EMC – According to Generic Standards. Puls CP20.241-M1

Add to My manuals
28 Pages

advertisement

EMC – According to Generic Standards. Puls CP20.241-M1 | Manualzz

CP20.241-M1

24V, 20A, S INGLE P HASE I NPUT CP-Series

16.

EMC – A

CCORDING TO

G

ENERIC

S

TANDARDS

In regard to EMC, the power supply is designed for applications in medical applications, industrial environment as well as in residential, commercial and light industry environment.

The device is investigated according to EN 61000-6-1, EN 61000-6-2, EN 61000-6-3 and EN 61000-6-4.

EMC Immunity

Electrostatic discharge

Electromagnetic RF field

Fast transients (Burst)

Surge voltage on input

EN 61000-4-2

EN 61000-4-3

EN 61000-4-4

EN 61000-4-5

Contact discharge

Air discharge

80MHz-2.7GHz

Input lines

Output lines

DC-OK signal (coupling clamp)

L  N

L  PE, N  PE

8kV

15kV

20V/m

4kV

2kV

2kV

2kV

4kV

Criterion A

Criterion A

Criterion A

Criterion A

Criterion A

Criterion A

Criterion A

Criterion A

Surge voltage on output

Surge voltage on Signals

Conducted disturbance

EN 61000-4-5

EN 61000-4-5

EN 61000-4-6

+  -

+ / -  PE

DC-OK signal  PE

0.15-80MHz

1kV

2kV

1kV

20V

Criterion A

Criterion A

Criterion A

Criterion A

Mains voltage dips

Voltage interruptions

Voltage sags

EN 61000-4-11 0% of 100Vac

40% of 100Vac

70% of 100Vac

0% of 200Vac

40% of 200Vac

70% of 200Vac

80% of 120Vac (96Vac)

70% of 120Vac (84Vac)

50% of 120Vac (60Vac)

0Vac, 20ms

40Vac, 200ms

70Vac, 500ms

0Vac, 20ms

80Vac, 200ms

140Vac, 500ms

Criterion A

Criterion C

Criterion A

Criterion A

Criterion A

Criterion A

EN 61000-4-11 0% of 200Vac

SEMI F47

0Vac, 5000ms Criterion C dips on the input voltage according to SEMI F47 standard

1000ms

500ms

200ms

Criterion A

Criterion A

Criterion A

Powerful transients VDE 0160 Over entire load range 750V, 0.3ms Criterion A

Criterions:

A: Power supply shows normal operation behavior within the defined limits.

C: Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazards for the power supply will occur.

EMC Emission

Conducted emission input lines

Conducted emission output lines **)

EN 55011, EN 55015, EN 55032,

FCC Part 15, CISPR 11, CISPR 32

IEC/CISPR 16-1-2, IEC/CISPR 16-2-1

Class B for AC Input voltages and Class A for DC input voltages

8dB higher than average limits for DC power port according to EN 61000-6-3 **)

Radiated emission

Harmonic input current

EN 55011, EN 55032

EN 61000-3-2

Class B

Class A fulfilled between 0A and 12A load

Class C fulfilled between 6A and 12A load

Fulfilled *) Voltage fluctuations, flicker EN 61000-3-3

This device complies with FCC Part 15 rules.

Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

*) Tested with constant current loads, non pulsing

**) For information only, not mandatory for EN 61000-6-3 or EN 61000-6-4

Restrictions apply only for applications in residential, commercial and light-industrial environments, where local DC power networks according to EN 61000-6-3 are involved. No restrictions for all kinds of industrial applications.

Aug. 2022 / Rev. 0.3 DS-CP20.241-M1-EN

All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

16/28