5.3 Basic Programming
When parameter A1-01 is changed to “0003” , additional programming parameters become available. These additional parameters give the user more options to use the features of the inverter without the burden of dealing with all of the options available. Refer to Appendix D for a complete parameter list.
Changing of the programming level from Quick Start to Basic and the setup of these additional parameters should not be attempted until the Quick Start Program has been completed and the motor is in operation at the Quick Start level.
Additional Monitor Options
Number Description
U1-15 Terminal 13 input voltage
U1-16 Terminal 14 input voltage
U1-17 Terminal 15 input voltage
U1-18 Motor Torque Current
U1-19 Motor Excitation Current
Units Explanation
% Displays speed reference in percent at terminal 13
% Displays speed reference in percent at terminal 14
% Displays speed reference in percent at terminal 15
% Displays the motor torque producing current (I q
) in percent
% Displays the motor excitation current (I d
) in percent
Additional Fault Tracing Options
Number Description
U2-15 Motor Torque Current
U2-16 Motor Excitation Current
Units Explanation
% Displays the motor torque producing current (I q
) at fault
% Displays the motor excitation current (I d
) at fault
Additional Application Options
B1 - 04 Prohibition of Reverse Motor Operation
This parameter allows the user to prevent the motor from operating in the reverse direction.
Setting Explanation
00 Reverse operation enabled
01 Reverse operation prohibited
Default
X
B2 – 01 Zero Speed Level
This parameter allows the user to set the speed at which the drive senses zero speed. This affects terminal outputs and shutoff after decelerating.
Minimum
00.00
Maximum
020.00
Description
Zero speed detection level
Default Setting
00.50
46 VS-616PS5 Installation & Quick Start Manual
VS-616PS5 Parameter Tree
U Monitor
A Initialize
B Application
C Tuning
D Reference
E Motor
F Option
H Terminal
L Protection
O Operator
T Tuning
Grou p
F5
F6
F9
F1
F2
F3
F4
H1
H2
H3
H4
D1
D2
D3
D4
D5
C1
C2
C3
C5
C6
E1
U1
U2
U3
A1
B5
B6
B7
B1
B2
B3
B4
Function
Monitor
Fault Trace
Fault History
Initialize
Sequence
Zero Speed Level
Magnetic Pull-in
Delay Timers
Pid Control
Reference Hold
Droop Control
Accel/decel
PG Origin Pulse Comp.
Voltage Limit Control
Asr Tuning
Carrier Frequency
Preset Reference
Reference Limit
Jump Speed
Hold Reference Memory
Torque Control
Motor Constant
PG Option Set-up
AI-14 Set-up
DI-08, 16 Set-up
AO-08, 12 Set-up
DO-02 Set-up
DO-08 Set-up
CP-916 Set-up
Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs
Quick-start
01-03, 05-14
01-14
01-08
01, 03, 04
01-03
Parameter No.
Basic Advanced
15-19
15,16
20-22,27-33,41-47, 49,50,53,54,55
17-22
04
01
01, 02
01-04, 09
03, 04, 09
01-04
05-08
01, 02
01-04
05-06
02, 04, 05
01, 02
01-08
01-04
01, 02
05-08, 10, 11
13
05
05-07
02
01,02,04,09-11,13
01
01
01-06
03, 05-08, 15-17
08-11, 13 02-05
01
01
01-06
01, 02
01
01-06
01-06
01-03
01-07
01-07
08-12
VS-616PS5 Installation & Quick Start Manual 47
Additional Tuning Options
C1 – 03
C1 – 04
Acceleration Time 2
Deceleration Time 2
These parameters are set to provide different ramp times when one of the input terminals (3 through 8) is programmed to “Multi-accel/decel 1” (setting “7”). See parameters H1-01 through H1-06. This allows the user to program different acceleration and deceleration rates for various conditions.
Minimum Maximum Description
0000.0
6000.0
Acceleration/Deceleration Time 2 Setting
Default Setting
0010.0
C1 – 09 Fast Stop Time
This parameter is set to provide a ramp time when one of the input terminals (3 through 8) is programmed to “Fast
Stop Command” (setting “15”). See parameters H1-01 through H1-06. This allows the user to program a rapid deceleration rates for a quicker than normal stop.
Minimum Maximum Description
0000.0
6000.0
Fast Stop Time
Default Setting
0010.0
NOTE: Attempting to stop the motor faster than it will coast to a stop by itself (with power off) may require the addition of a resistor-braking unit.
