED indicators
Node address thumbwheel
RTB removable handle
Removable Terminal
Block (RTB)
EtherNet network
RJ45 connector
DIN rail locking screw
(orange)
31533-M
Publication 1734-UM011D-EN-P - May 2011
10 Install the Adapter
Mount the Adapter on a DIN
Rail Before Installing
Modules
Use the following procedure to mount the adapter on a new system before you install any I/O modules.
43520
1. Position the adapter vertically above the DIN rail.
2. Press down firmly to install the adapter on the DIN rail, noting that the locking mechanism locks the adapter to the DIN rail.
3. Set the network address thumbwheel switches to the desired value. For
more information, see Set the Network Address on page 19.
WARNING
If you connect or disconnect the Ethernet cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
4. Slide the safety end cap up to remove it.
This exposes the backplane and power interconnections.
ATTENTION
Do not discard the adapter’s end cap. Use this end cap to cover the exposed interconnections on the last mounting base on the
DIN rail. Failure to do so could result in equipment damage or injury from electric shock.
Publication 1734-UM011D-EN-P - May 2011
Mount or Replace the Adapter to an
Existing System
Install the Adapter 11
Follow these steps to mount or replace an adapter.
1. Remove the existing adapter (if there is one) from the DIN rail as follows: a. Pull up on the RTB removal handle to remove the terminal block.
b. Disconnect the Ethernet connector from the adapter.
c. Remove the adjacent module from its base.
d. Use a small-bladed screwdriver to rotate the DIN-RAIL locking screw to a vertical position.
This releases the locking mechanism.
e. Lift straight up to remove.
2. For the replacement adapter, slide the safety end cap up to remove.
This exposes the backplane and power connections.
3. Position the replacement adapter vertically above the DIN rail.
4. Make certain the DIN rail lock is in the horizontal position.
5. Slide the adapter down, allowing the interlocking side pieces to engage the adjacent module.
6. Press firmly to seat the adapter on the DIN rail.
The adapter locking mechanism snaps into place.
7. Replace the adjacent module in its base.
8. Reconnect the Ethernet cable to the adapter.
9. Set the network address thumbwheel switches to the value used on the
replaced module. For more information, see Set the Network Address on page 19.
10. Insert the end of the terminal block (RTB) opposite the handle into the base unit.
This end has a curved section that engages with the wiring base.
11. Rotate the terminal block into the wiring base until it locks itself into place.
Publication 1734-UM011D-EN-P - May 2011
12 Install the Adapter
Wire Your Adapter
Refer to the illustration to wire the adapter.
WARNING
If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Network address
Thumbwheels
Module status
Network activity status
Network status
POINTBus status
Ethernet RJ-45 connector System Power
Field Power
NC = No Connection
CHAS GND = Chassis Ground
C = Common
V = Supply
This DC supply will be connected to the internal power bus.
V DC
12/24V DC
0
NC NC
1
6
2
Chas
4
Gnd
C
V
3
Chas
Gnd
5
C
7
V
NC
CHAS GND
C
V
43264
ATTENTION
Do not connect 120/240V AC power to this supply.
Publication 1734-UM011D-EN-P - May 2011
Install the Adapter 13
Mounting Dimensions
Refer to the figure for mounting dimensions.
millimeters
(inches)
54.9
(2.16)
76.5
(3.0)
36.51
(1.44)
133.4
(5.25) B
A = DIN rail
B = Secure DIN rail approximately every 200 mm (7.8 in.)
A
43520
1734-AENT
76.2H x 54.9W x 133.4D
(3.0H x 2.16W x 5.25D)
Publication 1734-UM011D-EN-P - May 2011
14 Install the Adapter
Notes:
Publication 1734-UM011D-EN-P - May 2011
15
Chapter
3
Configure the Adapter for Your EtherNet/IP
Network
What This Chapter Contains
Before using your adapter in an EtherNet/IP network, configure it with an IP address, subnet mask, and optional Gateway address. This chapter describes these configuration requirements and the procedures for providing them. Here are ways you can do this:
• Use the Rockwell BootP utility, version 2.3 or later, that ships with
RSLogix 5000 or RSLinx software.
You can also use this utility to reconfigure a device with an IP address you must change.
• Use a third party DHCP server.
• Use the Network Address thumbwheel switch.
• Have your network administrator configure the adapter via the network server.
See the table for a list of where to find information in this chapter.
Topic
Use the Rockwell BootP/DHCP Utility
Use DHCP Software to Configure Your Adapter
Page
ATTENTION
You must use series C POINT I/O modules with the
1734-AENT adapter. Series A or B POINT I/O modules will not work with this adapter.
Publication 1734-UM011D-EN-P - May 2011
16 Configure the Adapter for Your EtherNet/IP Network
Configuration
Requirements
Before you can use your adapter, you must configure its IP address, its subnet mask, and, optionally, gateway address. You can use the Rockwell BootP utility, version 2.3 or later, to perform the configuration. You can also use a DHCP server or the network address switches to configure these parameters.
9 9
9
Publication 1734-UM011D-EN-P - May 2011
IMPORTANT
IP address Ethernet address (MAC)
43519
If you set the thumbwheels on the adapter to the value 888 and then power cycle the module, the following will occur.
• The DHCP Enabled function is enabled (set to True).
• The Ethernet link is negotiated automatically (the Auto
Negotiate function will be set to True).
• The web server is enabled (the Disabled Web Server function is disabled).
• The password for this page resets to the factory default
(the word password is the factory default password).
Note the value of the switches before you enter the 888 value, because you return the adapter to those values once this process is complete.
IMPORTANT
If using the BootP/DHCP utility, you need to know the
Ethernet hardware address of your adapter. Rockwell
Automation assigns each 1734-AENT adapter a unique
48-bit hardware address at the factory. The address is printed on a label on the side of your 1734-AENT adapter as shown in the figure. It consists of six hexadecimal digits separated by colons. This address is fixed by the hardware and cannot be changed.
If you change or replace the 1734-AENT adapter, you must enter the new Ethernet hardware address of the adapter when you configure the new adapter.
Configure the Adapter for Your EtherNet/IP Network 17
IP Address
The IP address identifies each node on the IP network (or system of connected networks). Each TCP/IP node on a network (including the
1734-AENT adapter) must have a unique IP address.
The IP address is 32 bits long and has a net ID part and Host ID part.
Networks are classified A, B, C, (or other). The class of the network determines how an IP address is formatted.
Class A
Class B
Class C
0
0
0
10
0
110
Net ID
Net ID
7 8
Net ID
15 16
Host ID
Host ID
23 24
Host ID
31
31
31
You can distinguish the class of the IP address from the first integer in its dotted-decimal IP address as follows:
Range of first integer Class
0 …127 A
128 …191 B
Range of first integer Class
192 … 223 C
224 … 255 other
Each node on the same physical network must have an IP address of the same class and must have the same net ID. Each node on the same network must have a different Host ID thus giving it a unique IP address.
IP addresses are written as four decimal integers (0…255) separated by periods where each integer gives the value of one byte of the IP address.
EXAMPLE
For example, the 32-bit IP address:
10000000 00000001 00000000 00000001 is written as
128.1.0.1
Gateway Address
This section applies to multi-network systems. If you have a single network system, refer to the next section.
The Gateway Address is the default address of a network. It provides a single domain name and point of entry to the site. Gateways connect individual physical networks into a system of networks.
Publication 1734-UM011D-EN-P - May 2011
18 Configure the Adapter for Your EtherNet/IP Network
When a node needs to communicate with a node on another network, a gateway transfers the data between the two networks. The figure shows gateway G connecting Network 1 with Network 2.
A
128.1.0.1
Network 1
128.1.0.2
G
B C
128.2.0.3
128.2.0.1
128.2.0.2
Network 2
When host B with IP address 128.2.0.1 communicates with host C, it knows from C’s IP address that C is on the same network. In an Ethernet environment, B can then resolve C’s IP address into a hardware address (MAC address) and communicate with C directly.
When host B communicates with host A, it knows from A’s IP address that A is on another network (the net IDs are different). In order to send data to A, B must have the IP address of the gateway connecting the two networks. In this example, the gateway’s IP address on Network 2 is 128.2.0.3.
The gateway has two IP addresses (128.1.0.2 and 128.2.0.3). The first must be used by hosts on Network 1 and the second must be used by hosts on
Network 2. To be usable, a host’s gateway must be addressed using a net ID matching its own.
Subnet Mask
The subnet mask is used for splitting IP networks into a series of subgroups, or subnets. The mask is a binary pattern that is matched up with the IP address to turn part of the Host ID address field into a field for subnets.
EXAMPLE
Take Network 2 (a Class B network) in the previous example and add another physical network. Selecting the following subnet mask would add two additional net ID bits, allowing for four physical networks:
11111111 11111111 11000000 00000000 = 255.255.192.0
These two bits of the Host ID are used to extend the net ID.
Two bits of the Class B host ID are used to extend the net ID. Each unique combination of bits in the part of the Host ID where subnet mask bits are 1 specifies a different physical network.
Publication 1734-UM011D-EN-P - May 2011
Configure the Adapter for Your EtherNet/IP Network 19
The new configuration is:
A
128.1.0.1
Network 1
128.1.0.2
G
128.2.64.3
B
128.2.64.1
128.2.64.2
Network 2.1
G2
D
128.2.128.1
128.2.128.2
Network 2.2
128.2.128.3
A second network with Hosts D and E was added. Gateway G2 connects
Network 2.1 with Network 2.2.
Hosts D and E will use Gateway G2 to communicate with hosts not on
Network 2.2.
Hosts B and C will use Gateway G to communicate with hosts not on
Network 2.1.
When B is communicating with D, G (the configured Gateway for B) will route the data from B to D through G2.
Set the Network Address
The adapter ships with the thumbwheel switches set to 999 and DHCP enabled. You can set the network Internet Protocol (IP) address in these ways:
• Use the thumbwheel switches located on the module.
• Use a Dynamic Host Configuration Protocol (DHCP) server, such as
Rockwell Automation BootP/DHCP.
• Retrieve the IP address from nonvolatile memory.
Network address thumbwheel
Press either the + or - buttons to change the number.
43248
Publication 1734-UM011D-EN-P - May 2011
20 Configure the Adapter for Your EtherNet/IP Network
The adapter reads the thumbwheel switches only when you cycle power to determine if the switches are set to a valid number. Press either the + or - buttons to change the number.
Valid settings range from 001 to 254. When the switches are set to a valid number, the adapter’s IP address will be 192.168.1.xxx (where xxx represents the number set on the switches). The adapter’s subnet mask will be
255.255.255.0 and the gateway address is set to 0.0.0.0. The adapter will not have a host name assigned, or use any Domain Name System when using the thumbwheel settings.
If the switches are set to an invalid number (such as 000 or a value greater than
254), the adapter checks to see if DHCP is enabled. If DHCP is enabled, the adapter requests an address from a DHCP server. The DHCP server will also assign other Transport Control Protocol (TCP) parameters.
If DHCP is not enabled, the adapter will use the IP address (along with other
TCP configurable parameters) stored in nonvolatile memory. The factory default switch setting is 999, and DHCP is enabled.
Use the Rockwell
BootP/DHCP Utility
The Rockwell Automation BootP/DHCP utility is a stand alone program that incorporates the functionality of standard BootP software with a user friendly graphical interface. It is located in the Utils directory on the RSLogix 5000 software installation CD. The 1734-AENT adapter must have DHCP enabled
(factory default and the network address switches set to an illegal value) to use the utility.
To configure your adapter using the BootP utility, perform the following steps:
1. Run the BootP software.
In the BOOTP Request History panel you see the hardware addresses of devices issuing BootP requests.
Publication 1734-UM011D-EN-P - May 2011
Configure the Adapter for Your EtherNet/IP Network 21
2. Double-click the hardware address of the device you want to configure.
You see the New Entry dialog with the device’s Ethernet Address
(MAC).
3. Enter the IP Address you want to assign to the device, and click OK.
The device is added to the Relation List, displaying the Ethernet Address
(MAC) and corresponding IP Address, Hostname, and Description (if applicable).
When the address displays in the IP Address column in the Request
History section, it signifies that the IP address assignment has been made.
4. To assign this configuration to the device, highlight the device in the
Relation List panel, and click the Disable BOOTP/DHCP button.
When power is cycled to the device, it uses the configuration you assigned and not issue a DHCP request.
5. To enable DHCP for a device with DHCP disabled, highlight the device in the Relation List, and click the Enable DHCP button.
Publication 1734-UM011D-EN-P - May 2011
22 Configure the Adapter for Your EtherNet/IP Network
You must have an entry for the device in the Relation List panel to re-enable DHCP.
Save the Relation List
You can save the Relation List to use later. To save the Relation List perform the following steps:
1. Select Save As... from the File menu.
Publication 1734-UM011D-EN-P - May 2011
Configure the Adapter for Your EtherNet/IP Network 23
The Save As dialog appears.
2. Select the folder you want to save to.
3. Enter a file name for the Relation List (for example, control system configuration), and click Save.
You can leave the Save as type at the default setting:
Bootp Config Files (*.bpc).
You can then open the file containing the Relation List at a later session.
Use DHCP Software to
Configure Your Adapter
DHCP (Dynamic Host Configuration Protocol) software automatically assigns
IP addresses to client stations logging onto a TCP/IP network.
DHCP is based on BootP and maintains some backward compatibility. The main difference is that BootP was designed for manual configuration, while
DHCP allows for dynamic allocation of network addresses and configurations to newly attached devices.
Be cautious about using DHCP software to configure your adapter. A DHCP server typically assigns a finite lease time to the offered IP address.
When 50% of the leased time has expired, the 1734-AENT adapter attempts to renew its IP address with the DHCP server.
The possibility exists that the adapter will be assigned a different IP address, which would cause the adapter to cease communicating with the
ControlLogix controller.
Publication 1734-UM011D-EN-P - May 2011
24 Configure the Adapter for Your EtherNet/IP Network
ATTENTION
To avoid unintended control, the 1734-AENT adapter must be assigned a fixed IP address. The IP address of this adapter should not be dynamically provided. If a DHCP server is used, it must be configured to assign a fixed IP address for your adapter.
Failure to observe this precaution may result in unintended machine motion or loss of process control.
Publication 1734-UM011D-EN-P - May 2011
Chapter
4
Configure the Adapter for Direct Connection in RSLogix 5000 Software
What This Chapter Contains
In this example, a ControlLogix controller communicates with POINT I/O modules via the 1734-AENT adapter using a direct connection.
The adapter makes a direct connection to each of the modules referenced by the data. The modules presented in this chapter use RSLogix 5000 software, version 11.
Topic
Create the Example Application
Add the Local EtherNet/IP Bridge to the I/O
Add the POINT I/O Adapter to the I/O Configuration 30
Add the POINT I/O Modules to the I/O Configuration 33
Download the Program to the Controller
Verify the Module Chassis Size
Configure the Adapter with Fixed IP Address
Recover From an Overloaded Adapter
Page
ATTENTION
You must use series C POINT I/O modules with the 1734-AENT adapter. Series A or B POINT I/O modules will not work with this adapter.
Set Up the Hardware
In this example, a ControlLogix chassis contains the Logix5555 processor in slot 1 and a 1756-ENBT bridge module in slot 3.
25 Publication 1734-UM011D-EN-P - May 2011
26 Configure the Adapter for Direct Connection in RSLogix 5000 Software
We mounted the 1734-AENT adapter on a DIN rail in slot 0, with a
1734-OW2/C relay output module in slot 1, a 1734-OV4E/C sink output module in slot 2, and a power supply (not shown).
