Configuration parameters. Schneider Electric Software Communication Application-Specific Functions, Micro/Junior/Pro, 4.5
Advertisement
Advertisement
Configuration parameters
7
Introduction
Subject of this chapter
What's in this
Chapter?
This chapter introduces the configuration parameters for the different facilities used by the modules.
This chapter contains the following sections:
Section
7.1
7.2
7.3
7.4
7.5
7.6
7.7
Topic
Configuration parameters for TCP/IP facilities
Configuration parameters for the IO Scanning facility
Configuration Parameters for the Address Server Utility
Configuration parameters for the SNMP facility
Configuration Parameters of the Global Data Utility
Configuration Parameters of the Time Synchronization Service
ETHWAY profile configuration paramaters
Page
133
35011050 01 July 2006
Configuration parameters
7.1
Configuration parameters for TCP/IP facilities
Introduction
Subject of this sub-chapter
What's in this
Section?
This sub-chapter introduces the configuration parameters linked to the TCP/IP facility.
This section contains the following topics:
Topic
Configuration Parameters Linked to TCP/IP Utilities
Configuration Parameters for IP Addresses
Connection configuration parameters
Ethernet configuration parameters
Page
134
35011050 01 July 2006
Configuration parameters
Configuration Parameters Linked to TCP/IP Utilities
At a Glance The TSX ETY modules are comprised of configuration parameters linked to TCP/IP utilities.
Depending on the TSX ETY module selected, some configuration parameters cannot be accessed on the configuration screen. They are either not shown on the screen or are grayed out.
Availability of
Parameters
Parameters
X-WAY Address
IP Address
Connections
ETHERNET
The following table shows, for each ETHERNET module, the parameters that can be accessed from the configuration screen and the values that they can have.
TSX ETY 110
Default IP address
Configured IP Address
Subnetwork mask
Gateway address
Client/Server configuration
Connections which can be opened
Access control
Correspondence table X-WAY Address
IP Address
Protocol
Direct
Mode
ETHERNET II
802.3
X
X
X
X
By code selectors
X
-
X from 1 to 32
X
-
X
X
UNI-TE or Modbus
X
X
X
X
X
X
X
TSX ETY 410•/
PORT/510•
By PL7
X
X
X
-
X
UNI-TE or Modbus
X
Mono- or Multiconnections
-
Legends:
X Accessible
Not accessible
35011050 01 July 2006
135
Configuration parameters
Configuration Parameters for IP Addresses
At a Glance
By Default
This zone allows the IP address of a module to be defined in three distinct ways: z z z either using a default configuration, by manual configuration, or by using a configuration supplied by a BOOTP/DHCP server device.
Selecting the IP Address by default field allows the module's IP address to be calculated from the code selectors. See Common functions on the ETHWAY and
In this instance, you must code the network and station numbers on the code selectors located on the front of the module.
With this coding, the IP address is automatically derived by the system and the
IP Address , Subnetwork mask and Gateway Address fields are not significant and are grayed out.
Note: The default parameters should not be selected when the module is connected to a closed or private network.
Configured Selecting the Configured field allows manual configuration according to your own requirements: z module IP address, z z the subnetwork mask, which defines the part allocated to the subnetwork identifier in the IP address, the IP address of the default gateway, to which messages for other networks are transmitted.
Note: If the module is connected to an existing TCP/IP network, the IP addresses are administered globally, therefore the IP parameters must be configured.
Otherwise there is a risk of disturbance on the existing network caused by possible double allocation of the IP addresses.
136
35011050 01 July 2006
Client/Server
Configuration
Configuration parameters
Selecting the Client/Server configuration field allows the module's IP address to be configured from a remote device acting as a BOOTP server. See BOOTP and
.
In this instance, the IP address , Subnetwork mask and Gateway Address fields are not significant and are grayed out.
35011050 01 July 2006
137
Configuration parameters
Connection configuration parameters
Introduction
Connections which can be opened
This field enables you to : z configure the number of connections that can be opened by the module, z z activate an access check service, list the remote devices which can be connected to the module according to the communication protocol.
The Connections that can be opened field gives the maximum number of devices that can be connected in parallel to the module: z z
The default value is 8 connections.
The value is between 1 and 32 connections.
Note: You are recommended to set this parameter to the useful value in order to optimize the communication resources for each connection point.