ASR Tuning Options
The Automatic Speed Regulator (ASR) allows the user to adjust for optimum performance during changes in motor speed or load.
Torque Limit
Speed Reference
Speed Feedback
+
-
C5-01, C5-03
P
I
C5-02, C5-04
+
+
1
1+ST
C5-05
L7-01, L7-04
Secondary Current Reference
C5 – 01
C5 – 03
ASR Proportional Gain 1
ASR Proportional Gain 2
The Proportional Gain adjusts the speed in response to a speed deviation, and softens the effects of load changes.
Response becomes more noticeable as the gain is increased. High levels may cause instability.
ASR Proportional Gain 2 is activated by programming one of the input terminals (3 through 8) to “ASR Gain Switch
(setting “77”) and closing a contact to it.
Minimum Maximum Description
000.00
300.00
Automatic Speed Regulator Gain
Default Setting
020.00
48 VS-616PS5 Installation & Quick Start Manual
C5 – 02
C5 – 04
ASR Integral Gain 1
ASR Integral Gain 2
The Integral Gain adjusts the speed of response to a load change. Response become more noticeable as the gain is decreased. Low levels may cause instability.
ASR Integral Gain 2 is an additional integral gain adjustment.
Minimum Maximum Description
00.000
10.000
Automatic Speed Regulator Integral Time
Default Setting
00.500
Additional Reference Parameters
D1 – 05
D1 – 06
D1 – 07
D1 – 08
Preset Speed Reference 5
Preset Speed Reference 6
Preset Speed Reference 7
Preset Speed Reference 8
Minimum Maximum Description
000.00
100.00
Preset Speed References
Default Setting
000.00
There are now eight preset speed references available, which can be controlled by the input terminals.
Terminal 5
Set H1-03 = 3
OPEN
CLOSED
OPEN
CLOSED
OPEN
CLOSED
OPEN
CLOSED
Terminal 6
Set H1-04 = 6
OPEN
OPEN
CLOSED
CLOSED
OPEN
OPEN
CLOSED
CLOSED
Terminal 7 Selected Speed Reference
Set H1-05 = 7
OPEN
OPEN
OPEN
OPEN
Speed Reference 1 - D1-01 supplies speed reference
Speed Reference 2 - D1-02 supplies speed reference
Speed Reference 3 - D1-03 supplies speed reference
Speed Reference 4 - D1-04 supplies speed reference
CLOSED Speed Reference 5 - D1-05 supplies speed reference
CLOSED Speed Reference 6 - D1-06 supplies speed reference
CLOSED Speed Reference 7 - D1-07 supplies speed reference
CLOSED Speed Reference 8 - D1-08 supplies speed reference
VS-616PS5 Installation & Quick Start Manual 49
Reference Limits
D2 – 01 Reference Upper Limit
Sets the maximum reference as a percent of maximum speed, E7-06.
Minimum Maximum Description
000.0
110.0
Speed Reference Upper Limit
Default Setting
100.0
D2 – 02 Reference Lower Limit
Sets the minimum reference as a percent of maximum speed as entered in E1-06.
Minimum Maximum Description
000.0
100.0
Speed Reference Upper Limit
PG Option Set-up
F1 – 02 Disconnection Detection Stopping Method
Selects the stopping method when a disconnected PG is detected.
Setting Description
0 Ramp to stop - according to C1-02. (Declaration time 1)
1
2
3
Coast to stop (factory default).
Fast - stop - according to C1-09.
Alarm flashes, operation continues.
Default Setting
100.0
F1 – 03 Overspeed Detection Stopping Method
Selects the stopping method when an overspeed condition is detected.
Setting Description
0 Ramp to stop - according to C1-02 (Declaration time 1).
1
2
3
Coast to stop (factory default) .
Fast-stop - according to C1-09.
Alarm flashes, operation continues. (
F1 – 04 Deviation Detection Stopping Method
Selects the stopping method when excessive speed deviation is detected.
50
Setting Description
0
1
Ramp to stop - according to C1-02 (Declaration time 1).
Coast to stop.
2
3
Fast-stop - according to C1-09.
Alarm flashes, operation continues (factory default).
VS-616PS5 Installation & Quick Start Manual
PG-P2 Setup
F8 – 02 Pulse Input Moving Average Value
Sets the number of scans the pulse input reference signal is averaged over. A larger number will provide a more stable reference (internal). However, the inverter response to a rapid change in the pulse train frequency may be slow. A setting of “0” or “1”means no moving average will be used, and the pulse input reference will be updated every scan.
