Model FHC 50/FHM10 Fume Hood Controller/Monitor Operation and


Add to my manuals
105 Pages

advertisement

Model FHC 50/FHM10 Fume Hood Controller/Monitor Operation and | Manualzz

Calibration

The calibration section explains how to calibrate the controller and how to zero a TSI flow station pressure transducer (optional). The Fume Hood Monitor or Controller must be calibrated, after being installed on the fume hood, to provide accurate indication of fume hood face velocity and/or exhaust flow. The FHM10

Monitor and FHC50 Controller will warn the user with a display message if it has not been calibrated.

NOTE:

This section assumes that the appropriate sensor has been correctly installed. Inaccurate readings may be detected if sensor is not installed correctly. Review the Installation Instructions and verify that the sensor is installed correctly (usually only a problem on initial set up).

The following items are needed to calibrate a Model FHM10 Fume Hood Monitor or Model FHC50 Fume

Hood Controller:

Masking tape

Tape measure

Portable Air Velocity Meter such as TSI V

ELOCI

C

ALC

®

Model 9545 or Model 9515.

WARNING:

The controller is disabled during calibration. Containment may not be maintained.

To begin the calibration process, enter

CALIBRATION

menu (see Software Programming if not familiar

with keystroke procedure).

Face Velocity Calibration

Face velocity can be controlled using either a sidewall sensor or sash-position sensor with a venturi valve.

Sidewall Velocity Sensor—Sensor Zero

1.

Select VEL SENSOR ZERO item.

2.

The controller will prompt to “Tape over sensor, then press

.” Place a piece of tape over the velocity sensor opening to seal off air flowing past the sensor and press the

soft key.

3.

The display will indicate a countdown for the automatic sensor zero procedure, which takes

120 seconds. While counting down the 120 seconds, the controller will also display the current sensor voltage.

4.

After the 120 second countdown, the controller will display “Remove tape from sensor, then press

.” Remove tape from sensor and press the

key to save the zero point.

Sidewall Velocity Sensor—Sensor Span

NOTE:

Always zero sensor prior to adjusting the sensor span. A comparison thermal anemometer is required to calibrate the velocity span. Confirm a good average face velocity is present in the fume face before adjusting the span.

1.

Open the fume hood sash 60% (or to working height) and let the controller reach face velocity set point.

2.

Select VEL SENSOR SPAN item (30 second countdown). After the countdown, the VEL

SENSOR SPAN submenu will be displayed.

3.

Use a thermal anemometer to traverse the open sash area and obtain the average face velocity of the air passing into the hood.

49

4.

Compare the thermal anemometer reading to the

SPANNED VEL

reading on the controller.

5.

At the ENTER SPAN FACT menu item, press the quick keys to adjust the factor until the

SPANNED VEL

reading on the controller display matches the thermal anemometer velocity.

6.

Press the

ENTER (

)

soft key to save the sensor span calibration.

NOTE

: To verify proper calibration, re-enter

VEL SENSOR SPAN

item and compare

SPANNED VEL reading to a new thermal anemometer traverse.

7.

Exit menu, sidewall sensor calibration is complete.

WARNING:

Calibrating the sidewall velocity span on the controller may be an iterative process that takes 1 to 3 trials to get an accurate calibration. After adjusting the span factor, check the calibration to verify an accurate calibration.

Sash Position Calibration

1.

Calibrate flow using LOM VENTURI Calibration section.

2.

Calibrate vertical sash sensor using CALIBRATE SASH POT section.

3.

Enter

SASH FLOW CONTROL

item.

4.

Controller will prompt “Raise sash to 24 inches height then press

.” Open the sash(es) to the 24-inch height and press the

key. a.

The FHC50 controller will display following items:

Desired Flow

Show Sash % Open

Actual Flow

Save & Continue

Set flow for

Flow set point to achieve desired face velocity

Readout of current sash % open

Readout of current measured flow

Use to save data point

Desired face velocity b.

Perform a face velocity traverse using a thermal anemometer. Compare the face velocity traverse reading to the face velocity set point. c.

Adjust the Desired Flow to change the flow control set point for the 24-inch sash position until actual face velocity matches the Set flow for set point. d.

Repeat steps b. and c. as needed before selecting Save & Continue to save the high sash position calibration.

5.

Controller will prompt “Lower sash to 12 inches height then press

.” Lower the sash(es) to the

12-inch height, so the fume hood bypass (if present) is just covered, and press the

key. a.

The FHC50 controller will display following items:

Desired Flow

Show Sash % Open

Actual Flow

Save & Continue

Set flow for

Flow set point to achieve desired face velocity

Readout of current sash % open

Readout of current measured flow

Use to save data point

Desired face velocity b.

Perform a face velocity traverse using a thermal anemometer. Compare the face velocity traverse reading to the face velocity set point.

