Generic Point Selection Screens. Ampac LoopSense AS

Add to My manuals
68 Pages

advertisement

Generic Point Selection Screens. Ampac LoopSense AS | Manualzz

- Enter currently selected menu item

To - Select and enter menu item by corresponding number

- Return to previous menu

7.1.1 Generic Point Selection Screens

Within the menu system there are several instances in which points are required to be selected in order to proceed further and display and/or manipulate the selected points. Points include Zones,

Loops, Devices, Device Sub-Addresses, Panel Inputs, Panel Outputs and Add-Ons.

7.1.2 Zone Point Selection

SELECT ZONE: XXX

<selected zone descriptor>

►Z1 Z2 Z3 Z4 Z5

Z6 Z7 Z8 Z9 Z10

Z11 Z12 Z13 Z14 Z15

Z16 Z17 Z18 Z19 Z20

Z21 Z22 Z23 Z24 Z25

Z26 Z27 Z28 Z29 Z30

Zones 1 up to 999 can be selected.

Zone Address Prefixes:

 Z - Zone configured

 X - Zone not configured

Zone Address Suffixes:

 * - Zone Disabled

 S - Zone Sounders Disabled

7.1.3 Loop Point Selection

SELECT LOOP: X

<selected loop descriptor>

►L1 L2

Loop 1 or 2 can be selected.

This screen will be skipped if there is only one loop configured in the system except for in the programming menu where the prefix “L” next to the loop number will be replaced with an “X” if the loop is not configured and it can be se lected to configure the loop. The loop number suffix “*” indicates that the loop has been disabled.

7.1.4 Loop Device Point Selection

SELECT DEVICE: XXX <device type>

<selected device descriptor>

►D1 D2 D3 D4 D5

D6 D7 D8 D9 D10

D11 D12 D13 D14 D15

D16 D17 D18 D19 D20

D21 D22 D23 D24 D25

D26 D27 D28 D29 D30

Apollo device addresses 1 to 126 can be selected.

Device Address Prefixes:

 D - Device configured and fitted

 M - Missing device configured and not fitted

 T - Type mismatch configured and fitted with incorrect type

 E - Extra device not configured but fitted

 X - Device not configured and not fitted

Device Address Suffix:

 * - Device Disabled

7.1.5 Sub-Address Point Selection

SELECT SUB ADDRESS: X

<selected sub address descriptor>

1►I/P1 2:I/P2 3:I/P3 4:O/P1 5:O/P2

6:O/P3

Apollo loop device sub-address inputs 1-3 and outputs 1-3 can be selected.

Sub-Address Prefixes:

 I/P – Sub-Address Input

 O/P – Sub-Address Output

Sub-Address Suffix:

 * - Sub-Address Disabled

7.1.6 Add-On Point Selection

SELECT ADD-ON: XX <add-on type>

<selected add-on descriptor>

►A1 A2 A3 A4 A5

A6 A7 A8 A9 A10

A11 A12 A13 A14 A15

A16 A17 A18 A19 A20

A21 A22 A23 A24 A25

A26 A27 A28 A29 A30

Add-On module addresses 1 up to 30 can be selected, depending on type.

Add-On Address Prefixes:

 A – Add-On configured

 X – Add-On not configured

Add-On Address Suffix:

 - Add-On Disabled

7.1.7 Panel Input Point Selection

SELECT INPUT: X <input type>

<input descriptor>

►I/P1 I/P2 I/P3 I/P4

Panel digital inputs 1 to 4 can be selected.

Panel Input Prefix:

 I/P – Panel Input

Panel Input Suffix:

 * - Panel Input Disabled

7.1.8 Panel Output Point Selection

SELECT OUTPUT: X <output type>

<output descriptor>

►O/P1 O/P2 O/P3 O/P4

4 panel Supervised Outputs:

3 Relay Outputs

2 Open Collector Outputs

2 Auxiliary Outputs can be selected.

Panel Output Prefix:

 I/P – Panel Output

Panel Output Suffix:

 - Panel Output Disabled

7.1.9 Password User ID Selection

SELECT USER ID: X

►ID1 ID2

User IDs 1 and 2 can be selected at the panel.

8. Menu Structure and Navigation

The following should be read in conjunction with the complete “Menu Structure”.

The primary components of the Menu Structure are;

DISPLAY CONTROL EVENTS TOOLS SETUP PROGRAMMING

The sections below have been broken down by primary component for ease of explanation

8.1

Menu > Display

DISPLAY

1

1 6 8

FIRE

2

FAULT

3 4 5

PRE-ALARM EMERGENCY SECURITY USER

7

DISABLE TEST

9

ABOUT

Pressing

1

opens the “Display” menu. Here the operator can view any of the above facilities, 1 to 8 by following the screen prompts, (up), (down), to move through the menu. To view its status on the LCD press the number associated with that facility, for example press

3

DEF

to view any “Pre-alarms” that may be present on the system.

This process of navigation and following the screen prompts forms the basis for accessing,

viewing and / or programming.

DISPLAY MENU

1►FIRE xxx 6|USER xxx

2|FAULT xxx 7|DISABLE xxx

3|PRE-ALARM xxx 8|TEST xxx

4|EMERGENCY xxx 9|ABOUT

5|SECURITY xxx

In the DISPLAY menu, the menu items consist of all the displayable system conditions.

When a display condition is selected, the status screen of the condition to be shown is displayed at the zone level initially:

Zzzz <status>

<zone descriptor>

<date> <time> CONTROL*

ZONE <condition> XXX OF XXX DEVICE►

Pressing the “DEVICE►” forward button will allow the panel to display the individual devices or inputs with the associated condition.

<point location> <status>

<point descriptor> <type>

<date> <time> CONTROL*

<condition> XXX OF XXX ◄ZONE

Note: if there are no Zones with the selected condition and there are devices with the selected

condition, the zone screen will be bypassed and the device screen will be displayed immediately.

8.1.1 Menu > Display > About

If ABOUT is selected the following screen is presented:

<custom banner 1>

<custom banner 2>

<system status>

◄BACK SOFTWARE:VX.XX.XX.XXX PCB REV:XXX

8.2

Menu > Control

2

ABC

CONTROL

1

1

ZONE

3

PANEL

2

ABC

2

DEVICE

NOTE:

1: At Access Level 1, the entire menu is not accessible.

2: At Access Level 2, the PROGRAMMING & SETUP menu

items are not accessible, user can access level 3

functionalities via the correct password entry.

3: At access level 3, every option is available

3

DEF

4

GHI

4

GLOBAL CONTROL

Pressing

2

ABC

opens the “Control” menu from which the operator can select one of the “Control” functions shown above by pressing (up), (down), to move through the menu. To view its control options on the LCD press the number associated with that facility on the alpha numeric key pad or press to go directly to it.

