12 Maintenance and repair
English
Devices have to be repaired by R.STAHL only. The devices are maintenance-free.
Troubleshooting chart:
Error detection Malfunction cause(s) Trouble-shooting
“PWR” LED not lit
Output signals defective
2-wire calibration does not work
Power supply failure or device fuse is defective
Sensor is incorrectly connected
Incorrect DIP switch setting
Device is PC-programmed, however the DIP switch is not in the OFF position
2-wire calibration is blocked
2-wire calibration to large
Device malfunction.
Check power supply.
If device fuse is defective, send device in for repair.
Check connections (see 6.1)
Set DIP switch as per 6.2
Set DIP switch S2-12...1 to OFF
Set DIP switch S2-12 to OFF
Perform line balancing as per 7.1
Short-circuit the sensor
Return the device. Green "PWR" LED flashes continuously
Red "LF" LED is lit
Red "LF" LED flashs
Line error in the input
Out of measuring range
Check connections (see 6.1)
Configure an appropriate measuring range
If the procedure described above does not obtain the desired result, please contact your local R.STAHL sales and service representative. In order to quickly process your request, please provide us with the following information:
•
Type and serial number,
•
Purchase date(s),
•
Description of the error,
•
Application description (particularly the configuration of the input/output circuitry)
13 Accessories and spare parts
Use only original accessories and spare parts from R. STAHL Schaltgeräte GmbH.
Programming set 9199/20-02 Consists of PC software for Windows 98, NT,
2000, XP, 7 and programming cable for PC's
equipped with an RS 232 interface and RS 232 /
USB adapter
External cold junction compensation Terminal with integrated Pt 100 for a 2-wire circuit
9191/VS-0x
External Terminal for DIN Rail mounting
Single channel: 9191/VS-0x
Dual channel: 9191/VS-0x
32