Minimum Maximum Description
0 50 Pulse Input moving Scan width.
Default Setting
0
VS-616PS5 Installation & Quick Start Manual 51
Terminal Designation Options
When the inverter is initialized (A1-03) to “2220” (2-wire operation), terminal 1 is FWD RUN, and terminal 2 is REV
RUN. Connecting either input with a contact to terminal 11 causes the inverter to run in that direction as long as the contact is closed, and to stop running when the contact is opened.
When the inverter is initialized (A1-03) to “3330” (3-wire operation), terminal 1 is the START input and terminal 2 is the STOP input. The inverter runs after START is connected momentarily to terminal 11 provided STOP is already connected to terminal 11. The inverter will continue to run until the STOP input is opened. Terminal (5) will be set to
“00” to act as a FORWARD/REVERSE input.
H1 – 01 to H1 - 06 Multifunction Input Terminals Selection
Default assignments are as follows (all contact closures are to terminal 11):
Input
Terminal
3
4
5
6
7
8
Parameter
H1-01
H1-02
H1-03
H1-04
H1-05
H1-06
Default
Setting
24
14
3
4
6
8
Default Function
External Fault – close contact to trip inverter off
Fault Reset – close contact to reset faults in inverter
Preset Reference Selector 1 – close contact to select preset speeds
Preset Reference Selector 2 – close contact to select preset speeds
Jog Reference – close contact to select preset jog speed reference
External Baseblock (N.O.) – close contact to disable inverter output
The following settings are available for the terminals. Unless otherwise indicated, closing a normally open contact to terminal 11 activates the input terminal function.
15
1A
1B
1E
1F
24
71
77
F
10
11
12
13
14
9
A
B
C
E
6
7
8
Setting
0
1
2
3
4
5
Function
3-wire control
Local/Remote
Internal/Option
Preset Reference 1
Preset Reference 2
Preset Reference 3
JOG Reference
Accel/Decel Select 1
External Baseblock NO
External Baseblock NC
Accel/Decel Ramp Hold
Inverter OH2 Alarm
Terminal 16 Enable
ASR Integral Reset
No Operation
MOP Increase
MOP Decrease
Forward JOG
Reverse JOG
Fault Reset
Fast Stop
Accel/Decel Select 2
Program Lockout
Reference Sample Hold
Terminal 13/14 Switch
External Fault
Speed/Torque Control
ASR Gain Switch
The terminal set to “0” becomes the Forward/Reverse input
Selects the operation mode (open = Local). Inverter must be stopped.
Selects Reference source (open = internal, closed = option card)
Selects Preset Speed Reference when closed (see D1-01 thru D1-08)
Selects Preset Speed Reference when closed (see D1-01 thru D1-08)
Selects Preset Speed Reference when closed (see D1-01 thru D1-08)
Selects Jog Preset Reference when closed. RUN input must be active
Selects alternate Accel/Decel rates when closed (see C1-03 and C1-04)
Disables output of inverter when contact closes
Disables output of inverter when contact opens
Stops ramping when closed, resumes ramping when opened
External temperature alarm input, causes display to blink “OH2”
Enables the analog input at terminal 16 when closed
Resets Integral control values of inverter when closed
Terminal is not being used
Accelerate while closed with MOP decrease open, otherwise no effect
Decelerate while closed with MOP increase open, otherwise no effect
Run forward at Jog preset speed reference D1-09 while closed
Run reverse at Jog preset speed reference D1-09 while closed
Resets Inverter faults while closed; must be opened to run again
Causes inverter to stop at Fast Stop decel rate (C1-09)
Selects alternate Accel/Decel rates when closed
Prohibits changing of PS5 parameters while open
Samples frequency reference if closed for 100 ms or longer
Selects terminal 13 input (open) or terminal 14 input(closed)
Shuts off inverter when closed, displays “oPE_” on operator
Selects Speed control (open) or torque control (closed)
Switches Gain values in ASR (see C5-01 / C5-02)
Consult the VS-616PS5 Programming Manual for more comprehensive discussions of the parameters.
