Enviro Westport Owner's Manual


Add to my manuals
47 Pages

advertisement

Enviro Westport Owner's Manual | Manualzz

Westport

B Y : S H E R W O O D I N D U S T R I E S L T D

OWNER’S MANUAL

W

ARRANTY

enviro.com/warranty

REGISTRA

TION

SHERWOOD INDUSTRIES IS AN ENVIRONMENTALLY RESPONSIBLE COMPANY. THIS MANUAL IS PRINTED ON RECYCLED PAPER.

PLEASE KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE

INSTALLER:

Leave this manual with the appliance.

CONSUMER:

Retain this manual for future reference.

WHAT TO DO IF YOU SMELL GAS

• Open windows/extinguish any open flame.

• Do not try to light any appliance.

• Do not touch any electrical switch or use any phone in your building.

• Immediately call your gas supplier from a neighbour’s phone. Follow the gas supplier’s instructions.

• If you cannot reach your gas supplier, call the fire department.

FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance.

WARNING:

If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer, service agency or the gas supplier.

This appliance may be installed in an after-market permanently located, manufactured (mobile) home, where not prohibited by local codes.

This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.

Massachusetts installations (Warning): This product must be installed by a licensed plumber or gas fitter when installed within the Commonwealth of Massachusetts. Other Massachusetts code requirements: Flexible connector must not be longer than 36in., a shut off valve must be installed; only direct vent sealed combustion products are approved for bedrooms/bathrooms. A carbon monoxide detector is required in all rooms containing gas fired direct vent appliances. The fireplace damper must be removed or welded in the open position prior to installation of a fireplace insert.

Version Française: www.enviro.com/fr.html

50-1033

2

Safety Precautions

FOR SAFE INSTALLATION AND OPERATION OF YOUR “ENVIRO” HEATER,

PLEASE CAREFULLY READ THE FOLLOWING INFORMATION:

• All ENVIRO gas-fired appliances must be installed in accordance with their instructions. Carefully read all the instructions in this manual first. Consult the building authority having jurisdiction to determine the need for a permit prior to commencing the installation.

NOTE: Failure to follow these instructions could cause a malfunction of the fireplace, which could result in death, serious bodily injury, and/or property damage.

• Failure to follow these instructions may also void your fire insurance and/or warranty.

GENERAL

• Installation and repair should be done by a qualified service person. The appliance should be inspected before the first use and, at least, annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative the control compartments, burners and circulating air passageways of the appliance be kept clean.

• Due to high temperatures, the appliance should be located out of high traffic areas and away from furniture and draperies.

Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burn or clothing ignition.

• Young children should be carefully supervised when in the same room as the appliance.

• Clothing or other flammable materials should not be placed on or near the appliance.

FOR YOUR SAFETY

• Installation and service must be performed by a qualified installer, service agency or gas supplier.

• This installation must conform to local codes or, in the absence of local codes, to the current CAN/CGA-

B149 installation code (Canada) or National Fuel Gas

Code ANSI Z223.1.2 (USA)

• To prevent injury, do not allow anyone who is unfamiliar with the stove to operate it.

To prevent injury, if the pilot or pilot and

burners have gone out on their own, open the glass door and wait 5 minutes to air out before attempting to re-light the stove.

• Always keep the area around these appliances clear of combustible material, gasoline and other flammable liquids and vapours.

• These appliances should not be used as a drying rack for clothing or for hanging Christmas stockings/ decorations.

• Due to the paint curing on the stove, a faint odor and slight smoking will likely be noticed when the stove is first used. Open a window until the smoking stops.

Always connect this gas stove to a vent system and vent to the outside of the building envelope. Never vent to another room or inside the building. Make sure the specified vent pipe is used, properly sized and of adequate height to provide sufficient draft. Inspect the venting system annually for blockage and signs of deterioration.

WARNING: Failure to position the parts in accordance with the diagrams in this booklet, or failure to use only parts specifically approved with this appliance, may result in property damage or personal injury.

WARNING: Do not operate with the glass front removed, cracked or broken. Replacement of the glass should be done by a licensed or qualified service person.

• Never use solid fuels such as wood, paper, cardboard, coal, or any flammable liquids, etc., in this appliance.

• Do not use this heater if any part has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part of the control or gas control systems that have been under water.

• Do not abuse the glass by striking it or slamming the door shut.

Table of Contents

Safety Precautions..................................................................................................................2

Table of Contents...................................................................................................................3

Codes And Approvals..............................................................................................................4

Specifications.........................................................................................................................5

Dimensions................................................................................................................5

Rating Label Location.................................................................................................5

Operating Instructions............................................................................................................6

Pilot Lighting Instructions............................................................................................6

Pilot Light..................................................................................................................7

Air Shutter.................................................................................................................7

Remote controls (Optional).........................................................................................8

Blower Speed (Optional).............................................................................................8

Normal Sounds During Operation................................................................................8

Maintenance And Service........................................................................................................9

Routine Maintenance..................................................................................................9

Cleaning The Glass.....................................................................................................9

Cleaning The Firebox..................................................................................................9

Change Battery in Ignition Module...............................................................................9

Replacing the Glass..................................................................................................10

Glass Door Removal..................................................................................................10

Burner Removal........................................................................................................10

Fuel Conversion........................................................................................................11

Initial Installation.................................................................................................................13

Preparation For Installation.......................................................................................13

Clearances to Combustibles.......................................................................................13

Planning Your Installation..........................................................................................13

Vent Termination Restrictions....................................................................................15

Fireplace Horizontal Vent Kit 50-1235.........................................................................16

Other Approved Vent Parts........................................................................................17

Vent Configurations and Restrictor Settings..................................................................19

Horizontal Installation...............................................................................................20

Vertical Installation...................................................................................................22

Cathedral Ceiling Installation.....................................................................................24

Corner Installations..................................................................................................25

Venting into a Class ‘A’ Chimney.................................................................................26

Converting Top Vented into Rear Vented.....................................................................26

Installation of Rear Vented Appliance.........................................................................27

Installation of Top Vented; Horizontal Termination......................................................28

Installation of Top Vented; Vertical Termination...........................................................28

Freestanding Drafthood Adaptor - 50-841...................................................................29

Gas Line Connection and Testing...............................................................................32

Electrical Requirements For Gas Valve and Optional Blower..........................................33

Secondary Installation...........................................................................................................34

Installation of Optional Blower...................................................................................34

Installation of Log Set and Embers............................................................................34

Installation of Panel Set............................................................................................37

Trouble Shooting..................................................................................................................38

Parts List - Cast....................................................................................................................39

Parts Diagram - Cast.............................................................................................................42

Parts List - Components........................................................................................................43

Parts Diagram - Components.................................................................................................45

Warranty..............................................................................................................................46

Installation Data Sheet.........................................................................................................47

3

4

Codes And Approvals

DIRECT VENT ONLY: This type is identified by the sufix DV. This appliance draws all of its air for combustion from outside the dwelling, through a specially designed vent pipe system.

TOP VENT DV Certified for installation from 0-4500 ft (0-1372 m)

REAR VENT DV Certified for installation from 0-4500 ft (0-1372 m) with 36” (915 mm) snorkel (refer to ‘Converting Top Vented into Rear Vented’).

In the USA: The appliance may be installed at higher altitudes. Please refer to your American Gas

Association guidelines which state: the sea level rated input of Gas Designed Appliances installed at elevations above 2000 (610 m) feet is to be reduced 4% for each 1000 feet (305 m) above sea level.

Refer also to local authorities or codes which have jurisdiction in your area regarding the de-rate guidelines.

In Canada: When the appliance is installed at elevations above 4500 feet (1372 m), the certified high altitude rating shall be reduced at the rate of 4% for each additional 1000 feet (305 m).

• This appliance has been tested by INTERTEK (Warnock Hersey) and found to comply with the established VENTED GAS FIREPLACE HEATER standards in CANADA and the USA as follows:

VENTED GAS FIREPLACE HEATER (Westport DV; NG/LPG)

TESTED TO: ANSI Z21.88a-2003/CSA 2.33a-2003 VENTED GAS FIREPLACE HEATERS

CAN/CGA 2.17-M91 GAS FIRED APPLIANCES FOR HIGH ALTITUDES

CSA P.4.1-02 TESTING METHOD FOR MEASURING ANNUAL FIREPLACE EFFICIENCY

This ENVIRO WESTPORT Fireplace:

• Has been certified for use with either natural or propane gases. (See rating label.)

• Is not for use with solid fuels.

• Is approved for bedroom or bed sitting room. (IN CANADA: must be installed with a listed wall thermostat. IN USA: see current ANSI Z223.1 for installation instructions.)

• Must be installed in accordance with local codes. If none exist, use current installation code CAN/CGA B149 in Canada or ANSI Z223.1/NFPA 54 in the

USA.

• Must be properly connected to an approved venting system and not connected to a chimney flue serving a separate solid-fuel burning appliance.

IMPORTANT NOTICE (Regarding first fire up): When the unit is turned on for the first time, it should be turned onto high without the fan on for the first 4 hours. This will cure the paint, logs, gasket material and other products used in the manufacturing process. It is advisable to open a window or door, as the unit will start to smoke and can irritate some people.

After the unit has gone through the first burn, turn the unit off including the pilot, let the unit get cold then remove the glass door and clean it with a good gas fireplace glass cleaner, available at your local ENVIRO dealer.

Specifications

WARNING:

Operation of this heater when not connected to a properly installed and maintained venting system can result in carbon monoxide (CO) poisoning and possible death.

D imensions

:

25 ¾"

(65.3cm)

15 1 /

8

"

(39.0cm)

27"

(68.6cm)

27"

(68.5cm)

25 ¾"

(65.4cm)

15 ¾"

(40.0cm)

17 1 /

8

"

(43.5cm)

16 5 /

8

"

(42.2cm)

Floor to center of flue

REAR VENT

23½” (59.7 cm)

25 ¾"

(65.3cm)

Figure 1: Westport Exterior Dimensions.

R ating

L abeL

L ocation

:

The Rating Label is located on a plate hang on the back left of the unit.

5

Operating Instructions

For Your Safety, Read Safety Precautions And

Lighting Instructions Before Operating

WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY A FIRE OR EXPLOSION MAY

RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OF LOSS OF LIFE.

P iLot

L ighting

i nstRuctions

:

6

TH TP TH TP

T

OL

L I P

I

H

LO

Figure 2. Lighting Instruction Label

Operating Instructions

P iLot

L ight

:

1. Turn off the gas to the fireplace. If not recently done, remove the glass and let the unit air out

for at least five (5) minutes to clear out any gas. Turn on gas to the heater. Leak test all joints with soapy water. NEVER USE OPEN FLAME FOR LEAK TESTING.

2. Start the pilot by pressing the gas control knob and turning it to PILOT.

While holding the gas control knob in, press the piezo ignitor several times until the pilot light starts. Hold the gas control knob in for 30 seconds. Check that the pilot has fully engulfed the thermocouple assembly (see Figure 3).

3. Start the main burner by turning the gas control knob to ON and then turn the rocker switch to ON. Check that all burner ports have flame.

4. Leak test all gas joints again.

Thermopile

Thermocouple

Figure 3. Pilot Flame a iR

s hutteR

:

The air shutter is controlled with the primary air adjustment rod located behind the gas valve shown in

Figure 4.

