Appendix B

Specifications

A p

Specific ati ons x p e n d x B

Environment

Ambient Temperature Range

(operating)

-40°C to 70°C [ -40°F to 158°F]

Note:

Rectifier output derates above 50°C and below -10°C [14°F].

The maximum output current of APS12 models with the LVD option is limited to 400A (or less depending on ambient temperature). See System Output.

Relative Humidity

(operating and storage)

<95% (non condensing)

Dimensions H, W, D

APS6-300/APS6-500

APS12-300

6U, 19” mounting, 335 mm [13.2”]*

9U, 19” mounting, 335 mm [13.2”]*

* Additional clear air space is required at rear for rectifier exhaust air venting. See details on page

28

.

Weight

APS6-300/APS6-500

APS12-300

12kg [26.4 lb]*

18kg [40 lb]*

Rectifier module

* weight of a typical configuration, excluding rectifiers

1.7kg [3.7 lb]

System Input

Input Voltage

Refer to the rectifier specifications for range.

220-240V (nominal L-N)

208V (nominal L-L)

Maximum Input Current

(per phase @ V = 175V)

APS6 models 1P+N+PE (220-240V nom.):

2P+PE (208V nom.):

3P+N+PE (220-240V nom.):

3P+PE (208V nom.):

Frequency Range

Earth Leakage Current (maximum)

APS12 models

(with two ac feeds)

1P+N+PE (220-240V nom.):

2P+PE (208V nom.):

3P+N+PE (220-240V nom.):

3P+PE (208V nom.):

45-66Hz

1.3mA per rectifier

72A

72A

24A

42A

2 x 72A

2 x 72A

2 x 24A

2 x 42A

Copyright © 2007-2012 Eaton Corporation. All Rights Reserved.

IPN 997-00012-49F November 2012

73

Access Power Solutions Installation and Operation Guide (APS6-300/500 and APS12-300 Series)

System Output

Output Voltage (nominal)

Dependent on rectifier model.

Output Voltage Range

24V or 48V

21.5 - 32V / 43 - 57.5V

Output Power (maximum)

APS6-300 models:

APS6-500 models:

APS12-300 models:

Load Current (maximum)

APS6-300 models

Total Load

Essential (Priority) Load

Non-essential (Non-priority) Load

APR48-3G (48V)

187A

187A

187A

APS6-500 models (48V)

Total Load

Essential (Priority) Load

Non-essential (Non-priority) Load

187A

187A

187A

APS12-300 models

Total Load

Essential (Priority) Load

Non-essential (Non-priority) Load

360A

270A

270A

No LVD:

With LVD:

8.9kW* @ 48V

8.6kW* @ 48V

8.64kW* @ 28.8V or 12.0kW* @ 48V

No LVD: 17.2kW* @ 48V

With LVD:

17.2kW* @ 48V up to 40°C [104°F] ambient

16.1kW* @ 48V up to 45°C [113°F] ambient

15.0kW* @ 48V up to 50°C [122°F] ambient

APR48-ES (48V)

187A

187A

187A

210A**

60A**

150A**

360A

270A

270A

* subject to the maximum load currents as specified

** must include a minimum of three battery MCBs when battery connected

-

-

-

-

-

-

APR24-3G (24V)

280A

200A

200A

74

Copyright © 2007-2012 Eaton Corporation. All Rights Reserved.

IPN 997-00012-49F November 2012

Specifications

Rectifiers

Operating Ranges

APR24-3G/APR48-3G:

APR48-ES:

Input Current (maximum)

20°C [68°F]

Rated Output Power

Rated Output Current

Preset Voltage

Rectifier Input Fuses (internal)

Rated:

175 – 275V

Full output up to 50°C [122°F]

Extended:

90 – 300V

Reduced output power below 175V

Rated:

185 – 275V

Full output up to 50°C [122°F]

Extended:

90 – 300V

Reduced output power below 185V

APR24-3G:

APR48-3G:

APR48-ES:

APR24-3G:

APR48-3G:

APR48-ES:

APR24-3G:

APR48-3G:

APR48-ES:

9.5A @ 175V ac

12A @ 175V ac

12A @ 185V ac

1440W

1800W

2000W

50A @ 28.8V

37.5A @ 48V

41.7A @ 48V

APR24-3G:

APR48-3G:

APR48-ES:

16A, 250V

27V ± 0.1V

54.5V ± 0.1V

54.5V ± 0.1V

Digital Outputs/Alarm Relays (IOBGP)

Number of Digital Outputs/Relays

Contact Arrangement

Contact Rating

Connectors

Wire Size

Maximum Cable Length

6 (one also used for Monitor OK alarm)*

One changeover contact per relay

0.1A @ 60V dc maximum

Screwless terminal blocks

0.5 - 2.0mm

2

[20 - 14 AWG]

20m (65 feet)

Isolation Relay connections are isolated to 500V dc from all other circuitry, earth and system common.

