Selecting Cooling Fan Operation. YASKAWA V7 Drive, VS-606V7 Series
تبلیغات
تبلیغات
•
Selecting Cooling Fan Operation
In order to increase lifetime, the cooling fan can be set to operate only when inverter is running.
n039 = 0 (factory setting) : Operates only when inverter is running.
(Continuous operation for 1 minute after inverter is stopped.)
1 : Operates with power ON.
•
Using MEMOBUS (MODBUS) Communications
Serial transmission is available with VS-606V7 using programmable controller
(MEMOCON series) and MEMOBUS.
•
MEMOBUS (MODBUS) communications
MEMOBUS system is composed of a single master (PLC) and slaves (1 to 31
VS-606V7 units).
Communication between master and slave (serial communication) is controlled according to the master program with the master initiating communication and the slave responding.
The master sends a signal to one slave at a time. Each slave has a pre-registered address No., and the master specifies the number and conducts signal communication. The slave receives the communications to carry out designated functions and reply to the master.
•
Communications specifications
Interface
Synchronization
Communication parameters
RS-422, RS485
Asynchronous (Start-stop synchronization)
Baud rate: Selected from 2400/4800/9600/19200 bps
Data length: 8bit fixed
Parity: Selected from even/odd/none
Stop bits: 1bit fixed
Communication protocol
Max. number of inverters that can be connected
92
MEMOBUS (MODBUS) (RTU mode only)
31 units (When using RS-485
•
Communications connection terminal
Use the following S+, S-, R+ and R- terminals for MEMOBUS communications.
Change the termination resistor as shown below.
At RS-422, RS-485 communications: Turn ON SW2 ON/OFF switch of only the inverter at the termination viewed from the PLC.
Notes: 1.
Separate the wiring for communication from the main circuit wiring or other power lines.
2.
Use shielded cables for communication wiring; connect the shielded sheath to the ground terminal and terminate the other end to prevent it from being connected (to prevent noise malfunction).
3.
When communication is performed through
RS-485, connect S+ and R+, S- and R- terminals outside the inverter as shown right side.
•
Procedure for communications with PLC
The following shows the procedure for communications with PLC.
(1) Connect the communication cable between the PLC and the VS-606V7 with the power supply turned OFF.
(2) Turn the power ON.
(3) Set the parameters (n151 to n157) required for communication by using the digital operator.
(4) Turn the power OFF once to verify that the digital operator displays have been completely erased.
(5) Turn the power ON again.
(6) Communications with the PLC starts.
93
•
Setting necessary parameters for communication
Communication related parameters must be set for PLC communication. parameters n151 to n157 cannot be set during communication. Always set them prior to performing communication.
Parameter Name Description
Initial
Setting n003 n004 n151 n152 n153 n154 n155 n156 n157
Run command selection
Frequency reference selection
Timeover detection selection
Monitors transmission time between the receiving the correct data from the PLC
(Timeover: 2 sec)
Communication frequency
Reference monitor unit selection
0 : timeover detection (free run stop)
1 : timeover detection (coasting to a stop with speed reduction time 1)
2 : timeover detection (coasting to a stop with speed reduction time 2)
3 : timeover detection (continuous operation, warning display)
4 : timeover detection not provided
0 : 0.1Hz
1 : 0:0.1Hz
2 : 30000/100% (30000 = max. output frequency)
3 : 0.1%
Slave address
0 : operator
1 : control circuit terminals
2 : communication
3 : communication card (optional)
0 : Local potentiometer (digital operator)
1 : frequency ref. 1 (n024)
2 : control circuit terminals (voltage 0 to 10V)
3 : control circuit terminals (current 4 to 20mA)
4 : control circuit terminals (current 0 to 20mA)
5 : pulse train
6 : MEMOBUS communication (Register No. 000211)
7 : operator circuit terminals (voltage 0 to 10V)
8 : operator circuit terminals (current 4 to 20mA)
9 : communication card (optional)
Baud rate selection
Parity selection
Sending waiting time
RTS control
Setting range: 0 to 32*
0 : 2400 bps
1 : 4800 bps
2 : 9600 bps
3 : 19200 bps
0 : even parity
1 : odd parity
2 : no parity
Setting limit: 10 ms to 65 ms setting unit: 1 ms
0 : RTS control
1 : no RTS control (RS-422A 1 to 1 communication)
0
0
0
0
0
2
0
10 ms
0
* The slave does not respond to the command from the master when set to 0.
