Additional Installation Tips

6.7 Cable and Bus Termination RS485

Use shielded and twisted pair cable. The pair capacitance may not exceed 52.5

pF/m and area at least 0.25 mm 2 (AWG 24), if you want to use the maximum transfer distance and maximum transfer speed.

0 V, the reference voltage for communication should be included in the cabling. With two-way communication use two pairs; one pair for communication and one pair for 0 V.

The shield must be grounded at one end. The other end is usually grounded, but with longer distances or when there is a difference in the ground potential, the shield should be connected to the ground via 0.1 uF/250 V plastic capacitor to prevent ground current in the braided shield. A number of manufacturers recommend that the shield be grounded at each node. Various manufacturers have different systems for bus termination. The RS485 standard does not describe how the “Fail Safe” function would be carried out, just that the system should be able to handle the error.

Depending on the recipients’ design, the bus wires may be on the same level or require pull-up or pull-down to ensure that no faulty signals are detected when the bus is in resting mode (all transmitters are disconnected).

+5 V

0 V

1 K

120 ohm

1 K

1

120 ohm

2 3

Inside operator panel

+5 V 14

2

15

6

19

(120 ohm)

7

8

1 K

1 K

0 V

0 V

4

17

CAB8

50

Operator panel

RS422

2

15

3

16

17

4

+5 V

14

0 V

0 V

8

7

VCC

CAB8

VCC

1 K

120 ohm

1 K

Bus

RS485

5

6

3

4

7

1

2

8

Shield

0 V

0 V

Bus termination

5358

Some (older) operator panels had pull-up and pull-down resistance except for the actual bus termination at 120 ohm, similar to Westermo and Profibus. See 1 in drawing above.

Newer panels have another type of recipient, so-called built-in “Fail Safe”, where simple bus termination resistance is sufficient. See 2 in drawing above.

If other nodes on the RS485 network require pull-up and pull-down and the operator panel is at one end of the loop, one of the following procedures can be carried out:

Connect two 1k/0.25 W resistors in the 25-pole D-sub contact. See 3 in drawing above. Set jumper pins 6-19.

Use CAB8. It offers the option of bus termination with pull-up/-down. It is also easy to connect the bus cable via the screw terminal block. See 4 in drawing above.

Beijer Electronics, MAEN015A 23