Schneider Electric PCMCIA communication card protocols UNI-TELWAY, MODBUS/JBUS. User Guide
광고
광고
carte de communication PCMCIA protocoles
UNI-TELWAY, MODBUS/JBUS
PCMCIA communication card protocols
UNI-TELWAY, MODBUS/JBUS
VW3-A66301
guide d'exploitation user's manual
TE
Altivar 16
Carte de communication PCMCIA ............................................................................. page 2 protocoles
UNI-TELWAY, MODBUS / JBUS
PCMCIA communication card .................................................................................. page 52 protocols
UNI-TELWAY, MODBUS / JBUS
I
S
H
E
N
G
L
Ç
A
I
S
F
R
A
N
1
I
S
H
E
N
G
L
Although every care has been taken in the preparation of this document,
Schneider Electric SA cannot guarantee the contents and cannot be held responsible for any errors it may contain or for any damage which may result from its use or application.
NOTE way be considered contractual.
5 2
Contents
Introduction
Installing the card
Connection to the multidrop bus
Communication principle
Setting up the Altivar 16
Reading parameters
Writing parameters
Altivar 16 variables
UNI-TELWAY requests
MODBUS / JBUS protocol
Diagnostics
54
55
56 to 58
59 to 61
62 and 63
64
65
66 to 84
85 to 88
89 to 100
101
I
S
H
E
N
G
L
5 3
I
S
H
E
N
G
L
Introduction
The communication card, reference VW3-A66301, is designed to be used with Altivar 16 speed controllers which are fitted with a VW3-A16303 communication interface.
It is designed to integrate these power switching components into modern control system architectures by enabling them to be connected to an industrial multidrop bus.
Data exchanges enable all the functions of the Altivar 16 to be used :
• function configuration,
• downloading of settings,
• control and supervision,
• monitoring,
• diagnostics.
The VW3-A66301 communication card (PCMCIA type 3 format) has a 3 m connection cable fitted with a 15-pin SUB-D connector.
The card manages the following communication protocols :
• UNI-TELWAY,
• MODBUS/J BUS.
Only VW3-A16303 communication interface with software version above or equal to V1.3 IE04 can be used with VW3-A66301 PCMCIA communication card.
5 4
Installing the card
Before performing any operation on the speed controller switch it off and wait for the capacitors to discharge (approximately 1 min after switching off).
• Check that the speed controller is connected to earth via terminal G.
• Install the VW3-A16303 communication interface on the speed controller (see user's manual).
• Insert the VW3-A66301 communication card in its guide so that the connection cable, which is 3 meters long, falls towards the base of the product.
• Run the connection cable through the cable clamp located below the communication card slot.
Communication interface
Communication card
I
S
H
E
N
G
L
Cable clamp
5 5
I
S
H
E
N
G
L
5 6
Connection to the multidrop bus
SUB-D connector pinout
The RS 485 and RS 422 (RS 232 C compatible) standard transmission interface is electrically isolated from the speed controller. It is available on a 15-pin SUB-D connector.
TX
E
4,7 k
Ω
5V
OV
D (B)
5
15
14
0V
4,7 k
Ω
D (A)
7 enable transmission
RX
&
&
100 k
Ω
5V
RD (B)
2
3
8
8
7
6
5
4
3
2
1
10
9
15
14
13
12
11
0V
100 k
Ω
0V
RD (A)
Seen from external contact side
Connection to the standard RS 485 bus
Pins to use
SUB-D connector (15-pin) Automated system
PG
*
PG
Transmission
E
0V
D(B)
D(A)
15
14
7
Zt
0V
Reception
RXD+
A'
R
RXD-
B'
120
Ω
1 nF
RX
R
Reception
TXD+
A
E
TXD-
B
Transmission
Zt line terminator recommended at both ends of the line
0V
*
Connection of the shielding to both ends depends on installation constraints
Recommendations
• use a shielded cable with 2 pairs of twisted conductors,
• connect the reference potentials to each other,
• maximum length of the line : 1000 meters,
• maximum length of a tap-link : 20 meters,
• do not connect more than 28 stations on a bus,
• cable routing : keep the bus away from the power cables
(30 cm minimum), and make right-angle crossovers if necessary; connect the cable shielding to the earth of each device,
• fit a line terminator at both ends of the line.
Connection to multidrop bus
Connection to standard RS 422 bus
Pins to use
SUB-D connector (15-pin) Automated system
0V 15
Transmission
TXD+
E
RXD+
TXD-
0V
R
0V
RXD-
Reception
Rp Rp
5V
A
B
A'
B'
PG
14
7
3
8
Zt
*
0V
Zt
A'
B'
A
B
RXD+
R
Reception
RXD-
TXD+
E
Transmission
TXD-
PG
*
Connection of the shielding to both ends depends on the electrical constraints on the installation.
Using the ABE-6SD15F wiring interface enables connection to a screw terminal block via the
15-pin SUB-D connector.
RS 232 C connection
Pins to use
SUB-D connector (15-pin)
PG
Transmission
TXD
Reception
RXD
0V SG
7
8
3
14
2
15
5
*
Automated system (connection example using 25-pin SUB-D connector)
1
2
3
7
6
20
4
5
RTS
CTS
DSR
DTR
PG
TXD
Transmission
RXD
Reception
SG
I
S
H
E
N
G
L
*
Connection of the shielding to both ends depends on the electrical constraints on the installation.
Using the ABE-6SD15F wiring interface enables connection to a screw terminal block via the
15-pin SUB-D connector.
Configuring communication functions
Refer to the operating manual of the PCMCIA communication interface of Altivar 16.
5 7
I
S
H
E
N
G
L
Connection to the multidrop bus
The following accessories are available for connecting equipment.
TSX-CSA… cables for bus sold in 100, 200 or 500 m lengths.
TSX-SCA62 subscriber connector
This passive unit comprises a printed circuit fitted with screw terminals for connecting 2 devices to the bus. It includes an end of line terminator when the connector is located at the end. The switches on the connector must be set in the following way switch number
2
3 switch position
OFF
OFF
5 OFF the position of the other switches has no effect.
Example of connection to a UNI-TELWAY bus
TSX-SCM 21.6
TSX-CSAXXX
VW3-A16303
TSX-CSB015
VW3-A66301
TSX-SCA62
ATV-16
5 8
Communication principle
Connecting the speed controller
The Altivar 16 can be connected according to the diagrams shown in the catalogue.
The communication function provides the facility of remote control of the speed controller safety relay (contacts brought out to terminals SA-SC-SB). Using these contacts in the control circuit of the line contactor enables the power to be switched on and off remotely.
Note : Since the power and control supplies are the same, power-up through the serial link isn't possible. Therefore, the line contactor release stops the communication.
Nevertheless, the safety function of the relay is maintained, and continues to have priority over the remote control facility : the contact will open if a speed controller fault occurs.
Status of the Altivar 16
The following diagram shows the three stable states of the speed controller.
➀
FAULT
RESET
ZERO
FAULT
"LOCKING" FAULT
➁
CORRECTABLE
FAULT
"LOCKING" FAULT
➂
UNCORRECTABLE
FAULT
I
S
H
E
N
G
L
may disappear on its own (motor overheating, for example). This type of fault causes the speed controller safety relay to open.
When the fault has disappeared, if contacts SA-SC, SC-SB are not used in the speed controller supply sequence, the Altivar 16 reset command (bit 0 of word W3050) acknowledges the fault and re-energizes the safety relay.
which requires corrective action, occurs (overcurrent due to a short-circuit, for example).
The safety relay can only be reset by a speed controller switch-on sequence.
When a communication fault occurs, the speed controller can change to 2 states depending on its configuration :
- Changing from line mode to local mode via an application-specific card logic input : the speed controller changes from the line frequency to the frequency required at the analog inputs with the acceleration or deceleration ramp.