1734-AENT
10.88.70.2
POINT I/O
Slot 0 1 2 3
Local chassis
Data
Logix5555 controller (slot 1)
1756-ENBT
10.88.70.4 (slot 3)
Switch
10.88.70.26
Programming terminal
Slot 0 1 2 3 4
Create the Example
Application
31393-M
To work along with this example, set up your system as shown in the figure.
• In the example application, we assume that the Logix5555 controller and 1756-ENBT module (firmware revision 2.3, or later) are in the slots shown in the figure.
• Verify the IP addresses for your programming terminal, 1756-ENBT module, and 1734-AENT adapter.
• Verify the position (slot) of the I/O modules on the DIN rail.
• Verify that you connected all wiring and cabling properly.
• Be sure you configured your communication driver (for example,
AB_ETH/IP-1) in RSLinx software, as described in Appendix A
Configure the RSLinx Ethernet Communication Driver on page 87 of
this manual.
Perform the following steps to create the example application:
1. Start RSLogix 5000 Enterprise Series software to open the
RSLogix 5000 Main dialog.
Publication 1734-UM011D-EN-P - May 2011
Configure the Adapter for Direct Connection in RSLogix 5000 Software 27
2. From the File menu, select New.
The New Controller dialog opens.
Configure the I/O
3. Enter an appropriate Name for the Controller, for example,
POINT_IO_Controller.
4. Select the correct Version, Chassis Type, and Slot number of the
Logix5555 controller, and the folder where you want to save the
RSLogix 5000 file (Create In). The Description is optional.
RSLogix 5000 software version 11 or later lets you choose to enable redundancy. This example does not use redundancy. To use redundancy in your system, check the Redundancy Enabled checkbox so that a checkmark appears.
5. Click OK.
You now add the POINT I/O modules to the controller I/O configuration performing these procedures.
Publication 1734-UM011D-EN-P - May 2011
28 Configure the Adapter for Direct Connection in RSLogix 5000 Software
• Add the local 1756-ENBT module to the I/O configuration.
• Add the 1734-AENT adapter as a child of the 1756-ENBT module.
• Add the I/O modules as children of the 1734-AENT adapter.
IMPORTANT
Click the Help buttons on the configuration dialogs shown in this section if you need assistance in selecting and setting the parameters.
Add the Local EtherNet/IP Bridge to the I/O Configuration
1. Select the I/O Configuration folder in the project dialog, and click the right mouse button.
A dialog opens.
2. Click New Module.
Publication 1734-UM011D-EN-P - May 2011
Configure the Adapter for Direct Connection in RSLogix 5000 Software 29
The Select Module dialog opens.
3. Expand Communications to see the list of Communications modules.
4. Select the 1756-ENBT EtherNet/IP Bridge, and click OK.
The Select Major Revision dialog opens.
5. Select the number for Major Revision, and click OK.
Publication 1734-UM011D-EN-P - May 2011
30 Configure the Adapter for Direct Connection in RSLogix 5000 Software
The New Module dialog opens.
6. Enter values for Name, IP Address, Slot, Electronic Keying, and
Revision, noting that we used the following values:
Name
IP Address
Slot
Electronic Keying
Revision
Local_ENB
10.88.70.4
3
Compatible Keying
3.1
7. Click OK to accept the configuration.
The Module Properties dialog opens.
Publication 1734-UM011D-EN-P - May 2011
Add the POINT I/O Adapter to the I/O Configuration
Next, you must add the 1734-AENT adapter as a child of the local
1756-ENBT module.
1. In the Project dialog, right-click the local 1756-ENBT module under the
I/O Configuration folder, and select New Module from the dialog.
Configure the Adapter for Direct Connection in RSLogix 5000 Software 31
The Select Module dialog opens.
2. Expand Communications to see the list of Communications modules.
Publication 1734-UM011D-EN-P - May 2011
32 Configure the Adapter for Direct Connection in RSLogix 5000 Software
3. Select the 1734-AENT/A Ethernet adapter from the list, and click OK, noting that we used these values.
Name
IP Address
Comm Format
Chassis Size
POINT_IO_Adapter
10.88.70.2
None
3
Electronic Keying
Revision
Compatible Keying
1.1
The Slot field appears grey because the slot is automatically 0 for the 1734-AENT adapter.
IMPORTANT
The chassis size equals 1 for the adapter plus the number of
POINT I/O modules installed (physically present on the
POINT I/O backplane).
The New Module dialog opens.
Publication 1734-UM011D-EN-P - May 2011
Comm Format choices are the following.
• None – the adapter makes a direct connection to each of the modules referenced by the data.
• Rack optimization – digital I/O data is collected into a rack image.
This does not include analog or specialty I/O modules.
• Listen only - rack optimization – read or verify data only, but does not control the modules. When you have multiple controllers, one controller is used to control and the other controllers are used to monitor.
4. Choose None as Comm Format, because we are making a direct connection, and click OK.
Because you entered None as the Comm Format, the requested packet interval (RPI) is disabled.
Configure the Adapter for Direct Connection in RSLogix 5000 Software 33
The 1734-AENT adapter appears in the Ethernet folder.
Add the POINT I/O Modules to the I/O Configuration
You now add POINT I/O modules to the I/O Configuration List under the
1734-AENT adapter.
In this example, you add a 1734-OW2 relay output and a 1734-OV4E sink output module with standard configurations. Use these steps as a guide when configuring different I/O modules for your system.
TIP
This example application uses the I/O modules default configurations. For more information, see the POINT I/O
Selection Guide, publication 1734-SG001 .
Add the Relay Output Module
1. Right-click the remote 1734-AENT adapter under the I/O
Configuration folder and select New Module.
Publication 1734-UM011D-EN-P - May 2011
34 Configure the Adapter for Direct Connection in RSLogix 5000 Software
The Select Module dialog opens.
2. Expand Digital to see the list of Digital modules.
3. Select the 1734-OW2 relay output module from the list, and click OK.
The New Module dialog opens.
Publication 1734-UM011D-EN-P - May 2011
Configure the Adapter for Direct Connection in RSLogix 5000 Software 35
4. Enter values for Name and Slot, noting that we used the following values.
Name
Slot
POINT_Relay_Output
1
5. Choose Connection.
The RPI is selectable since it is a direct connection.
6. Enter 50 for requested packet interval (RPI) to set how often you exchange data with the 1734-AENT adapter.
IMPORTANT
To avoid overloading the 1734-AENT adapter, we recommend that RPI be no less than 10 ms for rack connections and 50 ms for direct connections.
7. Click OK to save the configuration.
The relay output module appears under Ethernet.
Publication 1734-UM011D-EN-P - May 2011
36 Configure the Adapter for Direct Connection in RSLogix 5000 Software
Add the Digital Output Module
1. Right-click the 1734-AENT adapter, and select New Module.
The Select Module dialog opens.
2. Expand Digital to see the list of Digital modules..
Publication 1734-UM011D-EN-P - May 2011
3. Select the 1734-OV4E digital output module from the list.
4. Click OK.
Configure the Adapter for Direct Connection in RSLogix 5000 Software 37
The New Module dialog opens.
5. Enter values for Name and Slot, noting we used the following.
Name
Slot
POINT_Digital_Output
2
6. On the Connection tab, enter 10 ms as the RPI for the 1734-OV4E module.
7. Click OK.
The I/O Configuration in the Project dialog should look similar to the following.
Publication 1734-UM011D-EN-P - May 2011
38 Configure the Adapter for Direct Connection in RSLogix 5000 Software
Edit the Controller Tags
When you add modules to the I/O configuration the system creates tags for those modules to use in the application program.
For the example application you need to add one more controller tags.
1. Double-click the Controller Tags folder in the project dialog.
The Controller Tags dialog opens. You see the tags created for the
1734-AENT adapter and digital I/O modules.
Tags created by the system
Enter the new tag here
2. Click the Edit Tags tab at the bottom of the Controller Tags dialog.
Publication 1734-UM011D-EN-P - May 2011
3. Create the following tag:
Tag
Parts_Count
4. Close the Controller Tags dialog.
Type
Counter
Configure the Adapter for Direct Connection in RSLogix 5000 Software 39
Create the Ladder Program
Next create the example ladder program to test the I/O.
1. Double-click Main Routine under the Main Program folder.
2. Enter the following ladder program using the tags previously created.
3. Save the program.
Download the Program to the Controller
Follow this procedure to download the program you just saved to the
ControlLogix controller.
Publication 1734-UM011D-EN-P - May 2011
40 Configure the Adapter for Direct Connection in RSLogix 5000 Software
1. From the main menu, choose Communications>Who-Active.
The Who Active dialog opens.
2. Navigate to select the slot where the controller is located in the chassis.
3. Choose Set Project Path.
4. Choose Download.
The Download dialog opens with a reminder of the following.
• The controller is in Remote Run mode.
• The mode changes to Remote Program prior to download.
Publication 1734-UM011D-EN-P - May 2011
Configure the Adapter for Direct Connection in RSLogix 5000 Software 41
5. From the Download dialog, choose Download to see the RSLogix 5000 software dialog.
6. Notice that the 1756-ENBT Bridge is now online.
If yellow triangles are present, see the following section.
Verify the Module Chassis
Size
You have now built the I/O tree in RSLogix 5000 software, and the
RSLogix 5000 software used the chassis size from the 1734-AENT General tab.
Now you need to download this new chassis size value into the 1734-AENT adapter hardware. This procedure synchronizes the chassis size value from the
RSLogix 5000 software into the 1734-AENT adapter hardware.
1. Verify that RSLogix 5000 is online.
2. Right-click the 1734-AENT adapter under I/O Configuration in the
Project dialog.
3. Select Properties.
4. Click the Connection tab.
Publication 1734-UM011D-EN-P - May 2011
42 Configure the Adapter for Direct Connection in RSLogix 5000 Software
You see the Module Fault error code.
Value from
RSLogix 5000 software
Value stored in 1734-AENT adapter
5. Click the Chassis Size tab.
6. Click Set Chassis Size in Module.
7. Read and acknowledge the warning dialog.
Publication 1734-UM011D-EN-P - May 2011
8. Click OK to continue.
Configure the Adapter for Direct Connection in RSLogix 5000 Software 43
Notice the chassis size in the module is modified to 3.
9. Click OK.
At this point, your POINTBus status LED should be solid green. All the yellow triangles in your I/O configuration should be gone.
Configure the Adapter with
Fixed IP Address
To configure the 1734-AENT adapter with a fixed IP address to prevent the adapter from ceasing to communicate with the ControlLogix controller:
1. Click the Port Configuration tab in the 1734-AENT adapter properties dialog.
2. Uncheck the Enable DHCP box.
3. Click the Set button.
Publication 1734-UM011D-EN-P - May 2011
44 Configure the Adapter for Direct Connection in RSLogix 5000 Software
4. Read and acknowledge the warning.
Recover From an
Overloaded Adapter
5. Click OK.
6. Click the Refresh button to verify the changes.
Each POINT I/O connection established with the 1734-AENT adapter consumes a portion of the microprocessor’s bandwidth. The amount of bandwidth used by a connection depends on a number of variables, including the requested packet interval (RPI), the number of POINT I/O modules involved in the connection, and the rate of change of the I/O.
The 1734-AENT adapter continuously monitors this bandwidth and rejects requests for new connections when there is insufficient bandwidth available to support the new connection.
The condition where the 1734-AENT adapter cannot support the connection due to a limit of the microprocessor’s bandwidth is shown in the following dialog.
Publication 1734-UM011D-EN-P - May 2011
If you encounter this condition, the only action you can take is to alter the existing connections to reduce the amount of microprocessor bandwidth consumed. The most likely fixes for this condition include the following.
• Increase the RPI.
• Decrease the number of connections.
45
Chapter
5
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000
Software
What This Chapter Contains
This chapter guides you through the steps required to configure your
POINT I/O Ethernet adapter for both direct connection and rack optimization using RSLogix 5000 software.
You can mix communication formats for different I/O modules communicating through the same adapter. I/O modules set up to use rack optimization communicate at the rate of the RPI configured for the
1734-AENT adapter.
I/O modules configured for direct communication communicate at their own set RPI and ignore the 1734-AENT adapter RPI. The modules presented in this chapter have a configuration using RSLogix 5000 software, version 15.
The chapter contains the following main sections:
Topic
Create the Example Application
Add the Local EtherNet/IP Bridge to the I/O
Add the POINT I/O Adapter to the I/O Configuration
Add the POINT I/O Module and Configure for Direction
Add the POINT I/O Module and Configure For Rack
Download the Program to the Controller
Verify the Module Chassis Size
Page
ATTENTION
You must use series C POINT I/O modules with the 1734-AENT adapter. Series A or B POINT I/O modules will not work with this adapter.
Publication 1734-UM011D-EN-P - May 2011
46 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
Set Up the Hardware
In this example, a ControlLogix chassis contains the Logix 5555 controller in slot 1 and a 1756-ENBT bridge module in slot 3. We mounted the
1734-AENT adapter on a DIN rail in slot 0, with a 1734-OW2/C relay output module in slot 1, a 1734-OV4E/C sink output module in slot 2, and a power supply (not shown).
1734-AENT
10.88.70.2
POINT I/O
Slot 0 1 2 3
Local chassis
Data
Logix5555 controller (slot 1)
1756-ENBT
10.88.70.4 (slot 3)
Switch
10.88.70.26
Programming terminal
Slot 0 1 2 3 4
31393-M
To work along with this example, set up your system as shown in the figure.
• Note that in the example application, the Logix5555 controller and
1756-ENBT module (firmware revision 2.3 or later) we assume are in the slots shown in the figure.
• Verify the IP addresses for your programming terminal, 1756-ENBT module, and 1734-AENT adapter.
• Verify the position (slot) of the I/O modules on the DIN rail.
• Verify that you properly connected all wiring and cabling.
• Be sure you configured your communication driver (such as
AB-ETHIP-1) in RSLinx software as described in Appendix A
Configure the RSLinx Ethernet Communication Driver on page 87 of
this manual.
Publication 1734-UM011D-EN-P - May 2011
Create the Example
Application
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software 47
Perform the following steps to create the example application:
1. Start the RSLogix 5000 Enterprise Series software.
You see the RSLogix 5000 main dialog.
2. From the File menu, select New.
The New Controller dialog opens.
3. Enter an appropriate Name for the Controller, for example,
POINT_IO_Controller.
4. Specify the following.
• Revision
• Chassis Type
• Slot number
• Description (optional)
5. Complete the Create In entry by selecting the folder where you want to save the RSLogix 5000 file.
Publication 1734-UM011D-EN-P - May 2011
48 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
6. To use redundancy in your system, check the Redundancy Enabled checkbox so that a checkmark appears.
RSLogix 5000 software, version 11 and later, includes enable redundancy. This example does not use redundancy.
7. Click OK.
Configure the I/O Modules
You now add the POINT I/O modules to the controller I/O configuration.
To do this, first add the local 1756-ENBT module to the I/O configuration.
Next, add the 1734-AENT adapter as a child of the 1756-ENBT module.
Then add the I/O modules as children of the 1734-AENT adapter.
IMPORTANT
Click the Help buttons on the configuration dialog shown in this section if you need assistance in selecting and setting the parameters.
Add the Local EtherNet/IP Bridge to the I/O Configuration
1. Select the I/O Configuration folder in the project dialog, and click the right mouse button.
Publication 1734-UM011D-EN-P - May 2011
A dialog opens.
