Part 2 Functions & Controls
3. Special Mode Controls
3.1 Jet Cool operation
• In the heating mode or Auto Changeover operation, the Jet cool function does not work.
When it is input while in other mode of operation (cooling, dehumidification, Air purification, Air circulation), the Jet cool operation takes place.
• In the Jet cool mode, the indoor fan is operated at super-high speed for 30 min. at cooling mode operation.
• In the Jet cool mode, the room temperature is maintained at a setting temperature of 18°C(64.4°F).
• When the sleep timer mode is input during the Jet cool operation, the Jet cool mode has the priority.
• When the Jet cool button is pressed, the horizontal vane of the unit is reset to those of the initial cooling mode and then operate so that the air outflow could reach further.
3.2 Jet Heat operation
• While in cooling mode or Auto Changeover operation, the Jet Heat function does not work.
When it is input while in the Heating mode operation (dehumidification), the Jet Heat mode operation takes place
• In the Jet Heat mode, the indoor fan operated at super-high speed for 60 min. at Heating mode operation.
• In the Jet Heat mode, the room temperature is maintained at a temperature of 30°C(86°F).
• When the sleep timer mode is input during the Jet Heat mode operation, the Jet Heat mode has the priority.
• When the Jet Heat button is pressed, the horizontal vane of the unit is the unit reset to those of the initial Jet heating mode and then operates so that the air outflow could reach under flow.
3.3 Energy saving operation in cooling mode
• During cooling and dehumidification mode of operation, the Energy saving button can be input.
• In this operation, before we feel cold the set temperature and air volume is set automatically to save energy.
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
- 12 -
LGE Internal Use Only
Part 2 Functions & Controls
4. Utility Functions
4.1 Forced operation
• To operate the appliance manually in case when the remote control is lost, the forced operation selection switch is on the main unit of the appliance, and operate the appliance in the standard conditions.
• The operating condition is set according to the outdoor temp. and intake air temperature as follows.
Indoor temp.
Operating Mode Setting temp.
Setting speed of indoor fan
over 24°C(75.2°F)
21~24°C(69.8~75.2°F) below 21°C(69.8°F)
Cooling
Healthy Dehumidification
Heating
22°C(71.6°F)
23°C(73.4°F)
24°C(75.2°F)
High speed
• Operating procedures when the remote control can't be used is as follows :
- The operation will be started if the ON/OFF button is pressed.
- If you want to stop operation, re-press the button.
- The ON/OFF switch is on the display PCB or side of indoor unit
4.2 Auto cleaning operation
• Function used to perform Self Cleaning to prevent the Unit from Fungus and bad odor.
• Used after the Cooling Operation before turning the unit off, clean the Evaporator and keep it dry for the next operation.
• The function is easy to operate as it is accessed through the Remote controller.
ON OFF
Comp.
Indoor Fan
Cooling CYCLE
ON
Setting Step
Fan
30 Min
OFF
Super Low
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
- 13 -
LGE Internal Use Only
Part 2 Functions & Controls
4.3 Air volume control
• UIndoor fan motor control have 6 steps or 8 steps.
• UAir volume is controlled "SH", "H", "MH", "M", "ML", "L" by the remote controller.
• "SL" step is selected in "Sleep Mode" operation.
4.4 Natural Air Control(Natural Wind)
• When the Auto Step is selected and then operated, the high, medium, or low speed of the airflow mode is operated for 2~15 sec. randomly by the Chaos Simulation.
Step
MH
H
SH
Auto
SL
L
ML
M
Description
Super Low
Low
Medium-Low
Medium
Medium-High
High
Super High
Natural Wind
4.5 Auto Swing
• By the Auto swing key input, the horizontal vane automatically operates with the Auto swing or it is fixed to the desired direction.
4.6 Sleep mode Auto control
• When the set sleep time is reached set time of [1,2,3,4,5,6,7hour] input by the remote control during the operation, the operation of the appliance stops.
• When the appliance is on pause, the sleep timer mode cannot be input.
4.6.1 Sleep timer operation for cooling cycle
• While in cooling mode , 30 min. after the start of the sleep timer, the setting temperature increases by 1 C(2 .
After another 30minutes lapse, it increases again by 1°C(2 .
Setting temp. (˚C)
1.0˚C(2˚F) up
1.0˚C(2˚F) up
Cooling ON temp.
(Setting temp. +0.5˚C(+1˚F))
Cooling OFF temp.
(Setting temp. -0.5˚C(-1˚F))
0.5
1 Sleep time (hour)
NOTE: Some Models are different by swing width and swing pattern.
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
- 14 -
LGE Internal Use Only
Part 2 Functions & Controls
4.6.2 Sleep timer operation for heating cycle
• While in heating mode, 60 min. after the start of the sleep timer, the setting temperature decreases by 1 C(2 .
After another 60minutes lapse, it decreases again by 1°C(2 .
Setting temp. (
°C)
Heating ON temp.
(Setting temp)
Heating OFF temp.
(Setting temp. +4.0
°C(+8°F))
1.0
°C(2°F) down
1.0
°C(2°F) down
1 2 Sleep time (hr)
4.7 Auto restart
• When the power comes back after a sudden power failure during operation, the mode before the power failure is kept on the memory of the appliance and it automatically operates in the saved mode on the memory.
• Operation mode that is kept on the memory
- State of operation ON/OFF
- Operation mode/setting temp./selected airflow speed
- Sleep timer mode/remaining time of sleep timer
- Auto Swing
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
- 15 -
LGE Internal Use Only
advertisement
Related manuals
advertisement
Table of contents
- 3 1. Safety Precautions
- 6 2. Nomenclature
- 8 1. List of Functions & Controls
- 9 2. Basic Mode Controls
- 11 3. Special Mode Controls
- 12 4. Utility Functions
- 16 1. Check before Test Run
- 17 2. Test Run Flow chart
- 18 3. Test Run Detail
- 20 1. 2-Way, 3-Way Valve
- 21 2. Pumping Down
- 22 3. Evacuation (All amount of refrigerant leaked)
- 23 4. Gas Charging (After Evacuation)
- 24 5. Cycle Troubleshooting Guide
- 25 6. Electric Parts Troubleshooting Guide
- 29 7. Self-diagnosis Function
- 21 1. 2-Way, 3-Way Valve
- 22 2. Pumping Down
- 23 3. Evacuation (All amount of refrigerant leaked)
- 24 4. Gas Charging (After Evacuation)
- 25 5. Cycle Troubleshooting Guide
- 26 6. Electronic Parts Troubleshooting Guide
- 30 7. Self-diagnosis Function