7. TROUBLESHOOTING

!

WARNING power before replacing the instrument.

before mounting or removing the instrument.

all the wiring is completed.

instrument.

experience in this type of work.

48

CAUTION

All wiring must be completed before power is turned on to prevent electric shock, instrument failure, or incorrect action.

The power must be turned off before repairing work for input break and output failure including replacement of sensor, contactor or SSR, and all wiring must be completed before power is turned on again.

This section lists some of the main causes and solutions for communication problems.

If you can not solve a problem, please contact RKC sales office or the agent, on confirming the type name and specifications of the product.

Problem

No response

Probable cause

Wrong connection , no connection or disconnection of the communication cable

Breakage, wrong wiring, or imperfect contact of the communication cable

Mismatch of the setting data of communication speed and data bit configuration with those of the host

Wrong address setting

Solution

Confirm the connection method or condition and connect correctly

Confirm the wiring or connector and repair or replace the wrong one

Confirm the settings and set them correctly

Continued on the next page.

IMR01D02-E3

7. TROUBLESHOOTING

Continued from the previous page.

Problem Probable cause

No response

Error in the data format

Transmission line is not set to the receive state after data send (for RS-485)

EOT return The specified identifier is invalid

Error in the data format

NAK return Error occurs on the line (parity bit error, framing error, etc.)

Solution

Reexamine the communication program

Confirm the identifier is correct or that with the correct function is specified.

Otherwise correct it

Reexamine the communication program

Confirm the cause of error, and solve the problem appropriately. (Confirm the transmitting data, and resend data)

BCC error

The data exceeds the setting range

The specified identifier is invalid

Confirm the setting range and transmit correct data

Confirm the identifier is correct or that with the correct function is specified.

Otherwise correct it

IMR01D02-E3 49

7. TROUBLESHOOTING

Problem

No response

Probable cause

Wrong connection , no connection or disconnection of the communication cable

Breakage, wrong wiring, or imperfect contact of the communication cable

Mismatch of the setting data of communication speed and data bit configuration with those of the host

Confirm the connection method or condition and connect correctly

Confirm the wiring or connector and repair or replace the wrong one

Confirm the settings and set them correctly

Solution

Error code

1

Error code

2

Error code

3

Error code

4

Wrong address setting

A transmission error (overrun error, framing error, parity error or CRC-16 error) is found in the query message

The time interval between adjacent data in the query message is too long, exceeding

24 bit’s time

Function cod error

(Specifying nonexistent function code)

When written to read only (RO) data,

When any address other than 0000H to

001AH is specified, etc.

When the data written exceeds the setting range, When the specified number of data items in the query message exceeds the maximum number of data items available

Self-diagnostic error

Re-transmit after time-out occurs or verify communication program

Confirm the function code

Confirm the address of holding register

Confirm the setting data

Turn off the power to the instrument. If the same error occurs when the power is turned back on, please contact RKC sales office or the agent.

50

IMR01D02-E3