Using Parameter Copy Function
Parameter copy function
The VS-606V7 standard digital operator JVOP-140 can store parameters for one inverter. A backup power supply is not necessary since EEPROM is used.
Parameter copy function is possible only for the inverters with the same product series, power supply specifications and control mode (V/f control or vector control).
However, some parameters may not be copied. It is also impossible to copy parameters between VS-606V7 and VSmini J7 inverters.
The prohibition of the reading of parameters from the inverter can be set at n177. The parameter data cannot be changed when this parameter is set.
If any alarm occurs during parameter copy, the PRGM will blink and copying will continue.
•
Parameter Copy Function Selection (n176)
Depending on the setting of n176 for parameter copy function selection, the following functions are available:
1. Read all the parameters from the inverter (READ) and store them in EEPROM in the digital operator.
2. Copies the parameters stored in the digital operator to the inverter (COPY).
3. Verify that the parameters in the digital operator and the parameters in the inverter are the same (VERIFY).
4. Displays the maximum applicable motor capacity and the voltage class of the inverter that has the parameters stored in the digital operator.
5. Displays the software number of the inverter that has the parameters stored in the digital operator.
116
Parameter
No.
n176
Name
Parameter copy function selection
Unit
-
Setting
Range rdy: READY rEd: READ
CPy: COPY vFy: Verify vA: Inverter capacity display
Sno: Software number display
Initial
Setting rdy
•
Prohibiting Parameter Read Selection (n177)
Select this function to prevent accidentally overwriting the parameters stored in
EEPROM or in the digital operator. Reading is not possible when this parameter is set to 0.
The parameter data is stored in the digital operator are safe from accidental overwriting.
When reading is performed while this parameter is set to 0, PrE will blink. Press the
DSPL or ENTER and return to the parameter No. display.
Parameter
No.
n177
Name
Prohibiting parameter read selection
Unit
1
Setting
Range
0: READ prohibited
1: READ allowed
Initial
Setting
0
Read function
Reads out the parameters in batch from the inverter and stores them in EEPROM inside the digital operator. When the read-out is executed, the previously stored parameters data in the EEPROM are cleared and replaced with the newly entered parameters.
117
[Example] Store the parameters read out from the inverter, in the EEPROM inside the digital operator .
• Enable the setting of the parameters n001 to n179.
Explanation
• Press DSPL to light [PRGM].
Operator display
• Press ENTER to display the set value.
• Change the set value to 4 by pressing or key.
• Press ENTER.
(Can be a different parameter No.)
( Lit )
(Can be a different set value.)
(Blinks)
(Lit for one second.)
(The parameter is displayed)
• Set parameter read prohibited selection (n177) to read enabled. *1
• Change the parameter No. to n177 by pressing or key.
( Lit )
• Press ENTER to display the set value.
• Change the set value to 1 by pressing or key.
• Press ENTER.
(Blinks)
(Lit for one second)
(The parameter displayed)
• Execute read-out (READ) by parameter copy function selection (n176).
• Change the parameter No. by pressing or key.
• Press ENTER to display the set value.
• Change the set value to rEd by pressing or key.
• Press ENTER.
(Lit)
(Lit)
READ)
(Blinks while executing
• Press DSPL or ENTER
(End is displayed after the execution of READ is completed.)
(The parameter is displayed.)
• Set Parameter read prohibited selection (n177) to READ disabled. *2.
• Change the parameter No. to n177by pressing or key.
(Lit)
• Press ENTER to display the set value.
• Change the set value to 0 by pressing or key.
• Press ENTER.
( Blinks )
( Lit for one minute )
(The parameter No. is displayed.)
*1 When READ is enabled (n177=1), this setting is not necessary.
*2 The setting is not necessary unless the READ prohibition is selected.
118
Copy Function
Writes the parameters stored inside the digital operator in batch to the inverter. Write-in is possible only for the inverters with the same product series, power supply specifications and control mode (V/f control or vector control).
Therefore, writing from 200 V class to 400 V class (or visa versa), from VS-606V7 to VSmini
J7 are not possible.
