Technical Data. Ampac Discovery

Add to My manuals
25 Pages

advertisement

Technical Data. Ampac Discovery | Manualzz

DISCOVERY PRODUCT GUIDE

Item No

201-0053

213-0067

58100-926

58100-927

58100-928

58100-929

58100-953

Colour

Red

Red

White

Yellow

Blue

Green

Yellow

Deformable

Element

Backbox for surface

Isolator

Non-

Isolator

Table 4 – Manual Call Point Item Numbers

9.3 Technical Data:

Specifications are typical and given at 23°C and 50% relative humidity unless specified otherwise.

Call Point Type: Deformable element

Waterproof

IP67 Rated

Call Point Principle:

Alarm Indicator:

Fault Indicator:

Supply Wiring:

Loop Connections:

Operating Voltage:

Communication

Protocol:

Operation of a switch

Red Light Emitting Diode (LED)

Amber/Yellow Light Emitting Diode (LED)

Two wire monitored supply, polarity insensitive

Terminal Block L1 –ve and L2 +ve supply in and out connections

17 - 28V DC

Apollo Discovery 5-9V peak to peak

Quiescent Current: 100µA at 24V DC

Power-up Surge Current: 1mA

Maximum power up time: 1s

Alarm Current, LED on: 4mA

Normal analogue value: 16

Alarm State Value:

Temperature Range:

Humidity:

64

-20°C to +60°C

0 to 90% relative humidity (no condensation)

To EN54-11: 2001, EN54-17:2005 AS1670-1 Compliance Standard:

IP Rating:

Dimensions:

Weights:

24D IP67 (weatherproof)

89mm x 93mm x 26.5mm (manual call point)

87mm x 87mm x 32mm (back box)

Flush Mounted: 110g

Surface Mounted: 160g

Housing: Red self-coloured polycarbonate/ABS Material:

Ancillary Items:

Item No

26729-152

26729-179

26729-155

Description

Hinged Cover

Security Locking Tags for above (pack of 5)

Discovery Glasses

16

MAN3050

advertisement