Access control The Access check box is used to activate or deactivate the check on remote devices that want to open a TCP connection to the module.
z
If the box is checked, access check management is activated and the
Access column in the table is de-grayed (active).
If the module is operating in server mode, only the remote devices selected by the Access box in the table are authorized to be connected as a client and then to communicate.
z
If the box is unchecked, check management does not operate and the
Access column in the table is grayed out (not active).
If the module is operating in server mode, third party remote devices can be connected as a client and then communicate with the module without having to be declared in the table.
Note: The access check only works on the TCP/IP profile and is used for the module to operate in server mode.
138
35011050 01 July 2006
Function table
Configuration parameters
This table enables you: z to list the remote devices with which the local module wishes to open a TCP z connection and then transmit (module operating in client mode), to provide a cross reference between the X-WAY address {network, station} and the IP address , z z z the network number must be less than or equal to 127, the station number is between 0 and 63 for a connection in UNITE or between
100 and 163 for a connection in Modbus.
to specify the communication protocol for each remote device during the connection using a scrolling menu: z z
UNI-TE (default value),
Modbus , z z when managing access checks, to nominate the remote devices authorized to open a TCP connection and then to send to the local module (module operating in server mode), for each remote IP address, to choose the Connection mode using a scrolling menu : z
Monoconnection : the module only allows one connection with the same z remote IP address,
Multiconnection : the module allows only one connection with the same remote IP address in client mode and several connections with the same remote IP address in server mode.
35011050 01 July 2006
139
Configuration parameters
Ethernet configuration parameters
Introduction This field is used to define the format of the Ethernet frame via TCP/IP: z the Ethernet II format: complying with the FRC 894 standard (the most commonly z used), the 802.3 format: complying with the FRC 1042 standard. This format is to be selected if the remote devices use this format.
140
35011050 01 July 2006
7.2
Configuration parameters
Configuration parameters for the IO Scanning facility
Introduction
Subject of this sub-chapter
What's in this
Section?
This sub-chapter introduces the configuration parameters linked to the IO Scanning facility.
This section contains the following topics:
Topic
Configuration Parameters Linked to the IO Scanning Utility
Configuration of general parameters for IO Scanning facility
Configuration of scanned peripheral devices
Page
35011050 01 July 2006
141
Configuration parameters
Configuration Parameters Linked to the IO Scanning Utility
At a Glance The TSX ETY modules are comprised of configuration parameters for the IO
Scanning utility.
Depending on the TSX ETY module selected, some configuration parameters cannot be accessed on the configuration screen. They are either not shown on the screen or are grayed out.
142
35011050 01 July 2006
Configuration parameters
Availability of
Parameters
Parameters
Input fallback
The following table shows, for each ETHERNET module, the parameters that can be accessed from the configuration screen and the values that they can have.
TSX ETY 110
Scanning adjustment Fast
Normal
Slow
Master %MW zones
Peripherals scanned
Read Ref.
Write Ref.
IP Address
Unit ID
Repetitive rate
Master RD ref.
Slave RD ref.
RD count
Master WR ref.
Slave WR ref.
WR count
Description
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
X
X
X
TSX ETY 410•/
PORT/510•
Fallback to 0/
Maintain set at 10 ms from 15 to 240 ms from 150 to 1000 ms
X
X
X
X
None/Fast/Normal/
Slow automatic
X
X automatic
-
Legends:
X Accessible
Not accessible
35011050 01 July 2006
143
Configuration parameters
Configuration of general parameters for IO Scanning facility
Introduction
Input fallback
Adjusting the scanning
To configure the IO Scanning service some parameters are general at the remote inputs/outputs: z z z the input fallback mode, adjusting the scanning periods, the read and write zones.
This sub window is used to configure the behavior of inputs when the inputs have not been refreshed (example : PLC set to Stop, device disconnection, …) : z z
Fallback to 0
Maintain
This sub window is used to configure the scanning period in milliseconds : z the Fast period : this period cannot be configured (field grayed out) and is set at
10 ms.
z z the Normal period : this period can be configured from 30 - 240 ms by increments of 15 ms.
the Slow period : this period can be configured from 150 - 1000 ms by increments of 50 ms.
Note: The value of the Normal period cannot be less than the value of the Slow period.
Master %MW fields
This sub window is used to define the internal word formats from the (%MW) memory application dedicated to the read and write zones.
For that you have to enter the following: z for the read zone Read Ref.
