5.5 Configure alert handling. Micro Motion 2700
Hirdetés
Hirdetés
Configure device options and preferences
October 2022
Configuration and Use Manual
MMI-20019053
5.4.2 Configure Response Time
Display
ProLink III
Field Communicator
Not available
Device Tools → Configuration → Process Measurement → Response → Response Time
Not available
Response Time is used to apply a different algorithm to the calculation of process variables from the raw process data.
Restriction
Response Time is available only on systems with the enhanced core processor.
Procedure
Set Response Time as desired.
Option
Normal (Legacy)
Description
Transmitter calculates process variables at the standard speed. This option is selected if this parameter was configured on an earlier version of ProLink III software.
Special (Legacy) Transmitter calculates process variables at a faster speed. This option is selected if this parameter was configured on an earlier version of ProLink III software.
Normal - Optimal Filtering Transmitter calculates process variables at standard filtering and speed.
Transmitter calculates process variables at the fastest speed.
Low Filtering - Fastest
Response
High Filtering - Smoothest
Output
Service
Transmitter calculates process variables at the smoothest (least noisy) response to changes in the process.
For factory use only.
5.5 Configure alert handling
The alert handling parameters control the transmitter’s response to process and device conditions.
5.5.1 Configure Fault Timeout
Display
ProLink III
Field Communicator
Not available
Device Tools → Configuration → Fault Processing
Configure → Alert Setup → Alert Severity → Fault Timeout
Fault Timeout controls the delay before fault actions are performed.
Restriction
Fault Timeout is applied only to the following alerts (listed by Status Alert Code): A003, A004, A005, A008,
A016, A017, A033. For all other alerts, fault actions are performed as soon as the alert is detected.
70 Micro Motion 2700 Transmitters with Configurable Input/Outputs
Configuration and Use Manual
MMI-20019053
Configure device options and preferences
October 2022
Procedure
Set Fault Timeout as desired.
The default value is 0 seconds. The range is 0 to 60 seconds.
If you set Fault Timeout to 0, fault actions are performed as soon as the alert condition is detected.
The fault timeout period begins when the transmitter detects an alert condition. During the fault timeout period, the transmitter continues to report its last valid measurements.
If the fault timeout period expires while the alert is still active, the fault actions are performed. If the alert condition clears before the fault timeout expires, no fault actions are performed.
5.5.2 Configure Status Alert Severity
Display
ProLink III
Field Communicator
Not available
Device Tools → Configuration → Alert Severity
Configure → Alert Setup → Alert Severity → Set Alert Severity
Use Status Alert Severity to control the fault actions that the transmitter performs when it detects an alert condition.
Restriction
• For some alerts, Status Alert Severity is not configurable.
• For some alerts, Status Alert Severity can be set only to two of the three options.
Tip
Use the default settings for Status Alert Severity unless you have a specific requirement to change them.
Procedure
1. Select a status alert.
2. For the selected status alert, set Status Alert Severity as desired.
Option
Fault
Description
Actions when fault is detected:
• The alert is posted to the Alert List.
• Outputs go to the configured fault action (after Fault Timeout has expired, if applicable).
• Digital communications go to the configured fault action (after Fault Timeout has expired, if applicable).
• The status LED (if available) changes to red or yellow (depending on alert severity).
Actions when alert clears:
• Outputs return to normal behavior.
• Digital communications return to normal behavior.
• The status LED (if available) returns to green and may or may not flash.
Configuration and Use Manual 71
Configure device options and preferences
October 2022
Configuration and Use Manual
MMI-20019053
Option Description
Informational Actions when fault is detected:
• The alert is posted to the Alert List.
• The status LED (if available) changes to red or yellow (depending on alert severity).
Actions when alert clears:
• The status LED (if available) returns to green and may or may not flash.
Ignore No action
A002
A003
A004
A005
A006
A008
A009
Status alerts and options for Status Alert Severity
Table 5-2: Status alerts and Status Alert Severity
Alert code
A001
A010
A011
A012
A013
A014
A016
A017
A018
A019
A020
A021
A022
Status message
EEPROM Error (Core
Processor)
Default severity Notes
Fault
RAM Error (Core Processor) Fault
No Sensor Response Fault
Temperature Overrange Fault
Mass Flow Rate Overrange Fault
Characterization Required Fault
Density Overrange Fault
Fault Transmitter Initializing/
Warming Up
Calibration Failure Fault
Fault Zero Calibration Failed:
Low
Zero Calibration Failed:
High
Fault
Zero Calibration Failed:
Unstable
Transmitter Failure
Fault
Sensor RTD Failure
T-Series RTD Failure
EEPROM Error
(Transmitter)
RAM Error (Transmitter)
Fault
Fault
Fault
Fault
No Flow Cal Value
Fault
Fault
Incorrect Sensor Type (K1) Fault
Configuration Database
Corrupt (Core Processor)
Fault Applies only to flowmeters with the standard core processor.