The air shutter allows the amount of air coming into the fireplace to be adjusted in order to accommodate different climates and venting arrangements. Start the pilot and then the burner. Make sure the pilot flame is burning normally and none of the burner ports are plugged. Let the fireplace burn for roughly fifteen (15) minutes and then examine the flames, compare the flames to Figure 61.

The ideal flame will be blue at the base and light orange above. The flames should be of medium height. If the flames look like this, no venturi adjustment is needed. If the flames are fairly short and mostly blue, the fireplace is getting too much air. Therefore, the air shutter should be closed slightly until the correct flames are achieved. Flames that are very orange, with tall, dark, stringy tips, are not getting enough air.

Open the venturi until the flames clean up. If the venturi is opened, or closed all the way, and the correct flames cannot be attained, turn off the gas and contact the dealer.

Table 1: Venturi Information.

Venturi Setting

Natural Gas Propane

1

/

16

” min.

3

/

16

” min.

Gas valve regulator

Gas valve

Primary air adjustment rod

Figure 4: Gas Valve In Place on Unit.

Warning: Incorrect venturi adjustment may lead to improper combustion, which is a safety hazard.

Contact the dealer if there is any concern about the venturi adjustment.

7

8

Operating Instructions

For Your Safety, Read Safety Precautions And

Lighting Instructions Before Operating

R emote contRoLs

(o

PtionaL

):

This fireplace can use an optional remote control or an optional cordless wall thermostat. If either of these are to be used to control the fireplace for the majority of the time, leave the ON/OFF switch (on the control panel) in the remote/thermostat position. Consult the instructions included with the remote/wall thermostat for operation guidelines.

b

LoweR

s

PeeD

(o

PtionaL

):

The blower will come on only when the fireplace is up to temperature (approximately 20 minutes). The speed of the fan can be changed by turning the fan control knob. To turn the blower off, turn the knob

COUNTER CLOCKWISE until it “clicks” off.

It is advisable not to operate the blower below

1

/

3

speed as it puts a strain on the windings of the blower and running the blower at lower speeds could also cause premature fan failure.

n oRmaL

s ounDs

D uRing

o

PeRation

:

Component

Westport

Burner

Temperature Sensor

Pilot Flame

Blower / Fan

Gas Control Valve

Table 2: Normal Sounds

Sound & Reason

Creaking when heating up or cooling down.

Light pop or poof when turned off; this is more common with LP units.

Clinking when it senses to turn the blower on or off.

Quiet whisper while the pilot flame in on.

Air movement that increase and decreases with the speed of the blower. The blower is pushing the heat from the fireplace into the room.

Dull click when turning on or off, this is the valve opening and closing.

Maintenance And Service

R outine

m aintenance

:

At least once a year, run through the following procedures to ensure the system is clean and working properly. Check the burner to see if all the ports are clear and clean. Check the pilot to make sure it is not blocked by anything. The pilot flame should be blue with little or no yellow on the tips.

Warning: Clearances must be sufficient to allow access for maintenance and service

Warning: Failure to position the parts in accordance with this manual, or failure to use only parts specifically approved with this appliance may result in property damage or personal injury.

The venting system must be periodically examined; it is recommended the examination is done by a qualified agency.

c

Leaning

t he

g

Lass

:

When the fireplace has cooled, remove the face of the fireplace along with the glass. See M aintenance a nd

S ervice

- G laSS

d oor

r eMoval

. Check the gasket material on the back of the glass, making sure that it is attached and intact.

During a cold start up, condensation will sometimes form on the glass. This is a normal condition with all fireplaces. However, this condensation can allow dust and lint to cling to the glass surface. Initial paint curing of the appliance can leave a slight film behind the glass, a temporary problem. The glass will need cleaning about two weeks after installation. Use a mild glass cleaner and a soft cloth; abrasive

cleaners will damage the glass and plated surfaces. Depending on the amount of use, the glass should require cleaning no more than two or three times a season. Do not clean the glass when it is

hot.

c

Leaning

t he

F iRebox

:

Remove the logs carefully, as they are very fragile. Gently remove all the embers and rock wool and place on a paper towel. Vacuum the bottom of the firebox thoroughly. Carefully clean any dust off the logs and remove any lint from the burner and pilot. At this time, inspect the burner pan for cracking or severe warping. If a problem is suspected, contact the dealer. Check the logs for deterioration or large amounts of soot; a small amount on the bottom side of the logs is normal. Replace the logs and embers as in the l oG

S et and

e

Mber

i nStallation

section. If new/more embers and rock wool are required, contact your nearest ENVIRO dealer.

c hange

b atteRy in

i gnition

m oDuLe

:

If the unit does not spark when lighting, the battery in the electronic ignition could need replacing.

Located on the left hand rear corner of the unit is a small rectangular hole. Located here is the electronic ignition module

(see Figure 5). Remove the battery cover, located on the left side of the module, and replace the AA battery.

Reinstall the battery cover and check for spark by depressing the pilot knob located on the control panel.

Electronic ignition module

Figure 5: Electronic Ignition Module

Location.

9

Maintenance And Service

R ePLacing the

g

Lass

:

The glass in the fireplace is a high temperature ceramic. If the glass is damaged in any way, a factory replacement is required (see P artS

l iSt

- c oMPonentS

). Wear gloves when handling damaged glass door assembly to prevent personal injury. When the glass door assembly is being transported, it must be wrapped in newsprint and tape and/or a strong plastic bag. Do not operate with the glass front removed, cracked or broken. Removal and replacement of the glass from the door must be done by a licensed or qualified service person. The glass must be purchased from an ENVIRO dealer. No substitute

materials are allowed.

To Replace:

• Open door, and remove the glass carefully.

• Install the new piece of glass with the large bulb in the gasket tape against the unit. Place the joint in the tape in a bottom corner. Close door.

g

Lass

D ooR

R emovaL

:

Turn unit off and wait until the appliance has cooled down. Remove the cast iron top from the unit by lifting straight up. Lift the two door handles located on either side of the door and lift the glass door assembly straight up and out (see Figure 6 and 7).

Carefully open the two doors and remove if necessary.

Ensure the door is properly fastened after cleaning before attempting to re-light the appliance.

10

Figure 6: Handles for Removing Door.

Figure 7: Removing of Door.

b uRneR

R emovaL

:

1. Remove the glass as shown in the M aintenance and

S ervice

- G laSS

d oor

r eMoval

.

2. Carefully remove the log set and ember material.

3. Remove the two (2) screws (located on the outside edges of the burner) that hold the burner to the chassis inside the fire box, see Figure 8. Remove the burner tray from the firebox.

Maintenance And Service

F ueL

c onveRsion

:

TO BE INSTALLED BY A QUALIFIED SERVICE AGENCY ONLY

Please read and understand these instructions before installing.

Warning: This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a fire, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualified service agency is responsible for the proper installation of this kit. The installation is not proper or complete until the operation of the converted appliance is checked as specified in the manufacturer’s instructions supplied with the kit.

Kit Parts List:

1 - Orifice (NG - #39 DMS or LP - #53 DMS)

1 - Pilot Injector (NG 0.62 mm; LP 0.35 mm)

1 - Installation instruction sheet

1 - Conversion label

Carefully inspect all parts supplied with this conversion kit. If any parts have been damaged or are missing, contact your dealer, distributor or courier company to have them replaced before starting this installation.

Conversion Kit Installation:

1. Turn control knob on the gas valve to the “OFF” position and shut the gas supply off at the shut-off valve upstream of the unit. CAUTION:

The gas supply must be shut off prior to disconnecting the electrical power and before proceeding with the conversion.

Allow the valve and unit to cool down to room temperature.

Rotate handles and remove the door and glass.

Pilot assembly moved from firebox for clarity.

2. Remove the glass as shown in the

M aintenance and

S ervice

- G laSS

d oor r eMoval

.

3. Carefully remove the log set and ember material if they are installed.

4. Remove the burner as shown in the

M aintenance and

S ervice

- b urner

r eMoval

.

5. Convert the burner orifice(s):

Lift off the pilot head and replace with proper pilot orifice for fuel type to be used.

a) Remove the main burner orifice with a

½ inch deep socket.

b) Put a bead of pipe-thread sealant or approved Teflon tape on the orifice threads before installing into the brass elbow. c) Install the new orifice(s) from the kit into the brass elbow.

Using a ½" deep socket remove/reinstall the main burner orifice.

Venturi adjustment bracket.

Figure 8: Unit burner shown apart.

Undo the two

(2) screws that hold burner in the firebox.

11

12

Maintenance And Service

6. Convert the pilot injector: a) Pull the pilot hood straight up to access the pilot injector. b) Using a

5

/

32

” or 4 mm Allen key, remove the pilot injector.

c) Install the new pilot injector supplied with this conversion kit. Simply screw the new injector inside the pilot hood using the Allen key, d) Reinstall the hood by placing the hood on the assembly, line up the key way, and snap into place.

7. Convert the SIT gas valve:

Figure 9:

Removing valve cap.

a) Remove the black protection cap from the HI/LO knob by hand shown in Figure 9.

b) Insert a

5

/

32

” or 4 mm Allen wrench into the hexagonal key-way of the screw (see

Figure 10), rotate it counter-clockwise until it is free and extract it.

Red o-ring is visible c) Check that the screw is clean and if necessary remove dirt.

T ighten

L oosen

Figure 10: Removing valve screw.

Red o-ring is not visible

Figure 11: Flip valve screw.

d) Flip the screw (refer to Figure 11).

e) Using the Allen wrench as shown in

Figure 10, rotate the screw clockwise

LPG Configuration

Figure 12: O-ring on valve screw.

until a torque of 9 inch lbs. WARNING! Do not over tighten the screw. It is recommended that you grip the wrench by the short side.

f) Verify that if the conversion is from NG to LPG, the screw must be reassembled with the red o-ring visible (refer to Figure 12). If the conversion is from LPG to NG, the red o-ring of the screw must be not visible.

g) Re-attach the black protection cap that was removed in step a (Figure 9).

8. Reinstall the burner, brick panels, log set, embers, and glass door. Also refer to S econdary

i nStallation

- l oG

S et and

e

MberS

i nStallation

. When re-installing the burner, ensure that the burner to pilot hood relationship is similar to what is shown in Figure 13. On some units you will need to pay special attention when installing the burner that the venturi adjustment rod is properly installed into the venturi adjustment piece welded to the burner venturi tube

Figure 13. Ignitor assembly beside the burner.

9. Reconnect the main gas line if it was disconnected and open the shut-off valve at the gas line to the unit.

10. Use a small brush to apply a warm soapy water solution to all gas connections (use a half dish soap and half warm water). If a gas leak is present, bubbling will occur. Gas leaks can be repaired by using an approved pipe thread sealant or approved Teflon tape. NEVER USE AN OPEN FLAME WHEN

TESTING FOR LEAKS.

11. Reconnect the electrical power to the unit.

12. Relight the main burner in both the “HI” and “LO” positions to verify proper burner ignition and operation and proper flame appearance. Also refer to S econdary

i nStallation

- l oG

S et and

e

MberS i nStallation

for a flame appearance picture.

13. MAKE SURE that the conversion label is installed on or close to the rating label to signify that the unit has been converted to a different fuel type.

