The Schneider Electric XGKS.../XGPS... Communication card allows data exchange between different systems using UNI-TELWAY and Modbus/Jbus protocols. With this card, you can connect your XG field station to a multidrop bus, enabling control and monitoring of various functions such as reading and writing data, resetting counters, and performing diagnostics. Additionally, the card provides signaling LEDs for status indication, helping you quickly identify any issues.
ಜಾಹಿರಾತು
ಜಾಹಿರಾತು
1 Hardware setup
Read and understand this bulletin in its entirety before installing or operating Inductel XG components.
Qualified personnel must perform installation, adjustment, and maintenance of the INDUCTEL XG components.
There are no user serviceable parts within this Inductel XG component.
No responsibility is assumed by Schneider Electric for any consequence arising out of the use of this material.
1.1
Presentation
The XG field station can be connected to UNITELWAY and Modbus / Jbus networks.
It is supplied with a 2.5 meter connection cable equipped with two connectors :
• a 9-pin SUB-D connector for connection to the card
• a 15-pin SUB-D connector for connection to the bus
The XG field station can receive and respond to data messages.
This exchange of data provides access to certain functions of the XG field station, such as :
• Control
• Monitoring
I
S
H
E
N
G
L
3
1
Hardware setup
Configuration
of
the
network
option
card
L
I
S
H
E
N
G
6.2
Configuration
of
the
network
option
card
6.2.1 Layout of the card
SW3
SW2
Standard card
2 Signaling LEDs
SW1
3
Configuration switches
1
0
1 8
1
Address switches
Network option card
Connector
6.2.2 Coding the network option card address
See diagram on page 5.
An XG field station is identified on the bus by its address, which is coded from 1 to 31.
The address corresponds to the binary number given by setting the switches c on the card to 1 or 0 (switches no.
3 to no.
7 are used).
The three other switches are not used.
Caution : The least significant bits are on the right.
4
1 Hardware setup
Configuration of the network option card
Examples :
1 1
0
1 2 3 4 5 6 7 8
0 address 2
1
0
1 2 3 4 5 6 7 8
1
0 address 5
Address 0 is prohibited.
The modified address will be validated when the XG field station is next switched on.
I
S
H
E
N
G
L
1.2.3 Configuration switches
The card has 2 switches e for configuring the RS 485 link.
UNI-TELWAY : (polarized RS 485 line).
Modbus / Jbus (non-polarized RS 485 line).
CAUTION
ELECTROSTATIC CHARGE
This products contains sensitive electronic components.
Set switches with unit switched off.
Failure to follow this instruction can cause equipment damage
5
1 Hardware setup
I
S
H
E
N
G
L
1.2.4 Selection of the network option card serial link speed
Caution : Switch SW2 is located on the standard card.
Functions
Setting the transmission speed
(bds) of the network option card
1
OFF
ON
OFF
ON
Micro-switch no.
2
OFF
OFF
ON
ON
3 4
Result obtained
19,200
9600
4800
2400
Data coding principle according to the chosen mode.
Specifications 8 RTU bits
Coding system
Number of bits per character
- Start bit
- Significant bits
- Parity
- Stop bit
Message organization
- Message
- Check
- End of frame
8 binary code bits
1
8
Even / Odd
1
MODBUS frame
CRC
3-character silence
1.2.5 Selection of the network option card protocol
Caution : Switch SW2 is located on the standard card.
Functions
Selection of the protocol for the network option card
1
Micro-switch no.
2 3
ON
OFF
4
Result obtained
UNI-TELWAY
MODBUS / JBUS
1.2.6 Signaling LEDs
The UNI-TELWAY, Modbus / Jbus card has two signaling LEDs d whose operation is described in detail in Section 5 - Diagnostics.