CONTROL MENU

1►ZONE 3|PANEL

2|DEVICE 4|GLOBAL CONTROL

8.2.1 Menu > Control > Zone

2

ABC

CONTROL

1

ZONE

1

1

DISABLE INPUTS

1

DISABLE

2

DISABLE SOUNDERS

2

SUB ADDR / REM I/O

NON

SOUNDER

3

1

3 4

SILENT WALK TEST WALK TEST

PRINT

DISABLE

4

ALARM LED ON

2

O N

SOUNDER

1

DISABLE

2

ALERT

3

3

DEVICE

PRINT

EVAC

2

DEVICE

4

PRINT

3

PANEL

4

GLOBAL CONTROL

1

Once in the “Control” menu press to open the “Zone” menu. By following the screen prompts select the type of control, 1 to 4. Once selected simply step through the menu again to implement.

Zzzz <status>

<zone descriptor>

1:DISABLE INPUTS 2:DISABLE SOUNDERS

3:SILENT WALK TEST 4:WALK TEST DEVICE►

Selecting the Zone Control menu prompts the user to select the zone number using the generic zone point selection screen followed by the corresponding zone control menu:

Actions are all context sensitive.

 Disable inputs becomes enable inputs.

 Disable sounders becomes enable sounders

 Walk test will start walk test and toggle to remove test

 Silent walk test will start silent walk test and toggle to remove test

Pressing

► will display device (or input) within the zone; these are scrollable using ▲▼

Device Screens

Zzzz Ppp Lll Dddd.s <status>

<device descriptor>

ACTION:<action type> <dev type>

AVALUE:XXX I:000 O:000 DRIFT:YYY MODE:X

◄ZONE 1:DISABLE 2:SUB ADDR 3:PRINT

4:ALARM LED ON

Note: option 2 shall be SUB ADDR (Sub-Address) or REM O/P (Remote Output) depending on

the type of device being displayed.

Input Screens

<point location> <status>

<point descriptor>

ACTION:<action type>

◄BACK 1:DISABLE 2:ON 3:PRINT

8.2.2 Menu > Control > Device

2

ABC

CONTROL

1

ZONE

2

DEVICE

1

L1

1

DISABLE

2

ABC

2

L2

2

SUB ADDR / REM I/O

NON

SOUNDER

NOTE: SUB ADDR AND REM O/P DEPEND

ON THE SELECTED DEVICE

3

PRINT

4

ALARM LED ON

1

DISABLE

2

O N

3

PRINT

SOUNDER

1

DISABLE

2

ALERT

3

EVAC

4

PRINT

3

PANEL

4

GLOBAL CONTROL

Selecting DEVICE from the control menu; the user shall be prompted to select loop and device address via generic point selection screens. The following device control menu is presented next:

Zzzz Ppp Lll Dddd.s <status>

<device descriptor>

ACTION:<action type> <dev type>

AVALUE:XXX I:000 O:000 DRIFT:YYY MODE:X

◄BACK 1:DISABLE 2:SUB ADDR 3:PRINT

4:ALARM LED ON

Selecting “2: SUB ADDR” will display the generic sub address selection screen if configured. Also “2:

SUB ADDR” will be replaced with “2: REM O/P” if the context displayed is a detector.

<input location> <status>

<input descriptor>

ACTION:<action type> <dev type>

◄BACK 1:DISABLE 2:ON 3:PRINT

Non-Sounder Output Screens

<output location> <status>

<output descriptor>

<assigned output type> <dev type>

◄BACK 1:DISABLE 2:ON 3:PRINT

Sounder Output Screens

<output location> <status>

<output descriptor>

<assigned output type> <dev type>

◄BACK 1:DISABLE 2:ALERT 3:EVAC 4:PRINT

8.2.3 Menu > Control > Panel

CONTROL

2

ABC

3

D E F

1

ZONE

3

PANEL

2

DEVICE

1

INPUT

1 DISABLE

4

GLOBAL CONTROL

2

OUTPUT

1

SUPERVISED O/P

NON

SOUNDER

2 3 4

RELAY O/P OPEN COLLECTOR O/P AUXILIARY O/P

1

DISABLE

2

O N

3

PRINT

SOUNDER

1

DISABLE

2

ALERT

3

EVAC

2 ON 3 PRINT

4

PRINT

3

ADD-ON

SELECT

ADD-ON TYPE

4

1

LOOP

DISABLE

5

PRINTER

1

ON-LINE

1

2

DISABLE

TEST

2 3

I/O

NON

SOUNDER

1

PRINT

DISABLE

SOUNDER

1

DISABLE

3

PRNT ALL

4

PRNT TYPES

2

2

O N

ALERT

6

POWER

2

F I RE MODE

E V E NT MODE

7

DELAY MODE

1

NOTE: DELAY MODE (7) MENU IS ONLY AVAILABLE

IF INVESTIGATION DELAYS ARE CONFIGURED

ON / OFF

3

PRINT

3

EVAC

4

PRINT

8.2.3.1 Menu->Control->Panel->Input

CONTROL PANEL MENU

1►INPUT 5|PRINTER

2|OUTPUT 6|POWER

3|ADD-ON 7|DELAY MODE

4|LOOP

Use the

▼▲ arrows to display the 4 available panel inputs

Ppp Ii Zzzz <status>

<input descriptor> <type>

ACTION:<action type>

◄BACK 1:DISABLE 2:ON 3:PRINT

8.2.3.2 Menu > Control > Panel > Output

CONTROL PANEL OUTPUT MENU

1►SUPERVISED O/P 3|OPEN COLLECTOR O/P

2|RELAY O/P 4|AUXILIARY O/P

8.2.3.2.1 Menu > Control > Panel > Output > Supervised O/P

Use the

▼▲ arrows to display the 4 available panel supervised outputs

Non-Sounder Outputs

Zzzz Ppp SUP:Oo <status>

<output descriptor> <type>

<assigned output type>

◄BACK 1:DISABLE 2:ON 3:PRINT

Sounder Outputs

Zzzz Ppp SUP:Oo <status>

<output descriptor> <type>

<assigned output type>

◄BACK 1:DISABLE 2:ALERT 3:EVAC 3:PRINT

8.2.3.2.2 Menu > Control > Panel > Output Relay O/P

Use the

▼▲ arrows to display the 3 available panel relay outputs

Zzzz Ppp SUP:Oo <status>

<output descriptor> <type>

<assigned output type>

◄BACK 1:DISABLE 2:ON 3:PRINT

8.2.3.2.3 Menu > Control > Panel > Output > Open Collector O/P

Use the

▼▲ arrows to display the 2 available panel auxiliary outputs

Zzzz Ppp OC:Oo <status>

<output descriptor> <type>

<assigned output type>

◄BACK 1:DISABLE 2:ON 3:PRINT

8.2.3.2.4 Menu > Control > Panel > Output > Auxiliary O/P

Use the

▼▲ arrows to display the 2 available panel auxiliary outputs

Zzzz Ppp AUX:Ooo <status>

<output descriptor> <type>

<assigned output type>

◄BACK 1:DISABLE 2:ON 3:PRINT

8.2.3.3 Menu > Control > Panel > Add-On

After the type of Add-On is selected using the

▼▲the generic Add-On point selection screen is presented allowing the Add-On address to be selected. The Add-On control menu is then presented:

SELECT ADD-ON TYPE: 8-WAY RELAY

CHANGE▼

◄BACK NEXT►

Se lecting “2:I/O” will display the individual inputs and/or outputs of the add-ons. Use the ▼▲ arrows to display the available inputs and outputs

<add-on location> <status>

<add-on descriptor>

<add-on type> <add-on version>

◄BACK 1:DISABLE 2:I/O 3:PRINT

Non-Sounder Outputs

<add-on location> <status>

<output descriptor> <type>

<assigned output type> <add-on type>

◄BACK 1:DISABLE 2:ON 3:PRINT

Sounder Outputs

<add-on location> <status>

<output descriptor> <type>

<assigned output type> <add-on type>

◄BACK 1:DISABLE 2:ALERT 3:EVAC 4:PRINT

8.2.3.4 Menu > Control > Panel > Loop

Use the

▼▲ arrows to display the available loops

Pppp Lll <status>

<loop descriptor>

<loop configuration> <loop current>

1:DISABLE 2:TEST 3:PRNT ALL 4:PRNT TYPES

8.2.3.5 Menu > Control > Panel > Printer

PANEL PRINTER <on-line status>

<fire/event mode>

◄BACK 1:ON-LINE 2:FIRE MODE

8.2.3.6 Menu > Control > Panel > Power

PANEL POWER

AC:xxxxxxxxx VBATT:xx.xDC TEMP:xxxC

BATTERY:xxxxxxxxx

◄BACK

AC Statuses include

NORMAL

FAIL

CHRG HIGH

CHRG LOW

8.2.3.7 Menu > Control > Panel > Delay Mode

BATTERY statuses include

NORMAL

DAMAGED

MISSING

CABLE FLT

LOW

This menu is only accessible if investigation delays have been configured and the panel is in the day or night modes in which delays are configured

INVESTIGATION DELAY MODE: ON

◄BACK 1:OFF

8.2.4 Menu > Control > Global Control

2

ABC

CONTROL

1

ZONE

3

PANEL

2

DEVICE

4

GLOBAL CONTROL

1

DISABLE SOUNDERS

2

ENABLE SOUNDERS

3

GLOBAL ENABLE

4

GHI

4 5

REMOVE MANUAL I/O REMOVE WALK TEST

GLOBAL CONTROL MENU

1►DISABLE SOUNDERS 4|REMOVE MANUAL I/O

2|ENABLE SOUNDERS 5|REMOVE WALK TESTS

3|GLOBAL ENABLE

8.3

3

DEF

Menu > Events

EVENTS

1

1

ALL

PRINT

1

CURRENT ENTRY

2

2

FIRE

2

DELETE

ALL

3

FAULT

4

PRE-ALARM

5

EMERGENCY

6

SECURITY

3

GOTO

3 4

RANGE BY DATE RANGE BY ENTRY No

1

MOST RECENT

2

BY DATE

7

USER

3

BY ENTRY

8

SYSTEM

9

DISABLE

The user can select to view any individual event type or all event types; revealing the following event screen:

EVENTS MENU

1►ALL xxx 6|SECURITY xxx

2|FIRE xxx 7|USER xxx

3|FAULT xxx 8|SYSTEM xxx

4|PRE-ALARM xxx 9|DISABLE xxx

5|EMERGENCY xxx

<event type> xxx/yyy <date> <time>

<location> <status>

<descriptor> <user id>

◄BACK 1:PRINT 2:DELETE 3:GOTO

8.3.1 Menu > Events > Print

PRINT <event type> EVENTS

1►CURRENT ENTRY 3|RANGE BY DATE

2|ALL 4|RANGE BY ENTRY

8.3.2 Menu > Events > Delete

DELETE <event type> EVENTS

1►CURRENT ENTRY 3|RANGE BY DATE

2|ALL 4|RANGE BY ENTRY

8.3.3 Menu > Events > Goto

GOTO <event type> EVENTS

1►MOST RECENT

2|BY DATE

3|BY ENTRY

8.4

Menu > Tools

4

GHI

TOOLS

1

DIRTY DEVICES

1

LOW%

2

MED%

3

HIGH%

2

LOOP STATISTICS

1

L1

2

1

RESET COUNT

L2

TOOLS MENU

1►DIRTY DEVICES

2|LOOP STATISTICS

8.4.1 Menu > Tools > Dirty Devices

The compensation threshold level can be set to the default Low, Medium or High percentage. The selected default Low, Medium or High compensation threshold is displayed, and an asterisk appears next to the current selection where the medium threshold is the default.

Only those devices which have a drift percentage higher than the threshold will be displayed.

If there are no dirty devices on the system found at the selected drift threshold the following screen is presented:

NO DIRTY DEVICES FOUND

AT SELECTED DRIFT THRESHOLD

◄BACK 1:005% 2*040% 3:080%

If devices are found with drift percentage values higher than the selected drift percentage threshold then the following screen is displayed:

Use the

▼▲ arrows to display the dirty devices. The control menu hotkey * can be used for direct access into the control menu for the current device being displayed.

Zzzz Ppp Lll Dddd.s <status>

DRIFT LEVEL: XXX

DIRTY DEVICES XXX OF XXX CONTROL*

◄BACK 1:005% 2*040% 3:080%

8.4.2 Menu > Tools > Loop Statistics

If 2 loops are available, selecting LOOP STATISTICS allows the user to select which loop they would like to view using the loop selection screen followed by the loop statistics menu screen:

This screen shows the number of bad polls and a percentage of bad/good polls from the date and time. “1: RESET COUNT” will reset the bad poll count and display new datum.

Noise level is the average level of noise on the loop. The noise status displayed shall be GOOD,

FAIR or BAD based on the preset thresholds.

BAD POLLS:xxxxxxxx (xx.xx%) <loop no.>

SINCE DD/MM/YYYY HH:MM:SS

LOOP NOISE LEVEL:xxmA - <noise status>

◄BACK 1:RESET COUNT

8.5

5

JKL

Menu > Setup

SETUP

1

DATE AND TIME

1

DATE

2

FORMAT

3

DAYLIGHT SAVE ON

4

TIME

5

FORMAT

2

DAY/NIGHT

1

SUNDAY

3

EARTH MON

2

MONDAY

3

TUESDAY

4

WEDNESDAY

5

THURSDAY

6

FRIDAY

7

SATURDAY

6

SET ALL

7

DISABLE

4

PASSWORDS

1 2

ID1 ID2

This menu is only accessible at access level 3. If the active access level is less than 3 the user will be prompted to enter password before allowing access to this menu.

SETUP MENU

1►DATE AND TIME 3|EARTH MONITORING

2|DAY/NIGHT 4|PASSWORDS

8.5.1 Menu > Setup > Date and Time

DATE AND TIME MENU

1►DATE :01/01/2008 4|TIME :10:05:33

2|FORMAT:DD/MM/YYYY 5|FORMAT:24 HOUR

3|DAYLIGHT SAVE ON

The date format can be changed by selecting 2, the time format can be changed by selecting 5 and the daylight savings mode can be tuned on or off by selecting 3.