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software 49
2. Click New Module.
The Select Module dialog opens.
3. Expand Communications to see the list of Communications modules.
4. Select the 1756-ENBT EtherNet/IP Bridge, and click OK.
The Select Major Revision dialog opens.
5. Select the value for Major Revision, and click OK.
Publication 1734-UM011D-EN-P - May 2011
50 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
The Module Properties dialog opens.
6. Enter values for Name, IP Address, Slot, Electronic Keying, and
Revision, noting we used the following values:
Name
IP Address
Slot
Electronic Keying
Revision
Local_ENB
10.88.70.4
3
Compatible Module
1.1
7. Click Finish to accept the configuration.
Add the POINT I/O Adapter to the I/O Configuration
Next, you must add the 1734-AENT adapter as a child of the local
1756-ENBT module.
1. In the Project dialog, right-click the local 1756-ENBT module under the
I/O Configuration folder, and select New Module from the dialog.
Publication 1734-UM011D-EN-P - May 2011
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software 51
The Select Module dialog opens.
2. Expand Communications to see the list of Communications modules.
3. Select the 1734-AENT/A Ethernet adapter from the list, and click OK.
The New Module dialog opens.
Publication 1734-UM011D-EN-P - May 2011
52 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
4. Enter values for Name, IP Address, Comm Format, Chassis Size,
Electronic Keying, and Revision, noting we used the following values.
Name
IP Address
Comm Format
Chassis Size
POINT_IO_Adapter
10.88.70.2
Rack Optimization
4
Electronic Keying
Revision
Compatible Keying
1.1
The Slot field appears grey because the slot is automatically 0 for the
1734-AENT adapter.
IMPORTANT
The chassis size equals 1 for the adapter plus the number of
POINT I/O modules installed (physically present on the
POINT I/O backplane).
Comm Format choices include:
• None – the adapter makes a direct connection to each of the modules referenced by the data.
• Rack optimization – digital I/O data is collected into a rack image.
This does not include analog or specialty I/O modules.
• Listen only - rack optimization – read or verify data only, but does not control the modules. When you have multiple controllers, one controller is used to control and the other controllers are used to monitor.
5. Choose Rack Optimization as Comm Format, because we are making a mixed connection that includes both a direct connection and rack-optimized connection.
6. Click OK.
The Module Properties dialog opens.
Publication 1734-UM011D-EN-P - May 2011
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software 53
7. Verify that the requested packet interval (RPI) is appropriate for your system.
You use this value for the rack-optimized connection to the I/O modules.
IMPORTANT
To avoid overloading the 1734-AENT adapter, we recommend that you set RPI no less than 10 ms for rack connections and 50 ms for direct connections.
8. Click OK.
The 1734-AENT adapter appears in the Ethernet folder.
Add the POINT I/O Module and Configure for Direction
Connection
1. Highlight the 1734-AENT adapter under the I/O Configuration folder, and select New Module.
The Select Module dialog opens.
Publication 1734-UM011D-EN-P - May 2011
54 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
2. Expand Digital to see the list of digital modules.
3. Select the 1734-OW2 relay output module from the list, and click OK.
The New Module dialog opens.
4. Enter values for Name and Slot. Note that we used the following values.
Name
Slot
POINT_Relay_Output
1
5. Choose Connection.
Publication 1734-UM011D-EN-P - May 2011
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software 55
The RPI is selectable, since it is a direct connection.
6. Verify that the requested packet interval (RPI) is appropriate for your system (10 ms for this example). You use this value for the rack-optimized connection to the I/O modules.
IMPORTANT
To avoid overloading the 1734-AENT adapter, we recommend that the RPI be no less than 10 ms for rack connections and 50 ms for direct connections.
7. Click OK to accept the configuration.
The 1734-AENT adapter appears indented under the local 1734-ENBT in the I/O Configuration folder.
Add the POINT I/O Module and Configure For Rack Optimization
1. Right-click the 1734-AENT adapter under the I/O Configuration folder, and select New Module.
IMPORTANT
If you exceed the 1734-AENT chassis size, trying to add more modules than you configured, the New Module selection appears dim and is disabled. Increase the
1734-AENT chassis size to add more POINT I/O modules.
Publication 1734-UM011D-EN-P - May 2011
56 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
The Select Module dialog opens.
2. Expand Digital to see the list of digital modules available.
Publication 1734-UM011D-EN-P - May 2011
3. Choose the 1734-OV4E/C module, and click OK.
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software 57
The New Module dialog opens.
4. From the New Module dialog, complete the following.
• Enter a value for Name.
• Enter a value for Slot.
• Click Change.
The Module Definition dialog opens.
5. From the Connection tab, select Rack Optimization.
6. Click OK.
The New Module dialog opens.
7. From the New Module dialog, click the Connection tab.
Publication 1734-UM011D-EN-P - May 2011
58 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
The New Module Connection tab dialog opens.
8. On the Connection tab, enter 50 for the requested packet interval (RPI).
9. Keep the following unchecked:
• Inhibit Module
• Major Fault on Controller If Connection fails While in Run Mode
10. Click OK.
11. Choose File → Save and enter the name and location of the
RSLogix 5000 file.
Download the Program to the Controller
Follow this procedure to download the program we just saved to the
ControlLogix controller.
1. From the main menu, choose Communications → Who-Active.
2. From the Who Active dialog, navigate to select the slot where the controller is located in the chassis.
Publication 1734-UM011D-EN-P - May 2011
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software 59
3. Choose Set Project Path.
4. Choose Download.
You see the Download dialog.
5. From the Download dialog, click Download.
You see this RSLogix 5000 dialog.
6. Notice that the 1756-ENBT Bridge is now online.
Verify the Module
Chassis Size
If yellow triangles are present, see the following section.
You have now built the I/O tree in RSLogix 5000, and the RSLogix 5000 software used the chassis size from the 1734-AENT General tab. Now you need to download this new chassis size value into the 1734-AENT adapter hardware. This procedure synchronizes the chassis size value from the
RSLogix 5000 software into the 1734-AENT hardware. You must be online to perform this procedure.
1. Verify that RSLogix 5000 software is online.
2. Right-click the 1734-AENT adapter under I/O Configuration in the
Project dialog.
Publication 1734-UM011D-EN-P - May 2011
60 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
3. Select Properties.
4. Click the Connection tab.
You see the Module Fault error code.
Value from
RSLogix 5000 software
5. Click the Chassis Size tab.
6. Click Set Chassis Size in Module.
Value stored in 1734-AENT adapter
Publication 1734-UM011D-EN-P - May 2011
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software 61
7. Read and acknowledge the warning dialog.
8. Click OK to continue.
9. Notice the chassis size in the module is modified to 3.
10. Click OK.
At this point, your POINTBus status LED should be solid green. All the yellow triangles in your I/O configuration tree should be gone.
11. Click OK to close the dialog.
12. Click File
→
Save to save the project.
Publication 1734-UM011D-EN-P - May 2011
62 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
Access Module Data
Use the following information to use the 1734 POINT I/O Ethernet adapter data in the ladder logic program.
• POINT_IO_Adapter = the name you gave to your Ethernet adapter
• # = slot number of POINT I/O module
• C = configuration, I = input, O = output
Publication 1734-UM011D-EN-P - May 2011
This value indicates that slot 2 is the only module participating in the rack-optimized connection with no errors.
Use the controller tags in your ladder program to read input data or write output data.
• For RSLogix 5000 programming instructions, refer to RSLogix 5000
Getting Results, publication 9399-RLD300GR .
• For ControlLogix controller information, refer to ControlLogix System
User Manual, publication 1756-UM001 .
• Slot Status Bits: The Slot Status bits display the connection status for each of the POINT I/O modules that use a rack-optimized connection.
– Bit 0 is reserved for the adapter and always reports a value of 1.
– Each of the other bits (1…63) correspond to a POINT I/O module that you install in the POINT I/O backplane.
– In this example, we configured the 1734-AENT adapter for both rack-optimized and direct connections.
The slot status bits indicate that we installed the module in slot 2 with it operating correctly:
• 0=module participating with no errors and
• 1=module not participating or connection error (typically, module removed/missing).
63
Chapter
6
LED Status Indicators
What This Chapter Contains
Read this chapter for information about LED status indicators.
Interpret the Status Indicators
Module Status
Network Activity
Network Status
POINTBus Status
System Power
Field Power
ATTENTION
43248aent
You must use series C POINT I/O modules with the
1734-AENT adapter. Series A or B POINT I/O modules will not work with this adapter.
Indication
Module Status
Probable Cause
Off
Flashing red/green
Solid green
No power applied to device
LED cycle power test (module self-test) present.
Device is operating normally.
Flashing red Recoverable fault has occurred:
Firmware (NVS) update present.
Address switches changed.
Solid red Unrecoverable fault has occurred:
Self-test failure present
(checksum failure, or RAMtest failure at cycle power).
Firmware fatal error present.
Recommended Action
Apply power to the device.
None
None
Complete firmware update.
Verify address switches.
Replace adapter.
Publication 1734-UM011D-EN-P - May 2011
64 LED Status Indicators
Publication 1734-UM011D-EN-P - May 2011
Indication Probable Cause
Network Activity
Off No link established.
Flashing green/Off
Transmit or receive activity present.
Steady green Link established.
Network Status
Off Device not initialized. The module does not have an IP address.
Flashing green No CIP connections present.
Device has an IP address, but no
CIP connections are established.
Solid green CIP connections present. Device online and has an IP address, and
CIP connections are established.
Flashing red One or more CIP connections has timed-out.
Solid red Duplicate IP address detected.
Verify network cabling, and correct, as needed.
None
None
Apply power to device, verify IP address, and correct, as needed.
None
None
Check for I/O module failure and controller operation, and correct, as needed.
Verify IP address setting and correct, as needed.
None Flashing red/green
The module is performing a self-test (only occurs during cycle power test).
POINTBus Status
Off Device not powered – check module status indicator.
Flashing red/green
Flashing red
LED cycle power test present.
Recoverable fault occurred:
Recommended Action
Apply power to device.
None
• At cycle power the number of expected modules does not equal the number of modules present
• A module is missing
• Node fault (I/O connection timeout) occurred.
Unrecoverable fault occurred – the adapter is bus off.
• Configure chassis size.
• Check for missing module and reinstall as needed.
• Check for I/O module failure and correct as needed.
Solid red 1. Cycle power to device.
2. If condition persists, replace device.
None Flashing green Firmware (NVS) update in progress.
Solid green Adapter online with connections established (normal operation,
Run mode).
None
LED Status Indicators 65
System Power
Off Not active; field power is off or
DC-DC converter problem present.
1. Verify power is on, and apply power if needed.
2. Verify backplane power not exceeded, and correct.
3. Replace 1734-AENT module.
None Green System power is on; DC-DC converter is active (5V).
Field Power
Off
Green
Not active; field power is off.
Power is on; 24V is present.
Apply field power.
None
Publication 1734-UM011D-EN-P - May 2011
66 LED Status Indicators
Notes:
Publication 1734-UM011D-EN-P - May 2011
67
Appendix
A
Adapter Web Pages
What This Appendix
Contains
Read this appendix for information about the adapter Web page diagnostics that offer extensive internal and network diagnostics.
Topic
Work with the Diagnostics Pages
Work with the Configuration Pages
Work with the Browse Chassis Page
Page
Work with the Home Page
Use the adapter diagnostics Home page to access other adapter diagnostics
Web pages and see the following information.
• Host Name
• Module Description
• Module Location
• IP Address
• Ethernet Address (MAC)
• DHCP Enabled
• Product Revision
• Serial Number
• Status
• Auto Negotiate
• Media Speed
• Half or Full Duplex
To display and work with the adapter diagnostics Home page, follow these procedures.
IMPORTANT
Make sure that your PC Internet LAN setting and your
TCP/IP settings are configured to access the subnet on which your adapter communicates.
Publication 1734-UM011D-EN-P - May 2011
68 Adapter Web Pages
Enter the adapter IP address to see the
Home page.
ATTENTION
You must use Series C POINT I/O modules with the 1734-AENT adapter. Series A or B POINT I/O modules will not work with this adapter.
1. From a browser such as Netscape or Microsoft Internet Explorer, enter the adapter IP address to see the Home page.
Click Expand to expand options.
2. From the Home page, click Expand to expand options, as in the figure, or Minimize to see Diagnostics, Configuration, and Browse Chassis options without the expansion.
Publication 1734-UM011D-EN-P - May 2011
Adapter Web Pages 69
3. From the Home page, complete one of these, as desired.
• Click one of these to go to http://www.ab.com/ .
– Allen-Bradley logo at the top of the page
– Visit ab.com
for additional information statement under Resources
• Click Rockwell Automation at the top right to go to http://www.rockwellautomation.com/ .
• Click these to see additional diagnostics Web pages.
– Diagnostics – Diagnostic overview, Network Settings,
Ethernet Statistics, I/O Connections, Diagnostic messaging
– Configuration - Identity, Network, Services
– Browse chassis
Work with the Diagnostics
Pages
To work with the Diagnostics options, follow these procedures.
1. From the Home page, click Diagnostics or Expand to see the following diagnostics options from the panel at the left.
• Diagnostic overview
• Network settings
• Ethernet statistics
• I/O connections
• Diagnostic messaging
2. From from the top of the page, as shown in the figure, if desired, type a refresh rate, noting that the default is 15 seconds.
3. From the panel at the left or tabs at the top of the page, as shown in the figure, click one of the diagnostics options to see the corresponding page.
Click tabs to see the corresponding page.
Click from this panel to see the corresponding page.
Type a refresh rate.
Publication 1734-UM011D-EN-P - May 2011
70 Adapter Web Pages
Use the Diagnostic Overview Page
To use the Diagnostic Overview page to view general diagnostics information, follow this procedure.
1. From the Web page, click the Diagnostic Overview tab at the top of the page or panel on the left.
The Diagnostic Overview tab opens.
Publication 1734-UM011D-EN-P - May 2011
2. From the Diagnostic Overview tab, view the following.
• Ethernet Link Status
– Media Speed
– Half or Full Duplex
– Autonegotiate Status
• System Resource Utilitization
– CPU Utilization
– Module Uptime
• CIP Connection Statics
– Current CIP MSG Connections
– CIP MSG Connection Limit
– Max Msg Connections Observed
– Current CIP I/O Connections
– CIP I/O Connection Limit
– Max I/O Connections Observed
– Conn Opens
Adapter Web Pages 71
– Open Errors
– Conn Closes
– Close Errors
– Conn Timeout
– Status
• Module Settings
– Chassis Size
– Switches
Use the Network Settings Page
To use the Network Settings page to view network related information, follow this procedure.
1. From the Web page, click the Network Settings tab at the top of the page or panel on the left.
The Network Settings tab opens.
Publication 1734-UM011D-EN-P - May 2011
72 Adapter Web Pages
2. From the Network Settings page, view the following.
• Network Interface
– Ethernet Address (MAC)
– IP Address
– Subnet Mask
– Default Gateway
– Primary Name Server
– Secondary Name Server
– Default Domain Name
– Host Name
– Name Resolution
• Ethernet Interface Configuration
– How the Network Configuration was obtained -
Static or Dynamic
• Ethernet Link
– Media Speed
– Half or Full Duplex
– Autonegotiate Status
Use the Ethernet Statistics Page
To use the Ethernet Statistics page to view information about the Ethernet link and interface and media counters, use this procedure.