- Changing from local mode to line mode : the speed controller brakes on the deceleration ramp and takes the speed and operating direction required by the serial link.
5 9
I
S
H
E
N
G
L
Communication principle
Data structure
The adjustment, control, supervision and monitoring of the Altivar 16 are performed using data
(or objects) which are specific to the product.
The data essentially comprises :
• BITS : named Bi (i = bit number) which are used to execute logic commands.
Example : B5 = start / stop command.
• WORDS (of 16 bits) : named Wi (i = word number) which are used for storage, either of complete digital values (- 32768 to + 32767), or of 16 independent logic states (in which case these words are termed registers).
Examples :
W3051 = frequency reference (digital value),
W3069 = fault register (16 fault bits).
Notation : W3069,2 designates the bit in row 2 of register W3069.
Access to data
The following tables give the list of parameters which can be accessed via the communication link. The exact function of each parameter and its effect on the behavior of the speed controller are described in the user's manual and catalogue for the speed controller.
Some data can be accessed in both read and write : these are the bits and words corresponding to adjustments, references and commands. This data is used by the speed controller.
However, data produced by the speed controller can only be accessed in read : signalling or fault data, etc. If written, they have no meaning and are rejected.
6 0
Communication principle
Units
These words are always expressed as signed numeric integer values (-32768 to +32767). The unit is defined for each of them.
Example : W3052 : frequency reference, unit = 0.1 Hz,
W3052 = 455 corresponds to a frequency reference of + 45.5 Hz.
Range
The range permitted by the speed controller is specified for each of the parameters.
A value which is outside limits is always accepted, but will be automatically adjusted by the speed controller to either its lower or upper limit.
Example : W3029 : slip compensation, range = 0.... 5 Hz.
Any negative value is adjusted to 0 (0 Hz).
Any value above 50 is adjusted to 50 (5 Hz).
Values on switching on
Each time it is switched on, the Altivar 16 is initialized with the configuration and the adjustments stored in the EEPROM memory.
The speed controller is systematically placed in LOCAL control mode (orders are expected on its terminal block).
To control it via the multidrop bus, its commands must be assigned to
LINE mode : command word W3050 is written by setting bits DLI and FLI to 1.
I
S
H
E
N
G
L
Altivar 16 variables
Some Altivar 16 variables can be accessed at two different addresses :
• in the 3000 to 3078 address zone reserved for the Altivar 16,
• in the 0 to 127 address zone already used by the Altivar 45 2.
While the control system is operating (control, monitoring or modification of the speed controller adjustments), only one zone should be used.
1– Address zone reserved for the Altivar 16 (3000 to 3078)
This address zone contains all the speed controller parameters for optimum use of the facilities of the Altivar 16.
2– Address zone (0 to 127) common to the Altivar 16 and the Altivar 45 2
This address zone should only be used when integrating an Altivar 16 in a control system which until now has only included Altivar 45 2 controllers. Not all Altivar 16 parameters appear here, in particular those connected with functions which require reconfiguration of the applicationspecific card. In certain cases, using these addresses avoids the necessity of modifying the program.
Small differences in relation to the Altivar 45 2 are shown in the comments.
6 1
I
S
H
E
N
G
L
Setting up the Altivar 16
Configuring communication
The following parameters can be set using the terminal :
• Pro : defines the communication protocol :
-
UtL
: UNI-TELWAY
- ASC : Modbus ASCII
- rtu
: Modbus RTU / JBUS
- FIP : FIPIO
• bdr : defines the data rate in kbps.
Possible values : 0.3 / 0.6 / 1.2 / 2.4 / 4.8 / 9.6 / 19.2
•
For
: format of the data frame
8 0 1
1 : 1 stop
2 : 2 stops
0 : odd parity
E : even parity n : no parity
8 : 8 data bits
7 : 7 data bits
• Adr : Logic address of the speed controller bdr
For
UtL
All values
8.0.1
rTu
All values
8.0.7 / 8.E.1
8.n.7 / 8.n.2
Adr
1 to 31 1 to 31
ASC
All values
8.0.7 / 8.E.1
8.n.1 / 8.n.2
7.0.1 / 7.E.1
7.0.2 / 7.E.2
1 to 31
FIP
1 to 63
6 2
Setting up the Altivar 16
Diagnostics
On power-up, and after the protocol has been configured, the COM lamp on the PCMCIA card indicates whether or not communication is functioning.
UNI-TELWAY - FIPIO protocol :
Green COM indicator lamp : Normal operation
Red ERR indicator lamp : Communication fault
Flashing green indicator lamp: Serial link not configured.
Modbus RTU/JBUS protocol :
Green COM indicator lamp : Data transfer in progress.
Red ERR indicator lamp : Waiting for data transfer
Note : For further information, refer to the diagnostics page.
List of faults which may or may not be reset via communication
When a fault occurs, the speed controller freewheels to a stop. To restart, the operator must acknowlege the fault and reset the speed controller (W3050.0). However, 2 types of fault cannot be reset via communication but require action on the speed controller (see table below) :
Description
Speed controller internal fault
Communication fault
EEPROM memory fault
External fault
Supply too low
Supply too high
Supply phase missing
Speed control fault
Overcurrent - overheating
Overvoltage due to harsh braking
Overcurrent due to harsh braking
Motor overload
Capacitor charging relay fault
Not possible to Possible to reset speed reset speed controller (1) controller (2)
X
X
X
X
X
X
X
X
X
X
X
X
X
Code displayed
SPF
DRF
OBF
OBF
OLF
CRF
INF
SLF
EEF
SRF
USF
OSF
PnF
(1) To reset the speed controller it is necessary to switch the power off then on again.
(2) The speed controller can be reset after the fault has been cleared.
I
S
H
E
N
G
L
6 3
I
S
H
E
N
G
L
Reading parameters
All the speed controller data can be read when the motor is running or stopped.
Signalling words (words W3060 - W3078) are read-only.
Example of reading words W3020 to 3043 (24 words) with the UNI-TELWAY protocol.
Description
Format
Code
Comments
Request Category
Code Code byte
H'36' read object byte
H'07' byte
H'68'
Type of object byte
H'07' internal specific words byte
Object address
Word
H'OBCC'
(3020 in hex)
Object number
Word
H'0018'
Number of words
(24 in hex)
Text block for transmission
TxTi, C = H'0736'
TxTi, L = 4
Transmission table
H'07' H'68'
H'CC'
H'18'
H'OB'
H'00'
Reception table
W3020 least sig.
H'07'
W3021 least sig. W3020 most sig.
W3021 most sig.
Response code :
- Positive response : H'FE'
- Negative response : H'FD' Reason : incorrect parameter number or wrong address
Note : For further information about the UNI-TELWAY protocol, refer to the
UNI-TELWAY requests page.
6 4
Writing parameters
It is possible to write Altivar 16 parameters for :
- command words (motor running or stopped),
- adjustment words (motor running or stopped),
- configuration words (motor stopped).
To control the speed controller from the multidrop bus, it is necessary to execute commands on line : command word W3050 is written by setting bits DLI and FLI to 1. Bits DLI and FLI of the command register offer the possibility of partially assigning the commands which can be executed from the bus.
Note : setting bit NTO to 1 in the command register inhibits the communication fault check
(Altivar 16 "SLF" fault).
For safety reasons, care must be taken when using this command.
Setting word W3050 to the value 5 with Modbus protocol (RTU frame)
Description
Format
Code
Comment
Slave no.
1 byte
01
Function
Code
1 byte
06
Writing a word
Word no.
2 bytes
OB EA
3050 in Hex.
= OBEA
Value of the word
2 bytes
00 05
CR16
2 bytes
6A 19
Note : For further information on Modbus frames, see the end of this guide (Modbus / Jbus
Protocol).
