4.3 Warning
▲ Warning
Electrical can result in death serious injury:
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
▲ Warning
Electrical can result in death serious injury:
Only qualified & trained personnel should be allowed to operate these transmitters.
4.4 Fail Mode Alarm
Kobold Smart Pressure Transmitter automatically and continuously performs selfdiagnostic routines. If the self-diagnostic routines detect a failure, the transmitter drives its output outside of the normal saturation values. The transmitter will drive its output low (down) or high (up) based on the position of the failure mode alarm jumper. See Table 4.1 for Output values.
[Table 4-1 Standard Alarm and Saturation Value]
Level 4~20 mA Saturation 4~20 mA Alarm
Low/Down
High/Up
3.9 mA
20.8 mA
≤ 3.75 mA
≥ 21.75 mA
Fail Mode Selection (Fail High/UP or Low/DOWN) can be configured using the appropriate jumper switch provided on the LCD Module or DIP switches included on the Main CPU Module. For units provided with a LCD module one can select desired fail safe mode directly from the jumper switch included in the front display and this setting overrides the DIP settings on the back-end Main CPU module, provided the DIP switch “2” on CPU module is DOWN. If DIP switch “2” on CPU module is UP, this setting overrides the jumper setting on LCD module. Default setting from the factory is “Fail Down” (DIP Switch “2” on CPU Module is DOWN).
However, in case of blind units please select your required DIP switch settings from the DIP switch labelled (2) marked on the Main CPU board. Recommended jumper & DIP settings are listed in the table below for ready reference.
Select Fail
Mode
Fail Down
Fail Up
Both LCD Module and CPU
Module
Only CPU
Module
CPU Module LCD Module CPU Module
Down
Down
D
U
D
U
Up U or D page 22 PAD K15/0522 ATEX
< Fail Mode Selection DIP Switch of CPU Module >
UP
DOWN
1. WR_EN (EEPROM Write Enable)
DOWN : ENABLE CONFIGURATION CHANGES
UP : DISABLE/ LOCK CONFIGURATION CHANGES
2. Fail Mode(Alarm)
DOWN : LOW
UP : HIGH
Note: DIP Switch (1) shown on Left in Fig 4-1 is for Write Enable/ Disable selection. DIP switch (2) shown on right in Fig 4-1 is for Fail Mode.
(Figure 4-1. Fail Mode and EEPROM-Write Selection DIP Switch)
< Fail Mode Selection Jumper Switch of LCD Module >
U O O O U O O
(FAIL MODE DOWN, place jumper to right)
O
FAIL MODE SELECT
D O O O D
(FAIL MODE UP, place jumper to left)
PAD
Figure 4-2 Fail Mode Selection Jumper Switch of LCD Module
PAD K15/0522 ATEX page 23
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 2 Contents
- 5 Introduction
- 5 Using This Manual
- 6 Overview of Transmitter
- 6 Software Compatibility
- 7 Transmitter Components
- 11 Handling Cautions
- 12 Unpacking
- 12 Models and Specifications Check
- 12 Storage
- 13 Selecting the Installation Locations
- 13 Performing Sensor Zero Trim after Installation
- 14 Pressure Connections
- 14 Waterproofing of Cable Conduit Connections
- 14 Restrictions on Use of Radio Transceivers
- 15 Insulation Resistance Test and Dielectric Strength Test
- 16 Installation of Explosion Protected Type Transmitters
- 21 Notes on the machine and pressure equipment directive
- 21 Transmitter Functions
- 21 Overview
- 21 Safety Message
- 22 Warning
- 22 Fail Mode Alarm
- 24 EEProm-Write Enable / Disable Mode Switch
- 25 Configuration of Alarm and Security Jumper Procedures
- 25 Configuration Using Zero and Span Push Buttons
- 36 Additional Functions (valid for PAD-F only)
- 43 Wiring Connections for External HHT/ Ammeter
- 44 Installation
- 44 Overview
- 44 Safety Message
- 45 Warning
- 46 Commissioning on the bench with Hand-Held Terminal
- 47 General Considerations
- 47 Electrical Considerations
- 48 Wiring
- 55 Mechanical Considerations
- 57 Environmental Considerations
- 58 On-line Operation
- 58 Overview
- 58 Safety Message
- 58 Configuration Data Review
- 59 Check Output
- 59 Basic Setup
- 60 Detailed Setup
- 60 Tag Information set up
- 61 Diagnostics and Services
- 61 Calibration
- 62 Advance Set Up
- 63 Maintenance
- 63 Overview
- 63 Safety Message
- 64 Hardware Diagnostics
- 65 Hardware Maintenance
- 69 Appendix I
- 71 EU Declaration of Conformance
- 73 EU Type Examination Ex d
- 75 EU Type Examination Ex ia