1. From the Web page, click the Ethernet Statistics tab at the top of the page or panel on the left.
Publication 1734-UM011D-EN-P - May 2011
The Ethernet Statistics tab opens.
Adapter Web Pages 73
2. From the Ethernet Statistics tab, view the following:
• Ethernet Link
– Media Speed, Half or Full Duplex, Autonegotiate Status
• Interface Counters
– In Octets, In UCast Packets, In NUcast Packets,
In Discards, In Errors, In Unknown Protos,
Out Octets, Out Ucast Packets, Out NUcast Packets,
Out Discards, Out Errors
• Media Counters
– Alignment Errors
– FCS Errors
– Single Collisions
– Multiple Collisions
– SQE Test Errors
– Deferred Transmissions
– Late Collisions
– Excessive Collisions
– MAC Transmit Errors
– Carrier Sense Errors
– Frame Too Long
– Mac Receive Errors
Publication 1734-UM011D-EN-P - May 2011
74 Adapter Web Pages
Publication 1734-UM011D-EN-P - May 2011
Use the I/O Connections Page
To use the I/O Connections page to view CIP I/O (Class 1) connection information, follow this procedure.
1. From the Web page, click the I/O Connections tab at the top of the page or panel on the left.
The I/O Connections tab opens.
The top value in this column representing
Lost shows the number of packets from the source missing.
The value for
Slot shows the slot number of the I/O module this connection is controlling.
2. From the I/O Connections page, view the following:
• Connection Number
• Uptime
• Receive and Transmit (Rcv/Xmt)
• Connection ID
• Source IP Address with an indication of the following
– (O) for originator
– (T) for target
• Destination IP Address
• Multicast Address
• Requested Packet Interval (RPI)
• Lost/Slot that shows the number of lost packets and the slot number for the connection, with a slot value of 0 indicating that this is a rack-optimized connection
• Size of data in bytes
Adapter Web Pages 75
Use the Diagnostic Messaging Page
To use the Diagnostic Messaging page to execute explicit, unconnected message services, use this procedure.
1. From the Web page, click the Diagnostic Messaging tab at the top of the page or panel on the left.
The Diagnostic Messaging tab opens.
2. From the Diagnostic Messaging tab, enter the following:
• Service – choose either Get Attribute Single or Get Attributes All
• I/O Module Slot Position (0…63 decimal)
• Class (decimal)
• Instance (decimal)
• Attribute (decimal)
• Timeout
Publication 1734-UM011D-EN-P - May 2011
76 Adapter Web Pages
3. From the Diagnostic Messaging tab, click Submit to see values similar to that in the figure.
Work with the
Configuration Pages
To work with the Configuration pages, follow these procedures, noting that values on these pages are stored in and retrieved from non-volatile memory.
IMPORTANT
The values on these pages are in non-volatile memory.
Changes to these parameters do not take effect until you reset or cycle power to the 1734-AENT adapter.
IMPORTANT
If you set the thumbwheels on the 1734-AENT adapter to the value 888 and then power cycle the module, the following occurs:
• The DHCP Enabled function is enabled (set to True).
• The Ethernet link is negotiated automatically. The Auto
Negotiate function is set to True.
• The Web server is enabled. The Disabled Web Server function is disabled.
• The password for this page resets to the factory default.
The word password is the factory default password.
Note the value of the switches before you enter the 888 value because you return the adapter to those values once this process is complete.
1. From the Home page, click Configuration or Expand to see the
Configuration options, if needed.
Publication 1734-UM011D-EN-P - May 2011
2. From the Configuration page, click one of these.
• Identity
• Network
• Services
The Enter Network Password dialog opens.
Adapter Web Pages 77
3. From the user name and password dialog, enter values, noting the following.
• The values for user name and password are case sensitive.
• The default user name is admin.
• The default password is password.
4. From the user name and password dialog, click OK to log in, noting that after you log in you can go to any of the Configuration pages without logging in again.
5. Refer to the section of this manual that describes which of these you clicked: Identity, Network, Services.
Use the Identity Page
To use the Identify page to make entries for the host name, module description, module location, and chassis size, use this procedure.
1. From the Web page, click Identity from the tab at the top of the page or panel on the left.
Publication 1734-UM011D-EN-P - May 2011
78 Adapter Web Pages
You see the Identity page.
Publication 1734-UM011D-EN-P - May 2011
2. From the Identity tab, complete entries for the following, noting that the description and location help you identify where modules are in the facility.
• Host Name – the name a Domain Name Server uses to resolve this adapter’s IP address
• Module Description
• Module Location
• Chassis Size – the value that shows the number of POINT I/O mdoules plus the adapter. This value must match the number of I/O modules plus one for the adapter before any I/O connections are allowed.
3. Click Apply Changes to save the modified values.
Use the Network Configuration Page
To use the Network Configuration page to make entries for enabling or disabling DHCP and setting TCP/IP parameters and Ethernet link operation, follow this procedure.
1. From the Web page, click the Network tab at the top of the page or panel on the left.
You see the Network Configuration page.
Adapter Web Pages 79
2. From the Network Configuration tab, complete these entries, noting that values for Network Interface are disabled when DHCP is Dynamic
DHCP and port speed and duplex mode are disabled when
Autonegotiate Speed and Duplex is selected.
• For Initial Network Configuration
Ethernet Interface Configuration
– Static
– Dynamic DHCP
• For Network Interface, select from these choices.
– IP Address
– Subnet Mask
– Gateway Address
– Primary Name Server
– Secondary Name Server
– Domain Name
• For Ethernet Link, select from these choices.
Autonegotiate Status
– Autonegotiate Speed and Duplex
– Force Speed and Duplex
Select Port Speed – 10 megabits, 100 megabits
Select Duplex Mode – Half Duplex, Full Duplex
3. Click Apply Changes to save the modified values.
Publication 1734-UM011D-EN-P - May 2011
80 Adapter Web Pages
Use the Services Page
To use the Services page to change the password for the Configuration web page or disable the Web server, complete these procedures.
1. From the Web page, click the Services tab at the top of the page or panel on the left.
The Services tab opens.
2. From the Services tab, make these entries:
• Click in the Enable box to change whether the Web server runs after the module is reset.
• Change the password by typing the new value for New Password and
Confirm Password, noting the following.
– The entry is case sensitive.
– The default value is the word password.
3. Click Apply Changes.
Work with the Browse
Chassis Page
Use the Browse Chassis page for the following.
• See what modules are present on the system.
• Run a query from slot 1 to slot 63.
• Display the modules found based on the query.
• Provide an easy way to see what modules the adapter is recognizing on your system.
Publication 1734-UM011D-EN-P - May 2011
Adapter Web Pages 81
To work with the Browse Chassis page, follow these procedures.
1. From the Home page, click Browse Chassis.
Before the query completes, this note about the disabled module hyperlinks appears.
Check Increase timeout to increase the time of the browse query and time the modules get to respond to the query, which is useful when browsing a busy system.
2. From the Browse Chassis page, leave the Display compact check box unchecked, if desired, unless you want to decrease the font size, making it easier to read the full page after the query.
3. Check the Increase timeout check box so a check mark appears, if desired.
This increases the time of the browse query and time the modules get to respond to the query. This function is useful when you are browsing a busy system.
4. Click Start to run the query, noting that you see a page such as the one in the the figure, which shows that module hyperlinks are disabled while browsing before the query completes or is cancelled.
Before the query completes, module hyperlinks are inactive.
If there is no response to the query, the Module not found message appears.
Before the query finds the module, the Requesting message appears.
Publication 1734-UM011D-EN-P - May 2011
82 Adapter Web Pages
After completion of a query, here is how a typical Browse Chassis page looks with the module hyperlinks active and the Display compact check box unchecked.
Click a module hyperlink to view information about the module.
Here is how a typical Browse Chassis page looks with the Display compact check box checked.
Publication 1734-UM011D-EN-P - May 2011
Click a module hyperlink to view information about the module.
5. From the Browse Chassis page, to view information about a particular module, click the Module Description hyperlink.
The Module Information page displays the following about the module:
• Product Name
• Vendor
• Product Type
• Product Code
• Module Revision
• Serial Number
• Status
Adapter Web Pages 83
Publication 1734-UM011D-EN-P - May 2011
84 Adapter Web Pages
Notes:
Publication 1734-UM011D-EN-P - May 2011
Appendix
B
Configure the RSLinx Ethernet
Communication Driver
What This Appendix
Contains
To communicate with your 1734-AENT adapter over your network you must configure the RSLinx EtherNet/IP driver (AB_ETH/IP). You need one of these drivers to download the example application programs in this manual.
See the table for a list of the contents of this appendix and where to find specific information:
Topic
Configure the AB_ETH/IP Driver
Page
ATTENTION
You must use series C POINT I/O modules with the 1734-AENT adapter. Series A or B POINT I/O modules will not work with this adapter.
Install the RSLinx Software
Use this procedure to install RSLinx software on your computer.
1. Insert the CD in the CD-ROM drive.
Note that the CD-ROM supports Windows Autorun. Once inserted into the CD-ROM drive, if you have Autorun configured, the installation automatically starts at the first setup screen.
If Autorun is not configured for your CD-ROM drive, go to step 2.
2. From the Start menu, choose Run.
The Run dialog appears.
3. Type d:/setup (if it doesn’t appear automatically), where d: is your
CD-ROM driver letter.
4. Click OK.
You see the progress bar, followed by the welcome screen.
87 Publication 1734-UM011D-EN-P - May 2011
88 Configure the RSLinx Ethernet Communication Driver
Configure the AB_ETH/IP
Driver
To configure the AB_ETH/IP Ethernet communication driver, perform the following steps.
1. Start RSLinx software.
2. From the Communications menu, select Configure Drivers.
3. Click the arrow to the right of the Available Driver Types box.
The Available Driver Types list appears.
4. Select EtherNet/IP Devices and click Add/New.
The Configure driver dialog opens.
Publication 1734-UM011D-EN-P - May 2011
Configure the RSLinx Ethernet Communication Driver 89
5. Make sure the Browse Local Subnet button is selected.
RSLinx software browses your local subnet and automatically reads the
IP address.
6. Click OK.
The AB_ETH/IP driver is now configured and appears in the configured drivers window.
7. Close RSLinx software
.
Publication 1734-UM011D-EN-P - May 2011
90 Configure the RSLinx Ethernet Communication Driver
Notes:
Publication 1734-UM011D-EN-P - May 2011
Appendix
C
POINT I/O Module and RSLogix 5000 Software
Controller Tag Reference
What This Appendix
Contains
Read this appendix for information about tag references.
ATTENTION
You must use series C POINT I/O modules with the 1734-AENT adapter. Series A or B POINT I/O modules will not work with this adapter.
1734 POINT I/O Catalog
Numbers
1734 POINT I/O
Catalog Number
Digital Modules
1734-IA2/C
1734-IB2/C
1734-IB4/C
1734-IM2/C
1734-IV2/C
1734-IV4/C
1734-OA2/C
1734-OB2E/C
1734-OB2EP/C
1734-OB4E/C
1734-OV2E/C
1734-OV4E/C
1734-OW2/C
1734-OX2/C
Analog Modules
1734-IE2C/C
1734-IE2V/C
1734-IR2/C
1734-IT2I/C
1734-OE2C/C
1734-OE2V/C
RSLogix 5000 Module Description
2 POINT 120V AC Input
2 POINT 10…28V DC Input, Sink
4 POINT 10…28V DC Input, Sink
2 POINT 240V AC Input
2 POINT 10…28V DC Input, Source
4 POINT 10…28V DC Input, Source
2 POINT 120V AC Output
2 POINT 10…28V DC Electronically Fused Output, Source
2 POINT 10…28V DC Electronically Fused Protected Output, Source
4 POINT 10…28V DC Electronically Fused Output, Source
2 POINT 10…28V DC Electronically Fused Output, Sink
4 POINT 10…28V DC Electronically Fused Output, Sink
2 POINT AC/DC Relay Output
2 POINT Relay Output N.O./N.C.
2 Channel Analog Current Input
2 Channel Analog Voltage Input
2 Channel RTD Input
2 Channel Thermocouple Input, Isolated
2 Channel Analog Current Output
2 Channel Analog Voltage Output
91 Publication 1734-UM011D-EN-P - May 2011
92 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
1734 POINT I/O
Catalog Number
Specialty I/O
1734-232ASC/C
1734-IJ/C
1734-IK/C
1734-SSI/C
1734-VHSC24/C
1734-VHSC5/C
RSLogix5000 Module Description
1 Channel ASCII Interface Module
1 Channel 5V DC Encoder/Counter
1 Channel 15…24V DC Encoder/Counter
1 Channel Synchronous Serial Interface
1 Channel 15…24V DC Very High-speed Counter
1 Channel 5V DC Very High-speed Counter
Note that all POINT I/O modules must be series C or above for
RSLogix 5000 software, version 11, compatibility.
The 1734-232ASC/A (series A) is presently the only exception to the series C requirement. With RSLogix 5000 software, version 11, use it as a generic
1734 module. With RSLogix 5000 software, version 12 or later, it is directly supported.
Valid Number Ranges for
RSLogix 5000 Data Types
Type
BIT
SINT
INT
DINT
Number
1 Bit
8 Bit
16 Bit
32 Bit
Range
0 or 1
-128…127
-32,768…32,767
-2,147,483,648…2,147,483,647
Accepted parameter values are dependent on POINT I/O module type and tag type.
Publication 1734-UM011D-EN-P - May 2011
Digital 2 POINT Input
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 93
1734-IA2
2 POINT 120V AC Input
1734-IB2
2 POINT 10…28V DC Input, Sink
1734-IM2
2 POINT 240V AC Input
1734-IV2
2 POINT 10…28V DC Input, Source
Configuration Data Data Type Default
Value
Filter Off On Time - POINT 0 INT 1,000
Filter On Off Time - POINT 0 INT 1,000
Filter Off On Time - POINT 1
Filter On Off Time - POINT 1
INT
INT
1,000
1,000
Valid Data Values
-32,768…32,767 µs (1)
(0…65,535)
-32,768…32,767 µs (1)
(0…65,535)
-32,768…32,767 µs (1)
(0…65,535)
-32,768…32,767 µs (1)
(0…65,535)
Input Data
Input Data - POINT 0, 1
Data Type Default
Value
SINT, BIT 0
Valid Data Values
0=Off
1=On
Output Data Data Type Default
Value
Valid Data Values
None
(1)
POINT I/O Modules support the Unsigned Integer data type UINT (0…65,535 range).
RSLogix 5000 software supports the signed Integer data type INT (-32,768 …+32,767 range).
To enter Filter values from +32,768…+65,535 µs, use this conversion formula:
Desired Filter Value (in µs) - 65536 = Entered Filter Value (in µs).
As an example, for a 40 ms filter time, 40000 - 65536 = -25536
Publication 1734-UM011D-EN-P - May 2011
94 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
Digital 4 POINT Input
1734-IB4
4 POINT 10…28V DC Input, Sink
1734-IV4
4 POINT 10…28V DC Input, Source
Configuration Data Data Type
Filter Off On Time - POINT 0 INT
Filter On Off Time - POINT 0
Filter Off On Time - POINT 1
Filter On Off Time - POINT 1
Filter Off On Time - POINT 2
Filter On Off Time - POINT 2
Filter Off On Time - POINT 3
Filter On Off Time - POINT 3
INT
INT
INT
INT
INT
INT
INT
Default
Value
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
Valid Data Values
-32,768…32,767 µs (1)
(0…65,535)
-32,768…32,767 µs (1)
(0…65,535)
-32,768…32,767 µs (1)
(0…65,535)
-32,768…32,767 µs (1)
(0…65,535)
-32,768…32,767 µs (1)
(0…65,535)
-32,768…32,767 µs (1)
(0…65,535)
-32,768…32,767 µs (1)
(0…65,535)
-32,768…32,767 µs (1)
(0… 65,535)
Input Data
Input Data - POINT 0, 1, 2, 3
Data Type
SINT, BIT
Default
Value
0
Valid Data Values
0=Off
1=On
Output Data Data Type Default
Value
Valid Data Values
None
(1)
POINT I/O Modules support the Unsigned Integer data type UINT (0…65,535 range).