I
S
H
E
N
G
L
The following table shows all the functions of the Altivar 16 with its various application-specific cards.
6 5
Altivar 16 variables
I
S
H
E
N
G
L
Applications ATV16 General usage
Materials handling
Variable torque
High speed
Drive functions
Maximum frequency
Voltage/frequency ratio selection (1)
Slip compensation
Switching frequency
Current limit
Braking to a standstill by DC injection (f<0.1 Hz)
Functions in the application-specific cards
•
±
10 V analog input
Summing
Speed regulation
PI controller
• Logic inputs
2nd ramps
Preset speeds
Current limit
+/- speed
Step by step operation (JOG)
Fast stop
Freewheel stop
DC injection
Automatic/manual
Start/stop
Reset after fault
Change motor power
Speed controller forced in local mode (3)
• Logic outputs
Brake control sequence
Speed reference reached
Low speed reached
High speed reached
Current limit reached
1.1 In overload reached
100% thermal state reached
• Analog output
Motor frequency
Motor current
Preprogrammed and programmable characteristics
– S ramps
– Skip frequencies
– Controlled stop on
AC supply break (2)
– Automatic catching a spinning load
– Automatic restart
▲
40 ... 200Hz
■ n-P-L
■ yes/no
■
5/10kHz
● 1.5 In
■ yes/no
■
■ yes/no
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
▲
40 ... 200Hz
▲
40 ... 200 Hz
▲
40 ... 70/80Hz
▲
40 ... 400Hz
■ n-L ■ n-L ● P ■ n-L
■ yes/no
■
5/10kHz
■
● yes/no
5kHz
▲ 0.5 to 1.5 In ● 1.5 In no
■
●
5/10kHz
1.2 In no
●
●
5kHz
1.2 In
■
■
■
■
■
■
■
(1) n : constant torque (normal applications), P : variable torque,
L : constant torque (heavily-loaded machines).
(2) ATV16 U..N4 speed controller only.
(3) Only the Altivar 16 with software version IE07.
●
- fixed, programmed function
■
- programmable function
▲
- function with adjustable value
6 6 no
■
■
■
■
■
■
■
■
■
■
▲
■
■
■
■
■
■
■ no
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■ yes/no
■
■
■
■
■
■
■
■
■
■
■
■
Altivar 16 variables
Address zone reserved for Altivar 16
Configuration words (read and write) (write when motor is stopped)
WORD NAME RANGE UNIT DESCRIPTION
W3000 LI1 0…10 Assignment of logic input LI1
W3001 LI2
W3002 LI3
W3003 AI1
0…11
0…10
0…5
Assignment of logic input LI2
Assignment of logic input LI3
Assignment of analog input AI1
POSSIBLE VALUES
0 = not assigned
1 = start/stop
2 = fast stop
3 = fault reset
4 = + speed
5 = freewheel stop
6 = switching to ramp 2
7 = reduction of current limit
8 = Jog
9 = change motor power
10 = local forcing
0 = not assigned
1 = 3rd speed
2 = fast stop
3 = fault reset
4 = - speed
5 = freewheel stop
6 = automatic / manual
switching
7 = switching to ramp 2
8 = reduction of current limit
9 = Jog
10 = change motor power
11 = local forcing
0 = not assigned
1 = 4th speed
2 = fast stop
3 = DC injection
4 = fault reset
5 = freewheel stop
6 = switching to ramp 2
7 = reduction of current limit
8 = Jog
9 = change motor power
10 = local forcing
0 = not assigned
1 = speed feedback
2 = speed feedback + backdriving control
3 = summing reference 2 input
4 = PI feedback
5 = manual reference input
I
S
H
E
N
G
L
6 7
Altivar 16 variables
I
S
H
E
N
G
L
Address zone reserved for Altivar 16
Configuration words (read and write) (write when motor is stopped)
WORD NAME
W3004
W3005
W3006
W3007
W3008
LO1
SAB
AO1
CPM
TIC
RANGE
0…6
0…4
0…2
0…4
0…3
UNIT DESCRIPTION
Assignment of logic output LO
POSSIBLE VALUES
0 = not assigned
1 = 100% thermal state reached
2 = frequency reference reached
3 = current limit reached
4 = LSP reached
5 = HSP reached
6 = 1.1 Ith overload reached
Assignment of relay S2A S2B 0 = not assigned
1 = 100% thermal state reached
2 = frequency reference reached
3 = HSP reached
4 = brake control
Assignment of analog output AO 0 = not assigned
1 = motor frequency
2 = motor current
Motor power coefficient 0 = coefficient 1/1
1 = coefficient 1/2
2 = coefficient 1/3
3 = coefficient 1/4
4 = coefficient 1/5
Type of DC injection 0 = no injection
1 = injection for f < 0.1 Hz
2 = injection for f < LSP
3 = injection for f < SRF
W3009 TFR 40…400 Hz 0.1 Hz Maximum frequency
W3010 UNS 0…7 Motor nominal voltage 0 = 208 V
1 = 220 V
2 = 230 V
3 = 240 V
4 = 380 V
5 = 400 V
6 = 415 V
7 = 460 V
W3011 FRS 40…400 Hz 0.1 Hz Motor nominal frequency
W3012 UFT 0…2 Type of voltage/ frequency ratio 0 = linear N
1 = quadratic P
2 = linear L
6 8
Altivar 16 variables
Address zone reserved for Altivar 16
Configuration words (read and write) (write when motor is stopped)
WORD NAME RANGE UNIT DESCRIPTION
W3013 CF1 Specific functions configuration register
RPS
FLR
ATR
SFR
W3013,0 Reserved
W3013,1 S ramp
W3013,2 Flying restart
W3013,3 Automatic restart
W3013,4 10 kHz switching frequency
W3013,5 Reserved
STP
BRA
SLP
RBL
SCE
BST
W3013,6 Controlled stop on AC supply break
W3013,7 Adaptation of the deceleration ramp
W3013,8 Slip compensation
W3013,9 Activation of the + / – speed reference
W3013,A Speed ref. in EEPROM memory
W3013,B Inhibit boost at start-up
W3013,C Reserved
W3013,D Reserved
W3013,E Reserved
W3013,F Reserved
W3014 to W3019 : Reserved
POSSIBLE VALUES
0 = linear 1 = S
0 = no 1 = yes
0 = no 1 = yes
0 = 5 kHz 1 = 10 kHz
0 = no
0 = no
0 = no
0 = no
0 = no
0 = no
1 = yes
1 = yes
1 = yes
1 = yes
1 = yes
1 = yes
I
S
H
E
N
G
L
6 9
Altivar 16 variables
I
S
H
E
N
G
L
Address zone reserved for Altivar 16
Adjustment words (read and write)
WORD NAME
W3020 LSP
RANGE
0…HSP
UNIT DESCRIPTION
0.1 Hz Low speed
W3021 HSP LSP…TFR 0.1 Hz High speed
W3022 ACC 0.1…600s 0.1 s Acceleration time
W3023 DEC
W3024 FLG
0.1…600s
0…100
0 1 s Deceleration time
1 Frequency loop gain (if FLG=100 : frequency loop inhibited)
W3025 UFR 0…100 1 Set voltage / frequency ratio
W3026 ITH 0.5…1.15 In 0.1 A Thermal current
W3027 IDC 0.5…1.5 Ith 0.1 A DC current amplitude
W3028 TDC 0…5.1 s 0.1s
DC injection time (if TDC= 5.1s : continuous
DC injection)
W3029 CGL
W3030 AC2
0…5 Hz
0.1…600 s
0.1 Hz Slip compensation
0.1 s Acceleration time 2
W3031 DE2 0.1…600 s 0.1 s Deceleration time 2
W3032 JOG 0.1…10 Hz 0.1 Hz JOG speed
W3033 SP3 LSP…HSP 0.1 Hz 3rd speed
W3034 SP4 LSP…HSP 0.1 Hz 4th speed
W3035 JF1
W3036 JF2
0…TFR
0…TFR
0.1 Hz
0.1 Hz
Skip frequency 1
Skip frequency 2
W3037 RGP
W3038 RGI
W3039 IBR
W3040 SMF
W3041 SRF
0…100
0…100
0.1
0.1
PI controller proportional gain
PI controller integral gain
0…1.15 ln 0.12 A Brake control level
0…LSP
0…LSP
0.1 Hz
0.1 Hz
Brake application level
Brake release level
W3042 TMF
W3043 LTI
0…5 s 0.1 s Brake application time
0.5…1.5 ln 0.1 A Current limit level
W3044 to W3049 : Reserved
7 0
Altivar 16 variables
Address zone reserved for Altivar 16
Command words (read and write)
WORD NAME
W3050 COM
RST
DLI
FLI
NTO
RUN
DCB
CAL
CAR
W3051 FRH LSP…HSP
W3052 LOL
W3053
EFL
AOL
RANGE
0…255
UNIT DESCRIPTION
Command register
W3050,0 Reset speed controller
W3050,1 Assign commands on line
W3050,2 Assign frequency reference on line (1)
W3050,3 Reserved
W3050,4 Communication check inhibited (2)
W3050,5 Start / stop command (1)
W3050,6 DC injection braking command
W3050,7 Reserved
W3050,8 Select freewheel stop
W3050,9 Select fast stop
W3050,A Reserved
W3050,B Reserved
W3050,C Reserved
W3050,D Reserved
W3050,E External fault command
W3050,F Store in EEPROM (3)
Signed line frequency reference
Write logic outputs on line
(only if they are not assigned)
W3053,0 Value applied at S2A-S2B
W3053,1 Value applied at LO
W3053,2 to F Reserved
Write analog output AO on line
(only if Al not assigned)
W3054 to W5059 : Reserved
The bits are active at state 1
(1) The same message should not be used to assign FLI and RUN. Use 2 messages, the 1st for FLI, the
2nd for RUN.