, the address of the start of the internal words table z for reading inputs, for the writing field Write Ref.
, the address of the start of the internal words table for writing outputs.,
The length of the tables has a maximum exchange capacity of: z
2 Kwords for the read zone, z
2 Kwords for the write zone.
Note: The tables must not overlap each other and an overrun check is carried out in the global validation.
144
35011050 01 July 2006
Configuration parameters
Configuration of scanned peripheral devices
At a Glance
The IP Address and Unit ID fields
The IP Address field is used to list the devices which must be scanned by the
ETHERNET module.
The Unit ID field is used to associate the slave address of the device connected to an ETHERNET/Modbus gateway with the IP address. See Architecture supported
by a Modbus communication on the TCP/IP profile., p. 73 .
z z values are from 0 to 255, the default value is 255.
Repetitive rate
Scanned peripheral devices are configured in a table which is used: z z to list remote devices to be scanned, using the IP address, to specify the scanning period allotted to it for each remote device, z z to configure, for each device, the amount of space the input and output words take up in the read and write zones, to add comments for each device.
The Repetitive rate field is used to associate an IP address with its scanning period.
See
.
The type of period is selected using a pull-down menu and can have the following values: z
NONE : this selection is used to deactivate scanning of the corresponding IP address, z z z
FAST : for fast scanning periods,
NORMAL : for nominal scanning periods,
SLOW : for slow scanning periods.
Note: When NONE is selected, the internal words reserved for the corresponding
IP address are saved in the read and write zones but are not updated.
35011050 01 July 2006
145
Configuration parameters
Master RD ref. and master WR ref.
These parameters give the addresses of the beginning of each range reserved for the device.
These parameters cannot be accessed. They are calculated automatically as the sum of: z z the address of the beginning of the Read Ref.
table and the Write Ref.
table, and the length of the RD count and WR count fields.
Example
The ETHERNET module scans two devices: z a Momentum at the address IP1, which has 4 input words.
z a Momentum at the address IP2, which has one input word.
Furthermore, the read field address starts at %MW100.
In this case, master RD ref.
for the address IP1 equals 100. The internal word range reserved for the address IP1 starts at %MW100 and is made up of 4 words.
Therefore, master RD ref.
for the address IP2 equals 104. The internal word range reserved for the address IP2 starts at %MW104 (=%MW100 + 4 input words).
Slave RD ref. and slave WR ref.
These fields correspond to the indices of the first word to be read and written for remote devices to be scanned.
z z slave RD ref.
: specifies the address of the first word to be read slave WR ref.
: specifies the address of the first word to be written
RD count and
WR count
These fields contain the number of words to be transmitted per device in read and write.
These values conveyed by the Modbus requests vary: z z from 0 to 125 for the RD count field (if it equals 0,the read request is not sent), from 0 to 100 for the WR count field (if it equals 0,the write request is not sent),
Note: If the device to be scanned does not respond to the Modbus (17) read/write requests, the remote device must be configured over two lines, one for reading with the WR count value at zero, and the other for writing with the RD count value at zero.
Description
146
Note: These two fields cannot both have the value 0. Otherwise, the remote device will not be managed.
This field is not used by the module. It is only used to locate the device in the configuration more easily.
It has a maximum size of 32 characters.
35011050 01 July 2006
7.3
Configuration parameters
Configuration Parameters for the Address Server
Utility
At a Glance
Aim of this
Section
What's in this
Section?
This Section introduces the configuration parameters linked to the BOOTP/DHCP address server.
This section contains the following topics:
Topic
Configuration Parameters Linked to the Address Server Utility
Address Server Configuration
Page
35011050 01 July 2006
147
Configuration parameters
Configuration Parameters Linked to the Address Server Utility
At a Glance The TSX ETY modules are comprised of configuration parameters linked to the address server utility.
Depending on the TSX ETY module selected, some configuration parameters cannot be accessed on the configuration screen. They are either not shown on the screen or are grayed out.
Availability of
Parameters
Parameters
The following table shows, for each ETHERNET module, the parameters that can be accessed from the configuration screen and the values that they can have.
TSX ETY 110
HTTP modification Locked in operation
Password
BOOTP/DHCP address table
-
-
-
X
X
TSX ETY 410•/
PORT/510•
X
-
Legends:
X Available
Not available
148
35011050 01 July 2006
Configuration parameters
Address Server Configuration
At a Glance
Utility
Parameters linked to the address server are divided into 3 categories: z
The type of server: BOOTP or DHCP z z rights to modify the utility via the HTTP server, the table of addresses for which service is provided.