RSLogix 5000 software supports the signed Integer data type INT (-32,768…+32,767 range).
To enter Filter values from +32,768…+65,535 µs, use this conversion formula:
Desired Filter Value (in µs) - 65536 = Entered Filter Value (in µs).
As an example, for a 40 ms filter time, 40000 - 65536 = -25536
Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 95
Digital 2 POINT Output –
Without Diagnostic Status
1734-OA2
2 POINT 120V AC Output
1734-OW2
2 POINT AC/DC Relay Output
1734-OX2
2 POINT Relay Output N.O./N.C.
Configuration Data
Fault Mode - POINT 0, 1
Fault Value - POINT 0, 1
Program Mode - POINT 0, 1
Program Value - POINT 0, 1
Data Type
SINT, BIT
SINT, BIT
SINT, BIT
SINT, BIT
Data Type
0
0
0
Default
Value
0
Valid Data Values
0=Fault Value
1=Hold Last State
0=Off
1=On
0=Program Value
1=Hold Last State
0=Off
1=On
Default
Value
Valid Data Values Input Data
None
Output Data
Output Data - POINT 0, 1
Data Type
SINT, BIT
Default
Value
0
Valid Data Values
0=Off
1=On
Publication 1734-UM011D-EN-P - May 2011
96 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
Digital 2 POINT Output –
With Over Load and Open
Load Diagnostic Status
1734-OB2E
2 POINT 10…28V DC Electronically Fused Output, Source
1734-OB2EP
2 POINT 10…28V DC Electronically Fused Protected Output, Source
Configuration Data Data Type Default
Value
Valid Data Values
Fault Mode - POINT 0, 1 SINT, BIT 0
Fault Value - POINT 0, 1 SINT, BIT 0
0=Fault Value
1=Hold Last State
0=Off
1=On
Program Mode - POINT 0, 1 SINT, BIT 0
Program Value - POINT 0, 1
No Load Enable - POINT 0, 1
(Wire Off Diagnostic)
Auto Restart Enable - POINT 0, 1
(Over Load Behavior)
Fault Latch Enable - POINT 0, 1
(Open Load or Over Load)
SINT, BIT
SINT, BIT
SINT, BIT
SINT, BIT
0
1
0
0
0=Program Value
1=Hold Last State
0=Off
1=On
0=Disabled
1=Enabled
0=Latch Off
1=Auto Retry
0=No Latching
1=Alarms Latch
Input Data
Status Data - POINT 0, 1
(Open Load or Over Load)
Output Data
Output Data - POINT 0, 1
Data Type
SINT, BIT
Data Type
SINT, BIT
Default
Value
0
Default
Value
0
Valid Data Values
0=Off
1=On (Load Fault)
Valid Data Values
0=Off
1=On
Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 97
Digital 2 POINT Output –
With Over Load Diagnostic
Status
1734-OV2E
2 POINT 10…28V DC Electronically Fused Output, Sink
Configuration Data Data Type Default
Value
Fault Mode - POINT 0, 1 SINT, BIT 0
Fault Value - POINT 0, 1
Program Mode - POINT 0, 1
Program Value - POINT 0, 1
Auto Restart Enable - POINT 0, 1
(Over Load Behavior)
Fault Latch Enable - POINT 0, 1
(Over Load)
SINT, BIT
SINT, BIT
SINT, BIT
SINT, BIT
SINT, BIT
0
0
0
0
0
Valid Data Values
0=Fault Value
1=Hold Last State
0=Off
1=On
0=Program Value
1=Hold Last State
0=Off
1=On
0=Latch Off
1=Auto Retry
0=No Latching
1=Alarms Latch
Input Data
Status Data - POINT 0, 1
(Over Load)
Output Data
Output Data - POINT 0, 1
Data Type
SINT, BIT
Default
Value
0
Valid Data Values
0=Off
1=On (Load Fault)
Data Type
SINT, BIT
Default
Value
0
Valid Data Values
0=Off
1=On
Publication 1734-UM011D-EN-P - May 2011
98 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
Digital 4 POINT Output –
With Over Load and Open
Load Diagnostic Status
1734-OB4E
4 POINT 10…28V DC Electronically Fused Output, Source
Configuration Data Data Type Default
Value
Fault Mode - POINT 0, 1, 2, 3 SINT, BIT 0
Valid Data Values
Fault Value - POINT 0, 1, 2, 3
Program Mode - POINT 0, 1, 2, 3
Program Value - POINT 0, 1, 2, 3
No Load Enable - POINT 0, 1, 2, 3
(Wire Off Diagnostic)
Auto Restart Enable - POINT 0, 1, 2, 3
(Over Load Behavior)
Fault Latch Enable - POINT 0, 1, 2, 3
(Open Load or Over Load)
SINT, BIT
SINT, BIT
SINT, BIT
SINT, BIT
SINT, BIT
SINT, BIT
0
0
0
1
0
0
0=Fault Value
1=Hold Last State
0=Off
1=On
0=Program Value
1=Hold Last State
0=Off
1=On
0=Disabled
1=Enabled
0=Latch Off
1=Auto Retry
0=No Latching
1=Alarms Latch
Input Data
Status Data - POINT 0, 1, 2, 3
(Open Load or Over Load)
Output Data
Output Data - POINT 0, 1, 2, 3
Data Type Default
SINT, BIT
Value
0
Data Type Default
Value
SINT, BIT 0
Valid Data Values
0=Off
1=On (Load Fault)
Valid Data Values
0=Off
1=On
Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 99
Digital 4 POINT Output –
With Over Load Diagnostic
Status
1734-OV4E
4 POINT 10…28V DC Electronically Fused Output, Sink
Configuration Data Data Type Default
Value
Fault Mode - POINT 0, 1, 2, 3 SINT, BIT 0
Valid Data Values
Fault Value - POINT 0, 1, 2, 3
Program Mode - POINT 0, 1, 2, 3
Program Value - POINT 0, 1, 2, 3
Auto Restart Enable - POINT 0, 1, 2, 3
(Over Load Behavior)
Fault Latch Enable - POINT 0, 1, 2, 3
(Over Load)
SINT, BIT
SINT, BIT
SINT, BIT
SINT, BIT
SINT, BIT
0
0
0
0
0
0=Fault Value
1=Hold Last State
0=Off
1=On
0=Program Value
1=Hold Last State
0=Off
1=On
0=Latch Off
1=Auto Retry
0=No Latching
1=Alarms Latch
Input Data
Status Data - POINT 0, 1, 2, 3
(Over Load)
Output Data
Output Data - POINT 0, 1, 2, 3
Data Type Default
Value
SINT, BIT 0
Valid Data Values
0=Off
1=On (Load Fault)
Data Type Default
Value
SINT, BIT 0
Valid Data Values
0=Off
1=On
Publication 1734-UM011D-EN-P - May 2011
100 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
Analog 2 Channel Input
1734-IE2C
2 Channel Analog Current Input
Configuration Data
Low Engineering Channel 0
High Engineering Channel 0
Digital Filter Channel 0
Low Alarm Limit Channel 0
High Alarm Limit Channel 0
Low Low Alarm Limit Channel 0
High High Alarm Limit Channel 0
Range Type Channel 0
Limit Alarm Latch Channel 0
Alarm Disable Channel 0
Low Engineering Channel 1
High Engineering Channel 1
Digital Filter Channel 1
Low Alarm Limit Channel 1
High Alarm Limit Channel 1
Low Low Alarm Limit Channel 1
High High Alarm Limit Channel 1
Range Type Channel 1
Limit Alarm Latch Channel 1
Alarm Disable Channel 1
Notch Filter (Channel 0 & 1)
Real-time Sample (Channel 0 & 1)
INT
INT
INT
INT
INT
INT
INT
SINT
Data Type Default
Value
INT
INT
3,277
Valid Data Values
-32,768…32,767
16,383 -32,768…32,767
INT
INT
INT
INT
INT
SINT
SINT
SINT
SINT
SINT
SINT
INT
0
3,113
2,867
0…10,000 ms
-32,768…32,767
16,547 -32,768…32,767
-32,768…32,767
16,793 -32,768…32,767
3 3=4…20 mA
8=0…20 mA
0
0
0=No Latching
1=Alarms Latch
0=Alarms Enabled
1=Alarms Disabled
3,277 -32,768…32,767
16,383 -32,768…32,767
0 0…10,000 ms
3,113 -32,768…32,767
16,547 -32,768…32,767
2,867 -32,768…32,767
16,793 -32,768…32,767
3 3=4-20 mA
8=0-20 mA
0
0
0=No Latching
1=Alarms Latch
0=Alarms Enabled
1=Alarms Disabled
2
100
1=50 Hz
2=60 Hz
4=250 Hz
6=500 Hz
0…10,000 ms
Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 101
1734-IE2C
2 Channel Analog Current Input
Input Data
Data Channel 0
Data Channel 1
Status Byte Channel 0
Status Byte Channel 1
Output Data
None
Data Type
INT
INT
SINT
SINT
Data Type
0
0
Default
Value
0
0
Valid Data Values
-32,768…32,767
-32,768…32,767
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange
Default
Value
Valid Data Values
Publication 1734-UM011D-EN-P - May 2011
102 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
1734-IE2V
2 Channel Analog Voltage Input
Configuration Data
Low Engineering Channel 0
High Engineering Channel 0
Digital Filter Channel 0
Low Alarm Limit Channel 0
High Alarm Limit Channel 0
Low Low Alarm Limit Channel 0
High High Alarm Limit Channel 0
Range Type Channel 0
Limit Alarm Latch Channel 0
Alarm Disable Channel 0
Low Engineering Channel 1
High Engineering Channel 1
Digital Filter Channel 1
Low Alarm Limit Channel 1
High Alarm Limit Channel 1
Low Low Alarm Limit Channel 1
High High Alarm Limit Channel 1
Range Type Channel 1
Limit Alarm Latch Channel 1
Alarm Disable Channel 1
Notch Filter (Channel 0 & 1)
Real-time Sample (Channel 0 & 1)
INT
INT
INT
SINT
INT
INT
INT
INT
INT
INT
INT
INT
Data Type Default
Value
INT
INT
0
Valid Data Values
-32,768…32,767
10,000 -32,768…32,767
INT
SINT
SINT
SINT
0
500
9,500
200
9,800
2
0
0
0…10,000 ms
-32,768…32,767
-32,768…32,767
-32,768…32,767
-32,768…32,767
0=-10…+10V
2=0…10V
0=No Latching
1=Alarms Latch
0=Alarms Enabled
1=Alarms Disabled
SINT
SINT
SINT
INT
0
0
500
-32,768…32,767
10,000 -32,768…32,767
0…10,000 ms
9,500 -32,768…32,767
200 -32,768…32,767
9,800 -32,768…32,767
2 0=-10…+10V
2=0…10V
0
0
2
100
-32,768…32,767
0=No Latching
1=Alarms Latch
0=Alarms Enabled
1=Alarms Disabled
1=50 Hz
2=60 Hz
4=250 Hz
6=500 Hz
0…10,000 ms
Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 103
1734-IE2V
2 Channel Analog Voltage Input
Input Data
Data Channel 0
Data Channel 1
Status Byte Channel 0
Status Byte Channel 1
Output Data
None
Data Type
INT
INT
SINT
SINT
Data Type
0
0
Default
Value
0
0
Valid Data Values
-32,768…32,767
-32,768…32,767
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange
Default
Value
Valid Data Values
Publication 1734-UM011D-EN-P - May 2011
104 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
1734-IR2
2 Channel RTD Input
Configuration Data
Limit Alarm Latch Channel 1
Data Type Default Value Valid Data Values
Low Engineering Channel 0
High Engineering Channel 0
Digital Filter Channel 0
Low Alarm Limit Channel 0
High Alarm Limit Channel 0 INT
Low Low Alarm Limit Channel 0 INT
High High Alarm Limit Channel 0 INT
Limit Alarm Latch Channel 0 SINT
INT
INT
INT
INT
Alarm Disable Channel 0
Sensor Type Channel 0
Temperature Mode Channel 0
Low Engineering Channel 1
High Engineering Channel 1
Digital Filter Channel 1
Low Alarm Limit Channel 1
High Alarm Limit Channel 1
Low Low Alarm Limit Channel 1
High High Alarm Limit Channel 1 INT
Alarm Disable Channel 1
SINT
SINT
SINT
INT
INT
INT
INT
INT
INT
SINT
SINT
1,000
5,000
0
-32,768
32,767
-32,768
32,767
0
0
1
1
1,000
5,000
0
-32,768
32,767
-32,768
32,767
0
0
-32,768…32,767
-32,768…32,767
0…10,000 ms
-32,768…32,767
-32,768…32,767
-32,768…32,767
-32,768…32,767
0=No Latching
1=Alarms Latch
0=Alarms Enabled
1=Alarms Disabled
0=Ohms
1=100 Ω Pt α 385
2=200 Ω Pt α 385
5=100 Ω JPt α 3916
6=200 Ω JPt α 3916
9=10 Ω Cu α 427
10=120 Ω Ni α 672
11=100 Ω Ni α 618
12=120 Ω Ni α 618
0=Custom Scale
1=°C
2=°F
3=°K
4=°R
-32,768…32,767
-32,768…32,767
0…10,000 ms
-32,768…32,767
-32,768…32,767
-32,768…32,767
-32,768…32,767
0=No Latching
1=Alarms Latch
0=Alarms Enabled
1=Alarms Disabled
Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 105
1734-IR2
2 Channel RTD Input
Configuration Data
Sensor Type Channel 1
Temperature Mode Channel 1
Notch Filter (Channel 0 & 1)