(2) The Altivar 16 changes to fault condition SLF :
• in UNI-TELWAY when there has been no polling for 10 s,
• in MODBUS if more than 10 s elapse between requests.
Setting this bit to 1 inhibits this check. For safety reasons, this should only be performed during debugging phases.
(3) Global command to store all the adjustments and the entire configuration in the speed controller EEPROM. The storage takes a few seconds, and access to the speed controller is refused while it is being performed. For this function, the speed controller must be on line and the motor stopped.
I
S
H
E
N
G
L
7 1
Altivar 16 variables
I
S
H
E
N
G
L
Address zone reserved for Altivar 16
Signalling words (read only)
RANGE WORD NAME
W3060 STR
LOC
RDY
FAI
REN
FLO
NTO
CFA
RNG
RVE
UNIT DESCRIPTION
Speed controller status register
W3060,0 All commands in local mode
W3060,1 Speed controller ready (RDY or SLC)
W3060,2 Faulty
W3060,3 Reset authorized
(following correctable fault)
W3060,4 Reserved
W3060,5 Speed controller forced in
Local mode
W3060,6 Communication check inhibited
W3060,7 Correctable fault
W3060,8 Motor running
W3060,9 Direction of rotation
W3061
BRE
SST
OVL
OBR
LIM
FRR
W3060,A DC injection braking
W3060,B Steady state
W3060,C Motor thermal overload alarm
W3060,D Overbraking alarm
W3060,E Current limit
W3060,F Reserved
0.1 Hz Actual rotation frequency
(signed value)
W3062
W3063
W3064
LCR
ULN
IOL
0.1 A Motor current
0.1 V Mains supply voltage
Speed controller logic I/O status register
W3064,0 FW input state
W3064,1 RV input state
W3064,2 Ll1 input state
W3064,3 Ll2 input state
W3064,4 Ll3 input state
W3064 5 S2A-S2B output state
W3064 6 LO output state
W3064,7 to W3064,F Reserved
W3065 AIV 0…10000
W3066 IAI -10000…+10000
W3067 IAO
W3068 FRE
0…255
AIV or AIC analog input value
Al analog input value
AO output value
0.1 Hz Effective frequency reference
(signed value)
POSSIBLE VALUES
0 = forward
1 = reverse
1= thermal state
≥
100%
7 2
Altivar 16 variables
Address zone reserved for Altivar 16
Signalling words (read only)
WORD NAME RANGE UNIT DESCRIPTION
W3069 FLT Fault register : fault which has caused speed controller to stop
INF
SLF
W3069,0 Speed controller internal fault (*)
W3069,1 Communication fault
EEF
SRF
W3069,2 Storage fault in EEPROM
W3069,3 External fault
(generated by an EFL command)
USF
OSF
PHF
W3069,4 Mains supply undervoltage
W3069,5 Mains supply overvoltage
W3069,6 Supply phase(s) failure
W3069,7 Reserved
W3069,8 Speed regulation fault / tachogenerator absent
W3069,9 Overcurrent, PWM overheating (*) DRF
OBF
OBF.
OLF
CRF
W3069,A Overvoltage caused by overbraking
W3069,B Overcurrent caused by overbraking
W3069 C Motor overload
W3069,D Reserved
W3069,E Reserved
W3069,F Capacitor charging relay fault
W3070 DPR
INF
SLF
EEF
SRF
USF
OSF
PHF
DRF
OBF
OBF.
OLF
CRF
Register of current faults
W3070,0 Speed controller internal fault
W3070,1 Communication fault
W3070,2 Storage fault in EEPROM
W3070,3 External fault
(generated by an EFL command)
W3070,4 Mains supply undervoltage
W3070,5 Mains supply overvoltage
W3070,6 Supply phase(s) failure
W3070,7 Reserved
W3070,8 Speed regulation fault / tachogenerator absent
W3070,9 Overcurrent
W3070,A Overvoltage caused by overbraking
W3070,B Overcurrent caused by overbraking
W3070,C Motor overload
W3070,D Reserved
W3070,E Reserved
W3070,F Capacitor charging relay fault
POSSIBLE VALUES
(*) These faults are uncorrectable and cannot be acknowledged by the communication link.
I
S
H
E
N
G
L
7 3
I
S
H
E
N
G
L
Altivar 16 variables
Address zone reserved for Altivar 16
Signalling words (read only)
WORD NAME RANGE UNIT
W3071 DP1
W3072 DP2
W3073 DP3
W3074 DP4
W3075 DP5
W3076 DP6
W3077 DP7
W3078 DP8
DESCRIPTION
Past fault 1
Past fault 2
Past fault 3
Past fault 4
Past fault 5
Past fault 6
Past fault 7
Past fault 8
POSSIBLE VALUES each of these words has the same structure as W3069
7 4
Altivar 16 variables
Address zone common to Altivar 16 and Altivar 45 2
Control bits (read and write)
BIT NAME DESCRIPTION
B0 TST De-energization of speed controller safety relay
B1 (*) RST Fault reset
(Speed controller reset)
B2 (*) CLO Assignment of control to LOCAL mode
B3 (*) CLI Assignment of control to LINE mode
FUNCTION
Disconnects the Altivar 16 power supply if the contact of the relay is used for the hold-in circuit of the line contactor
Acknowledges a correctable fault which has disappeared and resets the safety relay
The Altivar 16 can only be controlled via its terminals
(logic and analog inputs)
The Altivar 16 is controlled via the multidrop bus
B4
B5
B6
B7
B8
NTO Inhibition of communication check
RUN Start / stop command
The Altivar 16 changes to fault condition SLF :
• in UNI-TELWAY after no polling for 10 s
• in MODBUS if more than 10 s elapse between two requests
Setting this bit to 1 inhibits this check. For safety reasons this feature should only be used during debugging phases
1 = start 0 = stop
REV Frequency reference sign
1 = negative 0 = positive
The direction of rotation can be reversed by changing the state of this bit or by providing a frequency reference of opposite sign in word W19
DCB Braking control
CAL Selection of a freewheel stop
Takes priority over the RUN bit
Active when there is a stop command
B9
B10
CAR Selection of a fast stop
Reserved
Active when there is a stop command
I
S
H
E
N
G
L
(*) These bits initiate the action shown when they are written as 1. They are reset to zero by the speed controller.
