Additional Installation Tips
A good solution may be to use a shielded Ethernet cable, but to connect the shield at one end only.
One option is to break the shield, see 3 in drawing above.
A more elegant method is to expand the shielded Ethernet cabling with a piece of unshielded Ethernet cable, see 4 in drawing above.
The shield can be grounded via an external 0.1 μF/250 V film capacitor, see 5 in drawing above. This connects the HF transients to ground.
6.3 To Achieve Better EMC Protection
•
•
•
•
•
•
•
•
Initially, use the original cabling from Beijer Electronics primarily.
Use shielded cables for RS-232 communication.
Use twisted pair and shielded cabling for RS-422 and RS-485.
Use the cabling intended for the bus type; Ethernet, Profibus, CC-Link,
CAN, Device Net etc.
Install and connect according to applicable specifications for the relevant bus standard.
Use shielded cabling for Ethernet, preferably with foil and a braided shield.
D-sub covers should be shielded, and the shield should be connected to the cover 360° where the cable enters.
Connect the shield at both ends.
Ground plate
Ground plane 1
Shielded cable
0.1 μ F/250 V
Ground plane 2
Not same potential
Ground plate in another building
With longer distances, there is a risk that the ground potential may be different. In that case, the shield should only be connected at one end. A good alternative is to connect the other end of the shield to the ground via a 0.1 μF/250 V film capacitor.
Both ends are then connected to the ground in terms of HF, but only connected to the ground at one end in terms of LF, thus avoiding the 50/60 Hz grounding loops.
Metal cabinet
Terminal or connector
Metal cabinet
Terminal or connector
Cable clamp in steel
EMC cable gland
Shielded cable
Plastic cable gland
Shielded cable
1. Use an EMC cable gland or regular plastic cable gland, remove the outer jacket and connect the shield to the installation plate with a 360° metal cable clamp.
Beijer Electronics, MAEN275 23
advertisement
Related manuals
advertisement
Table of contents
- 7 1 Safety Precautions
- 7 General
- 7 Hazardous Materials
- 8 Disposal Requirements Under WEEE Regulations
- 8 UL and cUL Installation
- 9 During Installation
- 10 During Use
- 10 Service and Maintenance
- 10 Dismantling and Scrapping
- 11 2 Installation
- 11 Installation Process
- 12 Connections to the Controller
- 13 Other Connections and Peripherals
- 15 3 Technical Data
- 17 4 Chemical Resistance
- 17 Metal Casing
- 19 5 Operator Panel Drawings
- 19 Connectors
- 19 Communication Ports
- 20 BoX2 pro Outline
- 21 6 Additional Installation Tips
- 21 Grounding the operator panel
- 22 Ethernet Connection in the Operator Panel
- 23 To Achieve Better EMC Protection
- 24 Ambient Temperature
- 25 Safety
- 26 Galvanic Isolation
- 27 Cable and Bus Termination RS