8.5.2 Menu > Setup > Date and Time > Date

FORMAT: DD/MM/YYYY

CURRENT: 01/01/2008

NEW: _

▲DEL APPLY►

8.5.2.1 Menu > Setup > Date and Time > Time

CURRENT: 10:05:34

NEW: _

▲DEL APPLY►

8.5.3 Menu > Setup > Day/Night

DAY/NIGHT MENU <disabled status>

1►SUNDAY 6|FRIDAY

2|MONDAY 7|SATURDAY

3|TUESDAY 8|SET ALL

4|WEDNESDAY 9|DISABLE

5|THURSDAY

Day/Night mode can be enabled or disabled by selecting 9. The <disabled status> shall toggle accordingly as this is selected.

8.5.3.1 Menu > Setup > Day/Night > Day

DAY/NIGHT SETTINGS - SUNDAY

CURRENT - DAY: HH:MM NIGHT: HH:MM

NEW - DAY: _ NIGHT: DEL▲

◄BACK APPLY▼ NEXT►

Back will return to day/night menu or previous day if not on first day selected.

Next will proceed to the day/night settings for each of the remaining six days in sequence after which it will return to the day/night menu.

Pressing APPLY will set the CURRENT day/night settings to the new value and clear the new values to allow re-editing.

Cancel returns to the day/night menu on any day.

Selecting “8|SET ALL" from the Day/Night menu shall present the user with a screen similar to that above. The settings applied on this screen will be applied to all days of the week.

8.5.4 Menu > Setup > Earth Monitoring

EARTH MONITORING: ENABLED

-ENSURE EARTH MONITORING LINK IS FITTED-

CHANGE▼

◄BACK APPLY►

Note: LINK instructions

Press CHANGE▼ to toggle between enabled and disabled

8.5.5 Menu > Setup > Password

Selecting the password menu reveals the generic password user ID selection screen followed by the following:

Use ▼arrow to move edit point. Only password IDs 1 and 2 are editable at the panel. All other IDs need to be configured using the PC configuration tool.

ADD/EDIT PASSWORD

ID ►: 01

ACCESS LEVEL : 2 DEL▲

PASSWORD : 2222 SAVE►

8.6

Menu > Programming

6

M N O

PROGRAMMING (*)

ENTER PASSWORD

1

ZONE

2

DEVICE

1

ADD

2

DELETE

2

EDIT

3

PANEL

1

INPUT

2

OUTPUT

1

SUPERVISED O/P

3

LOOP

1

L1

2

RELAY O/P

4

DESCRIPTOR

2

L2

3 4

OPEN COLLECTOR O/P AUXILIARY O/P

4

SOUNDERS

1

GLOBAL

ACTIVATION

2

ZONE

ACTIVATION

5

LEARN OPTIONS

1 2

AUTO LEARN EXTRA DEVICES

1 1

Y E S LEARN

2

LEARN ALL

3

MISMATCHED DEVICES

1

RESOLVE

2

RESOLVE ALL

4

MISSING DEVICES

1

DELETE

2

DELETE ALL

6

VERSION

This menu is only accessible at access level 3. If the active access level is less than 3 the user will be prompted to enter password before allowing access to this menu.

PROGRAMMING MENU

1►ZONE 4|SOUNDERS

2|DEVICE 5|LEARN OPTIONS

3|PANEL 6|VERSION

The programming menu is divided into a series of programming wizards. Each individual programmable attribute will be displayed on each screen of the wizard and navigation and editing options are displayed.

If any changes to the configuration are made during the course of the programming a DO YOU

WANT TO SAVE screen is displayed:

CHANGES MADE

DO YOU WANT TO SAVE?

◄BACK 1:YES

If no changes were made a NO CHANGES MADE splash screen will be displayed for a short period before returning to the menu.

8.6.1 Menu > Programming > Zone

EDIT DESCRIPTOR

<descriptor>_

#CLEAR DEL▲

◄BACK NEXT►

When this is selected the user is presented with the generic zone number selection screen followed by the EDIT DESCRIPTION screen. Use the alpha-numeric keys to key in descriptor characters.

Pressing next (or enter) will update the programming.

For day and night mode, choices are:

INVESTIGATE (Timeout 1 / DAY MODE

ZONE CONFIGURATION: INVESTIGATION

CHANGE▼

◄BACK NEXT►

1. NORMAL (No Timeout)

3. INVESTIGATE (Timeout 1, Timeout 2, MCP Override, Inhibit Sounders, Inhibit Fire Outputs)

4. DEPENDANCY A (Timeout 1)

5. DEPENDANCY B (Timeout 1)

6. DEPENDANCY C (Inhibit Sounders, Inhibit Fire Outputs)

DAY MODE <zone configuration>

EDIT ZONE TIMEOUT 1: 60 (1-180 SECS)

#CLEAR

◄BACK NEXT►

Pressing next (or enter) will update the programming and prompt for respective timeout settings.

Pressing next (or enter) will update the programming and prompt for respective timeout 2 setting.

DAY MODE <zone configuration>

EDIT ZONE TIMEOUT 2: 300 (1-420 SECS)

#CLEAR

◄BACK NEXT►

Pressing next (or enter) will update the programming and prompt for MCP override setting.

DAY MODE <zone configuration>

MCP OVERRIDE: ENABLED

CHANGE▼

◄BACK NEXT►

Press change

▼ to DISABLE. Pressing next ► (or enter) will update the programming and prompt for Inhibit sounders setting.

DAY MODE <zone configuration>

INHIBIT SOUNDERS: ENABLED

CHANGE▼

◄BACK NEXT►

Press change

▼ to DISABLE. Pressing next ► (or enter) will update the programming and prompt for Inhibit fire outputs setting.

DAY MODE <zone configuration>

INHIBIT FIRE OUTPUTS: ENABLED

CHANGE▼

◄BACK NEXT►

Press change

▼ to DISABLE. The screens are then repeated for night mode. Then the user will be prompted to save changes if required.

8.6.2 Menu > Programming > Device

DEVICE MENU

1►ADD

2|DELETE

3|EDIT

The user may choose to Add, Delete or Edit devices. Once selected, the user will be prompted to select the loop and device to which to perform the selected action using the generic point selection screens.

8.6.2.1 Menu > Programming > Device >Add

SELECT DEVICE TYPE: <device type>

CHANGE▼

◄BACK NEXT►

In this wizard the user can scroll

▼ through, (press next►) the desired device type to be added. The user is also prompted to save changes if required.

8.6.2.2 Menu > Programming > Device > Delete

Once selected the device location and type shall be displayed:

Zzzz Ppp Lll Dddd.s <device type>

◄BACK DELETE►

The user shall then be prompted to save changes if required.