If they are written as zero they have no effect and are always read as zero.
7 5
Altivar 16 variables
Address zone common to Altivar 16 and Altivar 45 2
L
I
S
H
E
N
G
Adjustment words (read and write)
WORD NAME
W0
W1
–
–
W2
W3
W4
W5
W6
W7
W8
W9
W10
W11
CGL
–
–
–
IDC
TDC
UFR
ITH
FLG
RANGE
–
–
[0... 5Hz]
UNIT
–
–
DESCRIPTION
Reserved
Reserved
–
–
–
[0.5... 1.5Ifh]
[0... 4s]
[0... 100]
0.1Hz Slip compensation
– Not used
–
–
Not used
Not used
– Not used
0.1A
DC amplitude when stopping
0.1s
DC injection time when stopping
1 Voltage/frequency ratio adjustment coefficient
[0.45... 1.05In] 0.1A
Motor thermal current
[0... 99%] 1% Frequency loop gain
COMMENTS
With ATV 45 2 range from 0.5 to 1.5 In
With ATV 45 2 range from 0 to 99
With ATV 45 2 range from 0 to 100
W12
W13
W14 LSP
–
–
W15 HSP
W16 ACC
W17 DEC
–
–
[0...HSP]
[LSP... TFR]
[0.1... 600s]
–
–
Not used
Not used
0.1Hz Low speed
0.1Hz High speed
0.1s
Acceleration time
[0.1... 600s] 0.1s
Deceleration time
Adjust TFR in W3009
With ATV 45 2 range from 0.2 to 990 s
With ATV 45 2 range from 0.2 to 990 s
7 6
Altivar 16 variables
Address zone common to Altivar 16 and Altivar 45 2
Command words (read and write)
WORD NAME
W18 COM
RANGE
–
UNIT
–
W19 FRH [LSP... HSP] 0.1Hz
DESCRIPTION
Command register
W18,0 (RST) Reset speed controller
(fault reset)
W18,1 (DLI) Assign logic commands on LINE
W18,2 (FLI) Frequency reference on LINE
W18,3 Reserved
W18,4 (NTO) Inhibit communication check
W18,5 (RUN) Start / stop command
W18,6 (DCB) Braking control
W18,7 Reserved
W18,8 (CAL) Select freewheel stop
W18,9 (CAR) Select fast stop
W18,A Not used
W18,B Reserved
W18,C Reserved
W18,D Reserved
W18,E Reserved
W18,F Storage in EEPROM
Signed frequency reference
COMMENTS
See note 1
See notes 1 and 2
See note 2
See note 3
Signed value
The bits are active at state 1.
note 1 : Bits W18,1 and W18,2 can be used to partially assign commands which can be executed from the multidrop bus. It is important to set them correctly each time the COM register is written.
note 2 : Do not use the same message to assign FLI and RUN. Use 2 messages : the 1st for FLI, the 2nd for RUN.
note 3 : Global command to store all the adjustments (W0 to W17) and the entire configuration (W33 to
W66) in the speed controller EEPROM.
This command should be used with care : the storage takes a few seconds, and access to the speed controller is refused while it is being performed.
I
S
H
E
N
G
L
7 7
Altivar 16 variables
Address zone common to Altivar 16 and Altivar 45 2
L
I
S
H
E
N
G
Signalling words (read only)
WORD NAME
W20 STR
RANGE
–
UNIT DESCRIPTION
Status register
W20,0 (LOC) All commands assigned in LOCAL mode
W20,1 (RDY) Speed controller ready
W20,2 (FAI) Faulty
W20,3 (REN) Reset authorized
W20,4 Not used
W20,5 (FLO) Speed controller forced in LOCAL mode
W20,6 (NTO) Communication check inhibited
W20,7 (CFA) Correctable fault
W20,8 (RNG) Running
W20,9 (RVE) Direction of operation
W20,A (BRE) DC injection braking
W20,B (SST) Steady state
W20,C (OVL) Motor thermal overload alarm
W20,D (OBR) Overbraking alarm
W20,E (LIM) Current limit
W20,F Not used
COMMENTS
Motor rotating
0 = forward 1 = reverse
7 8
Altivar 16 variables
Address zone common to Altivar 16 and Altivar 45 2
Signalling words (read only)
WORD NAME
W21 FLT
RANGE
W22
W24
W26
W27
W28
LCR
W23 RFR
–
W25 ULN
–
–
–
UNIT
–
0.1A
0.1Hz
–
–
–
1V
–
DESCRIPTION
Fault register
W21,0 (INF) Speed contr. internal fault (*)
W21,1 (SLF) Communication fault
W21,2 (EEF) EEPROM fault
W21,3 (SRF) Fault generated by the
TST command
W21,4 (USF) Mains supply undervoltage
W21,5 (OSF) Mains supply overvoltage
W21,6 (PHF) Supply phase(s) failure
W21,7 Not used
W21,8 (SPF) Speed regulation fault
COMMENTS
W21,9 (DRF) Overcurrent, PWM overheating, With ATV 45 2, this bit underheating of PWM control (*) indicates an overcurrent
W21,A (OBF) Overvoltage caused by overbraking
W21,B (OBF.) Overcurrent caused by overbraking
W21,C (OLF) Motor overload
W21,D Not used
W21,E Reserved
W21,F (CRF) Charging relay fault
Motor current
Actual rotation frequency
Not used
Mains voltage
Not used
Reserved
Reserved
Signed value
I
S
H
E
N
G
L
(*)
These faults are uncorrectable and cannot be acknowledged by the communication link.
7 9
L
I
S
H
E
N
G
Altivar 16 variables
Address zone common to Altivar 16 and Altivar 45 2
Signalling words (read only)
WORD NAME RANGE
W29 DIN
UNIT
–
W30 DAI [0... 1000]
W31 –
W32 –
–
–
DESCRIPTION
Speed controller logic input status register
W29,0 FW input
W29,1 RV input
W29,2 Not used
W29,3 Not used
W29,4 Not used
W29,5 to W29,F : reserved
Value of speed controller analog input
Reserved
Reserved
COMMENTS
0 = 0V or 0 mA or 4 mA
1000 = 10V or 20 mA
8 0
Altivar 16 variables
Address zone common to Altivar 16 and Altivar 45 2
Configuration
Configuration words can only be written when the speed controller is stopped
They are stored in the EEPROM memory via the COM command register
(bit W18,F).