Initial Installation

QUALIFIED INSTALLERS ONLY

WARNING:

Operation of this heater when not connected to a properly installed and maintained venting system can result in carbon monoxide (CO) poisoning and possible death.

P

RePaRation

F oR

i nstaLLation

:

• Remove the packaging from the appliance, and check to make sure there is no damage. If damage is found, please report it to both the carrier and your dealer as soon as possible.

• Before beginning, carefully check the glass door and the log set

• Locate a position where the flue system of the stove can be properly installed without damaging the integrity of the building; e.g. cutting a wall or ceiling joist.

• Check stove and flue system clearance requirements.

• Locate the stove where it can be accessed by a gas supply line.

• Locate the stove in a large and open room that is centrally located in the house. This will optimize heat circulation and comfort.

• As the stove can be equipped with a convection fan, ensure that an electrical outlet is within 6 ft (1.8 m) of the stove.

• The flow of combustion and ventilation air must not be obstructed.

c

LeaRances to

c ombustibLes

:

A. Sidewall to unit 11 inches (27.9 cm)

B. Backwall to unit 2.5 inches (6.35 cm)

C. Corner to unit

D. Ceiling

E. Floor

2.5 inches (6.35 cm)

60 inches above floor (152.4 cm)

(hard wood and linoleum) 0 inches

Note: When installing on a carpeted surfaces a non- combustible hearth pad must be used.

Minimum Alcove Dimensions:

Width

Height

Depth (max)

48 inches (121.9 cm)

60 inches (152.4 cm)

24 inches (60.96 cm)

A

Back wall

B

Front

C

Adjacent wall

C

Fr on t

Figure 14: Clearances to combustibles.

CLEARANCES MUST BE SUFFICIENT TO ALLOW ACCESS FOR MAINTENANCE AND SERVICE.

P

Lanning

y ouR

i nstaLLation

:

When planning your installation, it will be necessary to select the proper length of vent pipe for your particular requirements. It is important to note when passing through a wall, the maximum allowable wall thickness is 10 inches (25.4 cm), 1½ inches (3.8 cm) clearance to combustibles must be maintained.

Select the amount of vertical rise desired for “vertical-to-horizontal” type installations. To determine the length of vent pipe required for vertical installations, measure the distance from the appliance flue outlet to the ceiling, the ceiling thickness, the vertical rise through the attic or second story, and allow for sufficient vent height above the roof line. For two story applications, a fire stop is required at each floor level. If an offset is needed in the attic, additional pipe and elbows will be required. To connect the venting system to the appliance flue outlet, a twist-lock adapter is built into the appliance at the factory.

Refer to i nitial

i nStallation

- v ent

c onfiGuration and

r eStrictor

S ettinGS

for venting parameters.

14

Round Support

Box/Wall Thimble

Initial Installation

QUALIFIED INSTALLERS ONLY

Horizontal

Termination

Your total vent pipe length must be within the shaded area of Figure 23. If a 90° elbow is used in the horizontal plane, 36” (91.4 cm) must be subtracted from the allowable horizontal run.

There are three (3) basic types of Direct Vent

System installations. The three (3) types of installations are shown in Figures 15 through

17.

90° Elbow

Pipelength

Vertical

Termination

Pipelength

Storm Collar

Flashing

Ceiling Firestop

Figure 15: Common Horizontal Installation.

Round Support

Box/Wall Thimble

36" (915 mm)

Snorkel

Cathedral Ceiling

Support Box

Pipelength

Round Support

Box/Wall Thimble

Pipelength

Figure 16: Common Vertical Installation.

Onto Stove

Adaptor

2 ft (610 mm)

Pipelength

Figure 17: Common Snorkel Installation.

v ent

t eRmination

R estRictions

:

Initial Installation

QUALIFIED INSTALLERS ONLY

D E

L

B

N

F

H

C

Fixed

Closed

B

Openable

B

Fixed

Closed

B

Openable

Termination Cap

A

J

Air Supply Inlet

G Gas Meter

G

M

I

Restriction Zone

(Termination not allowed)

Figure 18. Vent Termination Restrictions, refer to Table 3.

O

K

G

A

Letter

A

B

C

D

G

H

E

F

J

I

K

L

M

N

6 ft (1.83 m)

Table 3: Vent termination clearances, refer to Figure 18.

Canadian Installation

1

12 in (30 cm)

US Installation

2

12 in (30 cm) 9 in (23 cm)

12 in (30 cm)*

24 in (60 cm)*

18 in (45 cm)*

12 in (30 cm)*

3 ft (91 cm) within a height of

15 ft (4.5 m) above the meter/ regulator assembly

3 ft (91 cm)

12 in (30 cm)*

3 ft (91 cm) within a height of

15 ft (4.5 m) above the meter/ regulator assembly*

3 ft (91 cm)*

12 in (30 cm) 9 in (23 cm)

Description

Clearance above grade, verandah, porch, deck, or balcony.

Clearance from window or door that may be opened.

Clearance from permanently closed window (to prevent condensation).

Vertical clearance to ventilated soffit located above the terminal, within a horizontal distance of 2 ft (60 cm) from center line of terminal.

Clearance to unventilated soffit.

Clearance to outside corner.

Clearance to inside corner.

Clearance to each side of center line extended above meter/regulator assembly.

Radial clearance around service regulator vent outlet.

Clearance to non-mechanical air supply inlet to building, or the combustion air inlet to any other appliance.

Clearance to mechanical air supply inlet.

7 ft (2.13 m)t

3 ft (91 cm) above if within 10 ft (3 m) horizontally

7 ft (2.13 m)*t

12 in / 30 cm+

12 in (30 cm)*

12 in (30 cm)

12 in / 30 cm*+

Clearance above paved sidewalk or paved driveway located on public property.

Clearance under verandah, porch, deck, or balcony.

Clearance horizontally to any surface (such as an exterior wall) for vertical terminations.

Clearance above roof line for vertical terminations.

O

1 In accordance with the current CSA B149, Natural Gas and Propane Installation Code.

2 In accordance with the current ANSI Z223.1 NFPA 54, National Fuel Gas Code.

t A vent shall not terminate directly above a side walk or paved driveway that is located between two single family dwellings and it serves both dwellings.

+ Permitted only if verandah, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

NOTE: Venting terminals shall not be recessed into walls or siding.

15

16

Initial Installation

QUALIFIED INSTALLERS ONLY

F iRePLace

h oRizontaL

v ent

K it

50-1235:

Please read and understand these instructions before installing. Failure to follow these instructions carefully could cause property damage or personal injury.

KIT COMPONENTS:

Qnty Description

1 Horizontal direct vent termination cap

1

1

1

1

Flue collar adapter

Wall thimble

5’ (190 cm) length of Ø4” (10 cm) double walled flex pipe

5’ (190 cm) length of Ø6⅝” (16.8 cm) double walled flex pipe

12

8

1

1

Qnty Description

4 Wire spacers

4 oz tube Mill-Pac Sealant

4 oz tube RTV silicone

9/16” tech screws

1½” wood screws

Please ensure that all components are supplied with this kit. If components are missing or have been damaged, contact your dealer, distributor, or courier company. Do not attempt the installation if components are missing or damaged.

INSTALLATION INSTRUCTIONS:

1. Plan your installation and clearances to combustibles. Decide on a location for the unit that will meet the clearances noted in the venting section, and any or all local code requirements.

2. Set the appliance in the desired location. Determine if any wall studs, electrical wiring, or plumbing pipes are in the way of the venting system as it passes through the exterior wall. The fireplace location should be adjusted if obstructions are found in the wall.

3. Project a line from the center point of the flue outlet upward and outward to the desired flue outlet location on the exterior wall. Using this center point, scribe a 10” (25.4 cm) hole or square on the wall.

Cut the hole from the interior through the exterior wall surfaces.

4. Frame the hole as shown in Figure 26.

5. Trim the wall thimble to match the wall thickness as necessary. Install the wall thimble and secure it to the inner wall frame using four (4) 1½” wood screws. If a wall is greater than 8” (203mm) in depth, the clearance above the flex must be

4⅜” (111mm)

Figure 19: Wire Spacers.

6. Apply a bead of Mill-Pac Black sealant to the new Ø4” (10 cm) by 5” (12.5 cm) provided flue collar adaptor. Press the flue collar into the flue outlet of the fireplace so that the Mill-Pac seals the flue collar to the flue outlet.

7. Stretch both the Ø4” (10 cm) flex vent and the Ø6⅝” (16.25 cm) flex intake liner to the length needed to ensure the flex can be easily connected to the vent terminal.

8. Slide the Ø6⅝” (16.25 cm) flex intake liner over the flex vent. Install four (4) wire spacers around the flex pipe. Ensure the wire spacers are positioned at either end of the pipes, and at each end of any elbows in the liners (refer to Figure 19 and 20).

9. Install the flex pipe assembly through the wall thimble, ensure that this portion of pipe slides through the outside wall far enough to connect onto the vent termination cap.

Figure 20: Wire Spacer in Place.

Initial Installation

QUALIFIED INSTALLERS ONLY

10. Apply a bead of Mill-Pac Black sealant to the top section of the Ø4” (10 cm) by 5”

(12.5 cm) flue collar adaptor previously installed into the fireplace flue outlet.

Slide the Ø4” (10 cm) flex vent over the flue collar and secure with three (3) sheet metal screws evenly spaced.

11. Place a bead of high temperature silicone on the intake collar of the fireplace, slide the Ø6⅝” (16.25 cm) flex intake liner over the collar, secure the flex liner with three (3) sheet metal screws evenly spaced.

12. On the outside of the exterior wall, apply a bead of Mill-Pac Black sealant to the Ø4” (10 cm) pipe of the vent terminal. Slide the flex liner onto the vent terminal and secure with three (3) sheet metal screws evenly spaced.

13. Place a bead of high temperature silicone on the intake collar of the vent terminal, slide the Ø6⅝” (16.25 cm) flex intake liner over the collar, secure the flex liner with three (3) sheet metal screws evenly spaced.

Flue Pipe Adaptor

Horizontal Vent Termination

Wall Thimble

Fire Stop

Exhaust 4" Flex Pipe

Wire Spacers

Combusion Air 6 5 /

8

" Flex Pipe

Wall Framing

Figure 21: Installation of Fireplace Horizontal Vent Kit.

14. Attach the vent terminal to the outside of the house using four (4) wood screws provided.

15. Light the appliance and ensure proper operation.

o theR

a

PPRoveD

v ent

P aRts

:

Table 4: Approved Vent Manufacturers

Manufacturer

American Metal Products

Trade Name

AmeriVent Direct

Security Chimneys International LTD

Selkirk Metalbestos

Simpson Dura-Vent

Secure Vent

Direct-Temp

Direct Vent GS

Nominal Sizes

4” - 6 5/8”

4” - 6 5/8”

4” - 6 5/8”

4” - 6 5/8”

The Westport fireplace has been tested and certified for use with AMERICAN METAL PRODUCTS

“AMERIVENT DIRECT”, SIMPSON DURAVENT TYPE GS PIPE FOR GAS STOVES. SECURITY CHIMNEY’S

“SECURE VENT DIRECT VENT SYSTEM” and SELKIRK “DIRECT-TEMP VENT SYSTEM” kits are available for horizontal and vertical venting. When using Simpson Duravent, it is recommended that, before installation, a bead of RTV High Temperature Silicone should be applied to each outer vent joint, and Mil-

Pac to each inner joint. When planning an installation, it will be necessary to select the proper length of vent pipe for the particular requirements.