This zone allows the type of server to be selected (BOOTP or DHCP): z z
The BOOTP mode can be used when the "Replace faulty remote stations" is not wanted.
The DHCP mode is essential if the "Replace faulty remote stations" utility is required.
Note: BOOTP mode is the mode automatically selected if the applications have been created with PL7 (version V4.0 and later) and configure the
TSX ETY 410•/PORT/510• modules.
HTTP modification
Address Tables
This zone is used to define the access rights to the DHCP or BOOTP address table via the HTTP server.
The access rights are configured by two parameters: z the Locked in operation check box: which activates or deactivates access z control to the table, the Password field: the table is accessed via the HTTP server by means of a password of no more than 8 ASCII characters.
Depending on the selection made in the Utility zone,
The BOOTP table can be used: z to list, by their MAC address, the remote stations which need the BOOTP server to start up, z to provide a correspondence between the MAC and IP addresses,
The DHCP table can be used: z to list, by their MAC address or by name (16 character ASCII), the remote stations which need the DHCP server to start up, z to supply a connection between the MAC address or the name and the IP address of the remote station, the Netmask and the Gateway.
35011050 01 July 2006
149
Configuration parameters
7.4
Configuration parameters for the SNMP facility
Introduction
Subject of this sub-chapter
What's in this
Section?
This sub-chapter introduces the configuration parameters linked to the SNMP facility.
This section contains the following topics:
Topic
Configuration Parameters Linked to the SNMP Utility
Configuration of the SNMP Utility
Page
150
35011050 01 July 2006
Configuration parameters
Configuration Parameters Linked to the SNMP Utility
At a Glance The TSX ETY modules are comprised of configuration parameters linked to the
SNMP utility.
Depending on the TSX ETY module selected, some configuration parameters cannot be accessed on the configuration screen. They are either not shown on the screen or are grayed out.
Availability of
Parameters
Parameters
IP Address Managers
Agent
Community names
Security
The following table shows, for each ETHERNET module, the parameters that can be accessed from the configuration screen.
TSX ETY 110
Location (SysLocation)
Contact (SysContact)
SNMP Manager
Set
Get
Trap
Enable "Authentication Failure" trap
X
X
X
X
-
X
X
X
X
X
X
X
X
X
X
X
TSX ETY 410•/
PORT/510•
-
Legends:
X Accessible
Not accessible
35011050 01 July 2006
151
Configuration parameters
Configuration of the SNMP Utility
At a Glance Parameters linked to the SNMP module are divided into 4 categories: z the IP addresses of the SNMP module administrative devices, z z z the agents, the community names, security.
Note: Only 7-bit ASCII characters can be used in the character string entry fields.
Administrators
IP Addresses
Agent
This zone allows the completion of the SNMP administrators IP addresses. The modules authorize a maximum of two administrators.
These addresses are used during possible transmission of events (TRAP). See
SNMP Communication on UDP/IP, p. 95
.
This zone allows the localization and identification of an agent from the SNMP administrator.
It comprises two fields: z
The Location (SysLocation) field: indicates the physical location of the device z
(32 characters maximum).
The Contact (SysLocation) field: indicates the personnel to contact for device z management and the method of contact (32 characters maximum).
It is possible to select information assignment by a "SNMP Manager" tool for network management, rather than by PL7 software. To do this, check the SNMP
Manager box.
152
35011050 01 July 2006
Community
Name
Security
Configuration parameters
This zone allows the definition of a community name by utility family Set, Get and
Trap.
It comprises three fields: z
The Set field defines the community name for the Set utility (16 characters maximum). The default value of the field is Public .
z z
The Get field defines the community name for the Get utility (16 characters maximum). The default value of the field is Public .
The Trap field defines the community name for the Trap utility (16 characters maximum). The default value of the field is Public .
The purpose of these fields is to define the access rights for SNMP agent MIB objects (local module) in relation to requests transmitted by the administrator.
Example
If the administrator transmits a SetRequest request with the community name Test and the module has the community name Public , the request will not be executed.
This zone contains the Enable "Authentication Failure" trap check box.
Enabling this box allows the transmission of an event (TRAP) of an authentication failure to be confirmed from the SNMP agent to the administrator that originally posted the request.
