EMC Compatibility
!
Introduction
This section describes the measures necessary to comply with the EMC (Electro Magnetic Compatibility) Directive.
The manual's installation and wiring instructions must be followed for compliance.
Yaskawa products are tested by authorized organizations using the standards listed below.
Product standard: EN 61800-3:1996
EN 61000-3-2; A1, A2, A14:2000
!
Measures to Ensure Conformity of Installed Yaskawa Drives to EMC Directive
Yaskawa Drives are not required to be installed in a switch cabinet.
It is not possible to give detailed instructions for all possible types of installations, therefore this manual provides general guidelines.
All electrical equipment produces radio and line-borne interference at various frequencies. The power leads pass this on to the surrounding environment like an antenna. Connecting an item of electrical equipment (e.g. Drive) to a supply without a line filter can allow High Frequency (HF) or Low Frequency (LF) interference to penetrate the power distribution system. The basic countermeasures are isolation of the wiring of control and power components, proper grounding, and shielding of cables.
A large contact area is necessary for low-impedance grounding of HF interference. The use of grounding, straps instead of cables is therefore highly recommended.
Cable shields must be connected with ground clips.
!
Cable Installation
Measures Against Line-Borne Interference:
Line filter and Drive must be mounted on the same metal plate. Mount the two components as close to each other as possible, with cables kept as short as possible (see Figure G-2).
Use a power cable with a well-grounded shield. Use a shielded motor cable not exceeding 82 feet (25 m) in length. Arrange all grounds to maximize the end of the lead area in contact with ground (e.g. metal plate).
Use a shielded cable with braided shield and ground the maximum possible area of the shield. It is advisable to ground the shield by connecting the cable to the ground plate with metal clips (see Figure G-1).
EMC Compatibility G - 2
Electromagnetic Compatibility (EMC)
!
Recommended EMC Filters
Drive Model
CIMR-P7U
20P4
20P7
21P5
22P2
23P7
25P5
27P5
2011
2015
2018
2022
2030
2037
2045
2055
4015
4018
4030
4037
4045
4055
40P4
40P7
41P5
42P2
43P7
45P5
47P5
4011
FS5972-10-07
FS5972-18-07
FS5973-35-07
FS5973-60-07
FS5973-100-07
FS5973-130-35
FS5973-160-40
FS5973-240-37
Model Number
FS5972-10-07
FS5972-18-07
Current Rating
EMC Filter
Weight lb.
(kg)
208-240 Vac
10 A
18 A
35 A
60 A
100 A
2.43
(1.1)
2.87
(1.3)
3.09
(1.4)
6.61
(3)
10.8
(4.9)
130 A
160 A
9.48
(4.3)
13.23
(6)
24.25
(11)
240 A
480 Vac
10 A
2.43
(1.1)
18 A
2.87
(1.3)
FS5972-35-07
FS5972-60-07
FS5972-70-52
FS5972-130-35
35 A
60 A
70 A
130 A
EMC Compatibility G - 3
4.63
(2.1)
8.82
(4)
7.5
(3.4)
10.36
(4.7)
Dimensions inches
(mm)
Nominal
Hp
5.500 x 13 x 1.875
(141 x 330 x 46)
5.500 x 13 x 1.875
(141 x 330 x 46)
5.500 x 13 x 1.875
(141 x 330 x 46)
8 x 14 x 2.375
(206 x 355 x 60)
9.3125 x 16 x 3.125
(236 x 408 x 80)
3.5315 x 14.40625 x 7
(90 x 366 x 180)
4.750 x 17.750 x 6.6875
(120 x 451 x 170)
5.125 x 24 x 9.4375
(130 x 610 x 240)
0.5/0.75
1
1.5/2
3
5
7.5
10
15
20
25
30
40
50
60
75
5.500 x 13 x 1.875
(141 x 330 x 46)
5.50 x 13 x 1.875
(141 x 330 x 46)
8.125 x 14 x 1.9375
(206 x 355 x 50)
9.250 x 16 x 2.50
(236 x 408 x 65)
3 x 13 x 7.250
(80 x 329 x 185)
3.5 x 14.375 x 7
(90 x 366 x 180)
0.5/0.75
1
1.5/2
3
5
7.5
10
15
25
30
40/50
60
75
100
Drive Model
CIMR-P7U
4075
4090
4110
Model Number
FS5972-170-40
FS5972-250-37
Current Rating
170 A
250 A
EMC Filter
Weight lb.
(kg)
13.23
(6)
24.25
(11)
Dimensions inches
(mm)
4.750 x 17.750 x 6.6675
(120 x 451 x 170)
5.125 x 24 x 9.4375
(130 x 610 x 240)
Nominal
Hp
125
150
200
Ground clip Ground plate
Fig G.1 Grounding Surface Layout
The grounding surfaces must be highly conductive bare metal. Remove any varnish or paint from grounding surfaces.
•
Ground the cable shields at both ends.
•
Ground the motor of the machine/application.
EMC Compatibility G - 4
L1
L2
L3
PE
Grounding
Remove varnish or paint
Metal plate
EMC
Filter
Cable length
Maximum of 15.75”
Grounding
Remove varnish or paint
M
Motor cable
Length
Maximum of
82 feet
Fig G.2 EMC Filter Layout
Drive
EMC Compatibility G - 5
Notes:
EMC Compatibility G - 6