Wired Clock Circuit Option. American Time AllSync IQ ASQMSTR-00X2E, AllSync IQ ASQMSTR-00X6E, AllSync IQ ASQMSTR-00X8E

Add to My manuals
57 Pages

advertisement

Wired Clock Circuit Option. American Time AllSync IQ ASQMSTR-00X2E, AllSync IQ ASQMSTR-00X6E, AllSync IQ ASQMSTR-00X8E | Manualzz

Wired Clock Circuit Option

1:49

FRI OCT 3 2014

American Time 

800-328-8996

Wired Clock Circuit Installation

To install wired clock circuits:

1. Disconnect and lock out power to the AllSync IQ Master and any circuit wiring.

2. Remove the terminal block cover from the AllSync IQ.

a. Remove screw from each side of the cover.

b. Lift the cover up off the unit.

3. Route signal circuit wires into the wiring compartment of the AllSync IQ.

1:49

FRI OCT 3 2014

:45

AM

American Time 

800-328-8996

a. Remove knockout(s).

b. Use copper conductors only.

c. Use strain relief connector fittings in the knockout holes to secure the wires.

d. Route the wires into the wiring compartment, leaving enough slack to make all connections to the relay terminals.

4. Connect clock wires to the circuit relay terminals

H N

NO COM

CLOCK 1

NC NO COM

CLOCK 2

NC NO

BELL 1

COM NO

BELL 2

COM NO

BELL 3

COM NO

BELL 4

COM NO

BELL 5

COM NO

BELL 6

COM

Clock Circuit Terminals

Clock Circuit Fuses Surge Supression

ON/OFF Switches

See Appendix H on Page 50 for Clock Circuit Wiring Diagram

12

© American Time

1:49

FRI OCT 3 2014

American Time 

800-328-8996

Adjust Time Menu

The Adjust Time menu serves two functions:

1. Manual correction of impulse secondary clocks, and

2. Simple synchronization of the AllSync IQ to an external time source.

u

9 to access the Adjust Time Menu v

1 to enter Adjust System Clocks Menu w

1 to bring up the Calculated Adjust screen

Enter the time shown on the secondary clocks (to the nearest

minute). The time entered should be in 12 hour format as AM/PM

settings are irrelevant.

O . The time difference between the secondary clocks and

the system controller is displayed.

O to initiate automatic correction of the secondary clocks

and return to the Adjust Time screen.

x

2 in the Adjust System Clocks menu (#3 at right) brings

up the Manual Adjust screen.

> repeatedly to correct impulse clocks manually.

when finished to return to the Adjust Time menu.

y

2 in the Adjust Time screen (#2 above) causes the unit to attempt synchronization with external time sources* in order of priority. If successful, a message confirming this flashes before the Time Display screen appears.

*The time sync priority can be configured. Reference Settings and

Configuration on Page 33.

2

Adjust Time

Choose:

1=Adjust System Clks

2=Ethernet Sync Now

3

Adjust System Clocks

1=Calculated Adjust

2=Man. Adjust Impulse

0=Cancel

3a

4

Calc Clock Adjust

Enter Time Shown on secondary clocks

00:00

Adjust System Clocks

Manual Adj. Impulsed

>=Advance Clocks

(1 per min) OK=Done

© American Time