52 VS-616PS5 Installation & Quick Start Manual
H2 – 01 to H2 – 03 Digital Outputs
Default assignments are as follows:
Output
Terminals
9 – 10
25 – 27
26 - 27
Parameter
H2-01
H2-02
H2-03
Default
Setting
0
1
2
Default Function
RUN output – closes while inverter is running
Zero Speed output – closes while output speed is less than E1-09
Up to Speed – closes when set speed is attained within tolerance (L4-02)
Listed below are other settings for the digital outputs:
Setting
C
D
E
8
9
A
B
F
3
4
5
6
7
Function
Speed Match
Speed Low
Speed High
Inverter Ready
DC Bus Undervoltage
Baseblock 1
Speed from Operator
Control from Operator
Over Torque Detection
Reference Loss
DBR Overheat
Fault
No Operation
Speed Matches Setting – closes when output speed = L4-01 +/- L4-02
Speed Below setting – closes while output speed < L4-01
Speed Above Setting – closes while output speed > L4-01
Ready to Run – closes when inverter has no faults or alarms
Closes when DC Bus level or power supply is below trip level
Closes when inverter output is disabled by a Baseblock command
Closes while the speed reference is supplied from the digital operator
Closes when the RUN command comes from the digital operator
Closes when torque output exceeds setting
Closes when speed reference drops 90% in less than 400 ms
Closes while Dynamic Braking resistor is overheated or on DB fault
Closes when a fault occurs
Output is not being used
Consult the VS-616PS5 Programming Manual for more settings and more comprehensive descriptions.
H3 – 01 to H3 – 03 Analog Input 1
These parameters set up Analog input 1 (Terminal 13), with terminal 17 common
Parameter
H3-01
H3-02
H3-03
Function
Terminal 13 Signal 0: 0 to 10 VDC 1: +/-10 VDC
Terminal 13 Reference % Gain
Terminal 13 Reference +/- Bias
Units
- -
%
%
Range
0/1
0.0 – 1000.0
+/-100.0
Consult the VS-616PS5 Programming Manual for the setup of Analog Input 2 and Analog Input 3.
Default
0
100.0
0.0
H4 – 01 to H4 – 07 Analog Outputs
These parameters set up Analog input 1, with terminal 17 common
Parameter
H4-01
H4-02
H4-03
H4-04
H4-05
H4-06
H4-07
Description
Terminal 21 Analog Output Signal
Terminal 21 Output Gain
Terminal 21 Output Bias
Terminal 23 Analog Output Signal
Terminal 23 Output Gain
Terminal 23 Output Bias
Output Signal Selection (both)
Units
- -
- -
%
- -
- -
%
- -
Range
0…53
0.00 – 2.50
0.0 – 10.0
0…53
0.0 – 1000.0
0.0 – 10.0
0/1
Default
5
1.00
0.0
3
1.00
0.0
0
Consult the VS-616PS5 Programming Manual for further information on the Analog Outputs.
VS-616PS5 Installation & Quick Start Manual
Default Function
Motor Speed
Gain = 1
Bias = 0
Output Current
Gain = 1
Bias = 0
0 – 10 VDC
53
L2 Power Loss Ride-through
When momentary power loss occurs, Power Loss Ride-through function is disabled.
L2-01 Momentary Power Loss Ride-through
Selects whether the inverter stops when power loss is detected or “rides through” a momentary power loss. When ride-through operation is selected, speed search starts from the current output frequency.
Setting Explanation
0 Momentary Power Loss Disabled
1 Momentary Power Loss Enabled
Default
X
Momentary power loss ride-through is disabled (factory default) . When momentary power loss is detected, a fault contact trips, stopping the inverter.
L2-02 Momentary Power Loss Ride-through Time
Minimum Maximum Description
0.0
2.0
Momentary Power Loss Ride through Time (Sec).
Default Setting
Model Dependant
Sets the ride-through time allowed before the inverter trips, after momentary power loss. This setting is activated when L2-01 is set to “1.” If power is restored within this time, operation restarts automatically. If power is not restored within this time, a fault contact trips, stopping the inverter.
54 VS-616PS5 Installation & Quick Start Manual
L3 Stall Prevention/Current Limit
This function automatically adjusts the deceleration rates in order to continue operation without tripping the inverter.
L3-01 Over-voltage Protection (Stall Prevention During Deceleration)
If deceleration times are set too short for load conditions, the inverter automatically extends the deceleration time according to the main circuit DC bus voltage level. When using an optional braking resistor for the VS-616PS5, set parameter L3-01 to”0”.
Setting Explanation
0
Stall prevention during deceleration is disabled. An excessively short deceleration time will generate an overvoltage fault (OV), and the motor will coast.
1
Stall prevention during deceleration is enabled (factory default) .