In this way, the agent warns the administrator that the request has been refused following an identification error (community name configured in the administrator is different to the one configured in the agent).
CAUTION
Modifications to the SNMP parameters
The SNMP administrator is able to modify the value of certain parameters, which can be configured by PL7 (Enabling "Authentication failure", Location, Contact. etc.)
When there is a cold start, warm restart or application download, the values initially configured in PL7 are then restored.
Failure to follow this precaution can result in injury or equipment damage.
35011050 01 July 2006
153
Configuration parameters
7.5
Configuration Parameters of the Global Data
Utility
At a Glance
Aim of this
Section
What's in this
Section?
This Section introduces the configuration parameters linked to the Global Data utility.
This section contains the following topics:
Topic
Configuration Parameters Linked to the Global Data Utility
Configuring the General Parameters for the Global Data Utility
Configuration of the Variables Table
Page
154
35011050 01 July 2006
Configuration parameters
Configuration Parameters Linked to the Global Data Utility
At a Glance The TSX ETY modules are comprised of configuration parameters linked to the
Global Data utility.
Availability of
Parameters
Parameters
Global Data configuration
Table of variables
Group address
Distribution Period
Validity time out
Multicast Filtering
%MW Zone
Ident
Type
Symbol
Address
Length
-
Legends:
X Accessible
Not accessible
-
-
-
-
-
-
-
-
-
-
TSX ETY 110 TSX ETY 410•/
PORT/510•
X
X
X
X
X
X
X
X
X
X
35011050 01 July 2006
155
Configuration parameters
Properties The following table provides the Global Data utility properties.
Type
Number max. of publications
Size of a variable at publication
Number max. of subscriptions
Maximum variable size at subscription
Value
1
1 to 512 words
64
Total of 2K words
The application variables are stored in a contiguous %MW zone.
Each published or subscribed application variable in a Distribution Group is linked to a Global Data.
Each Global Data has a unique identification ( Ident.
) on the inside of a Distribution
Group. This identification corresponds to the status bit position in the Global Data status bit zone.
The link between published/subscribed application variable and Global Data is established during the configuration phase.
156
35011050 01 July 2006
Configuring the General Parameters for the Global Data Utility
Configuration parameters
At a Glance
Group Address
Distribution
Period
The following parameters can be entered in the Global Data Configuration zone of the configuration (See
Configuring the Global Data Utility, p. 252 ) screen:
z z
Group address
Distribution period z z z
Validity time out
Multicast filtering
%MW Zone
This zone allows the multicast IP address (class D) to be entered for the group to which the station belongs. The value 239.255.255.255 is the default value.
This zone allows the distribution period of the publication to be selected. The publication is synchronized with the PLC master task. The publication can be performed at each cycle of the Mast task (default value), or every n cycles of the
Mast. task.
Validity Time Out This zone allows the validity "time-out" value to be adjusted.
An associated status bit (%IW zone) is linked to each Global Data and allows monitoring if the data has been published and received by the end of the time indicated in this window. If yes, the value is 1, otherwise the bit is set to 0.
Multicast
Filtering
This check box activates the multicast filtering.
This function allows the reduction of data flow on large networks. Multicast filtering requires the use of commutators that support this function (GMRP IEEE 802.1D protocol).
%MW Zone This zone allows the configuration of the start word address in the memory zone reserved for variables. According to the variable used, the end zone word address is calculated automatically by the program and displayed. An error appears if the maximum length is exceeded.
35011050 01 July 2006
157
Configuration parameters
Configuration of the Variables Table
At a Glance
Ident. Zone
Type Zone
The Table of variables zone of the Global Data configuration screen enables you to configure the station variables.
Several zones are available: z
Ident.
z z z z
Type
Symbol and button labeled Update symbols
Address
Length
This column, numbered from 1 to 64 , indicates the identification numbers of the configurable variables.
This column enables you to choose the type of each variable: z
NONE : variable that is neither published nor subscribed z z
PUB : published variable
SUB : subscribed variable
Symbol Zone
Address zone
Length Zone
This column enables you to display the symbol given to a %MW zone, defined in the
PL7 application variables editor.
Use the Update symbols button to update the value following a modification.
This column displays the zone start address of a variable in %MW.
The word index of the preceding variables is automatically updated according to the length and the choice of address of the first word of the zone (See %MW Zone,
).
In this column enter the length of the variable wanted in number of words. The %MW zone is thus updated.
