NOTES FOR SAFE OPERATION
Read this instruction manual thoroughly before installation, operation, maintenance or inspection of the braking unit and the braking resistor unit. In this manual, NOTES FOR SAFE OPERATION are classified as “WARNING” or
“CAUTION.”
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury to personnel.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury to personnel and damage to equipment.
It may also be used to alert against unsafe practices.
Even items described in
CAUTION
may result in a vital accident in some situations. In either case, follow these important notes.
NOTE
: These are steps to be taken to insure proper operation.
5
WIRING
WARNING
S
Only commence wiring after verifying that the power supply is turned OFF.
Failure to observe this warning can result in an electrical shock or a fire.
(Ref. page)
27
S
High voltage exists at all terminals of braking unit and braking resistor unit.
Failure to observe this warning can result in an electrical shock.
S
Wiring should be performed only by qualified personnel.
Failure to observe this warning can result in an electrical shock or a fire.
S
When wiring the emergency stop circuit, check the wiring thoroughly before operation.
Failure to observe this warning can result in personal injury.
27
27
27
S
Make sure to ground the ground terminal .
(Ground resistance
200V class: 100Ω or less, 400V class: 10Ω or less)
Failure to observe this warning can result in an electrical shock.
27
S
Short Circuit Current Rating (SCCR)
Install adequate branch short circuit protection according to applicable codes.
Failure to comply could result in damage to the drive.
The device is suitable for circuits capable of delivering 31,000 RMS symmetrical Amperes, 240 Vac maximum (200V Class), 480 Vac maximum (400V
Class) and 575Vac (600V Class) or the SCCR rating of the drive it is connected to, which ever is greater.
7
CAUTION
S
Verify that the rated voltage of the braking unit and the braking resistor unit coincides with the AC power supply voltage.
Failure to observe this caution can result in personal injury or a fire.
(Ref. page)
27
S
Do not perform a withstand voltage test of the braking unit and braking resistor unit.
It may cause semi−conductor elements to be damaged.
S
Connect braking resistors, braking resistor units, and braking units as shown in the I/O wiring examples. Use properly rated wire in accordance with table 2 on page 31.
Otherwise, a fire can occur.
27
27
27
S
Tighten terminal screws to the specified tightening torque.
Failure to observe this caution can result in a fire.
S
Be sure to connect braking resistors or braking resistor units to the braking units.
If neither braking resistor nor braking resistor unit is connected to a braking unit, the fault contact may instantaneously turn ON when the power is turned ON, resulting in malfunction of the inverter.
27
8
OPERATION
WARNING
S
Only turn ON the input power supply after replacing the front cover. Do not remove the cover while current is flowing.
Failure to observe this warning can result in an electrical shock.
(Ref. page)
41
CAUTION
S
Never touch the heatsink or discharging resistor since the temperature is very high.
Failure to observe this caution can result in harmful burns to the body.
(Ref. page)
41
41
S
Do not check signals during operation.
The machine or the inverter may be damaged.
S
Alltheconstantsofthethebrakingunit andthe brakingresistor unit have been preset at the factory. Do not change the settings unnecessarily.
41
9
CAUTION
S
The control PC board employs CMOS ICs. Do not touch the
CMOS elements.
They are easily damaged by static electricity.
(Ref. page)
46
S
Do not connect or disconnect wires or connectors while power is applied to the circuit.
Failure to observe this caution can result in personal injury.
46
OTHERS
WARNING
S
Never modify the product.
Failure to observe this warning can result in an electrical shock or personal injury and will invalidate the guarantee.
11
WARNING INDICATION
A warning label is displayed on the front cover of the braking unit, as shown below.
Follow these instructions when handling the braking unit and the braking resistor unit .
Example of Braking Unit Model CDBR−4045B
12
13
2. INSTALLATION
2.1 LOCATION
If the units are temporarily stored or machine stops for an extended length of time, the following precautions should be taken. Store the units at pollution level 2 or less
(UL standard) and under the following conditions.
S
Free from rainfall and drops of water.
S
Clean and dry.
S
Free from corrosive gases and liquids.
S
Free from dirt and dust.
S
Ambient temperature: 14 to 104_F, −10 to 40_C.
S
Humidity: 90% RH or less (no condensation)
S
Free from vibration.
2.2 INSTALLATION
For full use of the braking resistor unit or braking unit functions, install the units at pollution level 2 or less (UL standard) and in a location to satisfy the following conditions:
Figs. 1 to 8 show the external dimensions and the spaces from the periphery.
S
Provide the spaces shown in Figs. 1 to 8 between the units and the periphery.
S
Since the braking resistor unit generates heat, provide sufficient spaces from devices which are weak against heat.
S
Install the units at such locations that all requirements described in Par.