WARNING: Do not mix parts from different vent manufacturers’ systems.

17

18

Initial Installation

QUALIFIED INSTALLERS ONLY

EXCEPTION TO WARNING: This product has been evaluated by Intertek for using a Direct Vent GS starting collar in conjunction with Secure Vent, Direct-Temp, and Ameri Vent Direct venting systems. Use of these systems with the Direct Vent GS starting collar is deemed acceptable and does not affect the

Intertek WH listing of the appliance.

Table 5: Vent part numbers (Must state if galvanized or black wanted, PART NUMBERS).

Direct Vent GS Direct-Temp Secure Vent Ameri Vent Direct Description

908 4DT-6 SV4L6 6” pipe length

907

906

904

903

902

945

990

950

942

953

963

988

4DT-9

4DT-12

4DT-24

4DT-36

4DT-48

4DT-EL45

4DT-EL90

4DT-VS

4DT-WT

4DT-SC

4DT-FS

4DT-WS/B

SV4L12

SV4L24

SV4L36

SV4L48

SV4EBR45

SV4EBR90

SV4VS

SV4RSN

SV4FC

SV4BF

SV4BM

4D7

4D12

4D2

4D3

4D4

4D45B

4D90B

4DWT

4DSC

4DFSP

4DWS

7” pipe length

9” pipe length

12” pipe length

24” pipe length

36” pipe length

48” pipe length

45° elbow, black

90° elbow, black

Vinyl siding standoff/sheild

Wall thimble

Storm collar

Fire stop

970 4DT-HKA SV0SHK 4DHTK1

Wall strap/support/band

Horizontal termination kit (SD: Basic Kit,

SEL: Kit A, SC: Standard Kit)

911

943

943S

4DT-AJ

4DT-AF6

4DT-AF12

SV4LA12

4D12A

4DF

4DF12

11” to 14 ⅝” pipe, adjustable

4” to 10” pipe , adjustable

1½” to 12” pipe , adjustable

Flashing, 0/12 to 6/12 roof pitch

943F

980

991

984

985

978

971

4DT-VC

4DT-HVC

4DT-HC

4DT-HHC

4DT-VKC

4DT-HKB

SV4FA

SV4FB

SV4F

SV4CGV

SV4CHC

SV0FAK

SV0SHK2

4DVC

4DHC

4DVTK

4DHTK2

Flashing, 7/12 to 12/12 roof pitch

Flashing, 1/12 to 7/12 roof pitch

Flashing, 8/12 to 12/12 roof pitch

Flat flashing

Vertical termination

High wind vertical termination

Horizontal square termination

High wind horizontal termination

Vertical termination kit

Horizontal termination kit

(SD: Kit A, SEL: Kit B, SC: Kit)

Initial Installation

QUALIFIED INSTALLERS ONLY

v ent

c onFiguRations anD

R estRictoR

s ettings

:

Figures 23 & 24 show the range of venting options, they show possible vent configurations if the unit is top vented (see Figure 23) or rear vented (see Figure 24), for vertical and horizontal terminations, any layout that remains within the shaded area is acceptable. Having the fewest number of elbows is ideal, as they tend to disrupt air movement. Using 45˚ elbows is preferable to using 90˚ elbows. Also, a shorter vent system will perform better than a longer one.

The ENVIRO WESTPORT has been designed with a built in restrictor plate. The restrictor is designed to enhance flame appearance when installing this unit with vertical chimneys as well as installations with longer horizontal vent applications. It does this by controlling the amount of air moving through the vent pipe.

Figure 23 shows the vent restrictor position required, relative to the length of vent pipe. Longer vertical vent lengths necessitate greater restriction; position 1 is open and position 5 is maximum restriction

(refer to Figure 22). To avoid injury, it is best to make this adjustment when the fireplace is cool or use welder’s gloves or oven mitts.

View showing fully closed restrictor plate

5

4

3

2

1

View showing fully open restrictor plate

5

4

3

2

1

Figure 22: Restrictor plate settings.

32’

(9.75 m)

30’

(9.14 m)

25’

(7.62 m)

20’

(6.10 m)

15’

(4.57 m)

10’

(3.05 m)

Note: 0,0 in Figures 23 & 24 represent the outlet of the flue collar elbow.

2

1

5

4

3 t c i r o r t s

R e n t

V e o n i t s i s

P o

To access vent restrictor remove the valve cover plate from the right rear corner of the unit by undoing the two fastening screws.

Loosen the ¼” hex head screw and adjust to the correct setting.

Slide the hex head screw to the next setting and re-tighten the screw to secure in place.

The numbers in this chart represent the actual vent restrictor settings. Although the numbers do not appear on the unit use this as a guide to follow.

Wait for unit to warm up to operating temperature to ensure proper and clean burning unit.

5’

(1.52 m)

5’

(1.52 m)

If top vented the vent pipe must rise a minimum of

2’ (0.61 m) straight off the top of the unit.

0’

(0 m)

0’

(0 m)

5’

(1.52 m)

10’

(3.05 m)

15’

(4.57 m)

18’

(5.49 m)

Figure 23. Possible Vent Configurations for Top Vented;

Vertical and Horizontal Terminations.

Above 2’ (0.61 m) vertical the rear vent chart and the top vent chart are the same.

0’

(0 m)

0’

(0 m)

2’ max

A 36” snorkel must be used if unit’s vent termination is in the dark grey shaded area.

(0.61 m)

5’

(1.52 m)

Figure 24. Possible Vent Configurations for Rear

Vented; Vertical and Horizontal Terminations.

19

20

Initial Installation

QUALIFIED INSTALLERS ONLY

h oRizontaL

i nstaLLation

:

1. Set the appliance in the desired location. Check to determine if wall studs or roof rafters are in the way when the venting system is attached. If this is the case, you may want to adjust the location of the appliance.

2. Direct vent pipe and fittings are designed with special twist-lock connections. Assemble the desired combination of black pipe and elbows to the appliance adapter with pipe seams oriented towards the wall or floor, as much out of view as possible.

Place a bead of Mil-Pac on the outer edge of the inner exhaust pipe

(non-flared end). Place a bead of high temperature silicone on the male edge of the outer pipe. Push the pipe sections completely together, then twist-lock one section clockwise approximately ¼ turn, until the two sections are fully locked. The female locking lugs will not be visible from the outside, on black pipe. They may be located by examining the inside of the female ends as shown in

Figure 25.

Sealant

Locking

Lugs

Male

Locking

Lugs

Notes:

(a) Twist-lock procedure: four (4) indentations, located on the female end of the pipes and fittings, are designed to slide straight onto the male ends of adjacent pipes and fittings, by orienting the four pipe indentations so they match and slide into the four entry slots on the male end.

(b) Horizontal runs of vent pipe must be supported every 36” (915mm).

Wall straps are available for this purpose, also when running horizontal pipe minimum clearances to combustibles must be maintained;

2” (51mm) at top, 1½” (38mm) at sides, 1½” (38mm) at bottom.

Figure 25: Twist-Lock Connection

3. With the pipe attached to the stove in the correct location, mark the wall for a 10” (25.4cm) x 10” (25.4 cm) square hole (refer to Figure

26). The center of the square hole should match the center line of the horizontal pipe. Cut and frame the 10” (25.4cm) x 10” (25.4cm) hole in the exterior wall where the vent will be terminated. Refer to

Figure 18. If the wall being penetrated is constructed of non-combustible material i.e. masonry or concrete, a 7”

(17.8cm) hole is acceptable.

1

1

/

4

"

(3.2cm)

Fold strap here

4. Position the horizontal vent termination in the center of the 10” (25.4cm) x 10”

(25.4cm) hole, and attach to the exterior wall with the four screws provided.

Before attaching the vent termination to the exterior

Sheet metal screws

Figure 26: Wall Framing Hole for

Horizontal Installation.

Woodscrews

Wall Thimble

Strap

Figure 27: Installing Decorative Wall Thimble.

Initial Installation

QUALIFIED INSTALLERS ONLY wall, run a bead of non-hardening mastic around the edges, so as to make a seal between the termination and the wall. The arrow on the vent termination should be pointing up, insure that the proper clearances to combustible materials are maintained.

5. Before connecting the horizontal run of the vent pipe to the vent termination, slide the black decorative wall thimble cover over the vent pipe.

6. Slide the appliance and vent assembly towards the wall, carefully inserting the vent pipe into the cap assembly. It is important that the vent pipe extend into the vent cap a sufficient distance with a minimum of 1¼” (3.2cm) overlap. Secure the connection between the vent cap pipe and the vent cap by attaching the two sheet metal straps extending from the vent cap assembly into the outer wall of the vent pipe. Use the two sheet metal screws provided to connect the straps to the vent pipe. Bend any remaining portion of the sheet metal straps back towards the vent cap, so the decorative wall thimble will conceal it (see left image in Figure 27).

7. Slide the decorative wall thimble up to the wall surface and attach with the screws provided. Apply decorative brass or chrome trim if desired (see right image in Figure 27).

NOTES:

(a) The four (4) wood screws provided should be replaced with the appropriate fasteners for stucco, brick, concrete, or other types of siding.

(b) For buildings with vinyl siding, a vinyl siding standoff, should be installed between the vent cap and the exterior wall (see Figure 28). Attach the vinyl siding standoff to the horizontal termination. The vinyl siding standoff prevents excessive heat from possibly melting the vinyl siding material. Note that the horizontal vent termination bolts onto the flat portion of the vinyl siding standoff (shaded area in Figure

28), so that an air space will exist between the wall and the vent termination.

(c) The horizontal run of vent pipe must be level and should have a ¼ inch rise for every one

foot of run towards the termination. Never allow the vent to run downward. This could cause high temperature and may present the possibility of a fire.

(d) The location of the horizontal vent termination on the exterior wall must not be easily blocked or obstructed. Refer to i nitial

i nStallation

- v ent

c onfiGurationS and

r eStrictor

S ettinGS

.

(e) When installing a vent pipe in a chase the minimum clearance to combustibles is 2” (51 mm).

(f) Maintain manufacturer’s clearances to combustibles with venting.

Cut vinyl siding away to fit standoff

Nut (x4) required

Wood screw (x4)

Bolt (x4) required

W ood screws (x4)

Figure 28: Installing Vent Cap with Vinyl Siding

Stand-Off.

Figure 29: Installing Horizontal Vent

Termination.

21

22

Initial Installation

QUALIFIED INSTALLERS ONLY

v eRticaL

i nstaLLation

:

1. Check the instructions for required clearances (air spaces) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, or other nearby combustible surfaces. Do not pack air spaces with insulation.

2. Set the gas appliance in the desired location. Drop a plumb bob down from the ceiling to the position of the appliance flue exit, and mark the location where the vent will penetrate the ceiling. Drill a small hole at this point. Next, drop a plumb bob from the roof to the hole previously drilled in the ceiling, mark the spot where the vent will penetrate the roof. Determine if ceiling joists, roof rafters, or other framing will obstruct the venting system. You may wish to relocate the appliance, or to offset, to avoid cutting load bearing members.