8.6.2.3 Menu > Programming > Device > Edit

SELECT DEVICE TYPE: <device type>

CHANGE▼

◄BACK NEXT►

Once the device is selected firstly the device type can be changed:

If the device type is changed the following confirmation screen is presented:

WARNING: SETTINGS WILL BE DEFAULT

EXCEPT ZONE NUMBER AND DESCRIPTOR

PROCEED WITH CHANGE

◄BACK 1:YES

Confirming this will change the device type. As each device type has a different set of configurable attributes only the device descriptor and zone number are common hence all other configurable attributes for the given device are set to their default value when the device type is changed.

EDIT DESCRIPTOR

<descriptor>_

#CLEAR DEL▲

◄BACK NEXT►

Edit the descriptor using the alphanumeric keys. Press NEXT

► to go to the next field.

ENTER ZONE NUMBER: X

#CLEAR DEL▲

◄BACK NEXT►

The zone number may then be changed:

EDIT ACTION TYPE: FIRE

CHANGE▼

◄BACK NEXT►

Press CHANGE

▼ to browse through the available action types. Press NEXT► to go to the next field.

INPUT TYPE: NON-LATCHING

CHANGE▼

◄BACK NEXT►

Press CHANGE

▼ to browse through the available latching state options. Press NEXT► to go to the next field.

EDIT PRE-DELAY: 0 (0-90 seconds)

#CLEAR DEL▲

◄BACK NEXT►

Key-in the new pre-delay value for the selected field. Press NEXT

► to go to the next field.

DAY SENSITIVITY: 100 (80-120%)

#CLEAR DEL▲

◄BACK NEXT►

Press NEXT

► to enter the sensitivity mode of the device. For non Discovery devices the following screens are presented:

NIGHT SENSITIVITY: 100 (80-120%)

#CLEAR DEL▲

◄BACK NEXT►

The fixed alarm and pre-alarm thresholds of the non Discovery devices will be multiplied by this sensitivity percentage for day and night; hence allowing increased (<100%) or reduced (>100%) sensitivity.

DAY SENSITIVITY MODE: 3

#CLEAR DEL▲

◄BACK NEXT►

For Discovery devices the Sensitivity mode setting adjust the analogue value within the detector.

INDICATE PRE-ALARM: ENABLED

CHANGE▼

◄BACK NEXT►

Press NEXT

► to select if the device should indicate a pre-alarm status at the panel.

The user is then prompted to save any changes if they have been made.

8.6.2.4 Menu > Programming > Device > Edit

– Sub Input

EDIT DEVICE TYPE: <device type>

CHANGE▼

◄BACK NEXT►

Once the device is selected firstly the device type can be changed:

WARNING: SETTINGS WILL BE DEFAULT

EXCEPT ZONE NUMBER AND DESCRIPTOR

PROCEED WITH CHANGE

◄BACK 1:YES

If the device type is changed this confirmation screen is displayed:

TYPE: <device type>

1 DEVICE

2►SUB ADDRESS

NEXT►

If the device type has sub-address inputs or outputs this screen is displayed next:

SELECT SUB ADDRESS: 1

<selected sub address descriptor>

1►I/P1 2:I/P2 3:I/P3 4:O/P1 5:O/P2

6:O/P3

Select 2 SUB ADDRESS and pressing NEXT

► displays the generic sub-address selection screen:

EDIT DESCRIPTOR

LOOP 1 DEVICE 1 INPUT 1_

#CLEAR DEL▲

◄BACK NEXT►

Select one of the sub inputs and press enter to edit the input configuration.

ENTER ZONE NUMBER: 1_

◄BACK NEXT►

Press NEXT

► to go to the next field.

EDIT ACTION TYPE: FIRE

CHANGE▼

◄BACK NEXT►

Press NEXT

► to go to the next field.

INPUT TYPE: NON-LATCHING

CHANGE▼

◄BACK NEXT►

Press NEXT

► to go to the next field.

EDIT CONTACT STATE: NORMALLY OPEN

CHANGE▼

◄BACK NEXT►

SUPERVISED: ENABLED

CHANGE▼

◄BACK NEXT►

Press NEXT

► to go to the next field.

EDIT PRE-DELAY: 0 (0-90 seconds)

#CLEAR DEL▲

◄BACK NEXT►

Press NEXT

► to go to the next field.

The user is then prompted to save any changes that may have been made.

8.6.2.5 Menu > Programming > Device > Edit

– Sub Output

EDIT DEVICE TYPE: <device type>

CHANGE▼

◄BACK NEXT►

Once the device is selected firstly the device type can be changed:

WARNING: SETTINGS WILL BE DEFAULT

EXCEPT ZONE NUMBER AND DESCRIPTOR

PROCEED WITH CHANGE

◄BACK 1:YES

If the device type is changed this confirmation screen is displayed:

TYPE: <device type>

1 DEVICE

2►SUB ADDRESS

NEXT►

If the device type has sub-address inputs or outputs the following screen is displayed next:

SELECT SUB ADDRESS: 4

<selected sub address descriptor>

1:I/P1 2:I/P2 3:I/P3 4►O/P1 5:O/P2

6:O/P3

Select 2 SUB ADDRESS and pressing NEXT

► displays the generic sub-address selection screen:

EDIT DESCRIPTOR

LOOP 1 DEVICE 1 OUTPUT 1_

#CLEAR DEL▲

◄BACK NEXT►

Select one of the sub outputs and press enter to edit the output configuration.

ENTER ZONE NUMBER: 1_

◄BACK NEXT►

Press NEXT

► to go to the next field.

FIXED ACTIVATION: NONE

CHANGE▼

◄BACK NEXT►

Press NEXT

► to go to the next field.

GLOBAL ACTION: <action type>

ENABLED

CHANGE▼

◄BACK NEXT►

Press NEXT

► to go to the next field.

ZONE ACTION: <action type>

ENABLED

CHANGE▼

◄BACK NEXT►

Press CHANGE

▼ to enable or disable the displayed global action. Press NEXT► to go to the next global action setting.

NORMALLY ENERGISED: DISABLED

CHANGE▼

◄BACK NEXT►

Press CHANGE

▼ to enable or disable the displayed zone action. Press NEXT► to go to the next zone action setting.

RESPOND TO ALERT/EVAC: ENABLED

CHANGE▼

◄BACK NEXT►

Press NEXT

► to go to the next field.

RESPOND TO CLASS CHANGE: ENABLED

CHANGE▼

◄BACK NEXT►

Press NEXT

► to go to the next field.

EDIT POST-DELAY: 0 (0-999 seconds)

#CLEAR

◄BACK NEXT►

Press NEXT

► to go to the next field.

The user is then prompted to save any changes if they have been made.

8.6.3 Menu > Programming > Panel

PANEL MENU

1►INPUT 3|LOOP

2|OUTPUT 4|DESCRIPTOR

Panel Inputs, Outputs, Loops and normal screen descriptors can be programmed from this menu.

8.6.3.1 Menu > Programming > Panel > Input

SELECT INPUT: 1 PANEL INPUT

<input descriptor>

►I/P1 I/P2 I/P3 I/P4

The user may select 1 of 4 panel inputs.

EDIT DESCRIPTOR

DIGITAL INPUT 1_

#CLEAR DEL▲

◄BACK NEXT►

Select desired input and press enter to edit it configuration settings.