2.1 “LOCATION” are satisfied.
16
2. INSTALLATION
S
Install the units in the directions shown in Figs. 1 to 8. There will be no problem if they are installed vertically.
4−M4 MTG HOLE
2.83 (72) 2.73 (66.5)
1.18 (30)
OR MORE
1.5 (38)
1.5 (38)
5.04 (128)
5.51 (140)
3−LEAD WIRE OUTLET
[0.87 (20) DIA RUBBER BUSH]
1.18 (30)
OR MORE
Fig. 1
4.51 (114.5)
5.45 (138.5)
Braking Unit Dimensions in inches (mm) CDBR−2015B, −2022B, −4030B,
−4045B
17
3.94 (100)
4−M6
MTG HOLE
MAIN CIRCUIT
TERMINAL M4
2.30
(58.5)
3−LEAD WIRE
OUTLET
1.10 (28) DIA
RUBBER BUSH
1.18 (30)
OR MORE
1.97 (50)
3.94 (100)
5.51 (140)
1.18 (30)
OR MORE
6.57 (167)
Fig. 2 Braking Unit Dimensions in inches (mm) CDBR−5037B
18
2. INSTALLATION
5.51 (140)
4−M6
MTG HOLE
Fig. 3
MAIN CIRCUIT
TERMINAL M5
3.86 (98)
WIRE OUTLET 1.10 (28)
DIA RUBBER BUSH
2−LEAD WIRE OUTLET
1.38 (35) DIA RUBBER
BUSH
3.94 (100)
2.32 1.97 (50)
(59)
5.51 (140)
7.09 (180)
1.18 (30)
OR MORE
1.18 (30)
OR MORE
4.37 (111)
6.14 (156)
7.87 (200)
Braking Unit Dimensions in inches (mm) CDBR−2045B
19
5.51 (140)
4−M6
MTG HOLE
MAIN CIRCUIT
TERMINAL M6
4.09
(104)
3.94 (100)
2.32 1.97 (50)
(59)
5.51 (140)
7.09 (180)
1.18 (30)
OR MORE
1.18 (30)
OR MORE
4.37 (111)
6.14 (156)
7.87 (200)
Fig. 4 Braking Unit Dimensions in inches (mm) CDBR−2110B
WIRE OUTLET 1.10 (28)
DIA RUBBER BUSH
2−LEAD WIRE OUTLET
1.38 (35) DIA RUBBER
BUSH
20
2. INSTALLATION
7.09 (180)
4−M6
MTG HOLE
MAIN CIRCUIT
TERMINAL M5
3.86 (98)
WIRE OUTLET 1.10 (28)
DIA RUBBER BUSH
2−LEAD WIRE OUTLET
1.38 (35) DIA RUBBER
BUSH
5.45 (138.5)
2.70
1.97 (50)
(68.5) 7.09 (180)
8.66 (220)
1.18 (30)
OR MORE
1.18 (30)
OR MORE
4.37 (111)
6.14 (156)
7.87 (200)
Fig. 5 Braking Unit Dimensions in inches (mm) CDBR−4090B, −5110B
21
8.27 (210)
4−M6
MTG HOLE
Fig. 6
MAIN CIRCUIT
TERMINAL M6
4.09
(104)
WIRE OUTLET 1.10 (28)
DIA RUBBER BUSH
2−LEAD WIRE OUTLET
1.38 (35) DIA RUBBER
BUSH
6.16 (156.5)
4.67 (118.5)
1.97 (50)
8.27 (210)
9.84 (250)
1.18 (30)
OR MORE
1.18 (30)
OR MORE
4.37 (111)
6.14 (156)
7.87 (200)
Braking Unit Dimensions in inches (mm) CDBR−4220B, −5300B
22
2. INSTALLATION b a b
Braking Resistor
Unit Model
(LKEB−j)
20P7
21P5
22P2
23P7
25P5
27P5
40P7
41P5
42P2
43P7
45P5
47P5
Fig. 7
A
Dimensions in inches (mm)
B C D
4.13 (105) 10.83 (275) 1.97 (50) 10.24 (260)
5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335)
5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335)
5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335)
9.84 (250) 13.78 (350) 7.87 (200) 13.19 (335)
9.84 (250) 13.78 (350) 7.87 (200) 13.19 (335)
4.13 (105) 10.83 (275) 1.97 (50) 10.24 (260)
5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335)
5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335)
5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335)
9.84 (250) 13.78 (350) 7.87 (200) 13.19 (335)
9.84 (250) 13.78 (350) 7.87 (200) 13.19 (335)
E
M5
M5
M5
M5
M6
M6
M5
M5
M5
M5
M6
M6
Braking Resistor Unit Dimensions in inches (mm) [for 0.5 to 10HP (0.4 to
7.5kW)]
23
Braking Resistor
Unit Model
(LKEB−j)
2011
2015
2018