Configuration words (read and write) (write when motor is stopped)
POSSIBLE VALUES WORD NAME
W33 –
W34 –
W35 –
RANGE
–
–
–
UNIT DESCRIPTION
Not used
Not used
Configuration register
W35,0 Not used
W35,1 Not used
W35,2 Not used
W35,3 Not used
W35,4 (SLP) Slip compensation
W35,5 Not used
W35,6 Not used
W35,7 Not used
W35,8 Not used
W35,9 Not used
W35,A Not used
W35,B Not used
W35,C Not used
W35,D Not used
W35,E Not used
W35,F Not used
0 = no and 1 = yes
I
S
H
E
N
G
L
8 1
Altivar 16 variables
Address zone common to Altivar 16 and Altivar 45 2
L
I
S
H
E
N
G
Configuration words (read and write) (write when motor is stopped)
W37
W38
W39
W40
W41 RPS
W42
W43
W44
W45 BRA
W46 UFT
WORD NAME
W36 –
0...1
–
–
–
0...1
–
–
–
–
RANGE
–
0...2
UNIT DESCRIPTION
Configuration register 2
W36,0 (FLR) Flying restart
(automatic catching a spinning load)
W36,1 Not used
W36,2 Not used
W36,3 (ATR) Automatic restart
W36,4 to W36,F : not used
Not used
Not used
Not used
Not used
Ramp shapes (1)
Not used
Not used
Not used
Deceleration ramp adaptation
Voltage/frequency ratio (2)
POSSIBLE VALUES
0 = no and 1 = yes
0 = no and 1 = yes
0 = linear 1 = S
0 = no
1 = yes
0 = linear N
1 = quadratic P
2 = linear L
(1) Parabolic ramp not available on the Altivar 16
(2) The F type does not exist on the Altivar 16
8 2
Altivar 16 variables
Address zone common to Altivar 16 and Altivar 45 2
Configuration words (read and write) (write when motor is stopped)
COMMENTS WORD NAME
W47
W48
–
–
W49
W50
W51
W52
W53
RANGE
–
–
–
–
–
IBR
–
–
–
0...In
AC2 0.1...600 s
UNIT DESCRIPTION
Not used
Not used
Not used
Not used
Not used
0.1 A Brake control level
0.1 s Acceleration time 2
W54 DE2 0.1...600 s 0.1 s Deceleration time 2 on the ATV 45 2 : adjustable from 0.2 to 990 s on the ATV 45 2 : adjustable from 0.2 to 990 s
W55
W56
–
–
–
–
Not used
Not used
I
S
H
E
N
G
L
8 3
Altivar 16 variables
Address zone common to Altivar 16 and Altivar 45 2
Configuration words (read and write) (write when motor is stopped)
COMMENTS WORD NAME
W57
W58
–
–
W59
W60
W61
W62
W63
–
–
–
–
–
RANGE
–
–
–
–
0...LSP
0...LSP
0...5 s
W64
W65
W66
–
–
–
–
–
40...200 Hz
W61 to W119 : Reserved
UNIT DESCRIPTION
Not used
Not used
Not used
Not used
0.1Hz
Brake application level
0.1 s Brake release level
0.1 s Brake application time adjustable from 0 to 4 s
Not used
Not used
0.1 s Nominal frequency
L
I
S
H
E
N
G
Maintenance
The following words can be used for diagnostics and maintenance. They contain a list of the 8 most
recent faults which have caused the speed controller to stop (power cuts are not considered as faults).
These 8 words are managed on a stacking principle : the appearance of a fault causes the stack to move downwards and the fault which has appeared is stored in the 1st W120 word.
This principle continues to be used when the stack is full.
These words cannot be modified or reset to zero.
Words for maintenance (read only)
WORD
W120
W121
.
.
to
.
.
W127
NAME
DP1
DP2
DP8
DESCRIPTION
Register of the most recent fault etc.
Register of the eighth fault recorded
COMMENTS
Each of these words has the same format as the FLT signalling register [W21]
The value 0 indicates that there is no fault
8 4
UNI-TELWAY requests
General
The exchange of data between computer systems, PLCs and other intelligent systems must be performed using a common language.
This language should be as simple as possible and understood by everyone involved. Nevertheless, it must be possible to check every exchange to ensure the integrity of the transfers. The variables exchanged are therefore inserted in a frame which generally comprises the following :
Heading Address Request
Data
Check
End
Each protocol defines the presence, the format and the contents of the various groups of variables which surround the data zone.
This structuring makes it possible to define the start and the size of messages, if necessary the system to which the data is addressed, the type of function required, the variables themselves, a control parameter and an end code which validates the whole message.
The form and content of this frame are different for each type of protocol.
List of requests
The following table describes the requests accepted by the Altivar 16 and their limits.
Details of the coding of the requests are given in the UNI-TELWAY reference manual.
Request
Identification
Protocol version
Status
Mirror
Read error counters
Reset counters
Read a bit
Write a bit
Read a word
Write a word
Read objects
Write objects
Event data
Specific
Code (hex)
H’0F’
H’30'
H’31'
H’FA’
H’A2'
H’A4'
H’00'
H’10'
H’04'
H'14'
H’36'
H’37'
–
H’F2'
Altivar 16
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
63 words max.
60 words max.
Yes
2 words
See later
I
S
H
E
N
G
L
Identification request - Request code H'OF'
Response given by Altivar
Response code
Product type
= H'3F'
= H'14' for Altivar
Sub-type
Product version
ASCII string*
= H'16' Altivar 16
= H'XX' software version (eg : H'21' for V2.1)
= product reference (eg : ATV-16U29N4)
* The first byte of an ASCII string always corresponds to the length of the string.
8 5
L
I
S
H
E
N
G
8 6
UNI-TELWAY requests
Request status - Request code H'31'
Response given by Altivar
Response code = H'61'
Current status = H'XX' bit 0 : internal fault bit 1 : correctable fault bit 2 : uncorrectable fault bit 3 : not significant bit 4 : not significant
Status mask bit 5 : not significant bit 6 : speed controller stopped (RDY or SLC or fault) bit 7 : speed controller in LOCAL control
= H'C7' indicates the significant bits for the current status
UNI-TELWAY frame
Heading
Target address
Transmitter address
Length of message
Category
+ request
Data Check
Requests to read and write objects
These requests are used to access several words within the limits described on the previous page.
These requests can be coded by specifying :
Question code (TXTi,C)
Category
Segment
Object type
= H’36' (read) or H’37' (write)
= 0...7
= H’68' (internal word)
= H’06' for a byte (8 bits) in reading or H’07' for a word (16 bits)
Object address in reading and writing
= H’xxxx’
Etc
Words reserved or not used are read to 0 and their write is not significant.
The response to a "write objects" request is accepted if a word is written at least.
Example : programming on a TSX7 PLC using a text block.
READ words W3020 to W3023 of the Altivar 16.
– Using word type object = H’07'
Transmission text block
TxTi,C = H’0736' (category + request)
TxTi,L = 6
+ transmission table
Transmission table
Internal word segment
Word type
H'07' H'68'
3020
4
4 words to read
Number of first word
Reception text block
TxTi,V = H’66' (confirm)
TxTi,S = 9 (9 bytes received)
+ reception table
Reception table
W3020 (least sig.) H'07'
W3021 (least sig.) W3020 (most sig.)
W3022 (least sig.) W3021 (most sig.)
W3023 (least sig.) W3022 (most sig.)
W3023 (most sig.)
The data received in the reception table is offset by one byte. It is the application program which must correct the data (for example by successive offsets) before using it.
UNI-TELWAY requests
– Using byte type object = H'06'
Transmission text block
TxTi,C = H'0736' (category + request)
TxTi,L = 6
+ transmission table
Transmission table
Internal word segment
Type of byte
H'06' H'68'
6039
9
Reception text block
TxTi,V = H'66' (confirm)
TxTi,S = 10 (10 bytes received)
+ reception table
Reception table
W3019 (most sig.)
W3020
H'06'
W3021
W3022
W3023
9 bytes to read (most significant bit of W3019 + 8 bytes comprising W3020 to W3023)
Number of first byte
(most significant bit of W3019 has address 2 x 3019 + 1 = 6039)
Reading the most significant bit W3019 can be used to obtain a correct framework of the following words in the reception table, and to avoid shifts between the most and least significant bits in these words.
Event data
The Altivar 16 transmits data on its own initiative to the UNI-TELWAY link master without having first received a question.
This data is sent via the "unsolicited data" request and does not require a response from the receiver.
Data is transmitted in the following 2 cases :
– When a fault appears or disappears (rising or falling edge at status register bit W3060,2).
