Installation Process. BeiJer iX Panel T4A, iX Panel TA150

Add to My manuals
24 Pages

advertisement

Installation Process. BeiJer iX Panel T4A, iX Panel TA150 | Manualzz

2.2 Installation Process

1. Unpack and check the delivery. If damage is found, notify the supplier.

Note:

Place the operator panel on a stable surface during installation.

Dropping it or letting it fall may cause damage.

2. Use the cut out dimensions that are included on the outline drawing to cut a correct opening in the cabinet. A separate cut out drawing is available for download from the Beijer Electronics web site.

3. Secure the operator panel in position, using all the fastening holes and the provided brackets and screws:

Installation x 4

0.5 - 1.0

Nm

Beijer Electronics, MAEN015A 7

Installation

4. Connect the cables in the specified order, according to the drawing and steps below.

Caution:

• Ensure that the operator panel and the controller system have the same electrical grounding (reference voltage level), otherwise errors in communication may occur.

• The operator panel must be brought to ambient temperature before it is started up. If condensation forms, ensure that the operator panel is dry before connecting it to the power outlet.

• Ensure that the voltage and polarity of the power source is correct.

• Use only shielded communication cables.

• Separate high voltage cables from signal and supply cables.

B

RS232/

RS422/

RS485

24V DC

C

D

A

Power

Controller

24V DC

Ethernet

Connect cable A.

Connect cable B, using an M5 screw and a grounding conductor (as short as possible) with a cross-section of minimum 2.5 mm 2 .

Connect cable C.

Connect cable D.

5. Carefully remove the laminated film over the operator panel display, to avoid static electricity that could damage the panel.

Note:

When connecting the operator panel to the power outlet for the first time, make sure not to interrupt power for a minimum of 48 hours in order to charge the battery completely. After that, the battery may be charged partly during a shorter period of time.

Beijer Electronics, MAEN015A 8