2022
4011
4015
4018
4022
4030
4037
4045
Dimensions in inches (mm)
A B C D E
10.48 (266) 21.38 (543) 9.69 (246) 13.39 (340) M8
14.02 (356) 21.38 (543) 13.23 (336) 13.39 (340) M8
17.56 (446) 21.38 (543) 16.77 (426) 13.39 (340) M8
17.56 (446) 21.38 (543) 16.77 (426) 13.39 (340) M8
13.78 (350) 16.22 (412) 12.99 (330) 12.80 (325) M6
13.78 (350) 16.22 (412) 12.99 (330) 12.80 (325) M6
17.56 (446) 21.38 (543) 16.77 (426) 13.39 (340) M8
17.56 (446) 21.38 (543) 16.77 (426) 13.39 (340) M8
14.02 (356) 37.64 (956) 13.23 (336) 29.13 (740) M8
17.56 (446) 37.64 (956) 16.77 (426) 29.13 (740) M8
17.56 (446) 37.64 (956) 16.77 (426) 29.13 (740) M8
Fig. 8 Braking Resistor Unit Dimensions in inches (mm) [for 15 to 60HP (11 to
45kW)]
24
2. INSTALLATION
2.3 REPLACEMENT OF CONVENTIONAL BRAKING
UNITS WITH NEW UNITS
To replace conventional braking units (models CDBR−2015, −2022, −4030, −4045) with new units (CDBR−2015B, −2022B, −4030B, −4045B), an exclusive−use attachment is required. Contact your YASKAWA representative.
0.79
(20)
ATTACHMENT
0.28(7)
4−M6 MTG HOLE
3.94 (100)
0.79
(20)
3.94 (100)
5.51 (140)
0.28(7)
0.39 (10
5.45 (138.5)
Code No.: DACT32732−AD
0.39 (10)
Fig. 9 Mounting Dimensions of Attachment in inches (mm)
25
The main circuit terminal symbols are different between conventional models and new models. Refer to the following table.
Table 1 Main Circuit Terminal Symbols
Conventional Models New Models
P
0
B
N
P
©
¨
¨
©
0
0
26
3.2 SECTION NAMES
Figs. 10, 11 and 12 show appearance and each section name of braking unit and braking resistor unit respectively.
Thermal overload relay protects the braking resistor unit for models LKEB−20P7 to −27P5, and thermal protector protects the braking resistor unit for models
LKEB−2011 to −2022 and −4018 to −4045.
WARNING
BRAKING UNIT
MODEL:CDBR−2015B
200V CLASS FOR 15kW
May cause injury or electric shock.
Please follow the instructions in the manual before installation or operation.
Disconnect all power before opening front cover of unit. Wait 3 minutes until DC Bus capacitors discharge.
Use proper grounding techniques.
Power Supply Selection
Connector
Master/Slave
Selection Connector
Calibration Resistor
(Adjusted Prior to
Shipment)
Operation Indicator
(Lights when Discharging.)
Charge Indicator
(Charge Lamp)
© ¨ ¨
0
©
0
1 2 5 6
Control Circuit
Terminals 1 to 6
Lead Wire Outlet
(3 Places: Rubber Bush)
Control Circuit Terminals
© ¨ ¨
0
©
0
Fig. 10 Braking Resistor Unit Model CDBR−2015B (Terminal Cover and
Indicationg Cover Removed)
28
3. WIRING
Thermal Overload Relay
(Automatically Reset)
Lead Wire Outlet
(Rubber Bush)
Fig. 11
Control Circuit Terminals
B, P, 1, 2
Braking Resistor Unit Model LKEB−20P7 (Front Cover Removed)
29
Resistor
Thermal
Overload
Protector
Lead Wire Outlet
(Rubber Bush)
Control Circuit Terminals
B, P, 1, 2
Fig. 12 Braking Resistor Unit Model LKEB−2022 (Front Cover Removed)
30
3. WIRING
3.3 CIRCUITS AND WIRING SPECIFICATIONS
Table 2
Name
Circuits and Wiring Specifications
Circuit
Terminals
Wire
Size
AWG
(mm
2
)
Max.