Monitoring run status from the PLC, setting/referencing of parameters, fault reset and multi-function input reference can be done regardless of run command or frequency reference selection.
Multi-function input reference from PLC becomes OR with input commands from S1 to S7 multi-function input terminals.
94
•
Message format
For communications, the master (PLC) sends a command to the slave (VS-606V7) and the slave responds to it. The configuration for sending and receiving is as shown to the right. The length of the data varies according to the contents of commands (functions).
The interval between messages must be maintained at the following amount.
VS-606V7 VS-606V7 VS-606V7
Slave address
Function code
Data
Error Check
• Slave address: Inverter address (0 to 32). Setting to 0 indicates simultaneous broadcasting. The inverter does not respond to the command from the master.
• Function code: Command codes (See below).
Function
Code
Function
01H
08H
10H
Reading holding
resistor contents
Loop back test
Write in several holding resistors
Reference Message Response Message
Minimum (Byte) Maximum (Byte) Minimum (Byte) Maximum (Byte)
8
8
11
8
8
41
7
8
8
37
8
8
• Data: Composes a series of data by combining holding register numbers (test codes for loop-back numbers) and their data. Data length depends on the contents of the commands.
• Error check: CRC-16 (Calculate the value by the following method.)
1. The default value at calculation of CRC-16 is normally 0. In the MEMOBUS system, change the default to 1 (all 1 to 16-bit).
2. Calculate CRC-16 assuming that the loop address LSB is MSB and the last data
MSB is LSB.
3. Also calculate CRC-16 for a response message from the slave and refer it to
CRC-16 in the response message.
95
• Read out holding register contents [03H]
Reads out the contents of the holding registers with the continuous numbers for the specified quantity. The contents of holding register is divided into the upper 8 bits and the lower 8 bits. They become the data items in response message in the order of numbers.
Example: Reads out status signal, fault contents, data link status and frequency reference from the VS-606V7 (slave 2).
Reference message
(at normal operation)
Slave address
Function code
Start number
Upper
Lower
02H
03H
00H
20H
Quantity
Upper
Lower
00H
04H
Upper 45H
CRC-16
Lower F0H
(For error code 03H, refer to page 99.)
Response message
(at normal operation)
Slave address
Function code
Number of data*
First holding resistor
Next holding resistor
Next holding resistor
Next holding resistor
Upper
Lower
Upper
Lower
Upper
Lower
Upper
Lower
Upper
CRC-16
Lower
02H
03H
08H
00H
65H
00H
00H
00H
00H
1H
F4H
AFH
82H
Reference message
(at fault occurrence)
Slave address
Function code
Error code
Upper
CRC-16
Lower
02H
83H
03H
F1H
31H
* Twice as much as the number of reference message.
• Example of loop-back test [08H]
Command message is returned as a response message without being changed. This function is used to check transmission between the master and the slave. Any arbitrary values can be used for test codes or data.
Example: Loop-back test of slave 1 and VS-606V7
Reference message
(at normal operation)
Slave address
Function code
Start number
Upper
Lower
Quantity
CRC-16
Upper
Lower
Upper
Lower
01H
08H
00H
00H
A5H
37H
DAH
8DH
Response message
(at normal operation)
Slave address
Function code
Start number
Upper
Lower
Quantity
CRC-16
Upper
Lower
Upper
Lower
01H
08H
00H
00H
A5H
37H
DAH
8DH
Reference message
(at fault occurrence)
Slave address
Function code
Error code
Upper
CRC-16
Lower
01H
89H
01H
86H
50H
96
• Writing to several holding registers [10H]
Specified data are written into the several specified holding registers from the specified number, respectively. Written data must be arranged in a command message in the order of the holding register numbers: from upper eight bits to lower eight bits.
Example: Set forward run at frequency reference 60.0 Hz to slave 1 VS-606V7 from the PLC.
