The heat pump and collector hose in general
The heat pump and collector hose in general
Transporting the heat pump
The heat pump should always be transported and stored in an upright position, never horizontally. Otherwise the suspension fi ttings inside the compressor can be damaged. If the heat pump must be tilted during entry to the installation site, this should be done for as short a time as possible. The outer cover panels should be removed to avoid damage, if the heat pump is moved without using the supplied pallet.
The heat pump must not be stored at temperatures below -10ºC.
Positioning the heat pump
It is important that the heat pump stands on a fl at surface as it contains sensitive parts. The fl oor must be stable and have a strength to carry at least 500 kg. Adjust the rubber feet so the heat pump does not lean.
The temperature surrounding the heat pump should be between 0ºC and 35ºC.
The installer should take sound insulation into consideration when positioning the heat pump.
Maximum working temperatures
The heat pump can work at a maximum return water temperature of approximately 57ºC. If the temperature rises above this value the heat pump will stop for safety reasons.
The electric heater will stop if the temperature rises above 55ºC. The maximum outgoing temperature to the heating system is around 65°C.
Minimum working temperatures
The heat pump supplied is preset to a minimum temperature of collector fl uid -10°C inlet and -10°C outlet. The heat pump can operate at inlet temperatures down to -5°C, lower inlet temperatures are not recommended.
The preset values can be changed during commissioning.
Fit the fi lters
The task of the fi lters is to fi lter out dirt before it can enter the heat pump.
Fit the fi lter for the collector circuit on the incoming pipe from the collector.
Fit the fi lter for the primary circuit on the incoming pipe from the heating system.
Both fi lters should be fi tted as close to the heat pump as possible and placed horizontally. Make sure that the direction of fl ow is correct.
9
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 3 BUILDING REGULATIONS
- 5 For the Installer
- 6 Important information to the installer
- 6 Technical support
- 6 Checklist
- 7 What the deliver y includes
- 8 Dimensions and plumbing connections
- 9 The heat pump and collector hose in general
- 9 Transporting the heat pump
- 9 Positioning the heat pump
- 9 Maximum working temperatures
- 9 Minimum working temperatures
- 9 Fit the fi lters
- 10 Collector hose
- 12 Installing the expansion vessel
- 13 Compact collector
- 14 Connecting the heat pump to the heating system
- 14 Fitting the unvented kit
- 17 Use in hard water areas
- 17 Connecting to the heating system without a bypass
- 18 Connect heat pump Combi model to the heating system
- 19 Individual temperature control in each room and increasing volume of internal water
- 20 Filling the heating system
- 20 Filling the collector circuit
- 23 Connecting the heat pump to the power supply
- 23 Installation of sensors
- 24 External connections to the heat pump
- 25 Connecting the general alarm, external input and softstart
- 26 Installer and ser vice menu (I/S)
- 26 How to use the control panel
- 27 Commissioning the heat pump
- 27 Manual test run of the heat pump
- 27 Start the heat pump
- 28 Menu displays which may need adjustment or checking
- 31 Drying program for fl oor screed
- 32 Start the heat pump with only additional heat
- 32 Important points to check after start up
- 33 Maintenance
- 33 Unscrew the front cover
- 33 Sight glass
- 34 Filters
- 34 Protective anode
- 35 Expansion vessel
- 36 What to do if a fault occurs
- 36 Menu display dimmed
- 37 Fuses and reset buttons on the heat pump
- 37 All alarms
- 46 Technical information
- 45 of heat pump
- 46 controls
- 47 language menu
- 49 alt. for P
- 47 heating
- 48 max temp
- 49 cooling
- 47 temperature