Torque lb⋅in
(N⋅m)
(
Braking Unit
( (Models CDBR
2015B 2022B
−4030B, −4045B,
−5037B)
Braking Unit
(Model CDBR
−2045B, −4090B,
−5110B)
Braking Unit
(Model
CDBR−2110B,
−4220B, −5300B)
Braking Resistor
Unit
(Model LKEB− j
)
Main
Control
Main
Control
Main
Control
Main
¨
©
¨
©
1 2 3
4 5 6
B
¨
©
¨
©
P
0
0
1 2 3
4 5 6
¨ ¨
0
© ©
0
1 2 3
4 5 6
0
0
12−10
(3.5−5.5)
18−14
(0.75−2)
10−8
(5.5−8) 600V
18−14
(0.75−2)
(High
Voltage)
*3
4 (22)
8−6
(8−14)
*1
18−14
(0.75−2) vinyl sheathed wire or equivalent
12−10
(3.5−5.5)
18−14
(0.75−2)
M5
M4
M6
M4
M4
(M5)
*2
(1.50)
21.7
(2.45)
15.6
(1.76)
43.4
(4.90)
15.6
(1.76)
15.6 (1.76)
(21.7(2.45))
Control
1 2 M4 15.6 (1.76)
*1 For wire size of 8−6 (8−14), use UL1283 heat−resistant vinyl−insulated wire or equivalent.
*2 M4 for Models LKEB−20P7 to −27P5 or −40P7 to −4015.
M5 for Models LKEB−2011 to −2022 or −4018 to −4045.
*3 Models−5037B, −5100B, and −5300B can reach an operating voltage of 1040 VDC.
Please select wire which is suitable for the operating voltage.
31
3.4 WIRING PRECAUTIONS
(1) Wiring Leading−in Method
Lead in the wire through the knockout hole on the unit bottom. Since the knockout hole is provided with a rubber bush, cut the rubber bush central crosswise with a blade and lead the wire through.
(2) Separation from Signal Lines
Since strong noise component is superimposed on the braking resistor unit and braking unit wiring, separate the units from signal lines which are weak against noise.
(3) Wiring Distance
Wiring distance between the braking resistor unit and braking unit or braking unit and inverter must be provided as shown in Fig. 13. Make sure to bundle the wires between the units.
Braking Resistor
Unit
Braking Unit
Inverter
32.8ft
(10m) or less
Fig. 13 Wiring Distance
16.4ft
(5m) or less
32
3. WIRING
(4) Grounding Method
S
Mount the braking resistor unit on a grounded metallic plate. When it cannot be mounted on a grounded metallic plate, pull out the lead wire from the mounting screw section to ground.
S
Braking unit grounding terminal must be provided with the ground resistance of 100Ω or less in 200V class ,or 10Ω or less in 400V class.
S
Use the sizes specified in “INTERNAL CONNECTION SPECIFI-
CATIONS” for grounding cables.
3.5 INTERCONNECTION
Figs. 14 to 20 show the interconnecting diagrams of the braking unit or braking resistor unit and VS−616G5.
Refer to Par. 3.3, “Wiring Precautions” for proper wiring in actual wiring design and work.
Be sure to connect braking resistors or braking resistor units to the braking units.
Connect only braking resistors or Braking Resistor Units (LKEB−XXXX) to Braking Units.
NOTE
If using another braking resistor instead of YASKAWA braking resistor unit, be sure to protect by thermal overload relay.
33
or 380
34
Fault Contact
3. WIRING
Level Detection
35
Fault Contact
Level Detection
36
Fault Contact
3. WIRING
Level Detection
37
Voltage Selection 460/440/415/ 400/380V
Fault Contact
Level Detection
38
) Voltage Selection
460/440/415/ 400/380V
Fault Contact
3. WIRING
Level Detection
39
Fault Contact
Level Detection
40
Voltage Selection 460/440/415/ 400/380V
Fault Contact
4. OPERATION
4. OPERATION
4.1 ADJUSTMENT
The braking resistor unit and braking unit do not have to be adjusted.
Especially, do not readjust the braking unit except in the case described in Par. 4.2,
“Power Supply Voltage Selection Connector Setting.”
4.2 POWER SUPPLY VOLTAGE SELECTION CON-
NECTOR SETTING
It may be necessary to select power supply voltage selection connector for braking unit according to main circuit power supply type. Table 3 shows the relationship between the power supply voltage selection connector and braking start voltage.
The following is the setting prior to shipment:
S
200V class : 220V
S
400V class : 440V
S
575V class : 575V
For removing the terminal cover and the indicating cover, refer to Par. 3.1.
41
WARNING
BRAKING UNIT MODEL:CDBR( 2015B
200V CLASS FOR 15kW
May cause injury or electric shock.
Please follow the instructions in the manual before installation or operation.
Disconnect all power before opening front cover of unit. Wait 3 minutes until DC Bus capacitors discharge.
Use proper grounding techniques.
