Address Descriptions. Emerson ROC364


Add to my manuals
39 Pages

advertisement

Address Descriptions. Emerson ROC364 | Manualzz

15

Fisher ROC Serial Driver Help

Address Descriptions

ROC addresses are divided first by Point Type, Logical Address, and then by Parameter Index within the Point

Type. The general format is T-L.P, where: l l l

T: The Point Type.

L: The Logical Address.

P: The Parameter Index.

Parameters are blocked together on Point Type and Logical Address to a size up to 236 bytes. Some parameters are broken down into individual bits. Those parameters are addressed as T-L.P:B, where: l B: The Bit Offset.

For example, the address 1-50.3:2 indicates the following: l l l l

Point Type: 1

Logical Address: 50

Parameter: 3

Bit Offset: 2

For a detailed listing of all point type parameters, access, data type, length, and description, refer to the ROC device's ROC Protocol User Manual. For more information on ROC addressing, select a link from the list below.

ROC Point Types

Logical / Point Number Details

User-Defined Point Types

Bit Assignments

ROC Point Types

The availability of point types varies by model and by how the particular unit is equipped. Points may be Physical

I/O or Internal I/O.

Physical I/O Points

Physical I/O points are one of Discrete Inputs (type 1), Discrete Outputs (type 2), Analog Inputs (type 3), Analog

Outputs (type 4) and Pulse Inputs (type 5). The logical address for physical I/O points is based on their position in the unit, known as Point Number. There are four slots for each rack. The I/O field is not typically fully populated.

Note: Rack and slot are ROC nomenclature; however, many ROC devices have no physical racks or slots.

Logical addresses are calculated from the Point Number reference. For information on reconciling the Point

Number to the Logical Address, refer to the table below.

ROCLINK Point Number

A1-A16

B1-B16

C1-C16

D1-D16

E1-E16

...

Server Logical Address

0-15

16-31

32-47

48-63

64-79

...

For example, an I/O Point with ROCLINK 800 Point Number "A5" would be Logical Address "4". An I/O Point with

ROCLINK 800 Point Number "C5" would be Logical Address "36" by the function A + B + C5 (or 15+16+5=36).

Internal I/O Points

Internal I/O points consist of PID settings, system flags, communications parameters and other internal information. The internal I/O logical address begins at 0 for each point type. A ROC unit may have one or several of a given internal point type. Each point type has a specific set of parameters. ROC drivers have no array types.

Point Type Tables

ROC Point Types for ROC300-Series

ROC Point Types for FloBoss 100-Series, FloBoss 407, and FloBoss 500-Series

www. kepware.com

Fisher ROC Serial Driver Help

ROC Point Types for RegFlo

ROC Point Types for ROC300-Series

For a detailed listing of all point type parameters' access, data type, length and description, refer to the device's

ROC Protocol User Manual.

Point

Types

Description

44

49

50

56

57

59

35

36

37

38

39

40

41

42

4

5

6

7

9

0

1

2

3

Configurable Opcode

Discrete Inputs (DI)

Discrete Outputs (DO)

Analog Inputs (AI)

Analog Outputs (AO)

Pulse Inputs (PI)

Proportional, Integral and Derivative (PID) Control

American Gas Association (AGA) Flow Parameters

Local Display Panel

10

11

12

13

14

15

16

17

AGA Flow Values

Tank Parameters

ROC Clock

System Flags

Communication Ports

System Variables (ROC Information)

Function Sequence Table (FST) Parameters

Soft Points

18

19

20

AI Calibration

Database Setup

ROC Tasks

21 Information for User Defined Points

22-31 User Defined Points

32 User Defined Typically Modem Config for COM1

33

34

User Defined Typically Modem Config for LOI and COM2

User Defined Typically Modbus Config for COM1

User Defined Typically Function Config for COM1

User Defined Typically Host Config for COM1

User Defined Typically Modbus Config for LOI and COM2

User Defined Typically Function Config for LOI and COM2

User Defined Typically Host Config for COM1

Multi-Variable Sensor (MVS) Parameters

AGA Run Parameters

Extra Run Parameters

Power Control

Upload to Disk

Download to ROC

AI Calibration

Keypad / Logon Security Parameters

Program Flash Control Parameters

Yes

Yes

Yes

Yes

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

ROC300-

Series

ROCPAC

Yes

Yes

Yes

Yes

No

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

No

No

No

ROC300-Series

FlashPAC

No

Yes

Yes

Yes

No

Yes

Yes

Yes

Yes

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes*

Yes

Yes

*Added via a user program.

