Audit Logs
PrismaSeT Active - Wireless Panel Server
The Wireless Panel Server generates audit logs that record events such as invalid login attempts and firmware updates.
The logs do not contain any personal information.
To detect unexpected behaviors (for example, frequent rebooting, incorrect firmware update, or invalid login attempts), EcoStruxure Power Commission App is used to retrieve the audit log file (syslog format).
Wireless Panel Server Pairing Control
Control of wireless communications between the Wireless Panel Server and wireless devices is enforced through a pairing mechanism. Only wireless devices that have been paired with the Wireless Panel Server can join the wireless network.
Using EcoStruxure Power Commission App, you can explicitly select IEEE
802.15.4 wireless devices that are authorized to connect to the Wireless Panel
Server. In addition, there is a locate feature for checking pairing with the right device.
Once the pairing is performed, it is recommended to periodically verify the list of paired devices configured in the Wireless Panel Server to make sure that the list of devices contains no unexpected or rogue devices.
Security Events Notification
When the Wireless Panel Server is connected to the Schneider Electric cloud, it sends a security notification through EcoStruxure Facility Expert App if one the following security events occurs:
• A temporarily-locked user access
• A denied user access
• A rejected invalid firmware
• A password recovery process started
Data Protection
Data collected by the Wireless Panel Server are sent encrypted up to the
Schneider Electric cloud over the LoRaWAN network. In this way data in transit over LPWAN network are protected from disclosure and modification.
DOCA0197EN-01 45
PrismaSeT Active - Wireless Panel Server
User Access Control
Presentation
User access to the Wireless Panel Server through the local Bluetooth Low Energy interface is done by using EcoStruxure Power Commission App and is passwordprotected. Once the user is successfully logged into the Wireless Panel Server, the user has access to all capabilities and functions of the Wireless Panel Server.
User Login
EcoStruxure Power Commission App is the tool for logging in to and commissioning the Wireless Panel Server. Before login, the smartphone must be paired with the Wireless Panel Server (see
Changing Password
At first connection to the EcoStruxure Power Commission App, the user is prompted to set the password.
To change the password, proceed as follows:
1. Activate Bluetooth wireless technology on the Wireless Panel Server.
2. Pair your smartphone to the Wireless Panel Server.
3. Use EcoStruxure Power Commission App to log in to the Wireless Panel
Server.
4. Change the password.
Password Requirements
A password must conform to the following rules:
• 6 to 32 characters
• At least one character in uppercase
• At least one character in lowercase
Password Lockout
In case of 10 invalid attempts to log in to the Wireless Panel Server, user access is locked. It remains locked for 10 minutes before the user can attempt to log in again.
Consecutive invalid attempts (up to 14) lock user access for 10 minutes after each invalid attempt.
After the fifteenth consecutive invalid attempts, the user access is locked for 60 minutes after each invalid attempt.
User account lock state remains if the Wireless Panel Server is rebooted, including reboot after power loss.
To unlock user access, the user must log in successfully after a lock period or apply the forgotten password process using EcoStruxure Power Commission App.