ENTER ZONE NUMBER: 1_

#CLEAR DEL▲

◄BACK NEXT►

Press NEXT

► to go to the next field.

EDIT ACTION TYPE: FIRE

CHANGE▼

◄BACK NEXT►

Press NEXT

► to go to the next field.

INPUT TYPE: NON-LATCHING

CHANGE▼

◄BACK NEXT►

Press NEXT

► to go to the next field.

EDIT CONTACT STATE: NORMALLY OPEN

CHANGE▼

◄BACK NEXT►

Press NEXT

► to go to the next field.

SUPERVISED: ENABLED

CHANGE▼

◄BACK NEXT►

Press NEXT

► to go to the next field.

EDIT PRE-DELAY: 0 (0-90 seconds)

#CLEAR DEL▲

◄BACK NEXT►

The user shall then be prompted to save any changes if they have been made.

8.6.3.2 Menu > Programming > Panel > Output

PANEL OUTPUT MENU

1►SUPERVISED O/P 3|OPEN COLLECTOR O/P

2|RELAY O/P 4|AUXILIARY O/P

The user may select between the four types of panel outputs.

SELECT OUTPUT: X <output type>

<output descriptor>

►O/P1 O/P2 O/P3 O/P4

There are 4 Supervised Outputs, 3 Relay Outputs, 2 Open Collector Outputs and 2 Auxiliary Outputs to choose from. Depending on the output type selected, the number of available outputs shall be displayed on the generic output point selection this screen

Press enter to edit the selected output configuration settings.

EDIT DESCRIPTOR

<output descriptor>_

#CLEAR DEL▲

◄BACK NEXT►

Press NEXT

► to go to the next field

ENTER ZONE NUMBER: 1_

#CLEAR DEL▲

◄BACK NEXT►

Press NEXT

► to go to the next field.

FIXED ACTIVATION: NONE

CHANGE▼

◄BACK NEXT►

Press NEXT

► to go to the next field

OUTPUT TYPE: SOUNDER

CHANGE▼

◄BACK NEXT►

Press CHANGE

▼ to enable or disable the displayed global action.

GLOBAL ACTION: <action type>

ENABLED

CHANGE▼

◄BACK NEXT►

Press NEXT

► to go to the next field.

Press CHANGE

▼ to enable or disable the displayed zone action.

ZONE ACTION: <action type>

ENABLED

CHANGE▼

◄BACK NEXT►

Press NEXT

► to go to the next zone action setting.

Press CHANGE

▼ to enable or disable the displayed zone action.

NORMALLY ENERGISED: DISABLED

CHANGE▼

◄BACK NEXT►

Press NEXT

► to go to the next field.

Press CHANGE

▼ to enable or disable the displayed zone action.

SILENCEABLE: ENABLED

CHANGE▼

◄BACK NEXT►

Press NEXT

► to go to the next field.

RESPOND TO ALERT/EVAC: ENABLED

CHANGE▼

◄BACK NEXT►

Press NEXT

► to go to the next field.

RESPOND TO CLASS CHANGE: ENABLED

CHANGE▼

◄BACK NEXT►

Press NEXT

► to go to the next field.

The user is then prompted to save any changes that may have been made.

EDIT POST-DELAY: 0 (0-999 seconds)

#CLEAR

◄BACK NEXT►

The user is then prompted to save any changes that may have been made.

8.6.3.3 Menu > Programming > Panel > Loop

SELECT LOOP: X

<selected loop descriptor>

►L1 L2

If there is more then one loop the user is prompted to select the loop using the generic loop selection screen.

EDIT DESCRIPTOR

LOOP 1_

#CLEAR DEL▲

◄BACK NEXT►

Press enter to edit the selected Loop configuration settings.

LOOP X TERMINATION: SINGLE-ENDED

CHANGE▼

◄BACK NEXT►

Press NEXT

► to go to the next field.

The user is then prompted to save any changes that may have been made.

8.6.3.4 Menu > Programming > Panel > Descriptor

EDIT CUSTOM BANNER 1

AMPAC TECHNOLOGIES PTY. LTD._

#CLEAR DEL▲

◄BACK NEXT►

The user may modify the two descriptors displayed on the normal screen

EDIT CUSTOM BANNER 2

LOOPSENSE (C) 2008_

#CLEAR DEL▲

◄BACK NEXT►

Press NEXT

► to go to the next descriptor.

The user is then prompted to save any changes that may have been made.

8.6.4 Menu > Programming > Sounders

SOUNDER MENU

1►GLOBAL ACTIVATION

2|ZONE ACTIVATION

This menu allows programming of the Zone and Global activation settings for sounders.

8.6.4.1 Menu > Programming > Sounders > Global Activation

GLOBAL <action type>

ACTIVATION MODE: EVACUATE

CHANGE▼

◄BACK NEXT►

The activation mode for each Global action type can be selected.

The activation mode choices are:

 EVACUATE

 ALERT

 ALERT TIMEOUT EVACUATE

 DELAYED

GLOBAL <action type>

ACTIVATION DELAY: 30 (0-999 SEC)

#CLEAR DEL▲

◄BACK NEXT►

The activation mode screens are repeated for all action types in which the delays can be edited

The user is then prompted to save any changes that may have been made.

8.6.4.2 Menu > Programming > Sounders > Zone Activation

SELECT ZONE: XXX

<selected zone descriptor>

►Z1 Z2 Z3 Z4 Z5

Z6 Z7 Z8 Z9 Z10

Z11 Z12 Z13 Z14 Z15

Z16 Z17 Z18 Z19 Z20

Z21 Z22 Z23 Z24 Z25

Z26 Z27 Z28 Z29 Z30

The user is first prompted to select the Zone number to be configured.

Press enter to continue.

The activation mode for each Zone action type can then be selected.

ZONE <action type>

ACTIVATION MODE: EVACUATE

CHANGE▼

◄BACK NEXT►

The activation mode choices are:

 EVACUATE

 ALERT

 ALERT TIMEOUT EVACUATE

 DELAYED

ZONE <action type>

ACTIVATION DELAY: 30 (0-999 SEC)

#CLEAR DEL▲

◄BACK NEXT►

The activation mode screens are repeated for all action types in which the delays can be edited.

The user is then prompted to save any changes that may have been made.

8.6.5 Menu > Programming > Learn Options

LEARN OPTIONS MENU

1►AUTO LEARN 3|MISMATCHED DEVICES

2|EXTRA DEVICES 4|MISSING DEVICES

Auto Learn can be used to learn all Loops, Loop Devices, Panel Inputs and outputs connected to the system and store the default configuration for all these points

Mismatched Devices is used to resolve any detected loop devices that do not match the configuration

Extra Devices is used to learn any newly detected loop devices that do not exist in the configuration

Missing Devices is used to remove any device that exist in the configuration but are removed from physical connection to the loop

8.6.5.1 Menu > Programming > Learn Options > Auto Learn

AUTO LEARN

CONFIGURATION WILL BE CHANGED

ARE YOU SURE?

