5-3 Input/Output Terminals
5-3 Input/Output Terminals
The following explains the Inverter's input/output signals.
5
Multi-function Input Selection
The following functions can be allocated to any of multi-function input terminals S1 to S7/EB to operate each function that has been set.
Terminals S1 to S7/EB correspond to C001 to C007.
You can select NO- or NC-contact input for each multi-function input.
The same function cannot be allocated to multiple multi-function input terminals. If the same function was allocated to multiple functions by mistake, the terminal to which the function was allocated last becomes effective. no is allocated to all terminals to which the function was allocated earlier, and their functions are disabled.
After allocating functions to terminals S1 to to S7/EB, make sure that the function settings have been stored.
Parameter
No.
C001 to C007
14
15
16
18
19
09
11
12
13
Data
03
04
05
06
00
01
02
07
08
Description Reference item Page
FW: Forward
RV: Reverse
CF1: Multi-step speed 1
RUN Command Selection
CF2: Multi-step speed 2
CF3: Multi-step speed 3
CF4: Multi-step speed 4
JG: Jogging
Multi-step Speed Operation
Function (Binary)
Jogging Operation
DB: External DC injection braking External DC Injection Braking
SET: Motor 2 Control Motor 2 Control Function
2CH: 2-step acceleration/ deceleration
2-step Acceleration/deceleration
Function
FRS: Free-run stop
EXT: External trip
USP: USP function
CS: Commercial switch
SFT: Soft lock
FV/FI: Analog input switch
RS: Reset
TH: PTC thermistor thermal protection
Free-run Stop
External Trip
Power Recovery Restart
Prevention Function
Commercial Switching
Soft Lock
Analog Input
Reset
Thermistor Trip Function
5-22
5-64
5-59
5-135
5-54
5-66
5-103
5-120
5-105
5-79
5-84
5-37
5-100
5-120
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
5-29
5-3 Input/Output Terminals
Parameter
No.
C001 to C007
59
60
61
62
65
53
56
57
58
40
41
42
44
46
34
35
36
37
38
29
31
32
33
39
47
50
51
52
Data
20
21
22
23
24
27
28
Description Reference item Page
STA: 3-wire start
STP: 3-wire stop
F/R: 3-wire forward/reverse
PID: PID disabled
PIDC: PID integral reset
UP: UP/DWN function accelerated
DWN: UP/DWN function decelerated
UDC: UP/DWN function data clear
OPE: Forced operator
SF1: Multi-step speed bit 1
SF2: Multi-step speed bit 2
SF3; Multi-step speed bit 3
SF4: Multi-step speed bit 4
SF5: Multi-step speed bit 5
SF6: Multi-step speed bit 6
SF7: Multi-step speed bit 7
OLR: Overload limit switching
3-wire Input Function
PID Function
Remote Operation Function
Forced Digital Operator Function
5-85
Multi-step Speed Operation
Function (Bit)
Overload Limit/Overload
Warning
5-56
5-73
5-71
5-65
5-114
TL: Torque limit enabled/disabled
TRQ1: Torque limit switching 1
TRQ2: Torque limit switching 2
BOK: Brake confirmation
LAC: LAD cancel
PCLR: Position deviation clear
ADD: Frequency addition
F-TM: Forced terminal block
ATR: Torque reference input permission
KHC: Integrated power clear
Torque Limit Function
Brake Control Function
Acceleration/Deceleration
Function
5-153
5-142
5-24
Simple Position Control Function 5-157
Frequency Addition Function
5-71
Forced Terminal Block Function
5-85
Torque Control
Integrated Power Monitor
5-155
5-7
Reserved.
AHD: Analog command held
−
Analog Command Hold Function
−
5-39
5
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)