Reference message
(at normal operation)
Slave address
Function code
Start number
Upper
Lower
Quantity
Upper
Lower
Number of data*
First
Data
Upper
Lower
Next data
CRC-16
Upper
Lower
Upper
Lower
01H
10H
00H
01H
00H
02H
04H
00H
01H
02H
58H
63H
39H
Response message
(at normal operation)
Slave address
Function code
Start number
Upper
Lower
Quantity
CRC-16
Upper
Lower
Upper
Lower
01H
10H
00H
01H
00H
02H
10H
08H
Reference message
(at fault occurrence)
Slave address
Function code
Error code
Upper
CRC-16
Lower
01H
89H
01H
86H
50H
* Sets twice as large as the actual number.
97
• Data
• Reference Data (available to read out/write in)
Register No.
0000H
0001H bit
Reserved
0 Run command
1
2
3
4
5
6
Reverse run
External fault
Fault reset
Multi-function input reference 1
Multi-function input reference 2
Multi-function input reference 3
7
8
9
Multi-function input reference 4
Multi-function input reference 5
Multi-function input reference 6
A Multi-function input reference 7
B-F (Not used)
Frequency reference (unit : n152)
V/f gain (1000/100%)
Description
1 : Run
1 : Reverse run
1 : Fault (EFO)
1 : Reset command
0 : Stop
0 : Forward run
(Function selected by n050)
(Function selected by n051)
(Function selected by n052)
(Function selected by n053)
(Function selected by n054)
(Function selected by n055)
(Function selected by n056)
Setting range : 2.0% ~ 200.0%
0002H
0003H
0004H-
0008H
Reserved
0009H
0
Multi-function output reference 1
(Effective when n057=18)
1
2
Multi-function output reference 2
(Effective when n058=18)
Multi-function output reference 3
(Effective when n059=18)
3-F (Not used)
( 1 : MA “ON” 0 = MA “OFF” )
( 1 : P1 “ON” 0 = MA “OFF” )
( 1 : P2 “ON” 0 = MA “OFF” )
000AH-
001FH
Reserved
Note: Write in “0” for unused bit. Never write in data for the reserved register.
• Simultaneous Broadcasting Data (available only for write in)
Register No.
0001H
0002H bit
0
1
2
3
4
Run command
Reverse run
(Not used)
(Not used)
External fault
Description
1 : Run
1 : Reverse run
0 : Stop
0 : Forward run
1 : Fault (EFO)
5 Fault reset
6-F (Not used)
1 : Fault reset command
30000/100% fixed unit
(Data is converted into 0.01 Hz inside the inverter, and fractions are rounded off.)
Bit signals not defined as the broadcast operation signals are used as the local station data signals.
98
• Monitor Data (available only for read out)
Register No.
0020H
0021H
B
C
9
A
7
8
5
6
3
4
1
2 bit
0
1
4
5
2
3
Run command
Reverse run
Inverter operation ready
Fault
6
7
Data setting error
Multi-function output 1
Multi-function output 2
Multi-function output 3
8-F (Not used)
0 Over current (OC)
Over voltage (OV)
Inverter overload (OL2)
Inverter overheat (OH)
(Not used)
(Not used)
PID Feedback loss (FbL)
External fault (EF, EFO)
Hardware fault (Fxx)
Motor overload (OL1)
Overtorque detection (OL3)
(Not used)
Power loss (UV1)
Description
1 : Run
1 : Reverse run
1 : Ready
1 : Fault
1 : Error
(1 : MA ON
(1 : P1 ON
(1 : P2 ON
0 : Stop
0 : Forward run
0 : Not ready
0 : MA OFF)
0 : OFF)
0 : OFF)
Emergency stop (STP)
0022H
0029H
3
4
1
2
D
E
F
0
Control power fault (UV2)
MEMOBUS communications timeover (CE)
Operator connection (OPR)
Data write in
(Not used)
(Not used)
Upper/lower limit fault
Consistency fault
0023H
5-F (Not used)
Frequency reference (Unit : n152)
0024H Output frequency (Unit : n152)
0025H-026H (Not used)
0027H
0028H
Output current (10/1A)
Output voltage reference (1/1V)
0
1
Load short circuit (SC)
Ground fault (GF)
4
5
2
3
Input open phase (PF)
Output open phase (LF)
Installed type braking resistor overheat
Braking transistor fault (RR)
6-F Not used
99
Register No.