The DC bus voltage level is monitored, and the deceleration rate is automatically extended to prevent an overvoltage condition. This deceleration time may be longer than the set value (C1-02).
Default
X
Frequency
Adjusts the deceleration time to prevent overvoltage fault (OV).
Time
Set Deceleration Time
VS-616PS5 Installation & Quick Start Manual 55
L4 Reference Detection
Used in conjunction with the multi-function digital outputs to indicate speed agree conditions.
Refer to section H2 , Digital Outputs , for more detailed information on setting these functions.
L4-01 Speed Agree Detection Level (without sign)
Sets the detection level for the desired frequency agree 1 and frequency detection 1 & 2 functions. The set detection level is effective during both FWD and REV operation.
Minimum Maximum Description
0.0
100.0
Speed agree Detection Level (without sign).
Default Setting
0.0
L4-02 Speed Agree Detection Width
Sets the detection width for frequency and desired frequency agree 1 and frequency detection 1 & 2 functions.
Minimum Maximum Description
0.0
100.0
Speed agree Detection Width.
Default Setting
2.0
56 VS-616PS5 Installation & Quick Start Manual
L5 Fault Restart
After a fault occurs, the inverter and its fault detection circuit can be reset. The automatic restart function allows the inverter to continue operation after certain faults.
L5-01 Number of Automatic Restart Attempts
Sets the number of automatic restart attempts. Setting to “0” disables this function.
Minimum Maximum Description
0.0
10 Number of Automatic Restart Attempts.
The inverter can be set to automatically restart after the following faults occur:
Overcurrent (OC)
Overvoltage (OV)
Undervoltage PUV (UV1)
Ground fault (GF)
Regenerative transistor fault (rr)
Default Setting
0
L5-02 Automatic Restart Operation Selection
Selects whether a fault contact output is activated during automatic restart.
Setting Explanation
0
No fault relay (factory default)
1
Fault relay is active
Default
X
VS-616PS5 Installation & Quick Start Manual 57
L6 Torque Detection
The overtorque detection circuit activates when the motor load causes the motor current (or torque) to exceed the overtorque detection level (L6-02) .
L6-01 Overtorque Detection 1 Selection
Activates overtorque detection, and selects whether detection generates an alarm or a fault.
Setting Explanation
0
Overtorque detection is disabled .
1
Overtorque detection is enabled whenever at the speed agree level (when inverter is not accelerating or decelerating). Continue running after detection (OL3 alarm).
2
3
Overtorque detection is enabled always. Continue running after detection (OL3 alarm).
Overtorque detection is enabled whenever at the speed agree level. Coast to a stop after detection (OL3 fault).
Default
X
4
Overtorque detection is enabled always. Coast to a stop after detection (OL3 fault).
Notes:
1.To detect torque during acceleration or deceleration, set to “2” or “4.”
2.To continue operation after overtorque detection, set to “1” or “2.” During detection, the digital operator dis plays an “ OL3 ” alarm (blinking).
3.To stop the inverter after an overtorque detection fault, set to “3” or “4.” During detection, the digital opera tor displays an “ OL3 ” fault.
L6-02 Overtorque Detection 1 Level
Sets the overtorque detection level as a percentage of motor rated torque.
Minimum Maximum Description
0 300 Overtorque Detection 1 Level.
Default Setting
150
L6-03 Overtorque Detection 1 Time
The overtorque detection delay time inserts a delay, between the time motor current (or torque) exceeds the overtorque detection level (L6-02) and when the overtorque detection function is enabled. The digital operator then displays “ OL3 .”
Minimum Maximum Description
0.0
10.0
Overtorque Detection 1 Time.
Default Setting
0.1
58 VS-616PS5 Installation & Quick Start Manual
L7 Torque Limit
The torque limit function limits the amount of motor torque in all four quadrants of vector control operation:
• Forward Motoring • Forward Regenerating
• Reverse Motoring • Reverse Regenerating
Torque limit is activated in both the speed and torque control modes.
L7-01 Forward Torque Limit
Sets the motoring side torque limit value during FWD run.
Default Setting
150
Minimum Maximum Description
0 300 Forward Torque Limitl.
L7-02 Reverse Torque Limit
Sets the motoring side torque limit value during REV run.
Minimum Maximum Description
0 300 Reverse Torque Limit.
Default Setting
150
L7-03 Regenerative Forward Torque Limit
Sets the regenerating side torque limit value during FWD run.
