CP20.241-M1
24V, 20A, S INGLE P HASE I NPUT CP-Series
16.
EMC – A
CCORDING TO
G
ENERIC
S
TANDARDS
In regard to EMC, the power supply is designed for applications in medical applications, industrial environment as well as in residential, commercial and light industry environment.
The device is investigated according to EN 61000-6-1, EN 61000-6-2, EN 61000-6-3 and EN 61000-6-4.
EMC Immunity
Electrostatic discharge
Electromagnetic RF field
Fast transients (Burst)
Surge voltage on input
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
Contact discharge
Air discharge
80MHz-2.7GHz
Input lines
Output lines
DC-OK signal (coupling clamp)
L N
L PE, N PE
8kV
15kV
20V/m
4kV
2kV
2kV
2kV
4kV
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Surge voltage on output
Surge voltage on Signals
Conducted disturbance
EN 61000-4-5
EN 61000-4-5
EN 61000-4-6
+ -
+ / - PE
DC-OK signal PE
0.15-80MHz
1kV
2kV
1kV
20V
Criterion A
Criterion A
Criterion A
Criterion A
Mains voltage dips
Voltage interruptions
Voltage sags
EN 61000-4-11 0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 200Vac
70% of 200Vac
80% of 120Vac (96Vac)
70% of 120Vac (84Vac)
50% of 120Vac (60Vac)
0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms
Criterion A
Criterion C
Criterion A
Criterion A
Criterion A
Criterion A
EN 61000-4-11 0% of 200Vac
SEMI F47
0Vac, 5000ms Criterion C dips on the input voltage according to SEMI F47 standard
1000ms
500ms
200ms
Criterion A
Criterion A
Criterion A
Powerful transients VDE 0160 Over entire load range 750V, 0.3ms Criterion A
Criterions:
A: Power supply shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazards for the power supply will occur.
EMC Emission
Conducted emission input lines
Conducted emission output lines **)
EN 55011, EN 55015, EN 55032,
FCC Part 15, CISPR 11, CISPR 32
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
Class B for AC Input voltages and Class A for DC input voltages
8dB higher than average limits for DC power port according to EN 61000-6-3 **)
Radiated emission
Harmonic input current
EN 55011, EN 55032
EN 61000-3-2
Class B
Class A fulfilled between 0A and 12A load
Class C fulfilled between 6A and 12A load
Fulfilled *) Voltage fluctuations, flicker EN 61000-3-3
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
*) Tested with constant current loads, non pulsing
**) For information only, not mandatory for EN 61000-6-3 or EN 61000-6-4
Restrictions apply only for applications in residential, commercial and light-industrial environments, where local DC power networks according to EN 61000-6-3 are involved. No restrictions for all kinds of industrial applications.
Aug. 2022 / Rev. 0.3 DS-CP20.241-M1-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany
16/28
advertisement
Related manuals
advertisement
Table of contents
- 3 Intended Use
- 3 Installation Instructions
- 5 AC-Input
- 6 DC-Input
- 7 Input Inrush Current
- 8 Output
- 10 Hold-up Time
- 10 DC-OK Relay Contact
- 11 Efficiency and Power Losses
- 12 Functional Diagram
- 13 Front Side and User Elements
- 13 Connection Terminals
- 14 Lifetime Expectancy
- 15 EMC – According to Medical Standards
- 16 EMC – According to Generic Standards
- 17 Environment
- 18 Safety and Protection Features
- 19 Dielectric Strength
- 20 Approved, Fulfilled or Tested Standards
- 20 Regulatory Product Compliance
- 21 Physical Dimensions and Weight
- 22 Accessories
- 22 ZM10.WALL - Wall/Panel Mount Bracket
- 23 ZM12.SIDE - Side Mounting Bracket
- 24 Application Notes
- 24 Peak Current Capability
- 25 Output Circuit Breakers
- 25 Charging of Batteries
- 26 Series Operation
- 26 Parallel Use to Increase Output Power
- 26 Parallel Use for Redundancy
- 26 Inductive and Capacitive Loads
- 26 Operation on Two Phases
- 26 Use in a Tightly Sealed Enclosure
- 27 Mounting Orientations