General Timer. Murphy Centurion C5 Series, Centurion C5
Murphy Centurion C5 is a configurable controller expressly designed to meet the requirements of screw compressors, reciprocating compressors, and pumps. It can be mounted on a standard DIN rail and is designed to work with any Modbus (Client) compliant HMI (Human Machine Interface) or with no operator interface at all. The controller is designed to monitor, control, protect and optimize small- to medium-sized gas-operated compressors and pumps in the field.
Reklaam
Reklaam
General Timer
General timers affect driver operation and also help define an event arming condition.
B1, B2 and S1-4 Timers are start-run lockout timers. Events configured to these class types do not arm for a specified time at start up.
C4 Timer is lockout until time after reaching a loaded condition.
No-Flow Timer is for class NF faults and enabled after the B1 expires.
Test Timer is time given to allow for maintenance testing of end devices without triggering a fault or shutdown condition.
Ignition On Timer and Fuel On Timer staggers the engines outputs at startup for engine fuel purge.
Ignition Off Timer allows unspent fuel to burn off after a stop.
State Timer
User may edit all state timers (except Panel Ready/Shutdown) if marked in use. When a state timeout value is reached, the state logic proceeds to the next in-use state.
A state timeout may also be configured to trigger a fault event, such as a prelube permissive failure; however, the operation depends on the configuration.
A setting of 65535 disables the timeout event.
Section 50
2021-06-22 - 23 -
00-02-1032