Specifications
System Input
Input Voltage
Rated Input Current
@ 120V RMS with APU48 rectifiers:
@ 240V RMS with APU48 rectifiers:
@ 208-240V RMS with APR48 rectifiers:
IEC AC Cord Sets
Cable
Connector 1 (AC supply)
Connector 2 (Data Power Solution)
Frequency Range
Maximum Earth Leakage Current
APU48: L-N: 95-275V RMS
APR48: L-N: 185-275V RMS
APS3: 21A (7A per ac power cord)
APS6: 42A (7A per ac power cord)
APS3: 10.5A (3.5A per ac power cord)
APS6: 21A (3.5A per ac power cord)
APS3: 24A (8A per ac power cord)
APS6: 48A (8A per ac power cord)
Cable rated according to AC voltage (refer to the Rated Input Current values) and local wiring regulations.
Refer to the Rated Input Current values according to AC voltage.
IEC type C-13
45-66Hz
1.5mA (per Access Power Rectifier)
System Output
Output Voltage (nominal)
Output Power (maximum)
APS3-058 and APS3-060:
APS3-059 and APS3-061:
APS6-058:
APS6-059:
48V
2.16kW with 3 APU48 rectifiers
4.50kW with 3 APR48 rectifiers
1.70kW with 3 APU48 rectifiers
3.00kW with 3 APR48 rectifiers
4.32kW with 6 APU48 rectifiers
9.00kW with 6 APR48 rectifiers
3.40kW with 6 APU48 rectifiers
7.10kW with 6 APR48 rectifiers
Environment
Ambient Temperature Range (operating)
Relative Humidity (operating and storage)
-10°C to +40°C [+14°F to 104°F]
<95% (non condensing)
28
Copyright © 2006-2009 Eaton Corporation. All Rights Reserved.
10640205 February 2009
Data Power Solutions Quick Start Guide
Dimensions H, W, D
APS3-058 and APS3-059
APS3-060 and APS3-061
3U, 19” mounting, 390mm [15.35”]*
150mm, 465mm, 415mm
[5.9", 18.31", 16.34”]*
6U, 19” mounting, 390mm [15.35”]* APS6-058 and APS6-059
Access Power Rectifier 3U, 66mm [2.6"], 280mm [11"]
* Additional clear air space is required at rear for rectifier exhaust air venting.
Weight
APS3
APS6
Access Power Rectifier
* Typical configuration, excluding rectifiers
6kg [13 lb]*
10kg [22 lb]*
1.9kg [4.2 lb]
Rectifiers
APR48
Rated Input Voltage Range
Maximum Input Current
Rated Output Power
185 - 275 Vrms
Full output up to 50°C
[122°F]
150 - 185Vrms
Full output up to 30°C
[86°F]
95 - 275 Vrms
Full output up to
50°C [122°F]
10Arms @ 185 Vrms 10 Arms @ 95 Vrms
1500W 720W
Rated Output Current
Preset Voltage
31A @ 48V
54.5V
15A @ 48V
54.5V
Copyright © 2006-2009 Eaton Corporation. All Rights Reserved.
10640205 February 2009
29
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 4 Worldwide Support
- 4 For Further Information and Technical Assistance
- 5 General Description
- 5 APS3 and APS6 Series (48V) DC Power Systems
- 5 Access Power Rectifiers
- 5 SM45 Supervisory Module
- 6 Low Voltage Disconnect (if applicable)
- 6 Pre-Installation
- 6 Warnings
- 6 Inputs
- 9 Equipment Classification
- 9 Outputs
- 10 Batteries (if applicable)
- 10 Rectifiers
- 12 Location and Environment
- 12 Servicing
- 13 EMC Compliance
- 14 Inspecting the Equipment and Reporting Damage
- 14 Installation
- 14 Mounting the APS DC Power System
- 16 Connecting the DC Load Cables
- 19 Installing the External Batteries (if applicable)
- 22 Connecting the Battery Cables (if applicable)
- 24 Installing the Battery Temperature Sensor (if batteries are fitted)
- 24 Connecting the APS DC Power System to the AC Supply
- 25 Commissioning
- 25 Inserting the Access Power Rectifiers
- 25 Pre-Power-Up Check
- 26 Applying AC Power
- 26 Configuring the APS DC Power System for Operation
- 26 Applying DC Power to the Load
- 27 Output Circuit Breaker Field Replacement and Repair
- 27 UL Listed Mark
- 27 Desktop variants APS3-060 & APS
- 27 Battery Input Circuit Breakers
- 27 Contact Information
- 28 Specifications