3. To install the Round Support Box/Wall Thimble in a flat ceiling, cut a 10” square hole in the ceiling, centered in the hole drilled in Step 2. Frame the hole as shown in Figure 30.

4. Assemble the desired lengths of black pipe and elbows necessary to reach from the appliance adapter up through the Round Support Box.

Insure that all pipe and elbow connections are in their fully twist-locked position.

Framing

Ceiling Joist

5. Cut hole in the roof centered on the small hole placed in the roof from Step 2. The hole should be of sufficient size to meet minimum requirements for Clearance to Combustibles, as specified. Continue to assemble lengths of pipe and elbows necessary to reach from the ceiling support box up through the roof line. Galvanized pipe and elbows may be utilized in the attic, as well as above the roof line. The galvanized finish is desirable above the roof line, due to the higher corrosion resistance.

Elbow Strap

6. Once the pipe sections have been joined, and run up through the hole in the roof, slip an elbow strap over the exposed sections, bend the support straps outwards, and push the elbow strap down to the roof level, as shown in Figure 31. Tighten the clamp around the pipe section.

Use a level to make sure the pipe is truly vertical. With roofing nails, secure the support straps to the roof. Seal the nails holes heads with non-hardening mastic. Trim the excess length of

Figure 30: Wall Framing for Hole for Vertical

Installation.

Vertical

Termination

Storm Collar

Flashing

Roofing nails

10” (25.4cm) x 10” (25.4cm) inside framing

1 1 /

2

” (4cm) long wood screw (x4)

Figure 31: Vertical Vent Termination Installation.

Initial Installation

QUALIFIED INSTALLERS ONLY the support straps that extend out beyond the edge of the flashing.

7. Slip the flashing over the pipe section protruding through the roof. Secure the base of the flashing to the roof with roofing nails. Use a non-hardening sealant between the uphill edge of the flashing and the roof. Insure the roofing material overlaps the top edge of the flashing as shown in Figure 30. Verify that you have at least the minimum clearance to combustibles at the roof line.

8. Continue to add pipe sections until the height of the vent cap meets the minimum code requirements.

Refer to Figure 32 and Table 6. Note that for steep roof pitches, the vent height must be increased. In high wind conditions, nearby trees, adjoining roof lines, steep pitched roofs, and other similar factors can result in poor draft, or down drafting. In these cases, increasing the vent height may solve the problem.

9. Slip the storm collar over the pipe, and push it down to the top of the roof flashing as shown in Figure

31. Use the non-hardening sealant around the joint between the pipe and the storm collar.

10. Twist-lock the vent cap.

Table 6: Minimum ‘H’ for Figure 32.

Roof Pitch Minimum Height

Dimension ‘H’ obtained from table below.

Figure 32: Height of Vertical Termination;

Reference Table 6.

H

Flat to 7/12

Over 7/12 to 8/12

Over 8/12 to 9/12

Over 9/12 to 10/12

Over 10/12 to 11/12

Over 11/12 to 12/12

Over 12/12 to 14/12

Over 14/12 to 16/12

Over 16/12 to 18/12

Over 18/12 to 20/12

Feet

1

1.5

2

2.5

3.25

4

5

6

7

7.5

Over 20/12 to 21/12 8 2.44

NOTES:

(a) If an offset is necessary in the attic to avoid obstructions, it is important to support the vent pipe every 3 feet (91 cm), to avoid excessive stress on the elbows, and possible separation. Wall straps are available for this purpose (see Figure 33).

(b) When ever possible, use 45° degree elbows instead of 90° degree elbows. The 45° degree elbow offers less restriction to the flow of flue gases and intake air.

(c) For multi story installations. A ceiling firestop is required at the second floor, and any subsequent floors (see Figure 34). The opening should be framed to 10” (25.4 cm) x 10” (25.4 cm) inside dimensions, in the same manner as shown in Figure 30.

(d) Any occupied areas above the first floor, including closets and storage spaces, which the vertical vent passes through, must be enclosed. The enclosure may be framed and sheet rocked with standard building materials. However consult the appliance manufactures installation instructions for the minimum allowable clearance between the outside of the vent pipe, and the combustible surfaces of the enclosure. Do not fill any required air spaces with insulation.

Meters

0.3

0.46

0.61

0.76

0.99

1.22

1.52

1.83

2.13

2.29

23

Initial Installation

QUALIFIED INSTALLERS ONLY

Nails

Ceiling firestop plumber’s tape connected to wall strap

Wall strap

45° elbows (x2)

Ceiling

Use clearances to as defined by appliance and vent pipe manufacturers.

Second floor

Figure 34: Multi-Story Vent Pipe Installation.

24

Figure 33: Use of Wall Straps.

c atheDRaL

c eiLing

i nstaLLation

:

1. Follow installation steps 1 & 2 under i nitial i nStallation

- v ertical

i nStallation

.

2. Using the plumb bob, mark the centerline of the venting system on the ceiling and drill a small hole through the ceiling and roof at this point. From the roof, locate the drill hole and mark the outline of the “Cathedral Ceiling

Support Box”.

3. Remove shingles or other roof coverings as necessary to cut the rectangular hole for the

“Support Box”. Cut the hole ⅛” larger than the “Support Box” outline.

4. Lower the “Support Box” through the hole in the roof until the bottom of the “Support Box” protrudes at least 2 inches (5 cm) below the ceiling. Align the “Support Box” both vertically and horizontally with a level as shown in

Figure 35. Temporarily tack the “Support Box” in the place through the inside walls and into the roof sheathing.

Figure 35: Cathedral Ceiling Support Box Leveling.

Initial Installation

QUALIFIED INSTALLERS ONLY

5. Using tin snips, cut the “Support Box” from the top corners down to the roof line, and fold the resulting flaps over the roof sheathing (Figure 36). Before nailing it in to the roof, run a bead of non-hardening mastic around the top edges of the “Support Box”, to make a seal between the box and the roof. Clean out any combustible material from the inside of the “Support Box”.

6. Complete the cathedral ceiling installation by following the same procedures outlined in Steps 4 through 9 for i nitial i nStallation

- v ertical

i nStallation

.

Figure 36: Cathedral Ceiling Support Box

Installation.

c oRneR

i nstaLLations

:

Do not interfere with the structural integrity of the walls.

When rear venting if a 90° bend is used the maximum horizontal vent that can be used is 6” (152mm) and if a 45° bend is used the maximum horizontal vent that can be used is 12” (305mm). For installations with a 36” (915 mm) snorkel refer to Figure 37 and i nitial

i nStallation

- v ent

c onfiGurationS and

r eStrictor

S ettinGS

. For other corner installations refer to Figure 38 and i nitial

i nStallation

- v ent

c onfiGurationS and r eStrictor

S ettinGS

.

36” (915 mm)

Snorkel

Inside Wall

Outside Wall

21/2”

(67 mm)

Outside Wall

21/2”

(67 mm)

Outside Wall

Figure 37: Corner installation rear vented with snorkel.

Figure 38: Corner installation top vented.

25

Initial Installation

v enting into a

c

Lass

‘a’ c himney

:

QUALIFIED INSTALLERS ONLY

This model is also certified and tested to vent into CLASS ‘A’ wood stove chimneys.

Place the freestanding direct vent appliance in the desired location.

Use a conversion kit from Simpson Duravent (931, 932, or 933), or Security Chimney (SV4CCK1, SV4CCK2, or

SV4CCK1). Which kit is used will depending on the inner diameter of the CLASS ‘A’ chimney that this appliance is to be vented into.

Place a bead of high temperature silicone or mil-pac at each connection to ensure a tight seal.

NOTE: An approved 4” (10 cm) diameter flex liner must be used in the application.

NOTE: Use Simpson Dura Vent from the top of the appliance until this vent reaches the CLASS ‘A’ chimney.

Install the retro adapter to the top section of GS direct vent pipe and install the flex liner to the retro adapter.

Fully line the CLASS ‘A’ chimney with a minimum 4” (10 cm) flex liner to the top of the CLASS ‘A’ chimney.

Place a bead of high temperature silicone to the Simpson

Cap adapter and securely attach the flex liner to the adapter.

Secure the cap adapter to the CLASS ‘A’ chimney ensuring an airtight seal.

Install the vertical termination cap.

Light the unit and ensure proper operation.

THE USE OF ANY EXISTING CHIMNEY AS AN AIR INTAKE

IS NOT COVERED UNDER THE ANSI Z21.88-2002 CSA

2.33a-2002 TEST METHODS AND THE RESULTING ITS/

WH PRODUCT CERTIFICATION. THE CODE AUTHORITY

HAVING JURISDICTION MUST BE CONSULTED PRIOR

TO PROCEEDING WITH THIS INSTALLATION METHOD.

Simpson GS

Dura Vent Cap

Cap Adapter

Class ‘A’

Chimney

Roof Flashing

4” (10cm) Flex Liner

Inside Class ‘A’ Chimney

Ceiling Rafters

GS Simpson Dura

Vent Pipe 4” x 6

5

/

8

Figure 39: Assembly of Venting into a Class ‘A’

Chimney.

26

c onveRting

t oP

v enteD into

R eaR

v enteD

:

This unit has been shipped as a 30,000 Btu/hr top-vented freestanding unit. This unit can be converted to a rear vented unit with a 36” (915 mm) snorkel for some installation applications.To convert this unit to a rear vented model you must remove the flue pipe adapter and turn to the rear vent position. See sections i nitial

i nStallation

- i nStallation of

r ear

v ented

a

PPliance

.

1. Carefully remove the trivet and the stovetop. Place on a soft surface as not to damage the porcelain finishes.

Initial Installation

QUALIFIED INSTALLERS ONLY

2. Remove the four (4) ¼” screws that hold the flue collar elbow to the unit body (see Figure 40).

3. Carefully remove the elbow being sure not to damage the gasket that is glued to the flue collar elbow, it seals the flue to the firebox.

4. Turn the elbow to the rear vent position and re-fasten with the screws removed in step 2 (see Figure

41).

Firebox Top

Flue Collar

Adapter

Undo four ¼" screws that hold flue collar elbow to unit.

Figure 40: Step 3 of Converting Top Vented into

Rear Vented.

Figure 41: Step 4 of Converting Top

Vented into Rear Vented.

i nstaLLation oF

R eaR

v enteD

a

PPLiance

:

Place the unit into position.

Attach a small section of pipe on the unit and mark exterior wall where vent would pass through the wall.

Cut a 10” (25.4 cm) minimum hole in the wall to maintain clearances to combustibles. Frame hole as shown in Figure 26.

Install a wall thimble.

Install interior finished collar.

Install the vent section through the wall.

THIS UNIT MUST BE VENTED WITH A 36” (91 cm) SNORKEL KIT

IF UNIT IS RATED FOR 30,000 Btu/hr NG and 26,000 Btu/hr LP.

Seal around the vent terminal to the structure using a non hardening mastic.

Also refer to i nitial

i nStallation

- v ent

c onfiGurationS and

r eStrictor

S ettinGS

.

Minimum vent terminal 36"

(91.4cm) high snorkel kit.

Siding

Exterior wall

Drywall

Wall thimble

Inside finished collar

Vent pipe

Figure 42: Installation for Rear Vented;

30,000 Btu/hr.