Data Type Default Value Valid Data Values
SINT
SINT
SINT
1
1
1
0=Ohms
1=100 Ω Pt α 385
2=200 Ω Pt α 385
5=100 Ω JPt α 3916
6=200 Ω JPt α 3916
9=10 Ω Cu α 427
10=120 Ω Ni α 672
11=100 Ω Ni α 618
12=120 Ω Ni α 618
0=Custom Scale
1=°C
2=°F
3=°K
4=°R
0=50 Hz
1=60 Hz
2=100 Hz
3=120 Hz
4=200 Hz
5=240 Hz
6=300 Hz
7=400 Hz
8=480 Hz
Input Data
Data Channel 0
Data Channel 1
Status Byte Channel 0
Status Byte Channel 1
Output Data
None
Data Type Default Value Valid Data Values
INT 0 -32,768…32,767
INT
SINT
0
0
-32,768…32,767
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange
SINT 0 Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange
Data Type Default Value Valid Data Values
Publication 1734-UM011D-EN-P - May 2011
106 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
1734-IT2
2 Channel Thermocouple Input, Isol.
Configuration Data Data Type
Cold Junction Notch Filter
Cold Junction Mode
SINT
SINT
Low Engineering Channel 0
High Engineering Channel 0
Alarm Disable Channel 0
Limit Alarm Latch Channel 0
Notch Filter Channel 0
Sensor Type Channel 0
Digital Filter Channel 0
Low Alarm Limit Channel 0
High Alarm Limit Channel 0
Low Low Alarm Limit Channel 0
High High Alarm Limit Channel 0
INT
INT
SINT
SINT
SINT
SINT
INT
INT
INT
INT
INT
Default
Value
1
1
0
7,000
0
0
Valid Data Values
0=50 Hz
1=60 Hz
0=None
1=Channel 0
2=Channel 1
3=Average Both
-32,768…32,767
-32,768…32,767
0=Alarms Enabled
1=Alarms Disabled
0=No Latching
1=Alarms Latch
1
5 0=mV
1=B
2=C
3=E
4=J
5=K
6=N
7=R
8=S
9=T
0=50 Hz
1=60 Hz
2=100 Hz
3=120 Hz
4=200 Hz
5=240 Hz
6=300 Hz
7=400 Hz
8=480 Hz
0 0…10,000 ms
-32,768 -32,768…32,767
32,767 -32,768…32,767
-32,768 -32,768…32,767
32,767 -32,768…32,767
Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 107
1734-IT2
2 Channel Thermocouple Input, Isol.
Configuration Data Data Type
Temperature Mode Channel 0 SINT
Cold Junction Enable Channel 0
Cold Junction Offset Channel 0
Low Engineering Channel 1
High Engineering Channel 1
Alarm Disable Channel 1
Limit Alarm Latch Channel 1
Notch Filter Channel 1
Sensor Type Channel 1
Digital Filter Channel 1
Low Alarm Limit Channel 1
High Alarm Limit Channel 1
Low Low Alarm Limit Channel 1
High High Alarm Limit Channel 1
SINT
INT
INT
INT
SINT
SINT
SINT
SINT
INT
INT
INT
INT
INT
1
1
0
0
Default
Value
7,000
0
Valid Data Values
0=mV/Custom Scale
1=°C
2=°F
3=°K
4=°R
0=Disabled
1=Enabled
0…7,000 (0.00…70.00)
-32,768…32,767
-32,768…32,767
0=Alarms Enabled
1=Alarms Disabled
0
1
0=No Latching
1=Alarms Latch
0=50 Hz
1=60 Hz
2=100 Hz
3=120 Hz
4=200 Hz
5=240 Hz
6=300 Hz
7=400 Hz
8=480 Hz
5 0=mV
1=B
2=C
3=E
4=J
5=K
6=N
7=R
8=S
9=T
0 0…10,000 ms
-32,768 -32,768…32,767
32,767 -32,768…32,767
-32,768 -32,768…32,767
32,767 -32,768…32,767
Publication 1734-UM011D-EN-P - May 2011
108 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
1734-IT2
2 Channel Thermocouple Input, Isol.
Configuration Data Data Type
Temperature Mode Channel 1 SINT
Cold Junction Enable Channel 1 SINT
Default
Value
1
1
0
Valid Data Values
0=mV/Custom Scale
1=°C
2=°F
3=°K
4=°R
0=Disabled
1=Enabled
0…7,000 (0.00…70.00) Cold Junction Offset Channel 1
Input Data
Data Channel 0
Data Channel 1
Status Byte Channel 0
INT
Data Type
INT
INT
SINT
Status Byte Channel 1 SINT
0
0
Default
Value
0
0
0
Valid Data Values
-32,768…32,767
-32,768…32,767
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange
-32,768…32,767 Cold Junction Data
Output Data
None
INT
Data Type Default
Value
Valid Data Values
Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 109
Analog 2 Channel Output
1734-OE2C
2 Channel Analog Current Output
Configuration Data
Fault Value Channel 0
Program Value Channel 0
Low Engineering Channel 0
High Engineering Channel 0
Low Limit Channel 0
High Limit Channel 0
Range Type Channel 0
Fault Mode Channel 0
Data Type
INT
INT
INT
INT
INT
INT
SINT
SINT
Idle Mode Channel 0
Limit Alarm Latch Channel 0
Alarm Disable Channel 0
Fault Value Channel 1
Program Value Channel 1
Low Engineering Channel 1
High Engineering Channel 1
Low Limit Channel 1
High Limit Channel 1
Range Type Channel 1
Fault Mode Channel 1
SINT
SINT
SINT
INT
INT
INT
INT
INT
INT
SINT
SINT
0
0
Default
Value
Valid Data Values
-32,768…32,767
-32,768…32,767
1,638
8,191
-32,768 -32,768…32,767
32,767 -32,768…32,767
0
-32,768…32,767
-32,768…32,767
1
0=4…20 mA
2=0…20 mA
0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value
1
0
0
0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value
0=No Latching
1=Alarms Latch
0=Alarms Enabled
1=Alarms Disabled
0
0
1,638
8,191
-32,768…32,767
-32,768…32,767
-32,768…32,767
-32,768…32,767
-32,768 -32,768…32,767
32,767 -32,768…32,767
0
1
0=4…20 mA
2=0…20 mA
0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value
Publication 1734-UM011D-EN-P - May 2011
110 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
1734-OE2C
2 Channel Analog Current Output
Configuration Data
Idle Mode Channel 1
Data Type
SINT
Limit Alarm Latch Channel 1
Alarm Disable Channel 1
Input Data
Status Byte Channel 0
Status Byte Channel 1
Output Data
Data Channel 0
Data Channel 1
SINT
SINT
Data Type
SINT
SINT
Data Type
INT
INT
Default
Value
1
0
0
Valid Data Values
0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value
0=No Latching
1=Alarms Latch
0=Alarms Enabled
1=Alarms Disabled
Default
Value
0
0
Valid Data Values
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
0
0
Default
Value
Valid Data Values
-32,768…32,767
-32,768…32,767
Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 111
1734-OE2V
2 Channel Analog Voltage Output
Configuration Data
Fault Value Channel 0
Program Value Channel 0
Low Engineering Channel 0
High Engineering Channel 0
Low Limit Channel 0
High Limit Channel 0
Range Type Channel 0
Fault Mode Channel 0
Data Type
INT
INT
INT
INT
INT
INT
SINT
SINT
Idle Mode Channel 0
Limit Alarm Latch Channel 0
Alarm Disable Channel 0
Fault Value Channel 1
Program Value Channel 1
Low Engineering Channel 1
High Engineering Channel 1
Low Limit Channel 1
High Limit Channel 1
Range Type Channel 1
Fault Mode Channel 1
Idle Mode Channel 1
SINT
SINT
SINT
INT
INT
INT
INT
INT
INT
SINT
SINT
SINT
0
0
Default
Value
Valid Data Values
0
10,000
1
1
-32,768…32,767
-32,768…32,767
-32,768…32,767
-32,768…32,767
-32,768 -32,768…32,767
32,767 -32,768…32,767
1=0…10V
3=-10…+10V
0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value
1
0
0
0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value
0=No Latching
1=Alarms Latch
0=Alarms Enabled
1=Alarms Disabled
0
0
0
10,000
-32,768…32,767
-32,768…32,767
-32,768…32,767
-32,768…32,767
-32,768 -32,768…32,767
32,767 -32,768…32,767
1
1
1=0…10V
3=-10…+10V
0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value
1 0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value
Publication 1734-UM011D-EN-P - May 2011
112 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
1734-OE2V
2 Channel Analog Voltage Output
Configuration Data
Limit Alarm Latch Channel 1
Alarm Disable Channel 1
Data Type
SINT
SINT
Input Data
Status Byte Channel 0
Status Byte Channel 1
Output Data
Data Channel 0
Data Channel 1
Data Type
SINT
SINT
Data Type
INT
INT
Default
Value
0
0
Valid Data Values
0=No Latching
1=Alarms Latch
0=Alarms Enabled
1=Alarms Disabled
Default
Value
0
0
Valid Data Values
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
0
0
Default
Value
Valid Data Values
-32,768…32,767
-32,768…32,767
Publication 1734-UM011D-EN-P - May 2011
Specialty I/O
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 113
1734-VHSC24
1 Channel 15…24V DC Very High-speed Counter
1734-VHSC5
1 Channel 5V DC Very High-speed Counter
Configuration Data Data Type Default
Value
Counter Config SINT 0
Config_0
Config_1
Config_2
Config_3
BIT 0
BIT 1
BIT 2
BIT 3
Valid Data Values
Mode_4
Mode_5
Mode_6
Z Input
Filter
Filter_0
Filter_1
Filter_2
Filter_3
FilterA
FilterB
FilterZ
Decimal Position
Time Base
(in 10 ms intervals)
Gate Interval
(Product of Time Base x Gate
Interval must be ≤ 3000 ms)
BIT 4
BIT 5
BIT 6
BIT 7
SINT
BIT 0
BIT 1
BIT 2
BIT 3
BIT 4
BIT 5
BIT 6
SINT
INT
SINT
120
(0x78H)
0
0
0
0000=0=Counter
0001=1=Encoder X1
0010=2=Encoder X2
0011=3=PWM
0100=4=Encoder X4
0101=5=Period/Rate
0110=6=Continuous/Rate
0111=7=Rate Measurement
1000=8=Pulse Generator
000=Store Count Disable
001=Store/Continue
010=Store/Wait/Resume
011=Store,Reset/Wait/Start
100=Store,Reset/Start
0=Z Input Not Inverted
1=Z Input Is Inverted
0000=No Filter
0001=50 kHz
0010=5 kHz
0100=500 Hz
1000=50 Hz
0=Input A/B/Z Not Filtered
1=Input A/B/Z Is Filtered
Counter Config 0, 1, 2, 3, 4:
-128…+127 (0…255)
Counter Config 5, 6, & 7:
-4…+2
Counter Config 3 & 7 only:
0…3000 ms (10 ms…3 sec)
Counter Config 3 & 7 only:
-128…+127 (0…200)
Publication 1734-UM011D-EN-P - May 2011
114 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
1734-VHSC24
1 Channel 15…24V DC Very High-speed Counter
1734-VHSC5
1 Channel 5V DC Very High-speed Counter
Configuration Data Data Type Default
Value
Scalar SINT 0
Output Ties 0
Out 0 Window 1
Out 0 Window 2
Out 0 Window 3
Out 0 Window 4
Output Ties 1
Out 1 Window 1
Out 1 Window 2
Out 1 Window 3
Out 1 Window 4
Rollover
Preset (< Rollover)
On Value 1
Off Value 1
On Value 2
Off Value 2
On Value 3
Off Value 3
On Value 4
Off Value 4
SS PWM Value
(<0 or >9500 =Hold Last State)
SS Counter Control
SINT
BIT 0
BIT 1
BIT 2
BIT 3
SINT
BIT 0
BIT 1
BIT 2
BIT 3
DINT
DINT
DINT
DINT
DINT
DINT
DINT
DINT
DINT
DINT
INT
SINT
Valid Data Values
Counter Config 5, 6, 8 only:
-128…+127 (0…255) Single Bit only:
0, 1, 2, 4, 8, 16, 32, 64, -128
0
0
0
0
0
0
0
0
0
0
0
0=Output 1 Not Tied
1=Output 1 Tied to Window
Counter Config 3 (PWM):
Output 1 Window 1 PWM In
16,777,215 1…16,777,216
0 0…16,777,215
Counter Config 3, 5, 6, 7:
0…16,777,215
Counter Config 0, 1, 2, 4:
0 to Rollover Value
0…9500
(0.00…95.00%)
0
0=Output 0 Not Tied
1=Output 0 Tied to Window
Counter Config 3 (PWM):
Output 0 Window 1 PWM In
SS Counter Reset BIT 0 0=Count Unchanged
1=Count Cleared
SS Counter Preset
SS Value Reset
(Stored / Accum. Count)
BIT 1
BIT 2
0=Count Unchanged
1=Count Set to Preset
0=Count Unchanged
1=Count Cleared
Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 115
1734-VHSC24
1 Channel 15…24V DC Very High-speed Counter
1734-VHSC5
1 Channel 5V DC Very High-speed Counter
Configuration Data Data Type Default
Value
SS Output Control SINT 0
SS Out 0 Force BIT 0
SS Out 0 En
SS Out 0 Electronic Fuse BIT 2
SS Out 0 Diagnostic Speed BIT 3
SS Out 1 Force
SS Out 1 En
BIT 1
BIT 4
BIT 5
SS Out 1 Electronic Fuse BIT 6
SS Out 1 Diagnostic Speed BIT 7
Valid Data Values
0=Output Off
1=Output Forced On
0=Output Disabled
1=Output Enabled
0=Auto Retry
1=Latch Off
0 < 8 ms Response
1=50 ms Response
0=Output Off
1=Output Forced On
0=Output Disabled
1=Output Enabled
0=Auto Retry
1=Latch Off
0 < 8 ms Response
1=50 ms Response
To enter values from +128…+255, use these conversion formulas:
Desired Decimal Position Value - 256 = Entered Decimal Position
Value.
As an example, for a divisor of 200, 200 - 256 = -56
Desired Gate Interval Value - 256 = Entered Gate Interval Value.
As an example, for a Gate Interval of 200, 200 - 256 = -56
Desired Scalar Value - 256 = Entered Scalar Value.
As an example, for a Scalar of 128, 128 - 256 = -128
Publication 1734-UM011D-EN-P - May 2011
116 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
1734-VHSC24
1 Channel 15…24V DC Very High-speed Counter
1734-VHSC5
1 Channel 5V DC Very High-speed Counter
Input Data
Present Data
Stored Data
Data Type
DINT
DINT
Status
Zero Frequency Detected
Stored Data Count_2
Stored Data Count_3
A Input Status
B Input Status
Z Input Status
Output Status_8 (Output 0)
Output Status_9 (Output 1)
Output Fault_10 (Output 0)
Output Fault_11 (Output 1)
Not Ready
EEPROM Fault
Program Fault
(incomplete / incorrect / conflict)
INT
BIT 1
BIT 2
BIT 3
BIT 4
BIT 5
BIT 6
BIT 8
BIT 9
BIT 10
BIT 11
BIT 13
BIT 14
BIT 15
Default Value Valid Data Values
0 0…16,777,215
0 -2,147,483,648…2,147,483,64
7
(0…4,294,967,295)
0
0=No Fault
1=Fault Detected
Cycles through 0, 1, 2, 3, 0,
Increments after update
0=Input A/B/Z is Off
1=Input A/B/Z is On
0=Output is Off
1=Output is On
0=No Fault
1=Open or Over Load
0=Module Ready
1=Module Initializing
0=No Fault
1=EEPROM data bad
0=No Fault
1=Bad Configuration
(Refer to Program Fault on page 117)
Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 117
Stored Data
To interpret values from -2,147,483,648 to -1, use this conversion formula:
Stored Data Tag Value + 4,294,967,296 = Actual Stored Data Tag Value.
As an example, for a read value of -1,794,967,296:
-1,794,967,296 + 4,294,967,296 = 2,500,000,000 actual value
Program Fault
Programming Fault Error bit – If an incomplete, incorrect, or conflicting set of configuration parameters is sent to the module, the Program Fault bit will be asserted and an error code will be placed in the Programming Error Code word (assembly 6816). The module will not enter a normal operational state.
Bit definitions (decimal) for the error codes are:
10 An invalid assembly was chosen for poll consumption (0, 105,
or 106 are valid).
9
8
7
6
5
The decimal point position is outside of the acceptable range.
Counter 0 window ON & OFF values are equal and not zero; or
Counter 0 window ON & OFF value is greater than Rollover.