50 Part Two

c.

Adjust the Desired Flow to change the flow control set point for the 24-inch sash position until actual face velocity matches the Set flow for set point. d.

Repeat steps b. and c. as needed before selecting Save & Continue to save the sash mid-point calibration.

6.

Controller will prompt “Lower sash to 2 inches height then press

.” Lower the sash(es) to the 2-inch height, so the sash(es) are nearly closed, and press the

key. a.

The FHC50 controller will display following items: b.

Perform a face velocity traverse using a thermal anemometer. Compare the face velocity traverse reading to the face velocity set point.

Desired Flow

Show Sash % Open

Actual Flow

Save & Continue

Set flow for

Flow set point to achieve desired face velocity

Readout of current sash % open

Readout of current measured flow

Use to save data point

Desired face velocity c.

Adjust the Desired Flow to change the flow control set point for the 24-inch sash position until actual face velocity matches the Set flow for set point. d.

Repeat steps b. and c. as needed before selecting Save & Continue to save the sash closed calibration.

7.

Controller will display “Sash position vs. flow is done calibrating. Press

.” Press the

key to save calibration and continue.

Flow Calibration

Flow can be measured using a Pressure Flow Station, Linear Flow Station, LOM Venturi, 6-Pt Venturi, or

Calculated from face velocity and open sash area.

Pressure Flow Station Calibration

NOTE:

Flow stations are optional and may not be installed in your system.

1.

Enter CALIBRATE FLOW item.

2.

Set

FLO STA AREA

to the duct area at the flow station location.

3.

Set

FLO STA PRESS FS

to match the range of the pressure transducer used.

Flow Station Pressure Transducer Zero

1.

Disconnect tubing between pressure transducer and flow station.

2.

Select FLO STA PRESS ZERO menu item.

3.

Press the

ENTER

(

)

soft key. Flow zero procedure, which takes 10 seconds, is automatic.

During the 10 second flow zero procedure, the display will indicate the current flow station pressure transducer voltage.

4.

Connect tubing between pressure transducer and flow station.

Technical Section

51

Low Flow Calibration

1.

Set FLO STA FS V to match the voltage output (0 to 10V or 0 to 5V) of the pressure transducer used.

2.

Close the sash.

3.

Select

FLO STA LO CAL

to enter a submenu with the following items:

FLO STA LO SETPT

PRESS ZERO VOLTAGE

PRESSURE VOLTAGE

MEASURED FLOW

ENTER ACTUAL FLOW

Damper position for low flow calibration

Voltage from pressure transducer during Flow Station Pressure

Transducer Zero

Current voltage from pressure transducer

Current flow rate

Input actual flow as measured with reference instrument here

5.

With the

FLO STA LO SETPT

at 0% (default), observe the

PRESSURE VOLTAGE

displayed on the screen, or use a voltmeter to read the voltage at the pressure input terminals 7-8 on the back of the controller.

6.

Slowly

increase

the

FLO STA LO SETPT

percentage value to adjust the damper position until the PRESSURE VOLTAGE (pressure transducer output) shows the first noticeable increase in voltage from the 0% position. A general rule of thumb is that the voltage change should occur with the damper between approximately 10 to 30% open.

NOTE:

Adjusting the FLO STA LO SETPT with the quick keys allows the

PRESSURE VOLTAGE to be displayed in real time.

7.

For reference only, the MEASURED FLOW item will display the default measured flow based on the current settings of the flow station (duct area, etc.).

8.

Determine the actual flow with a duct traverse.

9.

Enter the actual flow measurement under the

ENTER ACTUAL FLOW

menu item.

10.

Press the

ENTER

(

) soft key to save the flow data.

11.

The low flow calibration is complete. Exit the menu with the

ESC

key.

High Flow Calibration

1.

Enter CALIBRATION FLOW menu and raise the sash height to approximately 18 inches

(sash stop).

2.

Select

FLO STA HI CAL

to enter a submenu with the following items:

FLO STA LO SETPT

PRESS ZERO VOLTAGE

PRESSURE VOLTAGE

MEASURED FLOW

ENTER ACTUAL FLOW

Damper position for low flow calibration

Voltage from pressure transducer during Flow Station Pressure

Transducer Zero

Current voltage from pressure transducer

Current flow rate

Input actual flow as measured with reference instrument here

3.

With the FLO STA HI SETPT at 100% (default), observe the PRESSURE VOLTAGE displayed on the screen, or use a voltmeter to read the voltage at the pressure signal transducer input terminals 7-8 on the back of the controller.

4.

Slowly

decrease

the FLO STA HI SETPT percentage value to adjust the damper position until the

PRESSURE VOLTAGE

(pressure transducer output) shows the first noticeable

decrease

in

52 Part Two

voltage from the 100% position. A general rule of thumb is that the voltage change should occur with the damper between approximately 70 to 90% open.