27

28

Initial Installation

QUALIFIED INSTALLERS ONLY

i nstaLLation oF

t oP

v enteD

; h oRizontaL

t eRmination

:

This is the most common type of installation style.

Set the unit in place.

Install a minimum 24” (61 cm) vertical chimney.

Install a 90° elbow, and mark the exterior wall where the vent would pass through.

Cut a 10” (25.4 cm) minimum hole in the wall to maintain clearances to combustibles around vent pipe. Frame hole if as shown in Figure

26.

Install wall thimble.

Install interior finished collar

Install the vent section through the wall and then install the vent termination.

Seal around the termination using a non hardening mastic.

CORNER INSTALLATION:

This type of installation can be used in a corner installation. If a

90° elbow is used in the horizontal plane, 36” (91.4 cm) must be subtracted from the allowable horizontal run shown in Figure 23.

Termination

Inside finished collar

Wall thimble

Vent pipe

Drywall

Exterior wall

Siding

Figure 43: Installation for Top

Vented; Horizontal Termination.

i nstaLLation oF

t oP

v enteD

; v eRticaL

t eRmination

:

Place the unit in place.

Drop a plumb bob from the ceiling to the center point of the flue outlet.

Cut a 10” (25.4 cm) hole in the ceiling and the roof. Refer to

Figure 30.

Install the ceiling support and insulation guard.

Install the roof flashing. Ensure that the roof flashing is installed under the roofing material so that a watertight seal is created.

Install the flue pipe from the top of the unit through the roof.

Ensure that all flue pipe and unit maintain required clearances to combustibles.

CORNER INSTALLATION:

This type of installation can be used in a corner installation.

If a 90° elbow is used in the horizontal plane, 36” (91.4 cm) must be subtracted from the allowable horizontal run shown in Figure 23.

Vent cap

Roof flashing

Roof truss

Insulation gaurd

Ceiling support

Inside finished collar

Flue pipe

Figure 44: Installation for Top Vented;

Vertical Termination.

Initial Installation

QUALIFIED INSTALLERS ONLY

F

ReestanDing

D

RaFthooD

a

DaPtoR

- 50-841:

This Drafthood Adaptor is a complete assembly and is ready to fit onto your Westport in a vertical vent application only. With the Drafthood Adaptor correctly installed and wired to the gas control valve. Your

Direct Vent Fireplace can be vented like a B-Vent Fireplace.

INSTALLATION:

WARNING: This Freestanding Drafthood Adaptor must be fitted by a qualified service technician.

1. Remove the Drafthood Adaptor from the packaging. Ensure the unit and wire harness are undamaged. If there is damage contact your dealer, distributor, or courier company before starting this installation.

2. Install the adaptor so the wires exit to the rear of the fireplace. Slide the Drafthood Adaptor over the outlet pipe of the fireplace until the bottom of the adaptor collar stops on the top of the outlet. The

Drafthood Adaptor must be safely secured to the vent flanges with either self-tapping screws and/or high temperature sealant.

WARNING: During the fitting of the Drafthood Adaptor, ensure that the wires are not pinched between the adaptor and the collar and/or flue outlet. Ensure that the opening of the Drafthood Adaptor is not blocked or obstructed.

3. Being careful not to run any wiring tight across metal edges; connect them to the valve and “ON/OFF” switch (refer to Figure 45).

4. Adjust the restrictor plate to position 2.5 of 5. See the vent restrictor settings in the instruction manual.

Optional remote control receiver

ON / OFF / Remote thermostat switch

Drafthood adaptor

300 o

F (149 manual reset temperature sensor o

C)

5. Adjust the embers on the burner so they don’t cover the burner ports.

Purple

Grey

Blue

Grey

WIRING DIAGRAM:

Grey

The fireplace connections are labelled in Figure 45.

When installing the Drafthood

Adaptor onto a fireplace fitted with an optional wall switch or an optional thermostat, remove one wire from the switch to the gas valve and connect the

Drafthood Adaptor harness as shown in Figure 45.

Optional wall switch

Optional

Thermostat

Valve

Figure 45: Wiring Diagram for Electrical Connection.

GENERAL VENTING INFORMATION:

Canadian Installations

The venting system must be installed in accordance with the current CSA B149 installation code and/or local codes having jurisdiction.

U.S.A. Installations

The venting system must be installed in accordance with the current National Fuel Gas Code, ANSI

Z223.1, and/or local codes having jurisdiction.

29

30

Initial Installation

The minimum clearance to combustibles is 6” (150 mm) when using single wall venting and 1” (25 mm) when using “B-vent” venting.

We strongly recommend installing an approved chimney liner in an existing brick chimney. This will maximize the potential draft of the chimney and lessen the effects of slow chimney start-up.

VENTING OF A FIREPLACE FITTED WITH THE DRAFTHOOD ADAPTOR:

Note: Please refer to the chimney manufacturer’s installation instructions prior to commencing the installation.

This unit may be vented to an existing masonry chimney, or where no masonry chimney is available, an approved “B-vent” chimney, or any other approved constructed chimney/vent system (see Figure 46 &

47).

In either case, the fireplace may be connected to the chimney/vent using a 4” (10 cm) single wall vent connector.

6" (15cm) optional decorative cover

When an existing masonry chimney is utilized for the venting, we recommend the vent connector be connected to an approved 4” (10 cm) diameter flue liner running the full height of the chimney. In many jurisdictions this flue liner may be mandatory.

4" (10cm) vent

If 4” (10 cm) single wall vent is used, a minimum of

6” (15 cm) must be maintained between the vent connector and any combustibles.

If 4” (10 cm) “B-vent” is used a minimum of 1” (25

Figure 46: Unit top venting styles.

mm) must be maintained between the vent connector and any combustibles.

CAUTION: A minimum vent height of 12’ (3.6 m) from the floor is required to effectively vent this fireplace.

SPILLAGE TEST:

A spillage test must be performed prior to leaving the installed fireplace with the customer. Perform this test in the following manner:

Check vent draft at the top row of opening.

Figure 47: Unit rear venting style.

1. Close all windows and doors in the room.

2. Start all exhaust fans in the house and the furnace blower.

3. Light the fireplace and set to maximum flame adjustment.

4. After a minimum of 10 minutes operation, test the chimney draft with a smoke match at the top row of the pattern to confirm that there is adequate draft or ‘pull’ at the openings around the body of the Drafthood

Adaptor, as shown in Figure 48.

Figure 48: Draft test place.

Initial Installation

AUTOMATIC SAFETY SHUT DOWN:

If the spill switch is activated and shuts off the main burner the following procedure should be followed.

• Is the pilot flame still on? If not, the reason for the fireplace shut down is not the spill switch.

• Turn off the pilot flame and turn off all controls. Let fireplace to cool down.

• Check for blockages or restrictions in the flue and venting components.

• Restart the fireplace and check for vent draft as described earlier.

• Operate the fireplace in a normal manner.

• If the main burner shuts down again after a period of operation, turn off the fireplace and contact your service technician.

SPILL SWITCH REPLACEMENT:

Use the following instructions to replace the

Safety Spill Switch.

1. Turn the unit off and allow it to cool.

2. Disconnect the spill switch wires from the valve and on/off/remote rocker switch wire

(see Figure 45).

3. Remove the four mounting screws holding the spill switch bracket and remove the bracket (see Figure 49).

4. Remove and replace the spill switch with a

50-885 Spill Switch Assembly using a T-20 torx type driver.

5. Follow the reverse of the previous steps.

Figure 49: Spill switch installation.

OPTIONAL FINISHING:

In installations where the flue connector is running from the drafthood into a non-combustible chimney the following optional finishing technique can be used.

CAUTION: Installations where the flue connector or venting connects to, or passes through, combustible walls or ceilings, the inner vent components must be ‘B-vent’. It is not allowable in these applications to use single wall inner vent components.

For decorative purposes a 6” (15 cm) single wall black stove pipe may be installed over the 4” (10 cm) single wall or ‘B-Vent’.

Note: The use of these components is for aesthetic purposes only and does not effect the fact that the fireplace, when fitted with the Drafthood Adaptor, is a Natural Vent appliance and therefore draws air in through the Drafthood Adaptor intake ports.

31

32

Initial Installation

g as

L ine

c onnection anD

t esting

:

QUALIFIED INSTALLERS ONLY

WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to this appliance.

GAS LINE CONNECTION

Manifold

Pressure Tap

Inlet

Pressure Tap

• This stove is equipped with a certified flexible pipe located on the right side of the unit terminating in a ⅜” male NPT fitting. Consult your local authorities codes or the CAN/CGA B 149 (1 or 2) installation code in Canada, or in the USA gas installations follow either local codes or the current edition of the National Fuel Gas Code ANSI

Z223.1.

T

O

L I

P

I

H

LO

OUT

OF

F

P

O

N

IN

• The efficiency rating of this appliance is a product thermal efficiency rating determined under continuous operating conditions and was determined independently of any installed system.

Pilot Adjustment

Screw

Hi/Low

Knob

Gas Control

Knob

Figure 50: Fully Labeled Gas Valve.

The appliance and its shutoff valves must be disconnected from the gas supply piping system during any pressure testing where the pressure exceeds ½ PSIG (3.45 KPa) or damage will occur to the valve.

The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than

½ psig (3.45 KPa).

Always check for gas leaks with a soap and water solution after completing the required pressure test.

TO TEST VALVE PRESSURES

The pressure taps are located on the left side of the valve

• Turn set screw 1 turn counter clockwise to loosen,

• Place

5

/

16

” (8 mm) I.D. hose over pressure tap system.

• Check pressures using a manometer.

• When finished, release pressure, remove hose & tighten set screw.

Table 7: Pressure and BTU Information.

Main Burner

Manifold Pressure

Min. Manifold Pressure

Natural Gas

#39 DMS

3.8” W.C. / 0.95KPa

1.1” W.C. / 0.27KPa

Propane

#53 DMS

11.0” W.C. / 2.7KPa

2.7” W.C. / 0.67KPa

Max Supply Pressure

Min. Supply Pressure

7.0” W.C. / 1.74KPa

5” W.C. / 1.24KPa

13.0” W.C. / 3.28KPa

12.0” W.C. / 2.98KPa

Max BTU/hr Input

30,000 BTU/hr (8.80KW) 26,500 BTU/hr (7.76KW)

Min. BTU/hr Input 17,000 BTU/hr (4.98 KW)

14,000 BTU/hr (4.10KW)

Venturi Setting

1

/

16

” min.

3

/

16

” min.

NEVER USE AN OPEN FLAME FOR LEAK TESTING.

Initial Installation

QUALIFIED INSTALLERS ONLY

e

LectRicaL

R equiRements

F oR

g as

v aLve anD

o

PtionaL

b

LoweR

:

The ENVIRO WESTPORT will operate without electrical power. This model has a millivolt gas control, which uses the pilot flame to generate enough electricity to operate the main burners. The appliance when equipped with an optional blower must be electrically connected and grounded in accordance with local codes or in the absence of local codes, with the current CSA C22.1 CANADIAN ELECTRICAL CODE

Part 1, SAFETY STANDARDS FOR ELECTRICAL INSTALLATIONS, OR THE NATIONAL ELECTRICAL CODE

ANSI / NFPA 70 in the U.S.