Error Monitoring There is no monitoring of consistency between the configurations of the different stations.
In the case of a configuration error, the %MWxy.i.13 internal word indicates the type of error (see
158
35011050 01 July 2006
7.6
Configuration parameters
Configuration Parameters of the Time Synchronization Service
At a Glance
Aim of this
Section
What's in this
Section?
This section introduces the configuration parameters linked to the time synchronization service, which uses the Network Time Protocol (NTP).
This section contains the following topics:
Topic
Configuration Parameters Linked to the Time Synchronization Service (NTP)
Using the Time Synchronization Service
Configuration of the Time Synchronization Service (NTP)
Page
35011050 01 July 2006
159
Configuration parameters
Configuration Parameters Linked to the Time Synchronization Service (NTP)
List of
Parameters
Time Zones
Available
Configure or change the following parameters on the NTP Configuration page.
1.
IP address of primary NTP server z
Enter a valid IP address
2.
IP address of secondary NTP server z
Enter a valid IP address
3.
Polling Period (in seconds)
Enter a value z min = 1sec z z max = 120sec default = 5 sec
4.
Time Zone z
Select from drop-down menu z
Universal Time, Coordinated (GMT) = default
Custom time zone
5.
Automatically adjust clock for daylight saving change z
Parameter is selected by default (check mark appears) if daylight saving time is chosen.
Select one from drop-down menu.
Time Zone Description
Custom
(GMT-12:00) Dateline Standard Time [Eniwetok Kwajalein]
(GMT-11:00) Samoa Standard Time [Midway Is Samoa]
(GMT-10:00) Hawaiian Standard Time [Hawaii Honolulu]
(GMT-09:00) Alaskan Standard Time [Anchorage]
(GMT-08:00) Pacific Standard Time [Los Angeles Tijuana]
(GMT-07:00) Mexican Standard Time [Chihuahua La Paz Mazatlan]
(GMT-07:00) Mountain Standard Time [Arizona Phoenix]
(GMT-07:00) Mountain Standard Time [Denver]
(GMT-06:00) Central Standard Time [Chicago]
(GMT-06:00) Mexico Standard Time [Tegucigalpa]
(GMT-06:00) Canada Central Standard Time [Saskatchewan Regina]
(GMT-06:00) Central America Standard Time [Mexico_city]
(GMT-05:00) SA Pacific Standard Time [Bogota Lima Quito]
(GMT-05:00) Eastern Standard Time [New York]
No
No
Yes
No
Yes
Yes
No
Yes
Yes
No
No
Yes
Yes
DST
Available
Yes
No
160
35011050 01 July 2006
35011050 01 July 2006
Configuration parameters
Time Zone Description
(GMT-05:00) Eastern Standard Time [Indiana (East)] [Indianapolis]
(GMT-04:00) SA Western Standard Time [Caracas La Paz]
(GMT-04:00) Pacific SA Standard Time [Santiago]
(GMT-03:30) Newfoundland Standard Time [Newfoundland St Johns]
(GMT-03:00) E. South America Standard Time [Brasilia Sao_Paulo]
(GMT-03:00) SA Eastern Standard Time [Buenos Aires Georgetown]
(GMT-02:00) Mid-Atlantic Standard Time [South_Georgia]
(GMT-01:00) Azores Standard Time [Azores Cape Verde Island]
(GMT)
(GMT0)
Universal Coordinated Time [Casablanca, Monrovia]
Greenwich Mean Time [Dublin Edinburgh Lisbon London]
(GMT+01:00) Romance Standard Time [Amsterdam CopenHagen Madrid
Paris Vilnius]
(GMT+01:00) Central European Standard Time [Belgrade Sarajevo Skopje
Sofija Zagreb]
(GMT+01:00) Central Europe Standard Time [Bratislava Budapest Ljubljana
Prague Warsaw]
Yes
Yes
(GMT+01:00) W. Europe Standard Time [Brussels Berlin Bern Rome
Stockholm Vienna]
(GMT+02:00) GTB Standard Time [Athens Istanbul Minsk]
(GMT+02:00) E. Europe Standard Time [Bucharest]
Yes
Yes
Yes
(GMT+02:00) Egypt Standard Time [Cairo] Yes
(GMT+02:00) South Africa Standard Time [Johannesburg Harare Pretoria] No
(GMT+02:00) FLE Standard Time [Helsinki Riga Tallinn]
(GMT+02:00) Israel Standard Time [Israel Jerusalem]
(GMT+03:00) Arabic Standard Time [Baghdad]
(GMT+03:00) Arab Standard Time [Kuwait Riyadh]
Yes
Yes
