5-Inch Oval Installation in 2x4 Inch Stud Walls. M&G Duravent 3GV60, 5GVAF, 4GVRRA4, 3GVFS, 4GV60F, 3GVIS, 3GVRS4, 3GVFF, 4GVRS, 4GVX8
Add to My manuals28 Pages
advertisement
![5-Inch Oval Installation in 2x4 Inch Stud Walls. M&G Duravent 3GV60, 5GVAF, 4GVRRA4, 3GVFS, 4GV60F, 3GVIS, 3GVRS4, 3GVFF, 4GVRS, 4GVX8 | Manualzz 5-Inch Oval Installation in 2x4 Inch Stud Walls. M&G Duravent 3GV60, 5GVAF, 4GVRRA4, 3GVFS, 4GV60F, 3GVIS, 3GVRS4, 3GVFF, 4GVRS, 4GVX8 | Manualzz](http://s1.manualzz.com/store/data/060149644_1-24c904d0e31640ac39a7ff97a3d0d329-360x466.png)
5-INCH OVAL GAS VENT FOR
INSTALLATION IN 2” X 4” STUD
WALLS
MH6375 CATEGORY I APPLIANCES ONLY
Where pipe passes through the roof, maintain
1-inch minimum clearance to all combustible materials.
Install oval flashing, storm collar, and oval vent cap.
Gas vent shall extend at least 2 feet above the highest point where it passes through the roof, and at least 2-feet higher than any portion of the building within 8 feet.
Attach base plate to 2” x 4” support. Firestop spacers shall be installed as shown on all floors.
1.
Saw out portion of header between studs and install one firestop spacer.
2.
Nail the second firestop spacer in position, after oval pipe is in place.
3.
Additional floors above are installed in the same manner.
OVAL PIPE
FIRESTOP
SPACER
Use only vents labeled “For Exterior Use
Only”, above roofline. (Canada Only)
CAP
STORM COLLAR
ROOF FLASHING
FIRESTOP
SPACER
1 INCH MINIMUM
CLEARANCE TO
COMBUSTIBLES
OVAL
PIPE
OVAL
TEE
BASE PLATE
AND TEE
SUPPORT
2” X 4” SUPPORT
24
HIGH WIND CAP
DuraVent CAP
MALE END
STORM
COLLAR
ROOF
FLASHING SEE TABLE 1
SUPPORT
FEMALE END
1 INCH MINIMUM
CLEARANCE TO
COMBUSTIBLES
OVAL-TO-ROUND
ADAPTER
FIRESTOP SPACER
To assemble, align the two pieces, and push together until they click.
Use only vents labeled “For Exterior Use
Only”, above roofline. (Canada Only)
OVAL
PIPE
OVAL
TEE
BASE PLATE
AND TEE
SUPPORT
2” X 4” SUPPORT
Diagram showing transition from 5” oval to round vent pipe, and optional offset. Note that offsets must be supported
25
advertisement
Related manuals
advertisement
Table of contents
- 4 Round B Vent, General Information, Planning
- 7 Steps for Typical Installations
- 11 Bucket Support
- 11 Combination Cap
- 12 Adjustable Elbows, Male and Female Adapters
- 13 Relining Masonry Chimneys for use with Gas Appliances
- 17 Troubleshooting
- 18 Maintenance
- 19 Oval B Vent, Installation Notes
- 22 4-Inch Oval Installation in 2x4 Inch Stud Walls
- 24 5-Inch Oval Installation in 2x4 Inch Stud Walls
- 26 6-Inch Oval Installation in 2x6 Inch Stud Walls