002AH
002BH
002CH
002DH
0
1
E
F bit
0
1
Description
4
5
2
3
Operator stop (STP)
Sequence error (SER)
FWD - REV command simulation input (EF)
External baseblock (BB)
8
9
6
7
Overtorque detection (OL3)
Cooling fin overheat (OH)
Main circuit overvoltage (OV)
Main circuit undervoltage
A
B
Cooling fan fault (FAN)
Communication error
Option card communication error (BUS)
Not used
C Inverter overheat prediction (OH3)
D PID feedback loss (FBL)
Emergency stop (STP)
Communication waiting (CALL)
Terminal S1
Terminal S2
1 : Closed O : Open
1 : Closed O : Open
6
7
8
4
5
2
3
0
1
E
F
2
B
C
D
4
5
2
3
Terminal S3
Terminal S4
Terminal S5
Terminal S6
6 Terminal S7
7-F (Not Used)
0
1
Run
Zero - speed
9
A
1 : Run
1 : Zero - speed
1 : Agreed Frequency agreed
Minor fault (Alarm is indicated)
Frequency detection 1
Frequency detection 2
Inverter operation ready
Undervoltage detection
Baseblock
1: Output frequency
1
:
Output frequency
1 : Ready
≤
≥
(n095)
(n095)
1 : Under Voltage detection
Frequency reference mode
Run command mode
1 : Inverter output base block
1 : Other than communications
0 : Communications
1 : Other than communications
0 : Communications
1 : Detection or overtorque fault Overtorque detection
(Not used)
Fault restart
Fault (Including MEMOBUS communications timeover) 1 : Fault
MEMOBUS communications timeover 1 : Timeover
MA “ON”
P1 “ON”
1 : Closed 0 : Open
1 : Closed 0 : Open
P2 “ON”
(Not used)
1 : Closed 0 : Open
3-F
1 : Closed O : Open
1 : Closed O : Open
1 : Closed O : Open
1 : Closed O : Open
1 : Closed O : Open
100
Register No.
02EH
002FH-0030H
0031H
0032H
0033H-0034H
0035H
0036H
Register No.
0037H
0038H
0039H
003AH
003BH-003CH
003DH bit
0
1
2
3
4
5
6
7
Frequency ref. loss
Not used
Not used
Not used
Not used
Not used
Not used
Not used
8 - F Not used
Reserved
Main circuit DC voltage (1/1V)
Torque monitor
Not used
Cumulative operation time (I/IH)
Description
Not used bit Description
Output power (1/1W : with sign)
PID feedback value (100% / Input equivalent to max. output frequency; 10/1%; without sign)
PID input value (±100% / ± Max. output frequency ; 10/1%; with sign)
PID output value (±100% / ± Max. output frequency ; 10/1%; with sign)
Reserved
0 CRC error
3
4
1
2
5
6
P1 “ON”
(Not used)
Parity error
Overrun error
Framing error
Timeover
003EH-00FFH
7 (Not used)
Reserved
* Communications error contents are saved until fault reset is input. (Reset is enabled during run.)
101
• Storing parameters [Enter command] (can be written only.)
Register
Number
Name Contents Setting Range
0900H
ENTER command
Write-in parameter data to nonvolatile memory (EEPROM).
0000H to FFFFH
Default
-
When a parameter is written from the PLC by communications, the parameter is written to the parameter data area on the RAM in the VS-606V7. ENTER command is a command to write the parameter data on the RAM to the non-volatile memory in the
VS-606V7. Writing data (can be undefined) to register number 0900H during stop executes this ENTER command.
Maximum number of writing times of the non-volatile memory used for VS-606V7 is
100,000; do not execute the ENTER command excessively. When a parameter is changed from the digital operator, the parameter data on the RAM is written to the nonvolatile memory without ENTER command.
Register number 0900H is used only for write-in. If this register is readout, register number error (error code: 02H) occurs.
102
Error Codes
Error Code
01H
02H
03H
21H
22H
Contents
Function code error
• Function code from PLC is other than 03H, 08H or 10H.
Improper register number
• No register numbers to be accessed have been registered.
• ENTER command “0900H” that is an exclusive-use register for write-in was read out.
Improper quantity
• The number of data items to be read or write-in is not in the range between 1 and 16.
• The number of data items in a message is not the value obtained by multiplying the quantity by two in the write-in mode.