– When the speed controller is forced into local control via one of its logic inputs, if that input has been assigned to this function (rising or falling edge at this input), or via the local key on the interface for the PCMCIA communication card.
Size of event data : 2 words of 16 bits sent in the following order :
– STR status register (word W3060).
– FLT fault register (word W3069).
To transmit unsolicited data, the Altivar 16 must have an address between 1 and 32.
I
S
H
E
N
G
L
8 7
L
I
S
H
E
N
G
UNI-TELWAY requests
Summary
: the use of event data with a TSX PLC requires :
– Correct configuration of the UNI-TELWAY link master module.
– Regular monitoring of the indicators which display the arrival of unsolicited data and the addresses of the transmitters.
– Acquisition of this data via the request to read event data.
Specific control request
This request is used to control the Altivar 16 and to obtain in return data essential for controlling the speed controller.
Request format
Request code
Category
Specific request code
Reserved
Command
Reference
Acceleration
Deceleration
Confirm format
Response code
Specific response code
Reserved
Reference
Status register
Fault register
Motor current
: byte
: byte
: byte
: byte
: word
: word
: word
: word
: byte
: byte
: byte
: word
: word
: word
: word
= H'F2'
= 0...7
= 0
= 0
= COM
= FRH
= ACC
= DEC
= H'F2'
= H’30'
= 0
= FRH
= STR
= FLT
= LCR
Negative response
Response code : byte
Cause : incorrect number of parameters
= H'FD'
8 8
MODBUS / JBUS protocol
MODBUS frames
Note : In the rest of this document MODBUS and JBUS functions are grouped together under the heading MODBUS.
Two transmission modes can be used, only one of them being used in a system.
RTU mode
The frame defined for the MODBUS protocol has neither message heading bytes nor end of message bytes. It is defined as follows :
Address Request Data CRC16
The data is transmitted in binary code.
CRC16 : cyclical redundancy check.
The end of frame is detected on a silence of 3 characters or more.
ASCII mode
The frame is complete and is defined in the following way :
Heading
Address Request Data LRC
– heading = ":" (H’3A),
– the data is coded in ASCII : each byte is divided into 2 four-bit bytes, each
of which is coded by an ASCII character (0 to F),
– LRC : longitudinal redundancy check,
– end : "CR" "LF" (H’0D and H’0A).
End "CRLF"
I
S
H
E
N
G
L
89
MODBUS / JBUS protocol
Principle
The MODBUS protocol is a dialogue protocol which creates a hierarchical structure (a master and several slaves).
The MODBUS protocol enables the master to interrogate one or more intelligent slaves. A multidrop link connects the master and slaves.
Two types of dialogue are possible between master and slaves :
– the master talks to a slave and waits for a response,
– the master talks to all the slaves without waiting for a response (broadcasting principle).
The slaves are numbered from 1 to 255, and number 0 is reserved for broadcasting.
Master
The master manages the exchange and only it can take the initiative. The master repeats the question when there is an incorrect exchange, and declares the interrogated slave absent if no response is received within a given time envelope. Only one device can transmit on the line at any time.
No slave can send a message itself unless it is invited to do so.
L
I
S
H
E
N
G
Slave j
Slave i
Slave k
Note
No lateral communication (ie. slave to slave) can be performed directly.
The application software of the master must therefore be designed to interrogate a slave and send back data received to another slave.
90
MODBUS / JBUS protocol
Accessible data
The MODBUS protocol enables data (bits and words) to be exchanged between a master and several slaves, and checks these exchanges.
Consequently, bit areas are defined in each slave unit which will be read or written by the master.
An input object can only be read.
An output object can be read or written.
Master
MODBUS addressing
Slave i
Slave j
Input bits
Output bits
Input words
Output words
I
S
H
E
N
G
L
Slave k
Exchanges
The master, or supervision device, takes the initiative in exchanges. The master addresses a slave by supplying it with four types of data :
– the address of the slave,
– the function required of the slave,
– the data area (variable depending on the request),
– the exchange check.
The link master waits for the response of the slave before transmitting the next message, thus avoiding any conflict on the line. Operation in half duplex is therefore authorized.
91
MODBUS / JBUS protocol
Control and monitoring
All control of exchanges between two units which are communicating via asynchronous serial link naturally includes exception messages when exchange faults occur. Various incorrect messages may be sent to a slave. In this event, the slave will tell the master that it does not understand, and the master will decide whether or not to repeat the exchange.
Master
ATV 16
L
I
S
H
E
N
G
The master has access to a certain amount of data which is stored and managed by the slave. The master can access this data using special function codes (diagnostic mode, read event counter, etc).
92
MODBUS / JBUS protocol
MODBUS functions
MODBUS functions include :
– main functions for exchanging data,
– additional functions for exchange diagnostics.
The following table shows the functions which are managed by the ALTIVAR 16 communication function, and specifies its limits.
The definition of the "read" and "write" functions are understood from the point of view of the master.
Code Type of function D ALTIVAR 16
05
06
08
11
16
01
02
03
04
Read N output bits
Read N input bits
Read N output words
Read N input words
Write one output bit
Write one output word
Diagnostics (see details below)
Read event counter
Write N output words
D
D
D
1 max
1 max
63 max
63 max
Yes
Yes
Yes
Yes
60 max
Functions marked «D» can be broadcast.
The message transmitted by the master must specify slave number = 0.
A response message is never returned.
Detailed information on functions
Code 01 :
Code 02 : read N output bits.
This function is used to read output bits (bits which can be written and read in the slave by the master).
read N input bits.
As above, but applies to input bits (bits which the master can only read).
Code 03 :
Code 04 :
Code 05 :
Code 06 : read N output words.
This function is used to read output words (words which can be written and read in the slave by the master ).
read N input words.
As above, but applies to input words (words which the master can only read).
write an output bit.
Used to set an output bit to 0 or 1 (can only be accessed in write).
write an output word
Used to write a 16-bit output word (can only be accessed in write).
I
S
H
E
N
G
L
93
L
I
S
H
E
N
G
MODBUS / JBUS protocol
Diagnostic function code 08 is always accompanied by a sub-code.
Code 08/00 : echo.
This function requests the interrogated slave to send back the whole message sent by the master.
Code 08/01 :
Code 08/03 : channel reinitialization.
This function is used to reinitialize communication of a slave and in particular to make it leave listen only mode (LOM) by transmission of a data H'0000 ou H'FF00.
change of ASCII delimiter.
In ASCII mode, messages are delimited by the line feed character
(LF = H’0A). This function is used to change this character.
Code 08/04 : change to LOM mode.
This function is used to force a slave into listen only mode (LOM).
In this mode the slave does not process messages which are addressed to it, and only transmits a response when the channel is reinitialized.
Code 08/0A : counter reset.
This function resets to zero all the counters monitoring the exchanges of a slave.
Code 08/0B : number of correct messages seen on the line without CRC error or checksum error.This function reads a 16-bit counter
(incremented from 0 to H’FFFF) which totals the messages seen on the line and processed by the slave.
Code 08/0C : number of messages received with checksum error (reads a 16-bit counter).
Code 08/0D : number of exception responses.
Reads a 16-bit counter which totals the number of exception messages transmitted to the master by a slave (following an incorrect frame).
Code 08/0E : number of messages addressed to the slave except for broadcasts.
Reads a 16-bit counter which totals the number of all types of messages addressed to the slave.
Code 08/0F : number of broadcast messages received.
Reads a 16-bit counter which totals the number of all types of messages addressed to the slave.
Code 08/10 :
Code 08/11 :
Code 08/12 : read number of NAQ responses. The value read is always 0.
read of number of responses from the slave that is not ready. The value read is always 0.
read the number of characters which are not processed (incorrect).
94
MODBUS / JBUS protocol
Code 11 :
Code 16 : read event counter.
