Recommended Peripheral Devices. YASKAWA V7 Drive, VS-606V7 Series
โฆษณา
โฆษณา
•
Recommended Peripheral Devices
It is recommended that the following peripheral devices should be mounted between the AC main circuit power supply and VS-606V7 input terminals R/L1, S/L2, and T/
L3.
• MCCB (Molded-case circuit breaker)/fuse:
Be sure to connect it for wiring protection.
• Magnetic contactor:
Mount a surge suppressor on the coil (refer to the table shown below).
When using a magnetic contactor to start and stop the inverter, do not exceed one start per hour.
Recommended MCCB and magnetic contactor, and fuse
• 200V 3-phase
VS-606V7 model
Capacity (kVA)
V7
∗ ∗
20P1
0.3
Rated Output Current (A) 0.8
MCCB type NF30
(MITSUBISHI)
5A
Magnetic contactor type HI
(YASKAWA CONTROL)
Fuse (UL Class RK5)
HI-7E
5A
V7
∗ ∗
20P2
0.6
1.6
5A
HI-7E
5A
V7
∗ ∗
20P4
1.1
3
5A
HI-7E
5A
V7
∗ ∗
20P7
1.9
5
10A
V7
∗ ∗
21P5
3.0
8
20A
V7
∗ ∗
22P2
4.2
11
20A
HI-7E HI-10-2E HI-10-2E
10A 20A 20A
V7
∗ ∗
23P7
6.7
17.5
30A
HI-20E
30A
V7
∗ ∗
25P5
9.5
25.0
50A
V7
∗ ∗
27P5
13.0
33.0
HI-30E HI-50E
50A
60A
60A
• 200V single-phase
VS-606V7 model
V7
∗ ∗
B0P1
Capacity (kVA) 0.3
Rated Output Current (A) 0.8
MCCB type NF30, NF50
(MITSUBISHI)
Magnetic contactor type HI
(YASKAWA CONTROL)
Fuse (UL Class RK5)
5A
HI-7E
5A
V7
∗ ∗
B0P2
0.6
1.6
5A
HI-7E
5A
V7
3
∗ ∗
B0P4
1.1
10A
V7
∗ ∗
B0P7
1.9
5
20A
HI-7E HI-10-2E
10A 20A
V7
∗ ∗
B1P5
3.0
8
20A
HI-15E
20A
V7
∗ ∗
B2P2
4.2
11
40A
HI-20E
40A
V7
∗ ∗
B3P7
6.7
17.5
50A
HI-30E
50A
• 400V 3-phase
VS-606V7 model
Capacity (kVA)
V7
∗ ∗
40P2
0.9
Rated Output Current (A) 1.2
MCCB type NF30, NF50
(MITSUBISHI)
5A
Magnetic contactor type HI
(YASKAWA CONTROL)
Fuse (UL Class RK5)
V7
∗ ∗
40P4
1.4
1.8
V7
∗ ∗
40P7
2.6
3.4
V7
∗ ∗
41P5
3.7
4.8
V7
∗ ∗
42P2
4.2
5.5
V7
∗ ∗
43P0
5.5
7.2
V7
∗ ∗
44P0
7.0
9.2
V7
∗ ∗
45P5
11.0
14.8
V7
∗ ∗
47P5
14.0
18.0
HI-7E HI-7E HI-7E HI-10-2E HI-10-2E HI-10-2E HI-10-2E HI-20E HI-20E
5A
5A
5A
5A
5A
10A
10A
10A
10A
20A
20A
20A
20A
30A
30A
30A
30A
153