Data setting error
• A simple upper/lower limit error occurred with control data or parameter write-in.
• A parameter setting error occurred when a parameter was written.
Write-in mode error
• Attempt to write-in a parameter from PLC was made during running.
• Attempt to write-in an ENTER command from PLC was made during running.
• Attempt to write-in a parameter from PLC was made during UV occurrence.
• Attempt to write-in an ENTER command from PLC was made during UV occurrence.
• Attempt to write-in a parameter other than n001=12,13 (initialization) from PLC was made during “F04” occurrence.
• Attempt to write-in a parameter from PLC was made while data were being stored.
• Attempt to write-in data exclusive for read-out from PLC was made.
* Refer to the parameters list for parameters that can be changed during operation.
103
•
Performing self-test
VS-606V7 is provided with a function to perform self-diagnosis for operation check of the serial communication I/F circuit. This function is called self-test. In the self-test, connect the sending terminal with the receiving terminal in the communication section.
It assures if the data received by VS-606V7 is not being changed. It also checks if the data can be received normally. Carry out the self-test in the following procedure.
(1) Turn ON the VS-606V7 mini power supply. Set parameter n056 to 35 (self-test).
(2) Turn OFF the VS-606V7 mini power supply.
(3) Make the following wiring with the power supply turned OFF.
(4) Turn the power ON.
Normal operation: Operator displays frequency reference value.
Faulty operation: Operator displays “ signal is turned OFF.
”, fault signal is turned ON and inverter ready
104
•
Using Energy-saving Control Mode
Verify that the parameter n002 is set to 0 (V/f control mode) when performing energy-saving control. Setting n139 to 1 enables the energy-saving control function.
Energy-saving Control Selection (n139)
Parameters
No.
n139
Name
Energy-saving control selection
Unit
-
Setting
Range
0: Disabled
1: Enabled
Initial
Setting
0
Normally it is not necessary to change the setting. However, if the motor characteristics are different from a Yaskawa standard motor, refer to the description below and change the parameter setting accordingly.
• Energy-saving Control Mode (n140, n158)
Calculates the voltage for the best motor efficiency when operating in energysaving control mode. The calculated voltage becomes the output voltage reference.
The factory setting is set to the max. applicable motor capacity of a Yaskawa standard motor.
The greater the energy-saving coefficient is, the greater the output voltage becomes.
When using a motor other than a Yaskawa standard motor, set the motor code corresponding to the voltage and capacity to n158. Then, change the setting of the energy-saving coefficient K2 (n140) by 5% so that the output power becomes the smallest.
When the motor code is set to n158, the energy-saving coefficient K2, which corresponds to the motor code, is set n140.
Parameter
No.
Name n140 n158
Energy-saving control coefficient K2
Motor Code
∗
Setting depends on inverter capacity.
Unit
-
-
Setting
Range
0.0 to 6550
0 to 70
Initial
Setting
*
*
105
•
Energy-saving voltage lower/upper limit (n141, n142, n159, n160)
Sets the upper and lower limits of the output voltage. When the value calculated in the energy-saving control mode is larger than the upper limit (or smaller than the lower limit), the value is output as a voltage reference value. The upper limit is set to prevent over-excitation, and the lower limit is set to prevent stalls when the load is light. The voltage limit is set for machines using 6Hz/60 Hz. For any voltage other than 6Hz/60Hz, set the (value of the) voltage limit according to linear interpolation. The parameters are set in % for 200V/400V inverters.
Parameters
No.
Name Unit
Setting
Range
Initial
Setting n141 n142 n159 n160
Energy-saving voltage lower limit (60 Hz)
Energy-saving voltage lower limit (6 Hz)
Energy-saving voltage upper limit (60 Hz)
Energy-saving voltage upper limit (6 Hz)
%
%
%
%
0 to 120
0 to 25
0 to 120
0 to 25
50
12
120
16
106
*Doubled for the 400V class inverters.
Energy-saving search operation
In the energy control mode, the max. applicable voltage is calculated using the output power. However, a temperature change or the use of another manufacturer’s motor will change the fixed parameters, and the max. applicable voltage may not be emitted. In the search operation, change the voltage slightly so that the max. applicable voltage can be obtained.