Yes
No
(GMT+03:00) Russian Standard Time [Moscow St. Petersburg Volgograd] Yes
(GMT+03:00) E. Africa Standard Time [Nairobi] No
(GMT+03:30) Iran Standard Time [Tehran]
(GMT+04:00) Arabian Standard Time [Abu Dhabi Muscat]
Yes
No
(GMT+04:00) Caucasus Standard Time [Baku Tbilisi]
(GMT+04:00) Afghanistan Standard Time [Kabul]
(GMT+05:00) Ekaterinburg Standard Time [Ekaterinburg]
(GMT+05:00) West Asia Standard Time [Islamabad Karachi Tashkent]
Yes
No
Yes
No
No
Yes
No
Yes
Yes
Yes
Yes
Yes
No
DST
Available
No
No
161
Configuration parameters
Time Zone Description
(GMT+05:30) India Standard Time [Bombay Calcutta Madras New Delhi]
(GMT+06:00) Central Asia Standard Time [Almaty Dhaka]
(GMT+06:00) Sri Lanka Standard Time [Columbo]
(GMT+07:00) SE Asia Standard Time [Bangkok Hanoi Jakarta]
No
No
(GMT+08:00) China Standard Time [Beijing Chongqing Hong Kong Urumqi] No
(GMT+08:00) W. Australia Standard Time [Perth] No
DST
Available
No
Yes
(GMT+08:00) Singapore Standard Time [Singapore]
(GMT+08:00) Taipei Standard Time [Taipei]
(GMT+09:00) Tokyo Standard Time [Osako Sapporo Tokyo]
(GMT+09:00) Korea Standard Time [Seoul]
No
No
No
No
(GMT+09:00) Yakutsk Standard Time [Yakutsk]
(GMT+09:30) Cen. Australia Standard Time [Adelaide]
(GMT+09:30) AUS Central Standard Time [Darwin]
(GMT+10:00) E. Australia Standard Time [Brisbane]
(GMT+10:00) AUS Eastern Standard Time [Canberra Melbourne Sydney]
(GMT+10:00) West Pacific Standard Time [Guam Port Moresby]
(GMT+10:00) Tasmania Standard Time [Hobart]
(GMT+10:00) Vladivostok Standard Time [Vladivostok]
(GMT+11:00) Central Pacific Standard Time [Magadan Solomon Is New
Caledonia]
(GMT+12:00) New Zealand Standard Time [Auckland Wellington] Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
No
No
(GMT+12:00) Fiji Standard Time [Fiji Kamchatka Marshall Is] No
162
35011050 01 July 2006
Configuration parameters
Using the Time Synchronization Service
Establishing
Accuracy at
Power Up
Obtaining and
Maintaining
Accuracy
Before starting a system, the Ethernet network must be configured for a predefined interval within which the accuracy is established. Accuracy is established at powerup—the Ethernet module boots and then obtains the time from the NTP Server.
Several updates may be required to achieve peak accuracy. Once an accurate time is obtained, the time synchronization service sets the STATUS in the associated time service register.
The time service clock starts at 0 and increments until the Ethernet network time is fully updated from the module.
Model
Premium with PL7
Starting Date
January 1st 1980 00:00:00.00
z z z
Clock accuracy is not affected by issuing Stop/Run commands on the PLC
Clock updates are not affected by issuing Stop/Run commands on the PLC
Mode transitions do not affect the accuracy of the Ethernet network
Reinitializing the
Time Service
Register
After a download or an NTP server swap, the status clock value associated with the time service register in the CPU is reinitialized.
Two polling periods elapse before an accurate time is re-established.
35011050 01 July 2006
163
Configuration parameters
Configuration of the Time Synchronization Service (NTP)
Configuring the
Time Service with the NTP
Configuration
Page
You must use the module’s embedded Web page to configure the time service. No other method is available.
NTP Configuration
NTP Server Configuration
IP Address of Primary NTP Server:
IP Address of Secondary NTP Server:
Polling Period:
Time Zone
(GMT-05:00)Eastern Standard Time[New York]
15
192.168.5.100
0.0.0.0
sec
Automatically adjust clock for daylight saving change
Save Cancel Disable NTP
Time Service
Command
Buttons
Execute the following commands
Command Button Description
Save Stores new NTP (time service) configuration. Previous configuration is no longer valid.
