Filters. Lennox ML193DFE Gas Furnace

Add to My manuals
48 Pages

advertisement

Filters. Lennox ML193DFE Gas Furnace | Manualzz

Filters

This unit is not equipped with a filter or rack. A field-provid ed filter is required for the unit to operate properly. TABLE

3 lists recommended filter size.

A filter must be in place whenever the unit is operating.

IMPORTANT

If a high efficiency filter is being installed as part of this system to ensure better indoor air quality, the filter must be properly sized. High efficiency filters have a higher static pressure drop than standard efficiency glass/foam filters. If the pressure drop is too great, system capacity and performance may be reduced. The pressure drop may also cause the limit to trip more frequently during the winter and the indoor coil to freeze in the summer, resulting in an increase in the number of service calls.

Before using any filter with this system, check the specifications provided by the filter manufacturer against the data given in the appropriate Lennox Product

Specifications bulletin. Additional information is provided in Service and Application Note ACC002

(August 2000).

TABLE 3

Furnace Cabinet Width Minimum Filter Size

17-1/2”

21”

16 x 25 x 1 (1)

Duct System

Use industry-approved standards to size and install the supply and return air duct system. Refer to ACCA Manual

D. This will result in a quiet and low-static system that has uniform air distribution. See FIGURE 19 for proper duct installation.

Supply Air Plenum

If the furnace is installed without a cooling coil, a removable access panel should be installed in the supply air duct. The access panel should be large enough to permit inspection of the heat exchanger. The furnace access panel must always be in place when the furnace is operating and it must not allow leaks into the supply air duct system.

NOTE - This furnace is not certified for operation in heat ing mode (indoor blower operating at selected heating speed) with an external static pressure which exceeds 0.5 inches w.c. Operation at these conditions may result in improper limit operation.

Duct Installation

Down-Flow Unit

SUPPLY

AIR

FIGURE 19

Return Air Plenum

NOTE - Return air must not be drawn from a room where this furnace, or any other gas-fueled appliance (i.e., water heater), or carbon monoxide-producing device (i.e., wood fireplace) is installed.

When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in incomplete com bustion and the formation of carbon monoxide gas. This raw gas or toxic fumes might then be distributed throughout the house by the furnace duct system.

Use fiberglass sealing strips, caulking, or equivalent seal ing method between the plenum and the furnace cabinet to ensure a tight seal. If a filter is installed, size the return air duct to fit the filter frame.

Pipe & Fittings Specifications

All pipe, fittings, primer and solvent cement must conform with American National Standard Institute and the American Society for Testing and Materials (ANSI/ASTM) standards. The solvent shall be free flowing and contain no lumps, undissolved particles or any foreign matter that adversely affects the joint strength or chemical resistance of the cement. The cement shall show no gelation, stratification, or separation that cannot be removed by stirring.

Refer to the TABLE 4 below for approved piping and fitting materials.

Page 12

CAUTION

Solvent cements for plastic pipe are flammable liquids and should be kept away from all sources of ignition.

Do not use excessive amounts of solvent cement when making joints. Good ventilation should be maintained to reduce fire hazard and to minimize breathing of solvent vapors. Avoid contact of cement with skin and eyes.

TABLE 4

PIPING AND FITTINGS SPECIFICATIONS

Schedule 40 PVC (Pipe) D1785

Schedule 40 PVC (Cellular Core Pipe)

Schedule 40 PVC (Fittings)

Schedule 40 CPVC (Pipe)

Schedule 40 CPVC (Fittings)

SDR-21 PVC or SDR-26 PVC (Pipe)

SDR-21 CPVC or SDR-26 CPVC (Pipe)

Schedule 40 ABS Cellular Core DWV

(Pipe)

Schedule 40 ABS (Pipe)

Schedule 40 ABS (Fittings)

ABS-DWV (Drain Waste & Vent) (Pipe &

Fittings)

PVC-DWV (Drain Waste & Vent) Pipe &

Fittings)

F891

D2466

F441

F438

D2241

F442

F628

D1527

D2468

D2661

D2665

PRIMER & SOLVENT CEMENT

PVC & CPVC Primer

PVC Solvent Cement

CPVC Solvent Cement

ABS Solvent Cement

PVC/CPVC/ABS All Purpose Cement

For Fittings & Pipe of the same material

ABS to PVC or CPVC Transition Solvent

Cement

CANADA PIPE & FITTING & SOLVENT

CEMENT

PVC & CPVC Pipe and Fittings

PVC & CPVC Solvent Cement

ABS to PVC or CPVC Transition

Cement

POLYPROPYLENE VENTING SYSTEM

PolyPro® by Duravent

ASTM

SPECIFICATION

F656

D2564

F493

D2235

D2564, D2235,

F493

D3188

MARKING

ULCS636

InnoFlue® by Centrotherm

IMPORTANT

Exhaust and intake connections are made of PVC. Use

PVC primer and solvent cement when using PVC vent pipe. When using ABS vent pipe, use transitional solvent cement to make connections to the PVC fittings in the unit.