© ¨ ¨
0
©
0
1 2
5 6
200V class
200V
20
8V
2
20V
2
30V
400V class
380V
400V
4 15V
4
40V
4
60V
Fig. 21 Braking Unit Power Supply Voltage Selection
(Models CDBR−2015B, −2022B, −4030B, −4045B, Terminal Cover and
Indicating Cover Removed)
42
4. OPERATION
200V class
200V
20 8V
2 20V
2 30V
575V class
500V
400V class
380V
400V
4
15V
4 40V
4 60V
575V
Fig. 22 Braking Unit Power Supply Voltage Selection
(Models CDBR−2045B, −2110B, −4090B, −5037B, −5110B, −5300B,
Indicating Cover Removed)
Table 3
200V
Class*
Power
Supply
Voltage
230V
220V
208V
200V
−
Power Supply Voltage Selection Connector and Braking Start Voltage
Braking Start
Voltage
(PN Bus−bar
Voltage)
380V (TYP)
365V (TYP)
345V (TYP)
330V (TYP)
−
400V
Class*
Power
Supply
Voltage
460V
440V
415V
400V
380V
*Allowable voltage fluctuation is ±10%
Braking Start
Voltage
(PN Bus−bar
Voltage)
760V (TYP)
730V (TYP)
690V (TYP)
660V (TYP)
630V (TYP)
575V
Class*
Power
Supply
Voltage
575V
−
−
500V
−
Braking Start
Voltage
(PN Bus−bar
Voltage)
950V (TYP)
−
−
825V (TYP)
−
43
4.3 MASTER/SLAVE SELECTION CONNECTOR SETTING
Selection Connector Setting MASTER side is selected prior to shipment. Use the units without changing the setting.
SLAVE side is selected when more than one braking unit is combined to use and braking start levels must coincide. Refer to Par. 4.4, “Parallel Connection of Braking Unit” for details.
4.4 PARALLEL CONNECTION OF BRAKING UNIT
For using more than one parallel−connected braking unit, connect and select the connectors as follows. (See Fig. 23.)
S
Braking units have a MASTER/SLAVE selection connector. (See Fig.
10.) Select MASTER side only for braking unit 1 and select SLAVE side for braking units 2 and 3.
S
Connect thermal protector on the braking resistor unit and thermoswitch on the braking unit in parallel. Refer to Figs. 15 and 18 for proper wiring.
S
Use properly rated wire in accordance with table 2 on page 31.
S
Use twisted−pair wires of 1mm or less for connection between 5, 6 and
1, 2 of the braking units.
S
Parallel connection of braking unit is possible up to a maximum of 10 units.
44
4. OPERATION
¨
3
Inverter
Unit
©
1
2
©
¨
Braking Resistor
Overheat Contact
(Thermal Relay Trip Contact)
1
P
¨
0
2
Braking
B
Resistor
Unit
©
0
© ¨
MASTER
Braking Resistor
Overheat Contact
(Thermal Relay Trip Contact)
1
P
¨
0
MASTER
2
B
Braking
Resistor
Unit
©
0
©
¨
Braking Resistor
Overheat Contact
(Thermal Relay Trip Contact)
1 2
B
Braking
Resistor
Unit
P
¨
0
MASTER
©
0
Level Detection
SLAVE
+15
5 1
6
P
2
SLAVE
Braking Unit 2
5 1
6
P
2
SLAVE
Braking Unit 3
5
6
Braking Unit 1
3 4
Cooling Fin
Overheat Contact
(Thermoswitch Contact)
3 4
Cooling Fin
Overheat Contact
(Thermoswitch Contact)
3 4
Cooling Fin
Overheat Contact
(Thermoswitch Contact)
Fig. 23 Example of Parallel Connection of Three Braking Units
4.5 OPERATION
Check that required deceleration characteristics can be obtained. While the braking unit is operating, BRAKE lamp lights for easy check of operation.
NOTE
High voltage is applied to the braking unit. At normal operation, do not operate the unit without cover.
4 5
5. TROUBLESHOOTING
Only authorized personnel should be permitted to perform maintenance and inspections or replace parts.
No.
Fault Status Cause Corrective Action
S
Without braking unit
1
3
Braking resistor unit overload relay (or thermal p
) i h decelerating.
4
Braking unit trips by heat sink overheat.
Inverter built−in main circuit discharging transistor short circuited
S
With braking unit
Braking unit main circuit discharging transistor short circuited
Improper braking unit power supply voltage selection connector setting
(Power supply voltage > power supply voltage selection position)
Inverter trips at overvoltage (OV).
Insufficient braking resistor unit capacity
Improper wiring
Braking unit fault
Braking resistor unit overload relay (or thermal protector) sometimes trips.
Insufficient braking resistor unit capacity
Replace the inverter.
Replace the unit.
Set it again.
Examine the braking conditions again.
Check and repair.
Replace the unit.
Examine the braking conditions again.
Excessive start/stop switching frequency
Examine the operating conditions again.
Excessive load inertia
Improper combination of braking unit and braking resistor unit
Reset.
Ambient temperature 104_F (40_C) Reduce it.