Cancel
Disable NTP
Cancels new NTP (time service) configuration. Previous configuration is valid
IP of Primary and Standby set = 0.
NTP server not polled
Time in controller not updated.
164
35011050 01 July 2006
Configuration parameters
Changing Time
Service
Parameters
To make any changes to the time synchronization service,
Step
1
2
Action
Enter changes in the appropriate field on the NTP Configuration page for one or all of the configurable parameters.
Click Save.
Important
Information about the Time
Service
Note: About the Time Service
1.
Enable/Disable Daylight Savings Time parameter
If the Enable/Disable check box is selected, the module automatically corrects the local time to account for daylight savings time. Therefore, requiring no action, as the daylight savings time start and end are automatically changed each year.
2.
Polling Time Parameter
The time (in seconds) is the time between time updates from the NTP server.
The default is 5 Seconds.
3.
Storing the Time Service Configuration
The last time service configuration is saved internally in the Ethernet module.
4.
Replacing the Ethernet Module
If the Ethernet module has to be replaced, the stored configuration is lost, and the system returns to the default configuration.
35011050 01 July 2006
165
Configuration parameters
Customizing
Time Zone
Parameters
If you want a time zone not listed in the time zone table,
Step Action
1 Write the text rules for the custom time zone.
Comment
2 Using an FTP client, store your rules in the file:
/FLASH0/wwwroot/conf/NTP/customrules user ID: ntpupdate password: ntpupdate
3 When the rules are written, choose the drop down menu on the NTP Configuration web page, and configure (or reboot) the module by selecting
Time Zone = Custom
Root directory to store 'customrules' is set by the FTP server as
/FLASH0/wwwroot/conf/NTP
The NTP component looks for customrules, calls the tz compiler and generates a new file called
'tz_custom'. This file is binary file and should not be edited.
If the tz compiler detects a syntax error in customrules, the error is logged in the file:
/FLASH0/wwwroot/conf/NTP/ error.log
1.
NTP component is not launched
2.
NTP Status field in diagnostic web page displays NOT OK.
4 If you want more information, the syntax to write those rules along with a few examples are found in the module in
/FLASH0/wwwroot/conf/NTP/instructions.txt
166
35011050 01 July 2006
7.7
Configuration parameters
ETHWAY profile configuration paramaters
Introduction
Subject of this sub-chapter
What's in this
Section?
This sub-chapter introduces the configuration parameters linked to the ETHWAY profile.
This section contains the following topics:
Topic
Configuration Parameters Linked to the ETHWAY Profile
Configuration of ETHWAY data
Page
35011050 01 July 2006
167
Configuration parameters
Configuration Parameters Linked to the ETHWAY Profile
At a Glance
Availability of
Parameters
Parameters
ETHWAY data
(common words)
The TSX ETY modules have associated with them configuration parameters for the
ETHWAY profile.
Depending on the TSX ETY module selected, some configuration parameters cannot be accessed on the configuration screen. They are either not shown on the screen or are grayed out.
The following table shows, for each ETHERNET module, the parameters that can be accessed from the configuration screen and the values that they can have.
TSX ETY 110
None
Common read words
Common read/write words
Word size/station 4
8
16
32
64
Network address
X
X
X
X
X
X
X
X
X
-
-
-
-
-
-
-
-
-
TSX ETY 410•/
PORT/510•
-
Legends:
X Accessible
Not accessible
168
35011050 01 July 2006
Configuration parameters
Configuration of ETHWAY data
Introduction
None
The ETHWAY data parameters are used to configure the common words by: z selecting the type of service supported, z z the number of words allocated per station, the network address of the local station.
The selection of this field invalidates the management of common words in the application.
The module does not manage the common database.
Common reading words
The application has read only access to the common words.
Common reading
/writing words
The application has read and write access to the common words.
Size of words/ station
This field can be accessed when selecting reading/writing words .
Common reading words or Common
Filling in this field configures the number of common words managed by the local module.
Note: The size of common words must be the same for each network station.
Network address This field can be accessed when selecting Common reading words or Common reading/writing words .
Filling in this field identifies the network which supports the common words service.
35011050 01 July 2006
169
Configuration parameters
170
35011050 01 July 2006
Download