4.10 Ground Fault Interrupt (GFI)

Operation

See Graphic: wc_gr000545

The two 120V, 20 Amp receptacles (f) are protected by a ground fault circuit interrupt (GFI). The GFI shuts off the power to the receptacle when a ground fault occurs in the generator or to a piece of equipment attached to the generator.

The GFI should be tested for proper operation every time the generator is used.

To test GFI:

Start generator. Turn auto idle "OFF". Push TEST button (h) on receptacle in. The RESET button (g) will pop out. Power is now off at the receptacles. If the RESET button does not pop out, the GFI is not working. Do not run generator until the problem can be corrected. To restore power to receptacles, push the RESET button in.

If the RESET button pops out during operation, stop the generator and check generator and equipment for defects.

4.11 Twist Lock Receptacles

See Graphic: wc_gr000545

Twist-lock receptacles (c, j) are used at the 120V 30A and 120/240V

30A outlets. These receptacles are not protected by the GFI.

To attach a power cord to a twist-lock receptacle, insert the plug into the receptacle and turn it clockwise to lock it in place.

4.12 Engine Switch

See Graphic: wc_gr000545

GS 5.6A only:

The engine switch (a) completes the circuit to the engine's ignition system. The switch must be set to "START" and then held down to crank the starter motor and start the engine. When the switch is released it returns back to the "ON" position and must be kept in this position while the engine is running.

To stop engine, set switch to "OFF". wc_tx000152gb.fm

21

advertisement

Related manuals

Frequently Answers and Questions

What type of fuel does the G5.6A generator use?
The G5.6A generator uses unleaded gasoline with a minimum octane rating of 87.
How many receptacles does the G5.6A generator have?
The G5.6A generator has two 120V receptacles and one 240V receptacle.
What is the maximum wattage that the G5.6A generator can produce?
The G5.6A generator can produce a maximum of 5,600 watts of power.
Does the G5.6A generator have an electric start?
No, the G5.6A generator does not have an electric start. It must be started manually with a recoil starter.
How long can the G5.6A generator run on a full tank of fuel?
The G5.6A generator can run for up to 8 hours on a full tank of fuel at 50% load.