ON/OFF/Remote

Thermostat Switch

70 ° F

Optional

Remote

Control

Blue

Thermocouple

Thermopile

ON

OF

F

Purple

Manifold

Pressure Tap

Inlet

Pressure

Tap

Gas Control

Valve

Grey

70 ° F

UP

DOWN

COOL / HEAT

PROGRAM

Optional

Wall Switch

Optional

Thermostat

Pilot Adjustment

Screw

Figure 51: Gas Control Valve and Optional Thermostat Wiring.

Table 8. Recommended Thermostat

Wire Size.

Wire Size

14 gauge

Max. Length

100 ft (30.48 m)

16 gauge

18 gauge

20 gauge

22 gauge

60 ft (18.29 m)

40 ft (12.00 m)

25 ft (7.62 m)

18 ft (5.49 m)

White

Fan

White

Black

Black

Fan temperature sensor

Power

Supply

Fan controller

Figure 52. Wiring Diagram For Fan Control.

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

WARNING: Electrical grounding instructions. This appliance is equipped with a three-prong (grounding) plug for your protection against shock hazard, and must be plugged directly into a properly grounded three-prong outlet.

DO NOT cut or remove the grounding prong from this plug.

33

34

Secondary Installation

i nstaLLation oF

o

PtionaL

b

LoweR

:

1. Remove the pre-assembled blower from the packaging. Inspect the blower for damage. If damage is noticed call your dealer, distributor or courier company and have components replaced.

Control panel

(Fan control location)

2. Ensure the temperature sensor will touch the unit when mounted. If it does not touch, adjust the sensor so it does.

2. Place the fan assembly behind the unit and secure with the three screws provided, (as shown in Figure 53).

Screw hole

Valve cover

Fan assembly

3. Open the gas valve cover. Carefully cut the decal portion on the control panel and install the fan control switch in this location. See Figure 46 for wiring of optional blower.

4. Plug the fan assembly into the wall outlet and turn the unit on to ensure fan operation.

Figure 53: Optional Blower (Fan) Installation.

i nstaLLation oF

L og

s et anD

e mbeRs

:

The placement of the logs is not arbitrary. If they are positioned incorrectly, the flames can be “pinched” and will not burn correctly. The burner come with four (4) locator pins, and the right log has two (2) ledges which make alignment easier. Using the pictures provided, carefully set the logs in place.

NOTE: The logs are fragile and should be handled gently.

CAUTION: Use only the type of ember material supplied with this appliance. Due to the irregular size of the ember material there may be more than required. The use of other foreign materials on the burners may create dangerous conditions.

If over time, through cleaning and servicing, these embers require replacement, contact the nearest

ENVIRO dealer for replacement embers.

Figure 54: Step 1 of Log Placement.

Ledge for Left Rear Log

Placement Pin for Left Rear Log

Figure 55: Step 2 of Log Placement.

Secondary Installation

1. Carefully remove logs from box. Check to ensure there is no damage. It is very important to install all logs in their proper position to insure safe, optimum operating conditions.

Placement Pin for Center Log

2. Place the log set into the firebox. Locate each log by seating it down onto the burner tray support pins. Follow Figures

48 to 54 proper log placement.

Figure 56: Step 3 of Log Placement.

3. A bag of ceramic fiber embers and rock wool embers is provided gently remove the ember material from the plastic bag. Spread a layer loosely in a random manner across the burner tray. Do not allow any embers to rest against pilot assembly. (See diagram provided for proper ember placement.)

DO NOT pack this ember material as this could create an unsafe condition, leave embers loose.

Placement for

Front Left Log

4. Upon the first light up, watch for ignition to ALL burner ports.

If a long delay is noted: First, wait for the appliance to cool down.

• Open the front door of the appliance.

• Check to carefully reposition the embers making sure that burner ports are not plugged solid or blocked.

Figure 57: Step 4 of Log Placement.

Figure 58: Complete Log Placement.

Ledge for

Center Log

35

Secondary Installation

Important note: When the unit is turned on for the first time, It should be turned onto high without the fan on for the first four (4) hours. This will cure the paint, logs, gasket material and the other products used in the manufacturing process. It is advisable to open a window or door, as the unit will start to smoke and can irritate some people. After the unit has gone through the first burn turn the unit off including the pilot, let the unit get cold then remove the glass door and clean it with a good gas fireplace glass cleaner, available at your local ENVIRO dealer.

See M aintenance

a nd

S ervice

on how to remove door to clean glass.

Figure 59: Log Placement with Rock Wool.

Figure 60: Log Placement with Rock Wool & Embers.

36

Figure 61: Appliance Burning.

CAUTION: NEVER OPERATE THIS APPLIANCE WITH THE GLASS DOOR REMOVED.

i nstaLLation oF

P aneL

s et

:

Secondary Installation

Do not install when the unit is hot.

The brick panel set is fragile. Handle panels with care and avoid knocking them on the placement pins or any other object.

Figure 62: Brick panel bracket, slots shown.

1. Remove the two (2) screws from the rear of the baffle, use a ¼” socket or a flat head screwdriver. Place the provided brick bracket (Figure 62) at the rear of the baffle with the slots over the screw holes (see Figure 63).

Insert two (2) of the provided screws into the two (2) holes along the bottom of the baffle.

Figure 63: Top brick panel in place, screws shown.

Figure 65: Side brick panels in place.

Figure 64: Back brick panel in place.

2. Remove the two (2) screws from the front of the baffle. Slide the top brick panel into the bottom bracket and place the other brick bracket over the top of the panel and line up the slots on the bracket with the holes at the top of the baffle. Use two (2) of the provided screws to hold the bracket in place. Ensure the top panel is centered before tightening the four

(4) screws completely (refer to Figure 63).

3. Slide the bottom brick panel into place under/behind the top panel bracket, the notched side is to rest on the firebox bottom. The panel should rest flush with the back of the firebox (refer to Figure 64).

4. Slide each side brick panel into place along the sides of the firebox. The panels should rest flush with the back panel and the sides of the firebox (refer to

Figure 65).

37

38

Trouble Shooting

Problem

The main burner does not ignite when called for.

Spark will not light the pilot after repeatedly pressing the spark ignitor.

Pilot will not remain lit.

Possible Cause Solution

The gas valve may not be on.

• Check that the gas control knob is in the “ON” position.

Thermostat is not calling for heat.

• Adjust the thermostat several degrees above ambient temperature.

Problem with gas valve.

Defective piezo ignitor.

Broken spark electrode.

• Use a DC voltmeter to measure the voltage across the

TPTH and TP terminals. Main operator voltage: Open circuit ≥ 325mV Closed circuit ≥ 100mV

• If voltage is not present, check the control circuit for proper operation.

• If proper control system voltage is present, replace the gas control.

• Check connections to ignitor.

• If ignitor connections are good but no spark, replace ignitor.

• Check for broken ceramic insulation, replace electrode if broken.

Misaligned spark electrode.

Problem with thermocouple circuit.

• If spark is not arcing from electrode to pilot, loosen the screws on the pilot base adjust and tighten.

• Check for proper connection of the thermocouple to the rear of the valve. If loose, fully tighten.

• Check pilot for full flame impingement around thermocouple. If flame is too small, check gas pressure, adjust pilot rate screw, check pilot head for damage.

• Check thermocouple voltage at valve. It must be greater than 5 mV. If low, replace thermocouple.

Burners will not remain lit.

Flame lifting

Glass fogs up

Blue Flames

Flames are burning “dirty” or sooting

Remote control doesn’t work

Air in gas line (pilot dies while knob is depressed).

Problem with thermopile circuit.

Leak in vent pipe

Improper vent configuration

Terminal may be recirculating flue gases

• Check for leaks in vent connections.

• Check vent configuration with manual.

• Check to see if terminal is on correctly.

• May need to install high wind termination cap.

• Contact dealer.

Normal Condition: after the appliance warms up the glass will clear.

**Due to additives in gas, glass may get hazy during operation** Clean as needed.

Normal during start up: flames will yellow as the fireplace heats up.

Flame impingement

• Bleed line.

• Check gas line pressure.

• Contact dealer.

• Check gas line pressure .

• Check for flame impingement on thermopile. If low, see

“Pilot will not remain lit”.

• Check thermopile for minimum of 300 mV when burner is switched on.

• Check wiring to thermostat for breaks.

Problem with the remote

Problem with fireplace

• Check log positioning.

• Increase primary air by opening the venturi shutter and/ or by opening the vent restrictor.

See also “Burners will not remain lit.”

• One or more of the batteries are dead. See remote control instructions.

• The on/off switch is turned to OFF.

• The gas control valve is turned to PILOT or OFF.

• The pilot has gone out.