NOTE:

Adjusting the FLO STA HI SETPT with the quick keys allows the

PRESSURE VOLTAGE to be displayed in real time.

5.

For reference only, the MEASURED FLOW item will display the default measured flow based on the current settings of the flow station (duct area, etc.).

6.

Determine the actual flow with a duct traverse.

7.

Enter the actual flow measurement under the

ENTER ACTUAL FLOW

menu item

8.

Press the

ENTER

(

)

soft key to save the flow data.

9.

The high flow calibration is complete. Exit the menu with the

ESC

key.

NOTE

: Use

BALANCE MODE

to verify flow station calibration.

Linear Flow Station Calibration

NOTE:

Flow stations are optional and may not be installed in your system.

1.

Enter

CALIBRATE FLOW

item.

2.

Set FLO STA AREA to the duct area at the linear flow station location.

3.

Set

FLO STA TOP VEL

to match the range of the linear flow station used.

4.

Set FLO STA FS V to match the voltage output (0 to 10V or 0 to 5V) of the linear flow station used.

5.

Linear flow station calibration should be complete. Exit the menu.

NOTE

: Use BALANCE MODE to verify flow station calibration.

LOM Venturi Calibration

NOTE:

LOM Venturi Valves are optional and may not be installed in your system.

1.

Obtain the venturi valve minimum and maximum flow, either by reading the label on the venturi valve or by performing duct traverses when the venturi valve is fully closed and fully opened.

2.

Enter CALIBRATE FLOW item.

3.

Set

VENTURILOM MIN

to the minimum venturi valve flow.

4.

Set VENTURILOM MAX to the maximum venturi valve flow.

5.

LOM Venturi Calibration can be adjusted using the

Flow KFactor

item.

6.

LOM venturi valve calibration is now complete. Exit the menu.

NOTE

: Use BALANCE MODE to verify LOM Venturi calibration.

6Pt Venturi Calibration

NOTE:

6Pt Venturi Valves are optional and may not be installed in your system.

If venturi valve flow data cannot be obtained from venturi valve label, perform duct traverse with venturi valve at 0%, 20%, 40%, 60%, 80% and

100% open (see item

CONTROL_OUT

in

DIAGNOSTICS

menu).

1.

Obtain the venturi valve calibration data by reading the label on the venturi valve.

2.

Enter

CALIBRATE FLOW

item.

Technical Section

53

3.

Enter venturi valve minimum flow in item

VENTURI PT1

.

4.

Enter 2nd point flow in item VENTURI PT2 .

5.

Enter 3rd point flow in item

VENTURI PT3

.

6.

Enter 4th point flow in item VENTURI PT4 .

7.

Enter 5th point flow in item VENTURI PT5 .

8.

Enter 6th point flow in item

VENTURI PT6

.

9.

6pt venturi valve calibration is now complete. Exit the menu.

NOTE

: Use

BALANCE MODE

to verify 6Pt Venturi calibration.

Calculated Flow Calibration

NOTE:

Calibrating Calculated Flow requires first calibrating the Face Velocity using the Sidewall Sensor and calibrating the Sash Pot.

1.

Enter

CAL SASH AREA

menu item.

2.

Controller will display current sash position and prompt “Fully close sash then press

.” Close the sash and press the

key.” After closing the sash(es) and pressing the

, controller will count down for 5 seconds while it allows control to stabilize.

3.

Controller will prompt to “Enter Actual Flow”. Perform a duct traverse or otherwise measure fume hood exhaust volume and enter it into the controller.

4.

Press the

ESC

key to continue.

5.

Controller will display current sash pot position and prompt “Fully open sash then press

.” Open the sash and press the

key.” After opening the sash and pressing the

, controller will count down for 5 seconds while it allows control to stabilize.

6.

Controller will prompt to “Enter Actual Flow”. Perform a duct traverse or otherwise measure fume hood exhaust volume and enter it into the controller.

7.

Press the

ESC

key to continue.

8.

Controller will display “Sash area vs position is calibrated. Press

.” Press the

key to save calibration.

NOTE:

Use BALANCE MODE to verify Calculated Flow calibration or use

CALIBRATE FLOW item to adjust the

FLOW K-FACTOR

.

Sash Opening Calibration

The Sash Opening may be calibrated using a Sash Pot (Vertical Sash Sensor).

Calibrate Sash Pot

1.

Enter CAL SASH POT item.

2.

Controller will display current sash pot voltage and prompt “Fully close sash then press

.” Close the sash(es) and press the

key.

3.

Controller will display current sash pot voltage and prompt “Fully open sash then press

.” Open the sash(es) and press the

key.

4.

Controller prompts “Sash position sensor is calibrated. Press

.” Press the

key to save calibration and exit the menu.

54 Part Two

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement

Table of contents