Parameter Copy Function Selection (n176), Parameter Read Prohibited Selection (n177),
Fault history (n178), Inverter Software No. (n179), and hold output frequency are not written.
Following parameters are not written if the inverter capacity is different .
Parameter No.
n011 to n017 n036 n080 n105 n106 n107
V/f setting
Name
Motor rated current
Carrier frequency
Torque compensation iron loss
Motor rated slip
Motor resistance for one phase
Parameter No.
n108 n109 n110 n140 n158
Name
Motor leakage inductance
Torque compensation voltage limiter
Motor no-load current
Energy-saving coefficient K2
Motor code
[Example] Write the parameters from EEROM inside the digital operator to the inverter
• Enable the setting of the parameters n001 to n179.
Explanation
• Press DSPL to light [PRGM].
• Press ENTER to display the set value.
• Change the set value to 4 by pressing or key.
• Press ENTER.
Operator display
(Can be a different parameter No.)
( Lit )
(Can be a different set value.)
(Blinks)
(Lit for one second.)
• Execute write-in (COPY) by
Parameter Copy Function
Selection (n176).
• Change the parameter No. to n176 by pressing or key.
• Press ENTER to display the set value.
• Change the set value to CPy by pressing or key.
• Press ENTER.
(The parameter No. is displayed)
( Lit )
(Lit)
(Blinks while executing CPY)
• Press DSPL or ENTER (End is displayed after the execution of CPY is completed.)
(The parameter No. is displayed.)
119
A setting range check and matching check for the written-in parameters are executed after the parameters are written from the digital operator to the inverter. If any parameter error is found, the written parameters are discarded and the parameters stored before writing are restored.
When a setting range error is found, the parameter No. where an error occurs is indicated by blinking.
When a matching error is found,
… ( …: a number) is indicated by blinking.
120
VERIFY function
Collates the parameters stored in the digital operator with the parameters in the inverter. As well as write-in, VERIFY is possible only for the inverters with same product series, power supply specifications and control mode (V/f control or vector control).
When the parameters stored in the digital operator correspond to those in the inverter, vFy is displayed by blinking, then End is displayed.
[Example] Collate the parameters stored in EEPROM inside the digital operator with the parameters in the inverter.
• Enable the setting of the parameters n001 to n179.
Explanation
• Press DSPL to light [PRGM].
• Press ENTER to display the set value.
• Change the set value to 4 by pressing or key.
• Press ENTER.
Operator display
(Can be a different parameter No.)
( Lit )
(Can be a different set value.)
(Blinks)
(Lit for one second.)
(The parameter is displayed)
• Execute VERIFY by Parameter
Copy Function selection (n176)
• Change the parameter No. to n176 by pressing or key.
• Press ENTER to display the set value.
• Change the set value to vFY by pressing or key.
• Press ENTER.
(Lit)
(Lit)
(Blinks while executing
VERIFY)
• Display the unmatched parameter No.
• Display the parameter value in the inverter.
(Blinks) (When n001 is unmatched)
(Blinks)
• Display the parameter value in the digital operator.
• Continue the execution of
VERIFY.
• Press ENTER.
• Press ENTER.
• Press key.
(Blinks)
(Blinks while executing
VERIFY
• Press DSPL or ENTER (End is displayed after the execution of VERIFY is completed.)
(The parameter No. is displayed.)
While an unmatched parameter No. is displayed or a parameter value is displayed, pressing STOP/RESET interrupts the execution of VERIFY and End is displayed.
Pressing DSPL or ENTER returns to the parameter No.
121
Inverter Capacity Display
The voltage class and maximum applicable motor capacity (whose parameters stored in the digital operator are read out) is displayed.
[Example] Display the voltage class and maximum applicable motor capacity for the inverter whose parameters stored in EEPROM inside the digital operator.
• Enable the setting of the parameters n001 to n179.
Explanation
• Press DSPL to light [PRGM].
Operator display
• Press ENTER to display the set value.
• Change the set value to 4 by pressing or key.
• Press ENTER.
(Can be a different parameter No.)
( Lit )
(Can be a different set value.)
(Blinks)
(Lit for one second.)
(The parameter is displayed)
• Execute Inverter Capacity
Display (vA) by parameter copy function selection (n176)
• Change the parameter No. to n176 by pressing or key.