A tie has been connected to an unprogrammed window.
A configuration was selected that requires the scalar and none was programmed; or Multiple scalars were selected.
The preset is out of range (Rollover).
3
4 A rollover of zero was programmed through PWM was not or
A rollover was programmed and PWM was selected OR
Rollover is out of range (>0x01000000).
A configuration requiring a time base was selected and no gate interval was set; or
Gate interval is out of range (>200); or
Product of time base and gate interval is greater than 3 seconds.
2
1
0
A time base was entered that is not a multiple of 10; or
Time base is out of range (>3000, or 3 seconds).
ZF/BF/AF were selected and no filter was programmed; or
Multiple filters were selected.
A reserved configuration/mode was programmed.
Publication 1734-UM011D-EN-P - May 2011
118 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
1734-VHSC24
1 Channel 15…24V DC Very High-speed Counter
1734-VHSC5
1 Channel 5V DC Very High-speed Counter
Output Data Data Type
PWM Value INT
Counter Control
Counter Reset
SINT
BIT 0
Counter Preset
Value Reset
(Stored / Accumulated Count)
Output Control
Output 0 Force
Output 0 Enable
Output 0 Electronic Fuse
Output 0 Diagnostic Speed
Output 1 Force
Output 1 Enable
Output 1 Electronic Fuse
Output 1 Diagnostic Speed
BIT 1
BIT 2
SINT
BIT 0
BIT 1
BIT 2
BIT 3
BIT 4
BIT 5
BIT 6
BIT 7
0
0
0
0
0
0
0
Default
Value
0
Valid Data Values
0…9500
(0.00…95.00%)
0
0=Count Unchanged
1=Count Cleared
0=Count Unchanged
1=Count Set to Preset
0=Count Unchanged
1=Count Cleared
0
0
0
0
0
0=Output Off
1=Output Forced On
0=Output Disabled
1=Output Enabled
0=Auto Retry
1=Latch Off
0< 8 ms Response
1=50 ms Response
0=Output Off
1=Output Forced On
0=Output Disabled
1=Output Enabled
0=Auto Retry
1=Latch Off
0< 8 ms Response
1=50 ms Response
Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 119
1734-IJ
1 Channel 5V DC Encoder / Counter
1734-IK
1 Channel 15…24V DC Encoder / Counter
Configuration Data Data Type
Counter Config
Config_0
Config_1
Config_2
Config_3
SINT
BIT 0
BIT 1
BIT 2
BIT 3
Mode_4
Mode_5
Mode_6
Z Input
Filter
Filter_0
Filter_1
Filter_2
Filter_3
FilterA
FilterB
FilterZ
Decimal Position
Time Base
(in 10 ms intervals)
Gate Interval
(Product of Time Base x Gate Interval must be ≤ 3000 ms)
Scalar
Rollover
Preset (< Rollover)
BIT 4
BIT 5
BIT 6
BIT 7
SINT
BIT 0
BIT 1
BIT 2
BIT 3
BIT 4
BIT 5
BIT 6
SINT
INT
SINT
SINT
DINT
DINT
Default
Value
0
Valid Data Values
120
(0x78H)
0000=0=Counter
0001=1=Encoder X1
0010=2=Encoder X2
0100=4=Encoder X4
0101=5=Period/Rate
0111=7=Rate Measurement
000=Store Count Disable
001=Store/Continue
010=Store/Wait/Resume
011=Store,Reset/Wait/Start
100=Store,Reset/Start
0=Z Input Not Inverted
1=Z Input Is Inverted
0000=No Filter
0001=50 kHz
0010=5 kHz
0100=500 Hz
1000=50 Hz
0=Input A/B/Z Not Filtered
1=Input A/B/Z Is Filtered
0
0
0 Counter Config 0, 1, 2, 4:
-128…+127 (0…255)
Counter Config 5 & 7:
-4…+2
Counter Config 7 only:
0…3000 ms (10 ms…3 s)
Counter Config 7 only:
-128…+127 (0…200)
0 Counter Config 5 only:
-128…+127 (0…255)
0, 1, 2, 4, 8, 16, 32, 64, -128
16,777,215 1…16,777,216
0 0…16,777,215
Publication 1734-UM011D-EN-P - May 2011
120 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
1734-IJ
1 Channel 5V DC Encoder / Counter
1734-IK
1 Channel 15…24V DC Encoder / Counter
Configuration Data Data Type
SS Counter Control
SS Counter Reset
SINT
BIT 0
SS Counter Preset
SS Value Reset
BIT 1
BIT 2
Default
Value
0
Valid Data Values
0=Count Unchanged
1=Count Cleared
0=Count Unchanged
1=Count Set to Preset
0=Count Unchanged
1=Count Cleared
To enter values from +128…+255, use these conversion formulas:
Decimal Position
Desired Decimal Position Value - 256 = Entered Decimal Position
Value.
As an example, for a divisor of 200, 200 - 256 = -56
Gate Interval
Scalar
Desired Gate Interval Value - 256 = Entered Gate Interval Value.
As an example, for a Gate Interval of 200, 200 - 256 = -56
Desired Scalar Value - 256 = Entered Scalar Value.
As an example, for a Scalar of 128, 128 - 256 = -128
Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 121
1734-IJ
1 Channel 5V DC Encoder / Counter
1734-IK
1 Channel 15…24V DC Encoder / Counter
Input Data
Present Data
Stored Data
Data Type
DINT
DINT
Status
Zero Frequency Detected
Stored Data Count_2
Stored Data Count_3
A Input Status
B Input Status
Z Input Status
Not Ready
EEPROM Fault
INT
BIT 1
BIT 2
BIT 3
BIT 4
BIT 5
BIT 6
BIT 13
BIT 14
Program Fault
(incomplete / incorrect / conflict)
BIT 15
Default Value Valid Data Values
0 0…16,777,215
0 -2,147,483,648…
2,147,483,647
(0…4,294,967,295)
0
0=No Fault
1=Fault Detected
Cycles through 0, 1, 2, 3, 0,
Increments after update
0=Input A/B/Z is Off
1=Input A/B/Z is On
0=Module Ready
1=Module Initializing
0=No Fault
1=EEPROM data bad
0=No Fault
1=Bad Configuration
(See Program Fault Note)
Stored Data
To interpret values from -2,147,483,648… -1, use this conversion formula:
Stored Data Tag Value + 4,294,967,296 = Actual Stored Data Tag Value.
As an example, for a read value of -1,794,967,296:-1,794,967,296 +
4,294,967,296 = 2,500,000,000 actual value
Publication 1734-UM011D-EN-P - May 2011
122 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
Program Fault Note
Programming Fault Error bit – If an incomplete, incorrect, or conflicting set of configuration parameters is sent to the module, the Program Fault bit is asserted and an error code placed in the Programming Error Code word
(assembly 6816). The module will not enter a normal operational state. Bit definitions (decimal) for the error codes are:
7
6
9
8
10 An invalid assembly was chosen for poll consumption (0, 105, or 106 are valid).
The decimal point position is outside of the acceptable range.
Counter 0 window ON & OFF values are equal and not zero; or
Counter 0 window ON & OFF value is greater than the Rollover.
A tie has been connected to an unprogrammed window.
A configuration was selected that requires the scalar and none was programmed; or
Multiple scalars were selected.
3
5
4
The preset is out of range (Rollover).
A rollover of zero was programmed through PWM was not or
A rollover was programmed and PWM was selected; or
Rollover is out of range (>0x01000000).
A configuration requiring a time base was selected and no gate interval was set; or
Gate interval is out of range (>200); or
2
1
0
Product of time base and gate interval is greater than 3 seconds.
A time base was entered that is not a multiple of 10; or
Time base is out of range (>3000, or 3 seconds).
ZF/BF/AF were selected and no filter was programmed; or
Multiple filters were selected.
A reserved configuration/mode was programmed.
1734-IJ
1 Channel 5V DC Encoder / Counter
1734-IK
1 Channel 15…24V DC Encoder / Counter
Output Data Data Type
Counter Control
Counter Reset
SINT
BIT 0
Counter Preset
Value Reset
(Stored / Accumulated Count)
BIT 1
BIT 2
0
0
Default
Value
Valid Data Values
0
0
0=Count Unchanged
1=Count Cleared
0=Count Unchanged
1=Count Set to Preset
0=Count Unchanged
1=Count Cleared
Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 123
1734-SSI
1 Channel Synchronous Serial Interface
Configuration Data Data Type
Run
Gray Binary
Word Length
Data Speed
SINT
SINT
SINT
SINT
G2B Convert (Gray to Binary)
Standardization
(Divide / Shift using Trailing)
SSI Word Delay Time
Trailing (No. of Trailing Bits)
Input Latch Control
InputLatch_0
InputLatch_1
Sensor Resolution
(Positions per Rev. or Stroke)
Sensor Cycle
(Total Revolutions or Strokes)
Compare 0 Value
Compare 1 Value
Compare 0 Control
Compare0_0
Compare0_1
Compare 1 Control;
Compare1_0
Compare1_1
SINT
SINT
INT
SINT
SINT
BIT 0
BIT 1
INT
INT
DINT
DINT
SINT
BIT 0
BIT 1
SINT
BIT 0
BIT 1
0
0
1
1
64
0
0
Default
Value
1
1
13
5
0
0
0
0
Valid Data Values
0=Module Not Running
1=Module Is Running
0=Binary Code
1=Gray Code
2…31
5=125 Kbps
6=250 Kbps
7=500 Kbps
8=1 MB
9=2 MB
0=No Convert
1=Convert
0=No Standardization
1=Apply Standardization
-32,768…32,767 µs
(16…65,535)
0…16
00=Off
01=Falling Edge of Input
10=Rising Edge of Input
11=Both Edges of Input
-32,768……32,767 counts
(1…65,535)
-32,768…32,767 counts
(1…65,535)
-2,147,483,648…
2,147,483,647
(0…4,294,967,295)
-2,147,483,648…
2,147,483,647
(0…4,294,967,295)
00=Off
01=Up Direction
10=Down Direction
11=Both Directions
00=Off
01=Up Direction
10=Down Direction
11=Both Directions
Publication 1734-UM011D-EN-P - May 2011
124 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
SSI Word Delay Time
To enter Delay values from +32,768…+65,535 µs, use this conversion formula:
Desired Delay Value (in µs) - 65536 = Entered Delay Value (in µs).
As an example, for a 40 ms delay time, 40000 - 65536 = -25536
Sensor Resolution
To enter Resolution values from +32,768…+65,535 µs, use this conversion formula:
Desired Resolution Value - 65536 = Entered Resolution Value.
As an example, for a 40,000 count sensor, 40000 - 65536 = -25536
Sensor Cycle
To enter Cycle values from +32,768…+65,535, use this conversion formula:
Desired Cycle Value - 65536 = Entered Cycle Value.
As an example, for 50,000 sensor cycle rotations, 50000 - 65536 =
-15536
Compare 0,1 Value
To enter Compare values from +2,147,483,647…+4,294,967,295, use this conversion formula:
Desired Compare Value - 4,294,967,296 = Entered Compare Value.
As an example, for a 3,000,000,000 compare value,
3,000,000,000 - 4,294,967,296 = -1,294,967,296
Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 125
1734-SSI
1 Channel Synchronous Serial Interface
Input Data Data Type
Present Data
Latched Data
Status
Input Status
DINT
DINT
INT
BIT 0
Run
Decreasing Count
Increasing Count
Compare0 Reached
Compare1 Reached
Compare0 Status
Compare1 Status
Power Fault
Configuration Fault
Communication Fault
Input Data Fault
Data Latched
BIT 1
BIT 2
BIT 3
BIT 4
BIT 5
BIT 6
BIT 7
BIT 8
BIT 9
BIT 10
BIT 11
BIT 12
Default
Value
0
0
Valid Data Values
-2,147,483,648…2,147,483,647
(0…4,294,967,295)
-2,147,483,648…2,147,483,647
(0…4,294,967,295)
0
0=Input is Off
1=Input is On
0=Module is not Running
1=Module is Running
0=Count not Decreasing
1=Count is Decreasing
0=Count not Increasing
1=Count is Increasing
0=Compare not Reached
1=Compare was Reached
0=Compare Off
1=Compare On
0=No 24Vdc Power Fault
1=24Vdc Power Fault
0=No FPGA Config Fault
1=FPGA Config data bad
0=No FPGA Comm Fault
1=FPGA Comm Fault
0=No Input Data Fault
1=Input Power Fault (short)
0=Input Data Not Latched
1=Input Data Latched
Present / Latched Data
To interpret values from -2,147,483,648…-1, use this conversion formula:
Stored Data Tag Value + 4,294,967,296 = Actual Stored Data Tag Value.
As an example, for a read value of -1,794,967,296:
-1,794,967,296 + 4,294,967,296 = 2,500,000,000 actual value
Publication 1734-UM011D-EN-P - May 2011
126 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
1734-SSI
1 Channel Synchronous Serial Interface
Output Data Data Type
Control
Latch Acknowledge
SINT
BIT 0
Compare 0 Acknowledge
Compare 1 Acknowledge
Compare 0 Select
Compare 1 Select
BIT 1
BIT 2
BIT 3
BIT 4
Default
Value
0
0
Valid Data Values
0
0
0
0
0=Latch Not Cleared
1=Latch Cleared
0=Compare0 Not Reset
1=Compare0 Reset
0=Compare1 Not Reset
1=Compare1 Reset
0=Compare0 Not Selected
1=Compare0 Selected
0=Compare1 Not Selected
1=Compare1 Selected
Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 127
1734-232ASC
1 Channel ASCII Interface Module
Configuration Data
Serial Character Format
(ASCII Format:
Data Bits / Parity / Stop)
Serial Comm Speed
(Communication Rate of the Serial Port)
Max Receive Characters
Receive Start Delimiter Mode
Receive Start Delimiter Character
Receive Record End Mode
Receive End Delimiter
Receive String Data Type
Pad Mode
Pad Character
Receive Swap Mode
DeviceNet Handshake Mode
Max Transmit Characters
Data Type
SINT
SINT
SINT
SINT
SINT
SINT
SINT
SINT
SINT
SINT
SINT
SINT
SINT
Default
Value
0
0
20
0
58
(0x3A)
2
13
(0x0d)
1
1
0
(0x00)
0
1
20
Valid Data Values
0=7N2
1=7E1
2=7O1
3=8N1
4=8N2
5=8E1
6=8O1
7=7E2
8=7O2
0=9600 Kbps
1=1200 Kbps
2=2400 Kbps
3=4800 Kbps
4=19.2 KBps
5=38.4 KBps
-128…+127 (0…128)
0=No Start Delimiter
1=Exclude Start Delimiter
2=Include Start Delimiter
Any Valid ASCII Character
(Default is Colon [:])
0=No End Delimiter
1=Exclude End Delimiter
2=Include End Delimiter
Any Valid ASCII Character
(Default is Carr. Return)
0=Array
1=Short String
2=String
0=Pad Mode Disabled
1=Pad Mode Enabled
Any Valid ASCII Character
(Default is NULL)
0=Disabled
1=16-bit Swap Enabled
2=24-bit Swap Enabled
3=32-bit Swap Enabled
0=Master/Slave handshake
1=Produce Immediate
-128…+127 (0…128)
Publication 1734-UM011D-EN-P - May 2011
128 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
1734-232ASC
1 Channel ASCII Interface Module
Configuration Data
Transmit End Delimiter Mode
Transmit End Delimiter Character
Consume String Data Type
Transmit Swap Mode
DeviceNet Record Header Mode
Data Type
SINT
SINT
SINT
SINT
SINT
Default
Value
2
13
(0x0d)
1
0
0
Valid Data Values
0=No End Delimiter
1=Exclude End Delimiter
2=Include End Delimiter
Any Valid ASCII Character
(Default is Carr. Return)
0=Array
1=Short String
2=String
0=Disabled
1=16-bit Swap Enabled
2=24-bit Swap Enabled
3=32-bit Swap Enabled
0=Transmit Handshake
1=Transmit Immediate
Transmit Data / Receive Data / Delimiter / Pad Character
Note that 7 data bits allows ASCII Character data values of 0…127, which
RSLogix 5000 software does support in the signed Short Integer data type
SINT (-128…+127 range).
