This section presents the specific features of addressing linked to the discrete specific application.
This Section contains the following Maps:
Topic
Addressing of language objects associated with discrete in-rack I/O modules
Addressing of language objects associated with discrete I/O modules remoted on the FIPIO bus
Indexable discrete I/O objects.
Page
124
TLX DS 57 PL7 xx
Language words and bits
Addressing of language objects associated with discrete in-rack I/O modules
Presentation
Illustration
Addressing of bit and word objects is defined in Shared specific applications (See
Addressing input/output module objects in rack, p. 31).
This page describes the specific features linked to the discrete in-rack I/O modules.
Addressing principle:
% I, Q, M, K X, W, D, F
Symbol Object type Format
X
Rack
Y
Position i r
Channel no. Rank
Specific values The table below shows the values specific to the discrete in-rack I/O module objects.
Element Values Comment x y
0 to 1
0 to 7
00 to 14
(1)
TSX 5710/102/103/153, PMX 57102, PCX 571012.
Other processors
When the rack number (x) is other than 0, the position (y) has a 2 digit code: 00 to 14; however, if the rack number (x) = 0, the non-meaningful zeros are deleted (from the left) from "y" ("x" does not appear and "y" takes 1 digit for values of less than 9).
i r
0 to 63 or
MOD
MOD: channel reserved for management of the module and the parameters shared by all channels.
0 to 3 or
ERR
ERR: indicates a module or channel fault.
(1) : The number of slots requires the use of 2 racks at the same address.
TLX DS 57 PL7 xx
125
Language words and bits
Addressing of language objects associated with discrete I/O modules remoted on the FIPIO bus
Presentation
Illustration
Addressing of bit and word objects is defined in (See Addressing of language
objects for modules remoted on the FIPIO bus, p. 33).
This page describes the specific features linked to the discrete I/O modules remoted on the FIPIO bus.
Addressing principle:
% I, Q, M, K X, W, D, F
Symbol Object type Format
\ p.2.c
\
Module/channel address and connection point m
Module number i
Channel number r
Rank
Specific values The table below shows the values specific to remote discrete I/O module objects.
i
Element Values Comment
0 to 31 or
MOD
0 to 15 for TBX modules.
0 to 31 for Momentum modules.
MOD: channel reserved for management of the module and the parameters shared by all channels.
r 0 to 255 or ERR
ERR: indicates a module or channel fault.
126
TLX DS 57 PL7 xx
Language words and bits
Indexable discrete I/O objects.
Presentation All the discrete module I/O objects are indexable (apart from the TSX DMY 28RFK and TBX DMS 16P22 I/O module objects).
For in-rack TSX and TBX modules, indexing of %I and %Q objects is done independently.
For Momentum modules, indexing for %I objects continues for %Q objects of the same module.