3-2 Operation Method
3-2 Operation Method
To operate the Inverter, two commands are required including a RUN command and frequency reference. Take note that the Inverter does not operate if only one of these commands is issued, such as when a RUN command is issued but not a frequency reference (0 Hz setting), or a frequency reference is issued but not a RUN command.
3
RUN Command/Frequency Reference Input
Command/Reference Input From the Digital Operator
Operates the Inverter via the key operation of the standard Digital Operator or optional Remote
Operator.
Setting
Parameter
No.
Function name
A001
A002
F001
F004
Frequency
Reference
Selection 1
RUN Command
Selection 1
Output
Frequency
Setting
RUN Direction
Selection
Data
02 (Digital Operator)
02 (Digital Operator)
0.0 to Max. frequency
00 (Forward)
01 (Reverse)
Default value
02
02
6.00
00
Note
The RUN command enabled LED indicator is lit.
Parameters cannot be changed while the Inverter is operating.
Change the following parameters, if necessary:
Parameter
No.
Function name
F002
F003
Acceleration
Time Setting 1
Deceleration
Time Setting 1
Data
0.01 to 99.99 s 100.0 to 999.9 s
1,000. to 3,600. s
0.01 to 3,600 s 100.0 to 999.9
1,000. to 3,600. s
Default value
10.00 s
10.00 s
Lit when the RUN key is pressed to start operation.
Lit when the frequency data is displayed.
The RUN key is enabled and the RUN command enabled LED indicator is lit when A002 is set to 02.
5k0.0k0
3-7
Operation
Refer to "Test Run" on page 3-10.
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
3-2 Operation Method
Command/Reference Input From the Control Circuit Terminal Block
Operates the Inverter by connecting the external signals (frequency setting volume, switch, etc.) to the control circuit terminal block.
<Setting the Forward/Reverse Direction Using the FW/RV Input Terminal and Setting the Frequency Using the Frequency Volume>
Setting
Parameter
No.
Function name
A001
A002
C001
C002
Frequency
Reference
Selection 1
RUN Command
Selection 1
Multi-function
Input 1 Selection
Multi-function
Input 2 Selection
Data
01 (Control circuit terminal block)
01 (Control circuit terminal block)
00 (FW: Forward)
01 (RV: Reverse)
Default value
02
Note
02
00(FW)
01(RV)
If other input terminal is used, the parameter number becomes different.
If other input terminal is used, the parameter number becomes different.
3
Change the following parameters, if necessary:
Parameter
No.
F002
F003
Function name
Acceleration
Time Setting 1
Deceleration
Time Setting 1
Data
Default value
10.00 s 0.01 to 99.99 s 100.0 to 999.9 s
1,000. to 3,600. s
0.01 to 99.99 s 100.0 to 999.9 s
1,000. to 3,600. s
10.00 s
Wiring the Control Circuit Terminal Block
F/R setting
STP setting
STA setting
10 VDC
24 VDC
FS
FV
FI SC S3/GS1 S2 S1 SC PSC P24
Frequency setting volume
*1
*2
Reverse input
Forward input
*1 Allocate 16: FV/FI (Analog input switch) to a multi-function input to use as the voltage setting. If terminal
FV/FI is not allocated, the frequency reference becomes the sum of voltage input (FV) and current input
(FI). To use only one of voltage or current, therefore, short the other analog input to the SC terminal.
*2 This wiring diagram shows an example of using the built-in power supply of the Inverter. If an external
power supply is used, refer to "Connection to Programmable Controller (PLC)" on page 2-22.
Operation
Refer to "Test Run" on page 3-10.
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
3-8
3-2 Operation Method
3
3-9
<Running/Stopping the Inverter via 3-wire Input and Setting the Frequency Using an
Analog Current Signal>
Setting
Parameter
No.
Function name Data
Default value
Note
A001
A002
C001
C002
C003
Frequency Reference
Selection 1
RUN Command
Selection 1
Multi-function
Input 1 Selection
Multi-function
Input 2 Selection
Multi-function
Input 3 Selection
01 (Control circuit terminal block)
01 (Control circuit terminal block)
20 (STA: 3-wire start)*
21 (STP: 3-wire stop)
22 (F/R: 3-wire forward/reverse)
*
*
02
02
00 (FW)
01 (RW)
18 (RS)
If other input terminal is used, the parameter number becomes different.
If other input terminal is used, the parameter number becomes different.
If other input terminal is used, the parameter number becomes different.
Change the following parameters, if necessary:
Parameter
No.
Function name
F002
F003
Acceleration
Time Setting 1
Deceleration
Time Setting 1
Data
Default value
10.00 s 0.01 to 99.99 s 100.0 to 999.9 s
1,000. to 3,600. s
0.01 to 99.99 s 100.0 to 999.9 s
1,000. to 3,600. s
10.00 s
Wiring the Control Circuit Terminal Block
F/R setting
STP setting
STA setting
10 VDC
24 VDC
FS
FV
*1
FI SC S3/GS1 S2 S1 SC PSC P24
*2
Frequency setting
(4 to 20 mA)
Forward/ reverse
Stop
(NC contact)
Operate
(NO contact)
*1 Allocate 16: FV/FI (Analog input switch) to a multi-function input to use as the current setting. If terminal
FV/FI is not allocated, the frequency reference becomes the sum of voltage input (FV) and current input
(FI). To use only one of voltage and current, therefore, short the other analog input to the SC terminal.
*2 This wiring diagram shows an example of using the built-in power supply of the Inverter. If an external
power supply is used, refer to "Connection to Programmable Controller (PLC)" on page 2-22.
Operation
Refer to "Test Run" on page 3-10.
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)