◄BACK 1:YES

Selecting Auto Learn firstly prompts for confirmation.

Select 1 to confirm.

While the Auto Learn sequence is initialising all system functions cease, and the panel is prepared for Auto Learn.

AUTO LEARN

INITIALISING PLEASE WAIT

◄BACK NEXT►

The Auto Learn in Progress screen is displayed while all devices are learnt.

Upon completion the panel will restart with the newly learnt configuration.

Note: If an Auto Learn is executed the Auto-Learn Defaults for devices is outlined in section 11

Compatible Devices

8.6.5.2 Menu > Programming > Learn Options > Extra Device

Zzzz Ppp Lll Dddd.s <status>

TYPE: <detected type>

EXTRA DEVICES XXX OF XXX

◄BACK 1:LEARN 2:LEARN ALL

If extra devices are detected on the system, this screen is displayed. Here the user may select to learn the individual extra device currently being displayed or all extra devices detected.

If no extra devices were det ected the “NO EXTRA DEVICES” screen is briefly displayed before returning to the previous menu.

8.6.5.3 Menu > Programming > Learn Options > Mismatched Devices

Zzzz Ppp Lll Dddd.s <detected type>

CONFIGURED TYPE: <device type>

MISMATCHED DEVICES XXX OF XXX

◄BACK 1:RESOLVE 2:RESOLVE ALL

If mismatched devices are detected on the system, this screen is displayed. Here the user may select to resolve the individual device mismatch currently being displayed or all mismatched devices detected.

If no mismatch ed devices are detected the “NO MISMATCHED DEVICES” screen is displayed then returns to the previous menu.

8.6.5.4 Menu > Programming > Learn Options > Missing Devices

Zzzz Ppp Ll Dddd.s <status>

CONFIGURED TYPE: <device type>

MISSING DEVICES XXX OF XXX

◄BACK 1:DELETE 2:DELETE ALL

Missing devices screen. Here the user may select to delete the individual device from the configuration currently being displayed or all missing devices.

If no missing devices were detected the “NO MISSING DEVICES” screen is displayed for a short period before returning to the previous menu.

8.6.6 Menu > Programming > Version

SITE CONFIGURATION DATA

LAST MODIFIED: <date> <time>

VERSION: <major>.<minor>

◄BACK

The date and time is updated by the PC configuration tool upon alteration of the configuration information when saving and is also updated at the panel when configuration changes are made via programming.

The Configuration Major Version is incremented by the PC upon alteration of the configuration information when saving. When this occurs the Configuration Minor Version shall be cleared to zero.

If the Major or Minor version reaches 65535 it shall remain at this value unless reset by user intervention using the PC tool. The Configuration Minor Version shall be incremented upon alteration of the configuration at the panel via programming. Also, the major version shall default to 1 and minor version default to 0 upon auto learn at the panel

9. Event Logging

Events are logged into one of eight event type categories. Individual storage is pre-allocated for each event type amounting to a total of 1000 events:

Event Type

Fire

Fault

Disable

Pre-Alarm

Emergency

Security

User

System

Maximum Capacity

100

200

100

100

100

100

100

200

If an event exceeds the maximum capacity for that type the oldest event will be deleted allowing the most recent event to be stored.

Events that are logged may contain the following attributes:

 Event Type

 Event Status

 Date/Time of occurrence

 Event Origin

 Active Password ID (stored with event origin)

 Checksum

The system event log contains system input action type events as well as the following system events:

 Loop Test with password ID

 Walk Test with password ID

 Lamp Test with password ID

 Override key press with password ID

 Silence/Resound key press with password ID

 Reset key press with password ID

 Evacuate key press with password ID

 Access Level change with password ID

The fault event log contains input action type fault events as well as all reported faults within the

FACP. The disable event log contains all reported system disables. All other event types are only logged according to their assigned input action type events.

Note: The Transparent action type is not logged.

The events are viewed collectively or by individual type. The events can be printed or erased by individual entry, range by date/time, range by entry number, and all by entry number. Each event type can also be disabled or enabled.

All events can be uploaded using the PC configuration software which will format the event record to be viewable using Microsoft Excel or a standard text editor.

10. Complete Menu Structure

03h

03h

03h

103h

103h

10Bh

10Bh

0Eh

0Eh

0Eh

0Eh

106h

106h

31Dh

06h

06h

06h

06h

06h

11. Compatible Devices

Note: If an Auto Learn is executed the Auto-Learn Defaults for devices are also listed below

AMPAC

Type

Code

Auto

Learn

Default

Device type Displayed type (19 Chars)