5
The fault contact of a braking unit instantaneously turned ON when the power was turned ON.
Neither a braking resistor nor a braking resistor unit is connected to the braking unit.
Connect a braking resistor or braking resistor unit to the braking unit.
46
6. SPECIFICATIONS
6. SPECIFICATIONS
6.1 BRAKING UNIT AND BRAKING RESISTOR UNIT
APPLICATION LIST
The applicable braking unit and braking resistor unit models differ depending on the inverter model. Refer to the catalog of the relevant inverter.
Example: 200−V Class Inverter Model CIMR−G5 j
Inverter
Max Applicable
Motor Capacity
HP(kW)
Braking Unit
Model
(CDBR
− j)
Unit
Q’ty
Braking Resistor Unit
Model
(LKEB
− j)
Resistor Spec.
(per unit)
Unit
Q’ty
Approx.
Braking
Torque
(10%ED)
0.5 (0.4)
1 (0.75)
2 (1.5)
3 (2.2)
5 (3.7)
7.5 (5.5)
10 (7.5)
15 (11)
20 (15)
25 (18.5)
30 (22)
40 (30)
50 (37)
60 (45)
75 (55)
100 (75)
120 (90)
150 (110)
−
−
−
−
−
−
−
2015B
2015B
2022B
2022B
2015B
2015B
2022B
2022B
2110B
2110B
2110B
−
−
−
−
−
−
−
1
1
1
1
2
2
2
2
1
1
1
20P7
20P7
21P5
22P2
23P7
25P5
27P5
2011
2015
2018
2022
2015
2015
2022
2022
2022
2022
2022
70W 200Ω
70W 200Ω
260W 100Ω
260W 70Ω
390W 40Ω
520W 30Ω
780W 20Ω
2400W 13.6Ω
3000W 10Ω
4800W 8Ω
4800W 6.8Ω
3000W 10Ω
3000W 10Ω
4800W 6.8Ω
4800W 6.8Ω
4800W 6.8Ω
4800W 6.8Ω
4800W 6.8Ω
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
3
4
5
Note:
The above table lists the applicable braking unit and braking resistor unit models for the 200−V class inverter model CIMR−G5j. For other inverter models, refer to the catalog of the relevant inverter.
120
100
110
120
100
125
125
125
125
100
%
220
125
125
120
125
115
125
125
47
Example: 400−V Class Inverter Model CIMR−G5 j
Inverter
Max Applicable
Motor Capacity
HP(kW)
Braking Unit
Model
(CDBR
− j)
Unit
Q’ty
Braking Resistor Unit
Model
(LKEB
− j)
Resistor Spec.
(per unit)
Unit
Q’ty
Approx.
Braking
Torque
(10%ED)
%
0.5 (0.4)
1 (0.75)
2 (1.5)
3 (2.2)
5 (3.7)
7.5 (5.5)
10 (7.5)
15 (11)
20 (15)
25 (18.5)
30 (22)
40 (30)
50 (37)
60 (45)
75 (55)
100 (75)
150 (110)
200 (160)
300 (220)
400 (300)
800 (600)
−
−
−
−
−
−
−
−
−
4030B
4030B
4030B
4045B
4045B
4030B
4045B
4030B
4220B
4220B
4220B
4220B
−
−
−
−
−
−
−
−
−
1
1
1
1
1
2
2
3
1
1
2
4
40P7
40P7
41P5
42P2
43P7
45P5
47P5
4011
4015
4018
4022
4030
4037
4045
4030
4045
4030
4045
4037
4045
4045
70W 750Ω
70W 750Ω
260W 400Ω
260W 250Ω
390W 150
Ω
1
520W 100Ω
780W 75Ω
1040W 50Ω
1560W 40Ω
1
1
1
1
4800W 32
Ω
4800W 27.2Ω
1
1
6000W 20Ω
9600W 16Ω
9600W 13.6Ω
6000W 20Ω
9600W 13.6Ω
6000W 20Ω
9600W 13.6Ω
9600W 16Ω
1
1
1
2
2
3
4
5
9600W 13.6Ω 6
9600W 13.6Ω 12
1
1
1
1
125
125
125
125
135
135
130
135
125
125
135
230
130
125
135
145
100
140
110
110
110
Note:
The above table lists the applicable braking unit and braking resistor unit models for the 400−V class inverter model CIMR−G5j. For other inverter models, refer to the catalog of the relevant inverter.
48
6. SPECIFICATIONS
6.2 BRAKING UNIT FOR 575V CLASS APPLICATION LIST
Example: 575−V Class Inverter Model CIMR−G5 j
Inverter
Max Applicable
Motor Capacity
HP(kW)
Braking Unit
Model
(CDBR− j)
Unit Q’ty
Braking Resistor Unit
Resistor Spec.
Approx.
