Additional Installation Tips

6 Additional Installation Tips

When experiencing communication problems in for example noisy environments or when operating close to temperature limits, the following recommendations are to be noticed.

6.1 Grounding the Operator Panel

Mounting plate in the cabinet Door

Operator panel

3

2

Power supply

1

24 V DC

Ferrite core

6

5

4

5350

The operator panel’s mounting clamps do not provide a secure grounding connection between the panel and the device cabinet, see 1 in drawing above.

1. Connect a wire that is sized correctly according to local electrical codes between the operator panel’s quick-connect plinth and the panel’s chassis, see

2 in drawing above.

2. Connect a 6 or 4 mm 2 wire or grounding braid between the panel’s chassis and the closest grounding point on the door, see 3 in drawing above.

3. Connect a strong but short grounding braid between the door and the device cabinet, see 4 in drawing above.

4. Twist the cables onto the 24 V DC feed, see 5 in drawing above.

2 turns around the ferrite core provide 4 times the suppression of 1 turn.

3 turns around the ferrite core provide 9 times the suppression of 1 turn.

A ferrite core suppresses disturbances to the 24 V feed, see 6 in drawing above.

Note:

The grounding wires should be short and the conductor should have a large area.

A long, thin grounding wire has a very high impedance (resistance) at high frequencies and will not guide disturbances to the ground.

Multi-wire conductors are better than single wire conductors with the same area.

A braided conductor wire with the same area is even better. The best is a short, thick grounding braid.

Beijer Electronics, MAEN809F 18