Type

Desc

Optical

105h

11Dh

11Dh

11Dh

15h

1Dh

1Dh

31Dh

05h

05h

05h

05h

05h

05h

0Dh

105h

XP95 Optical

XP95 Optical with base sounder

S90 Optical

Xplorer Optical

Xplorer Optical with base sounder

XP95 Beam

XP95 Reflective beam

Discovery Optical

XP95 PHOTO

XP95 PHOTO + SNDR

S90 PHOTO

XPLORER PHOTO

XPLR PHOTO + SNDR

XP95 BEAM

XP95 REFLECT BEAM

DISC PHOTO

Discovery Optical with base sounder

Discovery Multisensor

DISC PHOTO + SNDR

DISC MULTISENSOR

Discovery Multisensor with base sounder DISC MULTI + SNDR

Discovery 0.5% Multisensor DISC 0.5% MULTI

XP95 Flame

XP95 Multisensor

XP95 Multisensor with base sounder

Enhanced Discovery Multisensor

XP95 FLAME

XP95 MULTISENSOR

XP95 MULTI + SNDR

EDSC MULTISENSOR

Enhanced Discovery Multi + base sounder EDSC MULTI + SNDR

Heat Detectors

XP95 Heat

XP95 Heat with base sounder

S90 Heat

Xplorer Heat

Xplorer Heat with base sounder

XP95 Hi temp

XP95 Hi temp with base sounder

Xplorer Hi temp

Xplorer Hi temp with base sounder

Discovery Heat

Discovery Heat with base sounder

Ionisation

XP95 HEAT

XP95 HEAT + SNDR

S90 HEAT

XPLORER HEAT

XPLR HEAT + SNDR

XP95 HI HEAT

XP95 HI HEAT + SNDR

XPLORER HI HEAT

XPLR HI HEAT + SNDR

DISC HEAT

DISC HEAT + SNDR

PHOTO

PHOTO

PHOTO

PHOTO

PHOTO

PHOTO

BEAM

PHOTO

PHOTO

MULTI

MULTI

0.5%OB

FLAME

MULTI

MULTI

MULTI

MULTI

HEAT

HEAT

HEAT

HEAT

HEAT

HHEAT

HHEAT

HHEAT

HHEAT

HEAT

HEAT

XP95 Ion

XP95 Ion with base sounder

S90 Ion

Discovery Ion

Discovery Ion with base sounder

Discovery Carbon Monoxide

Discovery Carbon Monoxide with base sndr

Manual Call Points

XP95 ION

XP95 ION + SNDR

S90 ION

DISC ION

DISC ION + SNDR

DISC CO

DISC CO + SNDR

ION

ION

ION

ION

ION

CO

CO

111h

02h

02h

02h

01h

01h

01h

01h

01h

07h

11Fh

1Fh

1Fh

1Fh

01h

02h

02h

02h

02h

02h

02h

1Ch

08h

10h

04h

04h

0Ch

0Ch

0Ch

S90 MCP

Discovery MCP

XP95 MCP

XP95 Mini switch monitor with interrupt

S90 MCP

DISC MCP

XP95 MCP

XP95 MINI SW + INT

MCP

MCP

MCP

MCP

Xplorer MCP

Sounders

XPLORER MCP

XP95 SOUNDER

MCP

SNDR XP95 sounder / sounder control unit

XP95 integrated base sounder

XP95 Intelligent base sounder

XP95 sounder beacon base

XP95 loop powered beacon

S90 sounder control unit

Discovery sounder beacon base/open area

I/O Units

XP95 input / output module XP95 I/O

XP95 three channel input / output module XP95 3I/O

XP95 output module

XP95 mains switching input / output module

S90 single channel I/O unit

S90 3 channel I/O unit

S90 3 channel analogue I/O unit

S90 switch monitor unit

Xplorer output module

XP95 INTGR BSE SNDR SNDR

XP95 INTEL BSE SNDR SNDR

XP95 SND BEACN BSE

XP95 LOOP PWR BEACN

S90 SCU

DISC SOUNDER BEACN

XP95 OUTPUT

XP95 MAINS I/O

S90 SINGLE I/O

S90 3I/O

S90 3I/O + ANALOGUE

S90 SWITCH

XPLORER OUTPUT

SNDR

SNDR

SNDR

SNDR

I/O

I/O

I/O

I/O

I/O

I/O

I/O

I/O

I/O

Zone Monitors

XP95 zone monitor

S90 zone monitor

XP95 switch monitor

XP95 mini switch monitor

XP95 switch monitor plus

FastSense XP95 APIC

User Defined

XP95 AM

XP95 AAF

XP95 ZONE MONITOR

S90 ZONE MONITOR

XP95 SWITCH

XP95 MINI SWITCH

XP95 SWITCH PLUS

XP95 FASTSENSE

XP95 AM

XP95 AAF

CONV

CONV

SWITCH

SWITCH

SWITCH

FSENSE

AM

AAF

12. Certification Information

The LoopSense is designed and manufactured by:

AMPAC TECHNOLOGIES PTY LTD

7 Ledgar Rd

Balcatta

WA 6021

Western Australia

PH: 61-8-9242 3333

FAX: 61-8-9242 3334

Manufactured to:

Certificate of Compliance Number:

Equipment Serial Number:

Date of Manufacture:

13. Glossary of Terms

ACKD : ACKNOWLEDGED

AH:

ALM :

COM :

CN :

C/O :

CPU :

EOL :

FACP :

FLT :

GND :

I/O :

LCD :

LED :

MCP :

N/C :

N/O :

PCB :

P/S :

TB :

AMP HOUR

ALARM

RELAY COMMON CONTACT (WIPER)

CONNECTOR

CHANGE OVER CONTACTS

COMMON PROCESSOR UNIT

END OF LINE

FIRE ALARM CONTROL PANEL

FAULT

GROUND (0 VOLTS) NOT EARTH

INPUT/OUTPUT

LIQUID CRYSTAL DISPLAY

LIGHT EMITTING DIODE

MANUAL CALL POINT

NORMALLY CLOSED RELAY CONTACTS

NORMALLY OPEN RELAY CONTACTS

PRINTED CIRCUIT BOARDS

POWER SUPPLY

TERMINAL BLOCK

14

15

16

17

18

19

20

10

11

12

13

Addr

1

2

3

4

5

6

7

8

9

21

22

23

24

25

14. Address Setting

BINARY ADDRESS SETTING (APOLLO)

SERIES XP95 - ADDRESS DATA

DIL SWITCH: ON = 1 OFF = 0 ADDRESS TAG FOR DETECTORS (I/O DEVICES)

DIL switch setting DIL switch setting DIL switch setting DIL switch setting DIL switch setting

0101000

1101000

0011000

1011000

0111000

1111000

0000100

1000100

0100100

1100100

0010100

1234567

1000000

0100000

1100000

0010000

1010000

0110000

1110000

0001000

1001000

1010100

0110100

1110100

0001100

1001100

39

40

41

42

43

44

45

35

36

37

38

Addr

26

27

28

29

30

31

32

33

34

46

47

48

49

50

1100010

0010010

1010010

0110010

1110010

0001010

1001010

0101010

1101010

0011010

1011010

1234567

0101100

1101100

0011100

1011100

0111100

1111100

0000010

1000010

0100010

0111010

1111010

0000110

1000110

0100110

64

65

66

67

68

69

70

60

61

62

63

Addr

51

52

53

54

55

56

57

58

59

71

72

73

74

75

0011110

1011110

0111110

1111110

0000001

1000001

0100001

1100001

0010001

1010001

0110001

1234567

1100110

0010110

1010110

0110110

1110110

0001110

1001110

0101110

1101110

1110001

0001001

1001001

0101001

1101001

89

90

91

92

93

94

95

85

86

87

88

Addr

76

77

78

79

80

81

82

83

84

96

97

98

99

100

1010101

0110101

1110101

0001101

1001101

0101101

1101101

0011101

1011101

0111101

1111101

1234567

0011001

1011001

0111001

1111001

0000101

1000101

0100101

1100101

0010101

0000011

1000011

0100011

1100011

0010011

110

111

112

113

114

115

116

117

118

119

120

Addr

101

102

103

104

105

106

107

108

109

121

122

123

124

125

126

0111011

1111011

0000111

1000111

0100111

1100111

0010111

1010111

0110111

1110111

0001111

1234567

1010011

0110011

1110011

0001011

1001011

0101011

1101011

0011011

1011011

1001111

0101111

1101111

0011111

1011111

0111111

O N

2

8 3 2

11

11

4

1 6 6 4

1 2 3 4 5 6 7 8

1

Figure 5: Switch and Xpert Card set to 11

UNCONTROLLED DOCUMENT

NOTE: Due t o AMPAC’s commitment to continuous improvement specifications may change without notice.

advertisement

Key Features

  • Multiple levels of access for enhanced security
  • Supports a comprehensive range of input and output devices for flexibility
  • Allows remote silencing and resetting for convenience
  • Provides diagnostic tools for simplified troubleshooting
  • User-friendly interface for ease of operation

Related manuals

Frequently Answers and Questions

How do I silence the buzzer on the Ampac LoopSense AS?
To silence the buzzer, press the SILENCE button.
How do I reset the Ampac LoopSense AS?
To reset the panel, press the RESET button.
How do I disable a zone or device on the Ampac LoopSense AS?
To disable a zone or device, press the CONTROL button, then select the ZONE or DEVICE menu. Select the zone or device you want to disable, and then press the DISABLE button.