Run Command
Run Command
This section explains input methods for the run command.
Selecting the Run Command Source
Set parameter b1-02 to select the source for the run command.
Related Parameters
Parameter
Number
Name
Display
Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Openloop
Vector
1
Flux
Vector
Open
Loop
Vector
2 b1-02
Run
Command
Selection
Run Source
Selects the run command input source.
0: Operator - RUN and STOP keys on
Digital Operator.
1: Terminals - Contact closure on terminals S1 or S2.
2: Serial Com - Modbus RS-422/485 terminals R+, R-, S+, and S-.
3: Option PCB - Option board connected on 2CN.
0 to 3 1 No Q Q Q Q Q
Performing Operations Using a Digital Operator
When b1-02 is set to 0, you can perform drive operations using the Digital Operator keys (RUN, STOP, JOG,
and FWD/REV). For details on the Digital Operator, refer to Chapter 3 Digital Operator and Modes .
Performing Operations Using Control Circuit Terminals
When b1-02 is set to 1, you can perform drive operations using the control circuit terminals.
Performing Operations Using a 2-wire Sequence
The factory setting is set to a 2-wire sequence. When control circuit terminal S1 is set to ON, forward operation will be performed, and when S1 is turned OFF, the drive will stop. In the same way, when control circuit terminal S2 is set to ON, reverse operation will be performed, and when S2 is turned OFF, the drive will stop.
Drive
Forward/stop
Reverse/stop
Sequence common
Fig 6.8 2-wire Sequence Wiring Example
6-
7
6
-8
Performing Operations Using a 3-wire Sequence
When any parameter from H1-01 to H1-10 (multi-function contact input terminals S3 to S12) is set to 0, terminals S1 and S2 are used for a 3-wire sequence, and the multi-function input terminal that has been set functions as a forward/reverse run command terminal.
When the drive is initialized for 3-wire sequence control with A1-03, multi-function input 3 becomes the input terminal for the forward/reverse run command.
Stop switch
(NC contact)
Operation switch
(NO contact)
Run command
(operates when ON)
Stop command
(stopped when ON)
Forward/reverse command
(multi-function input)
Sequence input common
Run command
Stop command
Forward/reverse command
Fig 6.9 3-wire Sequence Wiring Example
50ms min.
Can be either ON or OFF
OFF
(stopped)
OFF (forward) ON (reverse)
Motor speed
Stop Forward Reverse
Fig 6.10 Three-wire Sequence Time Chart
Stop Forward
Use a sequence that turns ON terminal S1 for 50ms or longer for the run command. This will make the run command self-holding in the drive.
INFO