Ductwork. Fedders A*PB24A1, AFPB36A1, AFPB24A1, A*PC48A1 Series, AFPB24B1, A*PA24B1 Series, AFPC60B1, A*PB24B1, AFPC48B1, A*PC48B1 Series
Add to My manuals16 Pages
advertisement
Ductwork
This air handler shall not be installed without supply plenums and proper ducting. Connect supply air duct over 1/2“ flanges on supply air opening. Secure duct to flange and seal connection.
Use flexible connectors between ductwork and unit at discharge connection. Ductwork passing through unconditioned space must be insulated and covered with vapor barrier.
Return Air Ducting
The dimensions of the return air duct or platform must be at a minimum the same size as the return air opening on the air handler, regardless of the air handler position.
When framing a return air platform, the opening size should be as shown below. If the air handler is to be installed in a closet, be sure to allow room for wiring and refrigerant lines.
Top View
C
D
F
LINE VOLTAGE CONNECTIONS
WARNING
BEFORE PERFORMING ANY WORK ON THIS EQUIPMENT,
POWER SUPPLY MUST BE TURNED OFF AT THE
HOUSEHOLD SERVICE BOX TO AVOID THE POSSIBILITY
OF SHOCK, INJURY, DAMAGE TO EQUIPMENT OR DEATH.
1. The power supply can be connected through the right side or top of the air handler. Conduit knockouts are provided for
1/2
”,
3/4
”, 1”, and 1
1/4
” conduit.
2. Refer to the Control System section for recommended lowvoltage wire gauges.
3. See Power Supply Table on page 9 for power supply specifications.
4. Use only copper conductors for supply wiring.
5. The air handler must be permanently grounded.
The ground lug is located in the field wiring box.
B
Framed-in
Opening
Air
Handler
Bottom
Conduit Knockout Locations
Top of air handler
Right side of air handler
MODEL
AFPB24A1
AFPB24B1
AFPB36A1
AFPC48A1
AFPC48B1
AFPC60A1
AFPC60B1
A
E
A B
IN CM IN CM IN
14 37.3 14 1 /
4
36.2 2
C
CM IN
5 2
D E F
CM IN CM IN CM
5 4 10.1 4 10.1
14 37.3 14 1 /
4
36.2 2
14 37.3 14
1
/
4
36.2 2
5 2
5 2
5 4 10.1 4 10.1
5 4 10.1 4 10.1
16
3
/
8
41.6 22
1
/
4
56.5 3 7.6
3 7.6 1
3
/
4
4.4
2 5
16
3
/
8
41.6 22
1
/
4
56.5 3 7.6
3 7.6 1
3
/
4
4.4
2 5
16
3
/
8
41.6 22
1
/
4
56.5 3 7.6
3 7.6 1
3
/
4
4.4
2 5
16
3
/
8
41.6 22
1
/
4
56.5 3 7.6
3 7.6 1
3
/
4
4.4
2 5
Return Air Platform Height
If the air handler is to be used in the upflow position, the height of the return air platform should be no smaller than the height listed below for the specific model of air handler.
Model
AFPB24A1, AFPB24B1
AFPB36A1
AFPC48A1, AFPC48B1
AFPC60A1, AFPC60B1
Platform
Inches
Height
Cm
12
14
16
18
30.5
35.6
40.6
45.7
Conduit knockouts
Grounding Lug Location
Field wiring box
(detail)
Grounding lug
Conduit knockouts
7
advertisement
Related manuals
advertisement
Table of contents
- 2 SERIES NOMENCLATURE
- 3 INTRODUCTION
- 3 INSPECTION AND UNPACKING
- 3 NOTES TO INSTALLER
- 3 INSTALLATION
- 3 Codes
- 3 Power Considerations
- 3 Electric Heat Kits
- 3 Location
- 3 Clearances
- 4 Upflow Application
- 5 Horizontal Applicaton
- 6 Downflow Application
- 7 Connect Refrigerant Piping
- 7 Factory and Field installed Expansion Valves
- 8 Ductwork
- 8 Return Air Ducting
- 8 Return Air Platform Height
- 8 LINE VOLTAGE CONNECTIONS
- 9 24 VOLT CONTROL SYSTEM
- 9 CONDENSATE PLUMBING
- 10 WIRING DIAGRAM
- 11 DIMENSIONS
- 12 BLOWER SPEED/STATIC OPERATION TABLE
- 13 ELECTRIC HEAT KIT
- 14 Heating Specifications
- 15 WARRANTY