Configurable?
No
No
Yes
Yes
Yes
No
Yes
Yes
No
No
Yes
No
No
Yes
Yes
Yes
No
Yes
No
Yes
72 Micro Motion 2700 Transmitters with Configurable Input/Outputs
Configuration and Use Manual
MMI-20019053
Configure device options and preferences
October 2022
Table 5-2: Status alerts and Status Alert Severity (continued)
Alert code
A023
A024
A025
A026
A027
A028
A031
A032
A033
A034
A035
A100
A101
A102
A103
A104
A105
Status message
Internal Totals Corrupt
(Core Processor)
Program Corrupt (Core
Processor)
Boot Sector Fault (Core
Processor)
Sensor/Transmitter
Communications Failure
Security Breach
Core Processor Write
Failure
Low Power
Meter Verification in
Progress: Outputs to Fault
Insufficient Right/Left
Pickoff Signal
Meter Verification Failed
Meter Verification Aborted Fault mA Output 1 Saturated mA Output 1 Fixed
Drive Overrange
Data Loss Possible (Totals and Inventories)
Calibration in Progress
Slug Flow
Default severity Notes
Fault Applies only to flowmeters with the standard core processor.
Fault
Fault
Applies only to flowmeters with the standard core processor.
Applies only to flowmeters with the standard core processor.
Fault
Configurable?
No
No
No
No
Fault
Fault
Fault
Varies
Fault
Fault
Informational
Informational
Informational
Informational
Informational
Informational
No
No
Applies only to flowmeters with the enhanced core processor.
Applies only to transmitters with
Smart Meter Verification.
If outputs are set to Last Measured
Value, severity is Info. If outputs are set to Fault, severity is Fault.
Applies only to flowmeters with the enhanced core processor.
Applies only to transmitters with
Smart Meter Verification.
Applies only to transmitters with
Smart Meter Verification.
Can be set to either Informational or Ignore, but cannot be set to
Fault.
Can be set to either Informational or Ignore, but cannot be set to
Fault.
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes Applies only to flowmeters with the enhanced core processor.
Can be set to either Informational or Ignore, but cannot be set to
Fault.
Can be set to either Informational or Ignore, but cannot be set to
Fault.
Yes
Yes
Configuration and Use Manual 73
Configure device options and preferences
October 2022
Configuration and Use Manual
MMI-20019053
Table 5-2: Status alerts and Status Alert Severity (continued)
Alert code
A106
A107
A108
A109
A110
A111
A112
A113
A114
A115
A118
Status message
Burst Mode Enabled
Power Reset Occurred
Basic Event 1 On
Basic Event 2 On
Frequency Output
Saturated
Frequency Output Fixed
Upgrade Transmitter
Software mA Output 2 Saturated mA Output 2 Fixed
No External Input or Polled
Data
Discrete Output 1 Fixed
Default severity Notes
Informational Can be set to either Informational or Ignore, but cannot be set to
Fault.
Informational
Informational
Informational
Normal transmitter behavior; occurs after every power cycle.
Applies only to basic events.
Informational
Applies only to basic events.
Can be set to either Informational or Ignore, but cannot be set to
Fault.
Informational
Informational
Informational
Informational
Can be set to either Informational or Ignore, but cannot be set to
Fault.
Applies only to systems with transmitter software earlier than v5.0.
Can be set to either Informational or Ignore, but cannot be set to
Fault.
Can be set to either Informational or Ignore, but cannot be set to
Fault.
Informational
Informational
A119
A120
A121
A131
A132
Discrete Output 2 Fixed
Curve Fit Failure
(Concentration)
Extrapolation Alarm
(Concentration)
Meter Verification in
Progress: Outputs to Last
Measured Value
Sensor Simulation Active
Informational
Informational
Informational
Informational
Informational
Can be set to either Informational or Ignore, but cannot be set to
Fault.
Can be set to either Informational or Ignore, but cannot be set to
Fault.
Applies only to transmitters with the concentration measurement application.
Applies only to transmitters with the concentration measurement application.
Applies only to transmitters with
Smart Meter Verification.
Configurable?
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Applies only to flowmeters with the enhanced core processor.
Can be set to either Informational or Ignore, but cannot be set to
Fault.
To Informational or Ignore only
74 Micro Motion 2700 Transmitters with Configurable Input/Outputs