Braking
Torque
(10%ED)
5 (3.7)
7.5 (5.5)
10 (7.5)
15 (11)
20 (15)
25 (18.5)
30 (22)
40 (30)
50 (37)
60 (45)
75 (55)
100 (75)
120 (90)
150 (110)
200 (160)
−
−
−
−
−
−
5037B
5037B
5037B
5037B
5037B
5110B
5110B
5110B
5300B
−
−
−
−
−
−
1
1
1
2
2
1
1
1
1
560W 150Ω
560W 150Ω
750W 100Ω
1100W 75Ω
1500W 50Ω
2300W 40Ω
2800W 38Ω
3900W 33Ω
4900W 27Ω
5900W 22Ω
7200W 18Ω
9800W 13.6Ω
12000W 11Ω
15000W 9Ω
21000W 6.8Ω
%
180
125
140
125
140
140
125
110
110
110
110
105
110
110
100
Note:
The above table lists the applicable braking unit and braking resistor unit models for the 575−V class inverter model CIMR−G5j. For other inverter models, refer to the catalog of the relevant inverter.
49
Conventional
Model
VS−616HII/H3
VS−616GII/G3
VS−676
VS−616HII/H3
VS−616GII/G3
VS−676
VS−616HII/H3
VS−616GII/G3
VS−676
VS−616HII/H3
VS−616GII/G3
VS−676
6.3 LIST OF APPLICABLE/NOT APPLICABLE COMBINA-
TIONS WITH CONVENTIONAL MODELS (VS−616HII/
H3, VS−616GII/G3, VS−676)
Braking
Unit
−
Model
CDBR−15H etc.
Models
CDBR
−2015,
−2015B etc.
Models
CDBR
−2015,
−2015B etc.
Braking Resistor Unit
Applicable/
Not Applicable
Model
LKEB−20P7 etc.
Model
LKEB−2015 etc.
Model
LKEB−4.8K
etc.
Model
LKEB−2015 etc.
Applicable
Applicable
Not applicable
Applicable
Remarks
See connection examples of Fig 14.
Use sequencer to break power supply side on thermal protector of the braking resistor unit side.
No thermal protective function of braking resistor unit.
See connection examples of Figs. 15 to 18.
50
6. SPECIFICATIONS
6.4 BRAKING UNIT SPECIFICATIONS
Braking Unit Model
CDBR−
Applicable Motor Output
HP (kW)
Output characteristics
Max. Discharge
Current(A)
(peak value) *
Rated Discharge
Current (A)
Braking Start
Voltage
Max. Hysteresis
Error
Power
Supply
Protective
Functions
VDC
Fin Overheat
Power Charge
Indication
Envionmental
Conditions
Location
Altitude
Ambient
Temperature
Storage
Transportation
Temperature
Humidity
Vibration
Protective Configuration
Heat Loss (W)
2015
B
20
(15)
200V to 300V
2022
B
30
2045
B
60
(22) (45)
40 60 100
2110
B
150
(110)
250
4030
B
40
(30)
380V to 460V
4045
B
60
4090
B
120
(45) (90)
40 60 100
4220
B
300
(220)
250
57
500V to 575V
5037
B
5110
B
150
5300
B
400
(37)
40
(110)
100
(300)
250
15 20 30
330/345/365/380V ±3V
80 15 18 30 80
630/660/690/730/760V ±6V
243 (1.35×200×0.9) to 400V peak
Approx. 8V Approx. 16V
460 (1.35×380×0.9) to 800V peak
Thermostat
Charge lamp stays ON until bus voltage drops below 50V.
Indoor (protected from corrosive gases and dust)
1000m max.
+14 to 104_F (−10 to +40_C) (not frozen)
15 30 80
825V/ 950V ±8V
Approx.
20V
607 (1.35×500×0.9) to 1000V
32 38
−4 to 140_F (−20 to +60_C)
90%RH (non−condensing)
1G at 10 to less than 20Hz, up to 0.2G at 20 to 50 Hz
31 64
Wall−mounted enclosed type
54 59 35 71 22 53 116
* Loading time rate can be used below 10% ED (max. 10 sec.)
