2 Installation
•
•
2.1 Space Requirements
Installation plate thickness: 1.5 - 7.5 mm (0.06 - 0.3 inch)
Space requirements when installing the operator panel:
100 mm
(4.0 inch)
152 mm
(5.98 inch)
50 mm
(2.0 inch)
50 mm
(2.0 inch)
100 mm
(4.0 inch)
100 mm
(4.0 inch)
202 mm
(7.95 inch)
57 mm
(2.24 inch)
Caution:
The openings on the enclosure are for air convection. Do not cover these openings.
2.2 Installation Process
1. Unpack and check the delivery. If damage is found, notify the supplier.
Installation
Panel cut out 180 x 130 mm
(7.09 x 5.12 inch) x 4
Note:
Place the operator panel on a stable surface during installation.
Dropping it or letting it fall may cause damage.
Beijer Electronics, MAEN809F 7
Installation
2. Place the panel cut out where the operator panel is to be situated, draw along the outer sides of the holes and cut according to the markings.
3. Secure the operator panel in position, using all the fastening holes and the provided brackets and screws: x 4
0.5 - 1.0 Nm
Beijer Electronics, MAEN809F 8
Installation
4. Connect the cables in the specified order, according to the drawing and steps below.
Caution:
• The operator panel must be brought to ambient temperature before it is started up. If condensation forms, ensure that the operator panel is dry before connecting it to the power outlet.
• Ensure that the operator panel and the controller system have the same electrical grounding (reference voltage level), otherwise errors in communication may occur.
• Ensure that the voltage and polarity of the power source is correct.
• Separate high voltage cables from signal and supply cables.
• Shielded communication cables are recommended.
B
RS422/
RS485
RS232
24V DC
C
D
A
Power
Controller
24V DC
Ethernet
–
–
–
–
Connect cable A.
Connect cable B, using an M5 screw and a grounding conductor (as short as possible), that is sized correctly according to local electrical codes.
Connect cable C.
Connect cable D.
5. Carefully remove the laminated film over the operator panel display, to avoid static electricity that could damage the panel.
Beijer Electronics, MAEN809F 9
advertisement
Related manuals
advertisement
Table of contents
- 4 1 Safety Precautions
- 4 General
- 4 UL and cUL Installation
- 6 During Installation
- 6 During Use
- 6 Service and Maintenance
- 6 Dismantling and Scrapping
- 7 2 Installation
- 7 Space Requirements
- 7 Installation Process
- 10 Mode Switches
- 10 Connections to the Controller
- 10 Other Connections and Peripherals
- 11 3 Technical Data
- 13 4 Chemical Resistance
- 13 Metal Casing
- 13 Touch Screen and Overlay Material
- 13 Autotex F
- 14 Touch Screen Surface
- 15 Touch Screen Protector
- 16 5 Operator Panel Drawings
- 16 Communication Ports
- 17 EXTER T60/T60m Outline
- 18 6 Additional Installation Tips
- 18 Grounding the Operator Panel
- 19 Ethernet Connection in the Panel
- 20 To Achieve Better EMC Protection
- 21 Ambient Temperature
- 22 Safety
- 23 Galvanic Isolation
- 24 Cable and Bus Termination RS