* Digital Output 6 is also used as the Monitor Fail alarm relay. It will de-energize if the I/O board loses power or loses communication with the SC200 or SC100.

Copyright © 2007-2012 Eaton Corporation. All Rights Reserved.

IPN 997-00012-49F November 2012

75

Access Power Solutions Installation and Operation Guide (APS6-300/500 and APS12-300 Series)

Digital Inputs (IOBGP)

Number of Digital Inputs

Connectors

Wire Size

Maximum Cable Length

Input Types

Input Range

Input Common

Input Protection

6

Screwless terminal blocks

0.5 - 2.0mm

2

[20 - 14 AWG]

20m (65 feet)

Voltage-free switch or relay contacts only

Live Bus to Live Bus + 5V

Same bus as used for current shunts (Live bus is standard)

Protected against damage from short circuit to live or common bus

Temperature Sense Inputs (IOBGP)

Number of Temperature Sense Inputs

Range

Resolution

Accuracy

Maximum Cable Length

Connector

Current Sense Inputs (IOBGP)

Number of Current Sense Inputs

Range

Resolution

Accuracy

Maximum Cable Length

Connector

2 -

One only connected as standard. Second input available (requires additional temperature sensor).

2.53V to 3.43V (-20 to +70°C [-4 to +158°F])

< 0.01V (< 1°C [1.8°F])

±1°C [1.8°F] at 25°C [77°F], ±2°C [3.6°F] over rated temperature range

20m (65 feet)

RJ45

3 (one used for internal current shunt)

–50 to +50mV

<50µV

±0.5% at 25°C [77°F], ±1% over rated temperature range

10m (32 feet)

RJ45

76

Copyright © 2007-2012 Eaton Corporation. All Rights Reserved.

IPN 997-00012-49F November 2012

Specifications

Battery Mid-point Monitoring (SC200 only)

Number of Strings

Range

Resolution

Accuracy

Maximum Cable Length

Standard:

Maximum:

4

24 (with additional IOBGP-01 I/O boards)

–35V to +35V

<30mV

±0.5% at 25°C [77°F], ±1% over rated temperature range

20m (65 feet)

Low Voltage Disconnect (IOBGP)

Number of contactor connections

Number of LVD channels

Contactor Type

Contactor Coil Voltage (nominal)

Maximum Hold-in Current

Maximum Cable Length

Connector

2 per IOBGP I/O board

SC100 systems: 2, SC200 systems: 16

Normally Open (NO) or Normally Closed (NC)*, with or without auxiliary contacts.

* For NC contactor operation the SC100 and

IOBGP must be powered from the battery side of the LVD.

With auxiliary contacts: 12V, 24V or 48V

Without auxiliary contacts: Equal to nominal system voltage

1.2A (per contactor)

3m (10 feet)

MTA156 (4-way)

Communications

USB (SC200 only)

RS232

Version:

Connector:

Interface:

Connector:

1.1 (12Mbits/s)

USB B (female)

RS232 (DTE)

DB9M

Ethernet (SC200 only)

External modem options

Interface:

Connector:

Protocols:

10baseT

RJ45

TCP/IP, SNMP, S3P over IP, http (Web), https (secure Web),

SNTP, Modbus-TCP, Serial

Server

MAC Address: See details in the System

Controller Operation

Handbook.

Web browser: Microsoft Internet Explorer 8 or later (IE6 is compatible but with reduced performance), Mozilla

Firefox 3.0 or later.

Type:

Operation:

* Can operate as a backup for Ethernet communications (SC200 only).

PSTN or GSM

Dial in/Dial out on alarm*

Copyright © 2007-2012 Eaton Corporation. All Rights Reserved.

IPN 997-00012-49F November 2012

77

Access Power Solutions Installation and Operation Guide (APS6-300/500 and APS12-300 Series)

78