Note that 8 data bits allows ASCII Character data values of 0 to 255.
To enter values from +128…+255, use this conversion formula:
Desired Decimal Value - 256 = Entered Decimal Value.
As an example, for an ASCII Character value of 128,
128 - 256 = -128
Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 129
1734-232ASC
1 Channel ASCII Interface Module
Input Data
Receive Record Number
Status
TX FIFO Overflow
RX FIFO Overflow
RX Parity Error
Handshake Error
New Data Flag
Length_Lo
Length_Hi
Data[128]
Output Data
Transmit Record Number
Receive Record Number
Status
TX FIFO Overflow
RX FIFO Overflow
RX Parity Error
Handshake Error
New Data Flag
Length_Lo
Length_Hi
Data[128]
BIT 6
BIT 7
SINT
SINT
SINT
Data Type
SINT
SINT
BIT 0
BIT 1
BIT 2
BIT 6
BIT 7
SINT
SINT
SINT
Data Type
SINT
SINT
SINT
BIT 0
BIT 1
BIT 2
20
0
0
0
0
Default
Value
Valid Data Values
-128…+127 (0…255)
0=No Error
1=TX FIFO Overflow Error
0=No Error
1=RX FIFO Overflow Error
0=No Error
1=RX Parity Overflow Error
0=No Error
1=Handshake Error
0=No New Data
1=New Data Present
-128…+127 (0…128)
0 or 1
Received ASCII Message
20
0
0
0
0
Default
Value
0
Valid Data Values
-128…+127 (0…255)
-128…+127 (0…255)
0=No Error
1=TX FIFO Overflow Error
0=No Error
1=RX FIFO Overflow Error
0=No Error
1=RX Parity Overflow Error
0=No Error
1=Handshake Error
0=No New Data
1=New Data Present
-128…+127 (0…128)
0 or 1
Transmitted ASCII Message
Publication 1734-UM011D-EN-P - May 2011
130 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
Transmit Record Number/ Receive Record Number / Length_Lo
Note that 7 data bits allows Transmit / Receive record Number of Length_Lo values of 0…127, which RSLogix 5000 software does support in the signed
Short Integer data type SINT (-128…+127 range).
Note that 8 data bits allows Transmit / Receive record Number of Length_Lo values of 0…255.
To enter values from +128…+255, use this conversion formula:
Desired Decimal Value - 256 = Entered Decimal Value.
As an example, for a Transmit / Receive record Number of Length_Lo value of 128, 128 - 256 = -128
Publication 1734-UM011D-EN-P - May 2011
Appendix
D
Quick Start
What This Appendix
Contains
In this quick start, you learn how to use the 1734-AENT adapter with a
ControlLogix controller for EtherNet/IP systems.
IMPORTANT
This quick start contains a simple set of steps and reminders that will help you avoid errors when you are configuring your POINT I/O system for and
EtherNet/IP network.
ATTENTION
You must use series C POINT I/O modules with the
1734-AENT adapter. Series A or B POINT I/O modules will not work with this adapter.
Necessary Prerequisites
Before you begin this quick start, make sure the following conditions are in place.
• The ControlLogix controller and RSLogix software version must be version 11 or later.
• The 1756-ENBT module must be revision 2.3 or later.
• The 1734 POINT I/O modules must be series C (except for the
1734-232ASC modules, which can be series A).
• The recommended RPIs are being used: Digital = 10 ms or higher,
Analog and Specialty = 50 ms or higher.
• The 1734-AENT POINT I/O adapter is a child to a local 1756-ENBT module.
131 Publication 1734-UM011D-EN-P - May 2011
132 Quick Start
Configure the Adapter
In the 1734-AENT Module Properties dialog, perform the following steps.
1. Complete the Name field.
2. Enter the following address into the IP Address field: 192.168.1.42
You are setting the last digit, because the first three digits are set for you as set by the push wheel switches on the adapter. The push wheel switches should be set to 042.
3. From the Comm Format menu, choose None if you do not want a rack-optimized connection, or choose Rack Optimization if you want a rack-optimized connection.
4. For the Electronic Keying field, select Compatible Module.
5. Enter the Chassis Size.
Regarding chassis size, the POINT I/O adapter itself takes up a count in the chassis. The default chassis size for the POINT I/O is 1, which covers the adapter only and allows for no I/O. To configure your
POINTBus modules, set the chassis size to the physical amount of your
I/O modules plus one for the adapter; otherwise, you get an error. For example, if you have six modules in the chassis, you must set chassis to
6+1=7.
6. Enter the Slot.
For the adapter itself, the slot number is always 0 and cannot be modified.
7. Click Finish.
Your I/O Configuration tree now looks similar to the following:
Publication 1734-UM011D-EN-P - May 2011
Enter Adapter Properties
Use this procedure to enter adapter properties.
1. Right-click the 1734-AENT adapter and select Properties.
The Module Properties dialog appears.
Quick Start 133
2. Click the Chassis Size tab.
Notice that the data under this tab is dimmed while offline. Use the
Chassis Size tab to send the module size from the General tab to the module itself once you are online. Otherwise, you get an error. We explore this later. For now, click OK to close this dialog:
3. Right-click the POINT I/O adapter under I/O Configuration to add a new module.
4. Select the module from the list and click OK.
Publication 1734-UM011D-EN-P - May 2011
134 Quick Start
5. In the Module Properties dialog, enter the following information.
a. Name b. Slot c. Comm Format d. Electronic Keying, choose Compatible Module to verify the major revision C, because only series C modules support EtherNet/IP.
e. Click Next on the bottom of the dialog.
f. Set the RPI to 10 ms for digital and 50 ms for analog or specialty.
6. Click Finish.
Add Another Module Under the Adapter
Use this procedure to add another module under the adapter.
1. Right-click the POINT I/O adapter under I/O configuration to add a new module.
Your second module is in slot 2.
2. Select the module from the Module Type list, and click OK.
3. In the Module Properties dialog, enter the following information: a. Name b. Slot c. Comm Format d. Electronic Keying, choose Compatible Module.
e. Click Next. f. Set the RPI to 10 ms for digital and 50 ms for analog or specialty.
4. Click Finish.
Continue to add modules to the adapter in this fashion until you have added all of the POINT I/O modules connected to the 1734-AENT adapter to the I/O Configuration tree.
Publication 1734-UM011D-EN-P - May 2011
Quick Start 135
Configure 1734 POINT I/O
Modules
For RSLogix 5000 software version 13 and earlier, configure your POINT I/O modules via the Controller Tags database, using the following steps. For
RSLogix 5000 software, versions 15 or later, the preferred method for module configuration is to use the Module Properties dialog for each POINT I/O module, as described in the individual user manual for the module.
1. Double-click the Controller Tags in the project dialog.
Look at the bottom of the screen to make sure you are in the Monitor
Tags tab.
We are going to assume there is an analog input module 1734-IE2V, which resides in slot 6. We configure Channel 0 of this module to operate over the range -10…+10V DC.
2. Click the configuration tag remote_POINT_IO:3:C.
From here you can set the module configuration and alarms.
In this configuration dialog, you enter the values that would correspond to the desired range. The range type default value for a 1734-IE2V module is 2, which is equal to 0…10V DC.
3. Click the configuration tag for the module in slot 4, remote_POINT_IO:3:Ch0RangeType.
4. Check the value in the tag remote_POINT_IO:3:C.Ch0RangeType.
It is set to 2, which is the default value. There are two settings that this module supports:
Publication 1734-UM011D-EN-P - May 2011
136 Quick Start
• 2 = 0…10V DC
• 0 = -10…+10V DC
Publication 1734-UM011D-EN-P - May 2011
5. Click the value 2 and change it to 0, which changes the voltage range to
-10…+10V DC for channel 0.
Note the following:
• The controller sends the configuration data only when connection is being established.
• Should you need to modify any of the tag values once you change the tag, you need to access the updated information and download it into the module. These are the ways to download the updated configuration information into the module.
– Ideally, you enter the correct code number in the Range Type field at the same time that you add the I/O to the I/O Configuration tree.
You then download later .
Quick Start 137
– If you downloaded the offline configuration into the module and then realize that you must modify any of the module’s configuration parameters, then the preferred way to make these changes online is to go to the Module Connection tab and inhibit the module, apply the changes, and then uninhibit the module. Doing this breaks the connection, causing the configuration information to be downloaded right after the connection is made.
IMPORTANT
Switching the controller from Program to Run mode does not change the module connection status and does not re-send module configuration data.
We highly recommend that you use the inhibit/uninhibit process and avoid power cycling.
6. Right-click the 1734-AENT adapter and select Properties.
7. Click the Connection tab.
You see the following message:
The module is faulted because, even though you set up the adapters
POINT I/O chassis size to the actual number of the modules plus the adapter, the adapter still remembers the size of 1 (the factory default value) until you reset this size manually. This option is available only online.
8. Click the Chassis Size tab.
9. Click the Set Chassis Size in Module button and set the chassis size in the adapter.
Remember to inhibit and unhibit the module for this to take effect.
Publication 1734-UM011D-EN-P - May 2011
138 Quick Start
Now you can put your controller in Run mode, and the connection should be successful.
IMPORTANT
The information found in the Controller Tag Reference section of this user manual is also available in the
RSLogix 5000 online help file. Use the Help file search function under the 1734 catalog number that you are configuring and select the Module Defined Data Types option. You see all of the configurable parameters and associated values.
Configure an Ethernet
Driver in RSLinx Software
To configure an Ethernet driver in RSLinx software, launch RSLinx software.
Launch RSLinx Software
Launching the RSLinx software enables you to configure the driver you use to communicate with the ControlLogix controller.
1. Double-click the RSLinx icon on the Desktop to launch RSLinx software.
2. Click the RSWho icon .
Publication 1734-UM011D-EN-P - May 2011
Quick Start 139
The Rockwell Software RSLinx Gateway - [RSWho - 1] screen appears.
TIP
TIP
The RSWho screen is actually RSLinx’s network browser interface, which lets you view all of your active network connections.
The left pane of this display is the Tree Control, which shows networks and devices in a hierarchical view. When a network or device is collapsed, as indicated by the + sign, you can click the + sign or double-click the network or device icon to expand the view and begin browsing. When a network or device is expanded, as indicated by the - sign, you can click the - sign or double-click the network or device icon to collapse the view. The right pane of the
RSWho display is the List Control, which is a graphical representation of all of the devices present on the network.
If there is a communication status error with a device (for example, when a recognized device is inadvertently unplugged), that device appears with a red X, indicating that RSWho previously recognized it, but now it cannot.
You can choose to remove the device from the RSWho display, or you can choose to correct the communication error.
Publication 1734-UM011D-EN-P - May 2011
140 Quick Start
Add the AB_ETHIP-1 (EtherNet/IP) Driver
1. From the Communications menu, choose Configure Drivers.
The Configure Drivers dialog appears.
Publication 1734-UM011D-EN-P - May 2011
2. From the Available Driver Types pull-down menu, choose EtherNet/IP
Driver.
3. Click the Add New button.
4. Click OK to accept the default name (AB_ETHIP-1).
Be sure that the radio button for Browse Local Subnet is enabled.
5. Click OK.
6. Verify that the driver you just configured is running, and click the Close button to exit the Configure Drivers dialog.
7. Click the X in the upper right corner of the RSWho dialog to stop
RSWho.
8. Click the minimize icon in the upper right corner of the RSLinx dialog to minimize RSLinx software.
Numerics
1734-POINT I/O catalog numbers 89
A
AB-ETHIP driver
8
85 access module data adapter features 4
12
16
62 replacing on system wiring auto negotiate autobaud
11
B
bandwidth, insufficient
BootP/DHCP utility 20 browse chassis page
44
80
C
catalog numbers chassis size 1 configuration 16
89
CIP Common Industrial Protocol
Common Industrial Protocol (CIP) compatibility hardware and software configure adapter
5
45, 25
27, 48
98, 107
91
95, 94, 93
92 with over load specialty I/O 111
97, 96
5
5 for direct connection and rack optimization in RSLogix 5000 software configure I/O modules controller tag reference analog 2 channel input digital 2 POINT input with over load
D
data types
RSLogix 5000 valid number ranges
DHCP (Dynamic Host Configuration
Protocol)
DHCP software direct connection
23
DHCP enabled function
23
7
16
90
Index disabled web server function 16
E
edit controller tags empty slots 2
38 empty terminal bases example applications
3
v
F
firmware revisions fixed IP address 43
5, 8
G
gateway address 17
H
hardware 25, 46
I
installing the 1734-AENT adapter mount adapter to existing system replacing adapter set the network address wiring
IP address
12
17, 43
11
11
11, 10
L
ladder program 39
LED status indicators 63
M
master/slave model connections
6 mix rack optimized and direct
7 mount adapter to existing system
13
10
11 mounting dimensions mounting modules on DIN rail before modules installed
N
network address 11, 19
O
overloaded adapter 44
Publication 1734-UM011D-EN-P - May 2011
142 Index
P
power up system for the first time producer/consumer model understanding program fault note publications related vi
6
115, 120
4
Q
quick start 129
R
rack optimized connection recover from an overloaded adapter reinsertion of modules relation list 22 removal of modules 2
2 replace adapter on system
2
7
11 replacement of adapter requested packet interval (RPI) 6
20
6
44
RIUP remove and replace under power
Rockwell BootP/DHCP utility
RPI requested packet interval
RSLinx Ethernet communication driver
85
RSLinx software install 85
RSLogix 5000 data types valid number ranges 90
2
S
set chassis size
18
1 set the network address software releases subnet mask
5
11
T
terminology third party DHCP server thumbwheel
vii
19 troubleshooting 63
15
U
upgrades hardware and firmware utils directory 20
5
V
verify module chassis size 41, 59
W
web page diagnostics
Browse Chassis page
Configuration page
Diagnostics page
Home page 67 what the adapter does wiring the adapter 12
80
76
69
67
5
Publication 1734-UM011D-EN-P - May 2011
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support/ , you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer
TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/ .
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or
Canada
Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html
or contact your local Rockwell Automation representative.
,
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States
Outside United States
Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.
Please contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002 , available at http://www.rockwellautomation.com/literature/ .
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Publication 1734-UM011D-EN-P - May 2011
Supersedes Publication 1734-UM011C-EN-P - January 2006 Copyright © 2011 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Download
Advertisement
Key features
EtherNet/IP communication
DIN rail mounting
Supports both direct and rack optimized connections
Supports connections from multiple controllers
Frequently asked questions
You must use series C POINT I/O modules with the 1734-AENT adapter. Series A or B POINT I/O modules will not work.
The default setting for the chassis size is 1 slot, which represents the adapter by itself.
RSLogix 5000 software, RSLinx software.
CIP is the application layer protocol specified for EtherNet/IP, as well as for ControlNet and DeviceNet networks.