FX1S Series Programmable Controllers
4.
Power Supply
4.1
4.2
Power Supply 4
Wiring Techniques
The wiring of FX
1S products has been designed to be safe and easy. If during the installation of these product or associated products concern is felt, please contact a professional electrician who is trained to the local and national standards applicable to the installation site.
Wiring Cautions
4.3
• Do not run input signals in the same multicore cable as output signals or allow them to share the same wire.
• Do not lay I/O signal cables next to power cables or allow them to share the same trunking duct. Low voltage cables should be reliably separated or insulated with regard to high voltage cabling.
• Where I/O signal lines are used over an extended distance consideration for voltage drop and noise interference should be made.
Power Supply
When wiring AC supplies the “Live” cable should be connected to the “L” terminal and the
“Neutral” cable should be connected to the “N” terminal. Do NOT connect the “Live” wire to the
“N” terminal, the user might receive a dangerous shock on powerup.
4-1
FX1S Series Programmable Controllers
4.4
Power Supply Characteristics
Power Supply 4
Table 4.1: AC Input Power Requirements, FX1S-**M*-ES/UL, ESS/UL
Description
Power supply
Max. allowable momentary power failure period
Fuse (size) rating
In-rush current
Power consumption *1
24V DC Service Supply
FX
1S
-10M FX
1S
-14M FX
1S
-20M FX
1S
-30M
100 - 240V AC, +10% -15%, 50/60 Hz
10ms; if less than 10ms, the PLC will continue operation.
If 10ms or more, the PLC will shut down
250V 1.0A 5
φ×
20mm (0.2
×
0.79 inches)
100V AC - Max. 15A for 5ms
200V AC - Max. 25A for 5ms
19W 19W 20W 21W
400 mA
*1 Includes the input current (5 or 7mA per point).
Table 4.2: DC Input Power Requirements, FX1S-**M*-DS, DSS
Description
Power supply
Max. allowable momentary power failure period
Fuse rating
In-rush current
Power consumption *1
FX
1S
-10M FX
1S
-14M FX
1S
-20M FX
1S
-30M
24 V DC +10% -15%
5 ms; if less than 5 ms, the PLC will continue operation.
If 5 ms or more, the PLC will shut down
6W 6.5W
0.8A
15A for 0.1 ms
7W 8W
4-2
FX1S Series Programmable Controllers
4.5
Power Supply Input Wiring
Figure 4.1: AC Input Example Wiring
FX
1S
Series
AC/DC
Converter
24+
24-
L
N
85-264V AC
50/60 Hz
MC
~
24V
0V
MC
PL
MC
MC
Power Supply 4
Power supply 100 - 240V AC, +10% -15%,
50/60 Hz
Circuit protector or Fuse
Emergency stop
Power supply switch
Power ON pilot indicator
Power supply for loads
Grounding resistor 100
Ω or less (class D)
Fuse
Main unit
Breaker
4-3
FX1S Series Programmable Controllers
Figure 4.2: DC InputExampleWiring
FX
1S
Series
DC/DC
Converter
Power Supply 4
+
_
20.4 - 26.4V DC
~
MC
MC
PL
MC
MC
Power supply 24V DC, +10% -15%
Circuit protector or Fuse
Emergency stop
Power supply switch
Power ON pilot indicator
Power supply for loads
Grounding resistor 100
Ω or less (class D)
Fuse
Main unit
Breaker
4-4
FX1S Series Programmable Controllers
4.6
Earthing / Grounding
Power Supply 4
Use a cable at least 0.2mm
2
(AWG24) to ground equipment. Ground resistance must be less than 100
Ω
(class D). Note that the ground cable must not be connected to the same ground as the power circuits. Grounding is recommended but if a proper ground cannot be provided the PLC will still operate correctly without being grounded.
4-5
FX1S Series Programmable Controllers
Power Supply 4
4-6
FX1S Series Programmable Controllers
1 INTRODUCTION
2 TERMINAL LAYOUTS
3 INSTALLATION NOTES
4 POWER SUPPLY
5 INPUTS
6 OUTPUTS
7 DIAGNOSTICS
Inputs 5
FX1S Series Programmable Controllers
Inputs 5
FX1S Series Programmable Controllers
5.
Inputs
5.1
24V DC Input Specifications
Table 5.1: FX
1S
Input Specifications
Input voltage
X0 - X7
FX
1S
Main Unit
X10 - X17
24V DC +/- 10%
Input current
Input switching current
Response time
Circuit isolation
Operation indication
24V DC,
7mA
OFF
à
ON >4.5mA
ON
à
OFF
Variable response time
24V DC, 5mA
>3.5mA
<1.5mA
10ms (default)
0 - 15ms for X000-X017 via use of the FX
1S digital filter.
Photocoupler
LED is lit
Inputs 5
5-1
FX1S Series Programmable Controllers
5.2
Wiring Diagrams
5.2.1
Input Wiring
Figure 5.1: Input Wiring Diagrams
FX
1S
-Source
PNP
24V 0V
S/S X0 X1 X2
FX
1S
-**M*-ES/UL, ESS/UL
1 24V DC Service Supply
2 PNP Sensor
3 NPN Sensor
4 Input Device Contact
5 FX
1S
Controller Main Body
FX
1S
-Sink
NPN
24V 0V
S/S X0 X1 X2
FX
1S
-**M*-ES/UL, ESS/UL
Inputs 5
5-2
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 21 1. Introduction
- 21 Model Name
- 21 World Specification
- 21 Serial Numbers
- 21 Configuration
- 21 1.4.1 Unit Accessories
- 21 1.4.2 Limits of Expansion
- 21 Backup Data
- 21 1.5.1 Data Backup
- 21 1.5.2 Capacitor backup
- 22 2. Terminal Layouts
- 22 FX1S-**MR-ES/UL
- 22 FX1S-**MR-DS
- 22 FX1S-**MT-DSS
- 22 FX1S-**MT-ESS/UL
- 40 3. Installation Notes
- 40 Product Outline
- 40 RUN/STOP Control
- 40 General Specifications
- 40 PLC Mounting Arrangements
- 40 DIN Rail Mounting
- 40 Termination of Screw Terminals
- 40 Installing Optional Units
- 40 3.7.1 Special Function Boards
- 40 3.7.2 FX1N-5DM Display Module
- 41 4. Power Supply
- 41 Wiring Techniques
- 41 Wiring Cautions
- 41 Power Supply
- 41 Power Supply Characteristics
- 41 Power Supply Input Wiring
- 41 Earthing / Grounding
- 51 5. Inputs
- 51 24V DC Input Specifications
- 51 Wiring Diagrams
- 51 5.2.1 Input Wiring
- 51 5.2.2 Input Circuit Connection
- 51 5.2.3 Diodes and Inputs Connected in Series
- 51 5.2.4 Resistors and Inputs Connected in Parallel
- 52 6. Outputs
- 52 Relay Output Example
- 52 Reliability Tests
- 52 Response Times
- 52 Transistor Output Examples
- 52 Applying Safe Loads
- 65 7. Diagnostics
- 65 Preliminary Checks
- 65 ERROR LED ON (CPU ERROR)
- 65 Common Errors
- 65 Maintenance
- 65 Operation and Error Flags
- 65 PLC Status Registers
- 65 Error Registers
- 65 Error Codes
- 65 Instruction List
- 65 7.10 Device List