Use PVC primer and solvent cement or ABS solvent cement meeting ASTM specifications, refer to TABLE 4.

As an alternate, use all purpose cement, to bond ABS,

PVC, or CPVC pipe when using fittings and pipe made of the same materials. Use transition solvent cement when bonding ABS to either

PVC or CPVC.

Low temperature solvent cement is recommended during cooler weather. Metal or plastic strapping may be used for vent pipe hangers. Uniformly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth of fitting socket.

Canadian Applications Only - Pipe, fittings, primer and solvent cement used to vent (exhaust) this appliance must be certified to ULC S636 and supplied by a single manu facturer as part of an approved vent (exhaust) system. In addition, the first three feet of vent pipe from the furnace flue collar must be accessible for inspection.

Page 13

Input Size

045

070

090

Vent Pipe

Dia. in.

6 1-1/2

2

2-1/2

3

6 1-1/2

2

2-1/2

3

2

2-1/2

3

Flush

Mount Kit

51W11

(US)

51W12

(CA)

3 YES

3 YES

3 YES

3 YES

3 YES

3 YES

3 YES

3 YES

3 YES

3 YES

3 YES

TABLE 5

OUTDOOR TERMINATION USAGE*

STANDARD

Wall Kit

3 inch 2 inch

22G44

(US)

4 30G28

(CA)

44J40 (US)

4 81J20

(CA)

Field

Fabricated

YES

YES

YES

YES

YES

YES

YES

YES

1

1

1

1

1

1

1

1

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

5

5

5

5

5

5

5

5

YES

YES

YES

YES

YES

YES

YES

YES

5 YES

5 YES

5 YES

1-1.2 inch

4

71M80

(US)

44W92

2

2

2

2

2

2

2

2

(CA)

YES

YES

YES

YES

YES

YES

YES

YES

CONCENTRIC

4

2 inch

69M29

(US)

44W92

(CA)

YES

YES

YES

3 inch

60L46 (US)

4 44W93

(CA)

YES

YES

YES

NOTE - Standard Terminations do not include any vent pipe or elbows external to the structure. Any vent pipe or elbows external to the structure must be included in total vent length calculations. See vent length tables.

* Kits must be properly installed according to kit instructions.

1Requires field-provided outdoor 1-1/2” exhaust accelerator.

2Concentric kits 71M80 and 44W92 include 1-1/2” outdoor accelerator, when uses with 045 and 070 input models. When using 1-1/2 inch vent pipe, transistion to 2” pipe before installing concentric kit.

3 Flush mount kits 51W11 and 51W12 includes 1-1/2 in. outdoor exhaust accelerator, required when used with 045, 070 and 090 input models. When using 1-1/2” vent pipe, transition to 2” pipe before installing flushmount kit .

4 Termination kits 30G28, 44W92, 4493 and 81J20 are certified to ULC S636 for use in Canada only.

5 See table 10 for vent accelerator requirements.

6 Requires field provided 2” to 1-1/2” reducer.

Joint Cementing Procedure

All cementing of joints should be done according to the specifications outlined in ASTM D 2855.

NOTE - A sheet metal screw may be used to secure the intake pipe to the connector, if desired. Use a drill or self tapping screw to make a pilot hole.

DANGER

DANGER OF EXPLOSION!

Fumes from PVC glue may ignite during system check.

Allow fumes to dissipate for at least 5 minutes before placing unit into operation.

1 - Measure and cut vent pipe to desired length.

2 - Debur and chamfer end of pipe, removing any ridges or rough edges. If end is not chamfered, edge of pipe may remove cement from fitting socket and result in a leaking joint.

3 - Clean and dry surfaces to be joined.

4 - Test fit joint and mark depth of fitting on outside of pipe.

5 - Uniformly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean inside socket

surface of fitting and male end of pipe to depth of fitting socket.

6 - Promptly apply solvent cement to end of pipe and inside socket surface of fitting. Cement should be applied lightly but uniformly to inside of socket. Take care to keep excess cement out of socket. Apply second coat to end of pipe.

NOTE - Time is critical at this stage. Do not allow primer to dry before applying cement

7 - Immediately after applying last coat of cement to pipe, and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe into socket until it bottoms out. Turn PVC pipe

1/4 turn during assembly (but not after pipe is fully inserted) to distribute cement evenly. DO NOT turn

ABS or cellular core pipe.

NOTE - Assembly should be completed within 20 seconds after last application of cement. Hammer blows should not be used when inserting pipe.

8 - After assembly, wipe excess cement from pipe at end of fitting socket. A properly made joint will show a bead around its entire perimeter. Any gaps may indicate an improper assembly due to insufficient solvent.

9 - Handle joints carefully until completely set.

Page 14

advertisement

Related manuals