Minimum Maximum Description
0 300 Regenerative Forward Torque Limit.
Default Setting
150
L7-04 Regenerative Reverse Torque Limit
Sets the regenerating side torque limit value during REV run
.
Minimum Maximum Description
0 300 Regenerative Reverse Torque Limit.
Default Setting
150
REV Run Regeneration
Torque Limit (L7-04)
REV Motor Rotation
Positive Torque Reference
0
REV Run Motor
Torque Limit (L7-02)
FWD Run Motor
Torque Limit (L7-04)
FWD Motor Rotation
FWD Run Regeneration
Torque Limit (L7-03)
Negative Torque Reference
VS-616PS5 Installation & Quick Start Manual 59
O Operator Parameters
O1-01 Monitor Selection
T
he operation menu allows the viewing of four monitor variables. These are N ref
, N out
, I out
, and a user-selected monitor. Using the table below, set this parameter to the setting corresponding to the monitor item desired for the user monitor.
48
49
50
51
52
44
45
46
47
33
41
42
43
29
30
31
32
21
22
27
28
17
18
19
20
Setting
5
6
7
15
16
8
9
Description
Motor speed
Output voltage (factory default)
DC bus voltage
Output power
Torque reference (internal)
Terminal 13 input voltage level
Terminal 14 input voltage or current level
Terminal 16 input voltage level
Motor secondary current (Iq)
Motor excitation current (Id)
SFS output frequency
ASR input
ASR output
Voltage reference (Vd output)
CPU ID number
Voltage limit control output qAxis current control output dAxis current control output
Output voltage reference (Vq)
Output voltage reference (Vd)
LED check
Internal control status 2
Command 1 from option
Command 2 from option
External torque reference
Torque compensation value
DO-08H output status
Momentary power loss decrease capacity
Control section software number
Speed detection PG counter value
PID feedback
DI-16H input status
60 VS-616PS5 Installation & Quick Start Manual
O1-02 Monitor Selection After Power-up
Selects the monitor to be displayed on the digital operator immediately after the power supply is turned ON.
Setting
1
2
3
4
Description
Displays frequency reference (factory default) .
Displays output frequency.
Displays output current.
Displays the monitor item set in O1-01 .
O1-03 Reverse Torque Limit
Units for parameters and monitors related to frequency can be scaled as shown below.
Setting
1
2 ~ 39
40 ~ 3999
Description
Unit: 0.01%. Speed reference is displayed as P ¨¨
.
¨¨
• Unit: rpm (Enter the # of poles in the motor).
• The speed reference is displayed as n ¨¨¨¨
Digits: 5th 4th 3rd 2nd 1st
0 0 0 0 0
The 1st through 4th digits determine the set value at 100% output frequency.
The decimal point position is set with the 5th digit of O1-03, as follows:
5th digit = 0: displayed as ¨¨¨¨
5th digit = 1: displayed as ¨¨¨ .
¨
5th digit = 2: displayed as ¨¨ .
¨¨
5th digit = 3: displayed as ¨ .
¨¨¨
(Example 1)
If 100% output speed is equal to 200.0 units:
Set O1-03 = “12000”
100% of this reference is displayed as 200.0 and 60% of this reference is displayed as 120.0.
Example 2
If 100% output speed is equal to 65.00:
Set O1-03 = “26500”
60% of this reference is displayed as 39.00.
VS-616PS5 Installation & Quick Start Manual 61
O2 Key Selection
O2-01 Local/Remote Key
Enables/disables the digital operator LOCAL/REMOTE key.
Setting Explanation
0
Local/Remote key is disabled.
1
Local/Remote key is enabled (factory default) .
Depressing the Local/Remote key switches operation commands between the digital operator and the settings of B1-01 & B1-02 .
Default
X
O2-02 STOP Key During External Terminal Operation
Enables/disables the digital operator STOP key, during operation from the external terminals and during serial communication.
Setting Explanation
0
The digital operator STOP key is disabled when Run command does not come from the digital operator
1
The digital operator STOP key is always enabled.
The STOP key is enabled even during external terminal operation and serial communication.
Default
X
O2-04 Inverter Model Selection
Sets the inverter capacity, according to the model number. Control parameters with defaults specific to the inverter’s capacity are set automatically (i.e. carrier frequency, motor data, etc.). This parameter does not need changing, unless the control board is replaced.
Minimum Maximum Description
00 FF Inverter Model Selection.
Default Setting
--
62 VS-616PS5 Installation & Quick Start Manual