ROC Point Types for FloBoss 100-Series, FloBoss 407, and FloBoss 500-Series

Point Types Description

0

1

2

Configurable Opcode

Discrete Inputs

Discrete Outputs

FloBoss

100-Series

Yes

Yes

Yes

FloBoss

407-Series

Yes

Yes

Yes

FloBoss

500-Series

Yes

Yes

Yes

16 www. kepware.com

17

33

34

35

36

37

8

10

12

13

14

15

16

17

19

20

3

4

5

6

7

21

22-23

24

25–31

32

38

53

54

55

56

57

58

59

60-77

80

85

44

45

46

47

48

49

50

52

39

40

41

42

43

Analog Inputs

Analog Outputs

Pulse Inputs

PID Control*

AGA Flow Parameters*

History Parameters

AGA Flow Values*

ROC Clock

System Flags

Communication Ports

System Variables (ROC Information)

FST Parameters

Soft Points

Database Setup

ROC Tasks

Diagnostics

Information for User Defined Points

User Defined Points

Reserved

User Defined Points

User Defined – Typically Modem Config for

COM1

User Defined – Typically Modem Config for LOI and COM2

User Defined – Typically Modbus Config for

COM1

User Defined – Typically Function Config for

COM1

User Defined – Typically Host Config for COM1

User Defined – Typically Modbus Config for LOI and COM2

User Defined: Typically Function Config for LOI and COM2

User Defined – Typically Host Config for COM1

Multi-Variable Sensor (MVS) Parameters

AGA Run Parameters*

Extra Run Parameters*

User Lists

Power Control

Meter Calibration and Sampler

Meter Configuration Parameters

Meter Flow Values

PID Control Parameters

Upload to Disk

Download to ROC

Battery Parameters

Modbus Configuration Parameters

Modbus Function Tables

Modbus Special Function Table

AI Calibration

Keypad / Logon Security Parameters

Revision Information

Program Flash Control Parameters

SAM User Defined Parameters

Enhanced Communication (ECM) Parameters

HART Parameters

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

Yes

Yes

No

N/A.

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

Yes

Yes

Yes

Yes

Yes

Fisher ROC Serial Driver Help

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

Yes

No

N/A.

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

Yes

Yes

No

Yes

No

No

No

Yes

No

No

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

N/A.

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

Yes

Yes

Yes

Yes

Yes

No

No

Yes

No

No

Yes

Yes

Yes www. kepware.com

Fisher ROC Serial Driver Help

18

98

117

118

120

121

86

88

89

93

94

122

Extended History Parameters

BLM User Lists

Chart User List Parameters

License Key Information Parameters

User C Program Parameters

Extended Soft Point Parameters

Modbus Configuration Parameters

Modbus Register Mapping Parameters

Modbus Master Modem Configuration

Modbus Master Polling Table Configuration

Parameters

DS800 Configuration Parameters

Yes

Yes

Yes

Yes

Yes

Yes**

Yes

Yes

Yes

Yes

Yes

No

No

No

No

No

No

No

No

No

No

No

*FloBoss 100-Series and FloBoss 500-Series Backward Compatibility.

**This point type is only supported by FloBoss 107.

ROC Point Types for RegFlo

3

4

8

13

Point Types Description

0

1

2

Configurable Opcode

Discrete Inputs

Discrete Outputs

Analog Inputs

Analog Outputs

History Parameters

System Flags

14

15

Communication Ports

System Variables 

57

80

81

84

Point Types

17

19

56

86

NA.

Description

Soft Points.

Database Setup.

AI Calibration.

Keypad / Logon Parameters.

Regulator Parameters.

Logic Alarm Parameters.

User Discrete Values.

Extended History Parameters.

NA.

No

No

No

No

No

No

No

No

No

No

No

Logical / Point Number Details

Within each point type, individual points are referenced by a Logical Number or a Point Number. The point numbers used by ROC protocol for point types 1 to 5 are based on a physical input or output (I/O) with a rack and module location. All other point types use a Logical Number, and are numbered in sequence.

Physical Point Numbers 0 to 69

For point types 1 through 5, there are point numbers for the field I/O and for the diagnostic inputs. They are as follows: l l

Point Numbers 0 to 63 are assigned to field I/O (built-in or modular, 64 maximum). For example, if there were ten I/O modules in a ROC364, they would be points 0 through 9. The ROC I/O point database would reference these points by rack and module location, such as A1 through A10.

Point Numbers 64 to 69 are assigned to the diagnostic (system) I/O. For example, the five diagnostic points in a ROC364 would be 64 through 68. The ROC I/O point database would reference these points by rack and module (namely, E1 to E5).

Logical Point Numbers 0 to 127

For all other point types (0 and 6–59), the point number is 0 to x, where x is one less than the total number of points that exist for that point type. For example, the four MVS points in a FloBoss 407 would be logical numbers

0 through 3.

Note: All parameters are 0-based for each point type.

User-Defined Point Types

User-Defined Points (UDP) make user program data available to ROCLINK and OPC clients. They are generally used for configuration purposes. When creating a User-Defined Point in the server, the server Configuration will always set the data type to Default. The data type will later be read live from the device.

Important: Users must reinitialize the server after upgrading the user program on a device; otherwise, the server will not be able to access the new points available in the upgraded user program.

www. kepware.com

19

Fisher ROC Serial Driver Help

Supported Device Models

All FloBoss 100 Series devices.

Supported User-Defined Point Range

22 to 23

25 to 39

178 to 189

Troubleshooting

To avoid potential issues, users should do the following: l l l

Verify that the point type is within the supported UDP range.

Verify that the point type exists in one of the user programs installed on the device.

Check the Event Log for the following error message, which will occur if the server fails to parse the UDP

configuration: Unable to parse the User-Defined Point configuration information for point type

'<point type>' on device '<device name>' .

Bit Assignments

The graphic below shows a sample bit assignment. The bits in each byte are numbered 0 to 7, right to left, with

Bit 7 shown the furthest to the left. A 1 in any bit indicates that it is active or enabled.

www. kepware.com

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement

Table of contents