– a status (always zero),
– a counter which is incremented each time a correct message sent to the slave is received (form and content) except for exception messages.
write N output words.
This function enables the master to write output words to the slave
(words which can be written or read).
95
I
S
H
E
N
G
L
L
I
S
H
E
N
G
MODBUS / JBUS protocol
Details of frames (RTU mode)
Read N bits : function 1 or 2
Question
Slave 01 or 02 n
°
1 byte 1 byte
N
°
of 1st bit
MS LS
2 bytes
Number of bits
MS
2 bytes
LS
CRC16
2 bytes
Response
Slave n
°
1 byte
01 or 02
1 byte
Number of bytes read
1 byte
Value
------------
Value CRC16
2 bytes
Example : read bit B4 of slave 2
Question 02
Response 02
01
01
0004
01
0001
00
BC38
51CC if B4 = 0
02 01 01 01 900C
Bit B4 can always be used and can be read at 1 or at 0.
if B4 = 1
Read N words : function 3 or 4
Question
Slave 03 or 04 n
°
1 byte 1 byte
Response
N
°
of 1st word
MS LS
2 bytes
Number of words
MS LS
2 bytes
CRC16
2 bytes
Slave n
°
03 or 04 Number of Value of 1st word bytes read
MS LS
-------
1 byte 1 byte 1 byte 2 bytes
Value of last word
MS LS
2 bytes
CRC16
2 bytes
Example : read words W3020 to W3023 of slave 2
Question
02
Response
02
04
04
0BCC 0004
08
33E1 xxxx
---------------------xxxx CRC16
Value of W3020
Value of W3023
96
MODBUS / JBUS protocol
Write an output bit
: function 5
Question
Slave n
°
1byte
05
1 byte
Bit n
°
MS LS
2 bytes
Bit value CRC16
2 bytes 2 bytes
The "bit value" field has two possible values only, and can take no other value :
– bit at 0 = 0000
– bit at 1 = FF00
Response
Slave n
°
1 byte
05
1 byte
Bit n
°
MS LS
2 bytes
Bit value
2 bytes
Example : write value 1 in bit B3 of slave 2
Question and response
02 05 0003 FF00 7C09
CRC16
2 bytes
Write an output word :
function 6
Question
Slave n
°
1 byte
Response
06
1 byte
Word number
MS
2 bytes
LS
Word value
MS
2 bytes
LS
CRC16
2 bytes
Slave n
°
1 byte
06
1 byte
Word number
MS
2 bytes
LS
Word value CRC16
MS LS
2 bytes 2 bytes
Example : write value H'0315' = 789 in word W3022 of slave 2 ( ACC = 78,9s )
Question
02 06 0BCE 0315 2B1D and response
I
S
H
E
N
G
L
97
L
I
S
H
E
N
G
MODBUS / JBUS protocol
Diagnostic : function 8
Question and response
Slave n
°
1 byte
04
0A
0B
0C
Sub-code
00
01
03
0D
0E
08
1 byte
Sub-code
2 bytes
Question data
XX YY
00 00
XX 00
00 00
00 00
00 00
00 00
00 00
00 00
Data
2 bytes
Response data
XX YY
00 00
XX 00
No response
00 00
XX YY
XX YY
XX YY
XX YY
CRC16
2 bytes
Function executed
Echo
Reinitialization
XX = new delimiter
Change to LOM mode
Reset counters to 0
XXYY = counter value
XXYY = counter value
XXYY = counter value
XXYY = counter value
Read event counter : function 11 ( H'0B' )
Question
Slave n
°
1 byte
0B CRC16
1 byte 2 bytes
Response
Slave n
°
1 byte
0B
1 byte
00
2 bytes
00 Counter value
MS LS
2 bytes
CRC16
2 bytes
Write N output words : function 16 (H'10' )
Question
Slave n
°
10
1 byte 1 byte
N
°
of 1st word Number Number Value of 1st word
MS LS of words of bytes MS LS
----
2 bytes 2 bytes 1 byte 2 bytes
CRC16
2 bytes
Response
Slave 10 N
°
of 1st word Number of words CRC16 n
°
MS LS MS LS
1 byte 1 byte 2 bytes 2 bytes 2 bytes
Example : write values 2 and 3 in words W3022 and W3023 of slave 2
Question 02
Response 02
10
10
0BCE 0002
0BCE 0002
04
2220
0002 0003 E3C6
98
MODBUS / JBUS protocol
Exception responses
An exception response is given by a slave when it is unable to perform the request which is addressed to it.
Format of an exception response :
Slave n
°
1 byte
Response Error code
1 byte code
1 byte
CRC16
2 bytes
Response code :
function code of the request + H’80 (the most significant bit is set to 1).
Error code :
1 = the function requested is not recognized by the slave.
2 = the bit and word numbers (addresses) indicated in the request do not exist in the slave.
3 = the bit and word values indicated in the request are not permissible in the slave.
4 = the slave has started to execute the request, but cannot continue to execute it completely.
CRC16 calculation
The CRC16 is calculated based on all the bytes of the message by applying the following method.
Initialize the CRC (16-bit register) to H’FFFF.
Enter the first to the last byte of the message :
CRC X0R <byte> —> CRC
Enter 8 times
Move the CRC one bit to the right
If the output bit = 1, enter CRC X0R H’A001—> CRC
End enter
End enter
The CRC obtained will be transmitted least significant byte first, then most significant.
X0R = exclusive OR.
I
S
H
E
N
G
L
99
L
I
S
H
E
N
G
MODBUS / JBUS protocol
ASCII mode
In this mode, the MODBUS frame has the following structure :
•
•
Slave n
°
Function Data
--------------------code
LRC
MS LS
CR LF
Data identical to RTU mode, but coded differently
Delimiters : ":" = H’3A’, CR = H’0D’, LF = H’0A’.
Data :
the data field is analogous to the RTU frames, but coded in ASCII characters. Each byte is divided into 2 four-bit bytes, each of which is coded by its ASCII equivalent.
Example : the byte containing the slave number 06 will be coded by 2 ASCII characters
"0" and "6", ie. by H’30' and H’36'.
LRC :
modulo 256 hexadecimal sum of the contents of the frame (without the delimiters) before
ASCII coding, 2's complement.
The byte obtained is then coded in the form of 2 ASCII characters as above.
Example : write value 1 in bit B3 of slave 2
Question and response
Hexadecimal
3A 30 32 30 35 30303033 46463030
ASCII
0 0 0 3 F F 0 0 : 0 2
LRC calculation
0 5
4637
F 7
Sum of the bytes in the frame :
H'02' + H'05' + H'00' + H'03' + H'FF' + H'00' = H'109' = 265
Modulo sum 256 : H'09' = 9
Modulo sum 256, 2's complement :
H'100' - H'09' = 256 - 9 = 247 = H'F7'
0D
CR
0A
LF
100
Diagnostics
Fault
For the communication fault codes refer to the user's manual for the PCMCIA communication card interface.
Additional diagnostics
Check the state of the two indicator lamps located on the front panel of the VW3-A66301 communication card.
PLC equivalent
ERR
COM
NET
RUN
Cable
Câble
State of indicator lights : 0 = off 1/2 = flashing
Probable causes Green light Red light
COM ERR
1 0
1/2 0
0
0
1
0
1 = on
Corrective actions
Normal operation
Incorrect communication configuration or communication fault with l'Altivar 16.
Check configuration.
Check software compatibility.
Communication fault on the bus Check the position of TSX-SCA62
(Wait for request in MODBUS or subscriber connector switches of no polling in UNI-TELWAY) the Altivar 16.
Check the connections. Check that master link is installed, and check its configuration and operation.
Fault of PCMCIA card or speed controller.
Check the Altivar 16 by removing the PCMCIA card. If necessary, replace the Altivar 16 or the card.
I
S
H
E
N
G
L
101
54749 1997-03