Parts List - Cast

4

4

4

4

4

4

4

3

4

3

3

3

3

3

3

2

3

2

2

2

2

2

2

1

2

Reference

Number

1

1

1

1

1

1

1

Part Description

Top Vent Insert Piece - Painted

Top Vent Insert Piece - Antique White

Top Vent Insert Piece - Diamond Black

Top Vent Insert Piece - Inferno Red

Top Vent Insert Piece - Pearl Grey

Top Vent Insert Piece - Wedgewood Blue

Top Vent Insert Piece - Westport Green

Top Vent Insert Piece - Antique Chestnut

Top Grate - Painted

Top Grate - Antique White

Top Grate - Diamond Black

Top Grate - Inferno Red

Top Grate - Pearl Grey

Top Grate - Wedgewood Blue

Top Grate - Westport Green

Top Grate - Antique Chestnut

Top Only (No Grate Or Vent Insert) - Painted

Top Only (No Grate Or Vent Insert) - Diamond Black

Top Only (No Grate Or Vent Insert) - Antique White

Top Only (No Grate Or Vent Insert) - Inferno Red

Top Only (No Grate Or Vent Insert) - Pearl Grey

Top Only (No Grate Or Vent Insert) - Wedgewood Blue

Top Only (No Grate Or Vent Insert) - Westport Green

Top Only (No Grate Or Vent Insert) - Antique Chestnut

Side Panel (Left) - Painted

Side Panel (Left) - Antique White

Side Panel (Left) - Diamond Black

Side Panel (Left) - Inferno Red

Side Panel (Left) - Pearl Grey

Side Panel (Left) - Wedgewood Blue

Side Panel (Left) - Westport Green

Side Panel (Left) - Antique Chestnut

Part Number

50-368

50-369

50-370

50-371

50-372

50-373

50-374

50-906

EGWP-504

EGWP-504AW

EGWP-504DB

EGWP-504IR

EGWP-504PG

EGWP-504WB

EGWP-504WG

50-871

EGWP-503

EGWP-503AW

EGWP-503DB

EGWP-503IR

EGWP-503PG

EGWP-503WB

EGWP-503WG

50-870

EGWP-502

EGWP-502AW

EGWP-502DB

EGWP-502IR

EGWP-502PG

EGWP-502WB

EGWP-502WG

50-869

39

40

Parts List - Cast

Reference

Number

8

8

8

8

8

8

8

8

7

7

7

7

7

7

7

7

6

6

6

6

6

6

6

6

5

5

5

5

5

5

5

5

Part Description

Side Panel (Right) - Painted

Side Panel (Right) - Antique White

Side Panel (Right) - Diamond Black

Side Panel (Right) - Inferno Red

Side Panel (Right) - Pearl Grey

Side Panel (Right) - Wedgewood Blue

Side Panel (Right) - Westport Green

Side Panel (Right) - Antique Chestnut

Cast Leg (Each) - Painted

Cast Leg (Each) - Antique White

Cast Leg (Each) - Diamond Black

Cast Leg (Each) - Inferno Red

Cast Leg (Each) - Pearl Grey

Cast Leg (Each) - Wedgewood Blue

Cast Leg (Each) - Westport Green

Cast Leg (Each) - Antique Chestnut

Ash Shelf - Painted

Ash Shelf - Antique White

Ash Shelf - Diamond Black

Ash Shelf - Inferno Red

Ash Shelf - Pearl Grey

Ash Shelf - Wedgewood Blue

Ash Shelf - Westport Green

Ash Shelf - Antique Chestnut

Cast Front Complete (Doors & Ash Shelf) - Painted

Cast Front Complete (Doors & Ash Shelf) - Antique White

Cast Front Complete (Doors & Ash Shelf)- Diamond Black

Cast Front Complete (Doors & Ash Shelf) - Inferno Red

Cast Front Complete (Doors & Ash Shelf) - Pearl Grey

Cast Front Complete (Doors & Ash Shelf)- Wedgewood Blue

Cast Front Complete (Doors & Ash Shelf)- Westport Green

Cast Front Complete (Doors & Ash Shelf) - Antique Chestnut

Part Number

EGWP-507

EGWP-507AW

EGWP-507DB

EGWP-507IR

EGWP-507PG

EGWP-507WB

EGWP-507WG

50-874

EGWP-506

EGWP-506AW

EGWP-506DB

EGWP-506IR

EGWP-506PG

EGWP-506WB

EGWP-506WG

50-873

EGWP-505

EGWP-505AW

EGWP-505DB

EGWP-505IR

EGWP-505PG

EGWP-505WB

EGWP-505WG

50-872

EGWP-508

50-375

50-376

50-377

50-378

50-379

50-380

50-875

Parts List - Cast

Reference

Number

Part Description

Top Complete (Top, Vent Insert, & Grate) - Painted

Top Complete (Top, Vent Insert, & Grate) - Antique White

Top Complete (Top, Vent Insert, & Grate) - Diamond Black

Top Complete (Top, Vent Insert, & Grate) - Inferno Red

Top Complete (Top, Vent Insert, & Grate) - Pearl Grey

Top Complete (Top, Vent Insert, & Grate) - Wedgewood Blue

Top Complete (Top, Vent Insert, & Grate) - Westport Green

Top Complete (Top, Vent Insert, & Grate) - Antique Chestnut

Complete Cast Body - Painted

Complete Cast Body - Antique White

Complete Cast Body - Diamond Black

Complete Cast Body - Inferno Red

Complete Cast Body - Pearl Grey

Complete Cast Body - Wedgewood Blue

Complete Cast Body - Westport Green

Complete Cast Body - Antique Chestnut

Part Number

EGWP-501

EGWP-501AW

EGWP-501DB

EGWP-501IR

EGWP-501PG

EGWP-501WB

EGWP-501WG

50-868

50-562

50-563

50-564

50-565

50-566

50-567

50-568

50-876

When using Forrest Paint for venting pipe use the following colour codes for the corresponding cast colour:

Antique White

Diamond Black

64EN7795

64E200

Inferno Red

Pearl Grey

Wedgewood Blue

Westport Green

Antique Chestnut

64DN8880

64EN7488

64EN6701

64EN6943

64E816

41

4

1

Parts Diagram - Cast

2

3

WESTPORT - Castings

January 2005

5

8

42

6

7

Parts List - Components

Reference

Number

9

10

11

11

11

11

11

12

13

13

14

14

14

14

15

16

17

18

Part Description

120° Ceramic Fan Temperature Sensor

S.I.T. Nova Valve Convertible

Thermocouple

Spark Electrode with Ignitor Cable

Thermopile

Pilot Orifice NG Threaded

Pilot Orifice LP Threaded

Pilot Gasket

S.I.T. Piezo Ignitor

Burner Switch

Fan Controller 115 V With Knob

Fan Controller Knob

Domestic Power Cord

HEYCO Strain Relief

DV Vent Kit With Coupler

Relief Door Gasket Only

Window Channel Tape

1 Piece Glass With Tape

Inner Door Only - Painted

Burner Control Assembly LP

Burner Control Assembly NG

Door Hinge Pin - Silver

Fireplace Screen

Shoulder Bolt, Hardened Bushing & Nut (Set of 2)

Levelling Bolts

Door Knob Clip

Door Latch Assembly - Nickel

Valve Mounting Bracket

Rear Shield

Rating Plate (Label)

Gas Valve Cover

Flue Connection

Part Number

EC-001

50-1421

EGWP-092

EGWP-099

EGWP-100

EGWP-510

EGWP-513

EF-124

30-013

30-029

30-033

30-047

30-048

30-049

30-050

30-051

EC-009

EC-011

EC-012

EC-019

EC-020

EC-021

EC-023

EC-026

EC-039A

EC-040

EC-042

EC-044

EC-061

EGWP-087

EGWP-089

EGWP-090

43

44

Reference

Number

19

20

21

22

23

24

25

26

27

28

29

Parts List - Components

Part Description

Inner Door Handles (2 per set)

Venturi Adjustment Rod

Firebox

Pan Burner Only

45° Elbow & Gasket

Fan Kit 180 C.F.M.

Door Knob - Brushed Nickel

Electronic Ignition Module Switch

Blank Orifice #73 - All Gas Models

Wiring Harness

Pressure Relief Door With Gasket, Rod & Brackets

Control Panel Decal

Inner Door Complete (With Glass & Handles)

Embers

4” Flex Coupler

Dual Convection Blower 115 V (No Mount)

Firebox Baffle

Valve Extension Rod With Knob (1 per set)

Electronic Ignition Module

Control Panel

Drafthood Adapter

Drafthood Adaptor Spill Switch Assembly (with

Wiring Harness)

Drafthood Adaptor Decorative Brass Ring

3 Flame Pilot Hood

Owner’s Manual

Brick Panel Set

Log Set With Embers - Complete

Convertion Kit from LG to NG Convertible

Convertion Kit from NG to LG Convertible

S.I.T. Valve Conversion Screw With O-Ring

S.I.T. Valve Conversion Screw Cap

Part Number

50-343

50-348

50-366

50-461

50-463

50-491

50-497

50-512

30-052

30-053

30-054

30-055

50-040

50-173

50-262

50-329

50-533

50-555

50-589

50-690

50-841

50-885

50-894

50-925

50-1033

50-1038

50-1041

50-1442

50-1443

50-1450

50-1451

10

27

15

16

17

13

Parts Diagram - Components

12

28

18

23

19

14

20

21

25

29

11

9

22

26

24

WESTPORT - Components

January 2005

45

Warranty for Enviro Gas Products

Sherwood Industries Ltd. (“Sherwood”) hereby warrants, subject to the terms and conditions herein set forth, this product against defects in material and workmanship during the specified warranty period starting from the date of original purchase at retail.

In the event of a defect of material or workmanship during the specified warranty period,

Sherwood reserves the right to make repairs or to assess the replacement of a defective product at Sherwood’s factory. The shipping costs are to be paid by the consumer.

All warranties by Sherwood are set forth herein and no claim shall be made against

Sherwood on any oral warranty or representation.

Conditions

ƒ

A completed warranty registration must be submitted to Sherwood within 90 days of original purchase via the online warranty registration page or via the mail-in warranty registration card provided. Have the installer fill in the installation data sheet in the back of the manual for warranty and future reference.

ƒ

This warranty applies only to the original owner in the original location from date of install.

ƒ

The unit must have been properly installed by a qualified technician or installer, and must meet all local and national building code requirements.

ƒ

The warranty does not cover removal and re-installation costs.

ƒ

Sherwood Industries Ltd. reserves the right to make changes without notice.

ƒ

Sherwood Industries Ltd. and its employees or representatives will not assume any damages, either directly or indirectly caused by improper usage, operation, installation, servicing or maintenance of this appliance.

ƒ

A proof of original purchase must be provided by you or the dealer including serial number.

Exclusions

An expanded list of exclusions is available at www.enviro.com/help/warranty.html

This warranty does not cover:

ƒ

Damage as a result of improper usage or abuse.

ƒ

Damage caused from over-firing due to incorrect setup or tampering.

ƒ

Damage caused by incorrect installation.

To the Dealer

ƒ

Provide name, address and telephone number of purchaser and date of purchase.

ƒ

Provide date of purchase. Name of installer and dealer. Serial number of the appliance. Nature of complaint, defects or malfunction, description and part # of any parts replaced.

ƒ

Pictures or return of damaged or defective product may be required.

To the Distributor

ƒ

Sign and verify that work and information are correct.

Sherwood Industries Ltd.

6782 Oldfield Road, Victoria, BC . Canada V8M 2A3

Online warranty registration: www.enviro.com/warranty/

46

Category

Parts 1

(unit serial number required)

Firebox Liner Panels

(excluding porcelain)

One Year Two Year

Ceramic

Limited Lifetime

(7yr)

Steel

Firebox

Heat Exchanger

Burner

Ceramic Logs 2

Ceramic Glass

3

Pedestal / Legs

(excluding finish)

Door Assembly

Surround Panels

(excluding finish)

Up to 5 years Exterior Panels

(excluding finish)

Electrical Components

Exterior Surface Finishing

4

Labour

1

Whereas warranty has expired, replacement parts will be warrantied for 90 days from part purchase date. Labour not included.

Unit serial number required.

2

Log set and panels excludes wear and tear or breakage caused by cleaning or service.

3

Glass is covered for thermal breakage. Photos of box, inside of door, and unit serial # must be supplied for breakage due to shipping.

4

Exterior Surface finishing covers plating, enamel or paint and excludes colour changes, chipping, and fingerprints.

Travel costs not included.

Jan 2013

Installation Data Sheet

The following information must be recorded by the installer for warranty purposes and future reference.

NAME OF OWNER:

_________________________________________

ADDRESS:

_________________________________________

_________________________________________

_________________________________________

PHONE:___________________________________

NAME OF DEALER:

_________________________________________

ADDRESS:

_________________________________________

_________________________________________

_________________________________________

PHONE:___________________________________

MODEL:___________________________________

SERIAL NUMBER:___________________________

DATE OF PURCHASE: _____________

(dd/mm/yyyy)

DATE OF INSTALLATION:___________

(dd/mm/yyyy)

NATURAL GAS (NAT)

PROPANE(LPG)

INLET GAS PRESSURE:_________in wc

MAIN BURNER ORIFICE:__________# DMS

PILOT ORIFICE #_________OR________in diam.

INSTALLER’S SIGNATURE:

_________________________________________

NAME OF INSTALLER:

_________________________________________

ADDRESS:

_________________________________________

_________________________________________

_________________________________________

PHONE:___________________________________

MANUFACTURED BY:

SHERWOOD INDUSTRIES LTD.

6782 OLDFIELD RD. SAANICHTON, BC, CANADA V8M 2A3 www.enviro.com

January 22, 2013

C-13834

47

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement

Table of contents