•
Search Operation Voltage Limit (n144)
Limits the range where the voltage can be controlled. The parameters are set in % for 200V/400V inverters. The search operation is not performed when set to 0.
Parameters
No.
n144
Name
Search operation voltage limit
Unit
%
Setting
Range
0 to 100
Initial
Setting
0
•
Search Operation Voltage Step (n145, n146)
Sets the voltage fluctuations for one cycle of the search operation. Increase the value and the fluctuation of the rotation speed will also increase. Sets the range.
The value calculated by linear interpolation is set for voltage other than above.
Parameters
No.
n145 n146 n143
Name
Search operation voltage step (100%)
Search operation voltage step (100%)
Search operation control cycle
Unit
%
% x24 ms
Setting
Range
0.1 to 10.0
0.1 to 10.0
1 to 2000
Initial
Setting
0.5
0.2
1 (24ms)
Output voltage
107
•
Search Operation Power Detection Hold Width (n161)
When the power fluctuation is less than this value, the output voltage is held for 3 seconds. Then the search operation mode is activated. Set the hold width in % of the power which is currently held.
Parameter
No.
Name Unit
Setting
Range
Initial
Setting n161
Search operation voltage limit
% 0 to 100 0
•
Power Detection Filter Time Parameter (n162)
Response at load change is improved when this value is small. However, at low frequency, unstable rotation will result.
Parameter
No.
Name Unit
Setting
Range
Initial
Setting n162
Power detection filter time parameter x 4 ms 0 to 255 5 (20 ms)
Parameter
No.
n162
Name
Power detection filter time parameter
Unit x 4 ms
Setting
Range
0 to 255
Initial
Setting
5 (20 ms)
108
Motor Code
The energy-saving coefficient K2 (n140) is set to a value that corresponds with that motor code (n158).
Motor Type
YASKAWA
Generalpurpose
Motor
YASKAWA
Inverter
Motor
Voltage Class Capacity
200V
400V
200V
400V
5.5 kW
7.5 kW
0.1 kW
0.2 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.7 kW
5.5 kW
7.5 kW
0.2 kW
0.1 kW
0.2 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.7 kW
5.5 kW
7.5 kW
0.2 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.0 kW
3.7 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.0 kW
3.7 kW
5.5 kW
7.5 kW
Motor Code: n158
44
45
47
49
50
61
29
30
40
41
42
43
65
66
67
69
70
62
63
64
24
25
26
27
10
21
22
23
7
9
4
5
2
3
0
1
245.8
245.8
189.5
145.4
481.7
356.9
300.9
224.7
160.4
138.9
106.9
84.1
71.7
713.8
Energy-saving coefficient K2: n140
481.7
356.9
288.2
223.7
169.4
156.8
122.9
94.8
72.7
713.8
576.4
447.4
338.8
313.6
601.8
449.4
320.8
277.8
213.8
213.8
168.3
143.3
109
•
Using PID Control Mode
For details of the PID control setting, refer to the block diagram of the Inverter’s internal PID control or the block diagram of the operator analog speed reference.
PID Control Selection: n128
Parameter
No.
n128
Target
Value
Name
PID control selection
The currently selected frequency reference
Unit
n128 Settings
Setting
0
1
2
3
4
5
6
7
8
Function
Disabled.
Enabled: deviation is subject to differential control.
Enabled: feedback signal is subject to differential control.
Enabled: frequency reference + PID control, and deviation are subject to differential control.
Enabled: frequency reference + PID control, and feedback signal are subject to differential control.
Enabled: deviation is subject to differential control.
Enabled: feedback signal is subject to differential control.
Enabled: frequency reference + PID control, and deviation are subject to differential control.
Enabled: frequency reference + PID control, and feedback signal are subject to differential control.
PID Output Characteristics
Forward
Reverse
Set one of the above values when using PID control.
The following table shows how to determine the target value and the feedback value to be input when the PID control is enabled.
Input
Setting
Range
0 to 8
Initial
Setting
0
Condition
Determined by the frequency reference selection (n004)
When the local mode is selected, the target value is determined by frequency reference selection in local mode
(n008).
When the multi-step speed reference is selected, the currently selected frequency reference becomes the target value.
Feedback
Value
The frequency reference that is set to the PID feedback value selection (n164)
n164 setting
0
1
4
5
2
3
Description
Control circuit terminal FR (Voltage 0 to 10V).