• Press ENTER to display the set value.
(Lit)
(Lit)
• Change the set value to vA by pressing or key.
• Press ENTER.
• Press DSPL or ENTER.
(Lit) (For20P7)*
(The parameter No. is displayed.)
The following shows the explanation of Inverter Capacity Display
2 b
4
Voltage class
Three-phase 200V
Single-phase 200V
Three-phase 400V
0.7
1.5
2.2
3.0
4.0
0.1
0.2
0.4
Max. applicable motor capacity
200V class
0.1kW
400V class
-
0.25kW
0.55kW
1.1kW
1.5kW
0.37kW
0.55kW
1.1kW
1.5kW
2.2kW
-
4.0kW
2.2kW
3.0kW
4.0kW
122
Software No. Display
The software No. (of the inverter whose parameters stored in the digital operator are read out) is displayed.
[Example] Display the software No. of the inverter whose parameters stored in
EEPROM inside the digital operator.
Operator display
• Enable the setting of the parameters n001 to n179.
Explanation
• Press DSPL to light [PRGM].
• Press ENTER to display the set value.
• Change the set value to 4 by pressing or key.
• Press ENTER.
(Can be a different parameter No.)
(Can be a different set value.)
(Blinks)
(Lit for one second.)
(The parameter is displayed)
• Execute Software No. Display
(Sno)* by Parameter copy function selection (n176)
• Change the parameter No. to n176 by pressing or key.
• Press ENTER to display the set value.
• Change the set value to Sno by pressing or key.
• Press ENTER
• Press DSPL or ENTER
(Lit)
(Lit)
(software version: VSP010013)
(The parameter No. is displayed)
* Displays Lower 4 digits of the software version.
123
Display List
Operator display
Description
Lit: Setting for parameter copy function selection enabled
Lit: READ selected
Flashed: READ under execution
Lit: Writing (COPY) selected
Blinks: Writing (COPY) under execution
Lit: VERIFY selected
Flashed: VERIFY under execution
Lit: Inverter capacity display selected
Corrective action
-
-
-
-
-
Lit: Software No. Display selected -
Lit: READ, COPY (writing), or VERIFY completed
Blinks: Attempt to execute READ while
Parameter Read Prohibited Selection (n177) is set to 0.
-
Confirm the necessity to execute READ, then set parameter Read Prohibited selection (n177) to 1 to execute READ.
Blinks: The parameter could not be read properly by READ operation. Or, a main circuit low voltage is detected during READ operation.
Blinks: A sumcheck error occurs in the parameter data stored in the digital operator.
Confirm that the main circuit power supply voltage is correct, then re-execute READ.
The parameter stored in the digital operator cannot be used.
Re-execute READ to store the parameters in the digital operator.
Check if they are the same product series Blinks: The password for the connected inverter and that for the parameter data stored in the digital operator do not agree.
[EX.]Writing (Copy) from VS-606V7 to Vsmini
J7
Blinks: No parameter data stored in the digital operator.
Execute READ
Blinks: Attempt to execute writing (COPY) or
VERIFY between different voltage classes or different control modes
Blinks: A main circuit low voltage is detected during writing (COPY) operation.
Check each voltage class and control mode.
Lit: A sumcheck error occurs in the parameter data stored in the inverter.
Blinks: Attempt to execute VERIFY between different inverter capacities.
Confirm that the main circuit power supply voltage is correct, then re-execute writing
(COPY).
Initialize the parameters. If an error occurs again, replace the inverter due to a failure of parameter memory element (EEPROM) in the inverter.
Press ENTER to continue the execution of
VERIFY. Press STOP to interupt the execution of VERIFY.
Blinks: A communication error occurs between the inverter and the digital operator.
Check the connection between the inverter and the digital operator.
If a communication error occurs during READ operation or writing (COPY) operation, be sure to re-execute READ or COPY.
Note: While rEd, CPy, or vFy is displayed by blinking, key input on the digital operator is disabled.
While rEd, CPy and vFy are not displayed by blinking, pressing DSPL or ENTER redisplays the parameter No.
124