Front Panel Key Functionality. Murphy TTD Series Configurable
Pubblicità
Pubblicità
Front Panel Key Functionality
The operator can interface with the TTD Annunciator in one of two ways. One is via the Front
Panel keypad. The second way an operator can interface is with the Murphy
Mconfig™ software. This provides the user with a Template displaying the TTD Annunciator setup and status by reading the Modbus registers. Set-up selections can be made and the configuration saved to file for future reference. The software is free and can be downloaded from www.fwmurphy.com
TTD Keypad Features
NOTE: Because the keys have more than one function depending on the operational mode the system is in at the time, the following TTD Keypad
Functionality blocks indicate the keypad action seen if that key is pressed.
The LOW BATT icon can show in any mode if the battery charge is low.
Section 50
2016-02-22
- 15 -
00-02-0697
Shutdown Mode
SHUTDOWN indicates the TTD identified a fault condition and alerts the operator with cause of shutdown code.
The current condition on the display indicates the SHUTDOWN icon is on.
Key
Read Hours
Setup/Enter
Up Arrow
Down Arrow
Function
(B) Shows the operation hours for the displayed History record*.
Press and hold the key for 5 seconds to access the Setup Menu: The model number displays (C) and then the
SETUP icon displays (D).
Shows the previous History record
(E)*.
Shows the next History record*.
Reset
Press [RESET] to start the Run Mode.
*When not in the Setup Mode, History contains records for last 10 shutdowns and last 4 alarms.
Section 50
2016-02-22
- 16 -
00-02-0697
Run Mode
The condition on the display indicates the RUN and RPM icons are shown and the ALARM icon may be on.
Section 50
2016-02-22
Key
Read Hours
Setup/Enter
Timer 0 / Up Arrow
Test / Down Arrow
Reset
Stop
Function
(G) Shows the current operation hours. RUN icon indicates the hour meter is in increment mode.
Press and hold the key for 5 seconds to access the Setup
Menu: The model number displays and then the SETUP icon displays.
Press [TIMER 0] to clear the active displayed timer. For example: B1, B2 and other timers. Also used for exiting or ending test mode operation.
Press [TEST] to enable the Test
Mode timer. Also used for extending or resetting the test timer. (H)
Press [RESET] to reset the active displayed timer.
DO NOT use to reset Test Mode Timer. This reset button will reset all class lockout timers.
Press [STOP] to begin the Shutdown sequence.
- 17 -
00-02-0697
Setup Mode
– Menus
The condition on the display indicates the RUN and SHUTDOWN icons may be on.
Key
Setup/Enter
Up Arrow
Down Arrow
Reset/ESC
Stop
Function
If the unit is in SETUP 0, pressing [ENTER] exits the unit from the
Setup Mode. If the unit is in any other Setup, pressing [ENTER] accesses the submenu for that Setup.
Press [UP ARROW] to navigate to the next menu.
Press [DOWN ARROW] to navigate to the previous menu.
Press [ESC] to exit from the Setup Menu and return to the operational display for the current mode.
If the system is in Run Mode, pressing and holding the [STOP] key for 2 seconds will begin the Shut-down sequence.
Setup Mode
– Edit Settings
The condition on the display indicates the SETUP icon shows, and either the RUN or
SHUTDOWN icons may show.
Key
Setup/Enter
Up Arrow
Down Arrow
Reset/ESC
Stop
Function
Press [ENTER] to exit or advance a Setup menu and save changes.
Press [UP ARROW] to increment the value to the maximum range.
Holding the key accelerates the incrementing action.
Press [DOWN ARROW] to decrement the value to the minimum range.
Holding the key accelerates the decrementing action.
Press [ESC] to exit or advance the Setup Menu without saving your changes.
If the system is in Run Mode, pressing and holding the [STOP] key for 2 seconds will begin the Shut-down sequence.
NOTE: Editing of selected setpoints can be accomplished during run mode. Please note these changes will NOT take effect until unit has returned to a Shutdown state. During the Shutdown state, these settings are written to the EEProm, which stores settings for operation. This
EEProm CANNOT be written to during a Run operation.
Section 50
2016-02-22
- 18 -
00-02-0697