Control circuit terminal (Current 4 to 20 mA)
Control circuit terminal (Current 0 to 20 mA)
Operator terminal (Voltage 0 to 10V)
Operator terminal (Current 4 to 20 mA)
Pulse train
110
Notes: 1. When selecting frequency reference from the control circuit terminal FR as the target or feedback value, the V-I switch of SW2 on the control circuit board must be selected depending on the input method (current or voltage input).
2. Never use the frequency reference from the control circuit terminal FR for both the target and feedback values. The frequency reference for both the target value and the feedback value becomes the same.
(Example)
When the frequency reference from the control circuit terminal FR, with a voltage of 0 to 10 V, is selected as the target value and n004=2, and when at the same time the frequency reference from the control circuit terminal FR, with a current of 4 to 20 mA, is selected as the feedback value and n164=1, the feedback value will be set as the frequency reference from the control circuit terminal FR.
3. When using the analog signal (0 to 10V / 4 to 20mA) which inputs to the CN2 terminal of the digital operator JVOP-140 as the target or feedback value of
PID control, never use it as a multi-analog input. Parameter n077 (multifunction analog input) should be set to 0 (disabled).
•
Proportional gain (P), Integral time (I), Differential time (D)
(n130, n131, n132)
Adjust the response of the PID control with the proportional gain (P), intregal time (I), and differential time (D).
Parameter
No.
n130 n131 n132
Name
Proportional gain (P)
Intregal Time
Differential Time (D)
Unit
Multiples
1.0s
1.0s
Setting
Range
0.0 to 25.0
0.0 to 360.0
0.00 to 2.50
Initial
Setting
1.0
1.0
0.00
Optimize the responsiveness by adjusting it while operating an actual load (mechanical system). Any control (P, I, or D) that is set to zero (0.0, 0.00) will not operate.
111
•
Intregal (I) Limit (n134)
Parameter
No.
n134
Name
Intregal (I) limit
Unit
%
Setting
Range
0 to 100
Initial
Setting
100
This parameter prevents the calculated value of the integral control from exceeding the fixed amount. There is normally no need to change the setting.
Reduce the setting if there is a risk of load damage, or of the motor going out of step by the inverter’s response when the load suddenly changes. If the setting is reduced too much, the target value and the feedback value will not match.
Set this parameter as a percentage of the maximum output frequency with the maximum frequency as 100%.
•
PID Offset Adjustment (n133)
Parameter
No.
n133
Name
PID Offset adjustment
Unit
%
Setting
Range
-100 to 10.0
Initial
Setting
0
Parameter n133 adjusts the PID control offset.
If both the target value and the feedback values are set to zero, adjust the inverter output frequency to zero.
•
PID Primary Delay Time Parameter (n135)
Parameter
No.
n135
Name
PID primary delay time parameter
Unit
Seconds
Setting
Range
0.0 to 10.0
Initial
Setting
0.0
Parameter n135 is the low-pass filter setting for PID control outputs.
There is normally no need to change the setting.
If the viscous friction of the mechanical system is high or if the rigidity is low causing the mechanical system to resonate, increase the setting so that it is higher than the resonance frequency period.
112
•
PID Output Gain (n163)
Parameter
No.
n163
Name
PID Output gain
This parameter adjusts the output gain.
Unit
Multiples
Setting
Range
0.0 to 25.0
•
PID Feedback Value Adjusting Gain (n129)
Parameter
No.
Name Unit
Setting
Range n129
PID feedback value adjusting gain
Multiples 0.0 to 10.0
Parameter n129 is the gain that adjusts the feedback value.
Initial
Setting
1.0
Initial
Setting
1.00
•
PID Feedback Loss Detection (n136, n137, n138)
Parameter
No.
Name Unit
Setting
Range n136 n137 n138
Selection of PID feedback loss detection
PID feedback loss detection level
PID feedback loss detection time
-
%
%
0: No detection of PID feedback loss
1: Detection of PID feedback loss
(Operation continued: FbL alarm)
2: Detection of PID feedback loss
(Output shut down: fault)
0 to 100
100%/Max. output frequency
0.0 to 25.5
Initial
Setting
0
0
1.0
113
114
Int
115