51
Model
(LKEB
− j)
42P2
43P7
45P5
47P5
4011
4015
4018
4022
4030
4037
4045
20P7
21P5
22P2
23P7
25P5
27P5
2011
2015
2018
2022
40P7
41P5
6.5 BRAKING RESISTOR UNIT SPECIFICATIONS
200 to
380 to
Specifications
70W 200Ω
260W 100Ω
260W 70Ω
390W 40Ω
520W 30Ω
780W 20Ω
2400W 13.6Ω
3000W 10Ω
4800W 8Ω
4800W 6.8Ω
70W 750Ω
260W 400Ω
260W 250Ω
390W 150Ω
520W 100Ω
780W 75Ω
1040W 50Ω
1560W 40Ω
4800W 32Ω
4800W 27.2Ω
6000W 20Ω
9600W 16Ω
9600W 13.6Ω
Allowable
Average
Dissipated
Power
(W)
600
740
880
1200
1500
1800
89
150
220
300
440
600
740
880
30
60
30
60
89
150
220
300
440
Allowable
Average
Current
(Effective Value)
(A)
3.9
4.8
5.7
7.7
9.7
11.5
0.60
1.0
1.5
2.0
3.0
7.7
9.6
11.4
0.20
0.39
0.39
0.77
1.1
1.9
2.7
3.9
5.7
Allowable
Ambient
Temperature
+14 to 122_F
( 10 to +50_C)
52
6. SPECIFICATIONS
6.6 MODELS AND CODE NOS. OF BRAKING UNIT AND
BRAKING RESISTOR UNIT
(1) Braking Unit
Inverter
Voltage HP (kW)
200 to
230V
380 to
460V
500 to
575V
20 (15) CDBR−2015B 72600−R2150B
30 (22) CDBR−2022B 72600−R2220B
60 (45) CDBR−2045B 72600−R2450B
150 (110) CDBR−2110B 72600−R21100B
40 (30) CDBR−4030B 72600−R4300B
60 (45) CDBR−4045B 72600−R4450B
120 (90) CDBR−4090B 72600−R4900B
300 (220) CDBR−4220B 72600−R42200B
50 (37) CDBR−5037B 72600−R5370B
150 (110) CDBR−5110B 72600−R51100B
400 (300) CDBR−5300B 72600−R53000B
53
(2) Braking Resistor Unit
Inverter
Voltage HP(kW)
1 (0.75)
200 to
230V
2 (1.5)
3 (2.2)
5 (3.7)
7.5 (5.5)
10 (7.5)
15 (11)
20 (15)
25 (18.5)
30 (22)
1 (0.75)
380 to
460V
2 (1.5)
3 (2.2)
5 (3.7)
7.5 (5.5)
10 (7.5)
15 (11)
20 (15)
25 (18.5)
30 (22)
40 (30)
50 (37)
60 (45)
Resistor Spec.
(per unit)
70W 200Ω
260W 100Ω
260W 70Ω
390W 40Ω
520W 30Ω
780W 20Ω
2400W 13.6Ω
3000W 10Ω
4800W 8Ω
4800W 6.8Ω
70W 750Ω
260W 400Ω
260W 250Ω
390W 150Ω
520W 100Ω
780W 75Ω
1040W 50Ω
1560W 40Ω
4800W 32Ω
4800W 27.2Ω
6000W 20Ω
9600W 16Ω
9600W 13.6Ω
LKEB−20P7 72600−K2P70
LKEB−21P5 72600−K2010
LKEB−22P2 72600−K2020
LKEB−23P7 72600−K2030
LKEB−25P5 72600−K2050
LKEB−27P5 72600−K2070
LKEB−2011
LKEB−2015
LKEB−2018
72600−K2110
72600−K2150
72600−K2180
LKEB−2022 72600−K2220
LKEB−40P7 72600−K4P70
LKEB−41P5 72600−K4010
LKEB−42P2 72600−K4020
LKEB−43P7 72600−K4030
LKEB−45P5 72600−K4050
LKEB−47P5 72600−K4070
LKEB−4011
LKEB−4015
LKEB−4018
LKEB−4022
LKEB−4030
LKEB−4037
LKEB−4045
72600−K4110
72600−K4150
72600−K4180
72600−K4220
72600−K4300
72600−K4370
72600−K4450
54
英文 No.10-4(B6) インバータ製品用
YASKAWA AC Drive-Option
BRAKING UNIT,
BRAKING RESISTOR UNIT
INSTRUCTIONS
IRUMA BUSINESS CENTER (SOLUTION CENTER)
480, Kamifujisawa, Iruma, Saitama, 358-8555, Japan
Phone: 81-4-2962-5696 Fax: 81-4-2962-6138
YASKAWA ELECTRIC CORPORATION
New Pier Takeshiba South Tower, 1-16-1, Kaigan, Minatoku, Tokyo, 105-6891, Japan
Phone: 81-3-5402-4511 Fax: 81-3-5402-4580 http://www.yaskawa.co.jp
YASKAWA ELECTRIC AMERICA, INC.
2121 Norman Drive South, Waukegan, IL 60085, U.S.A.
Phone: (800) YASKAWA (800-927-5292) or 1-847-887-7000 Fax: 1-847-887-7310 http://www.yaskawa.com
YASKAWA ELÉTRICO DO BRASIL COMÉRCIO LTDA.
Avenda Fagundes Filho, 620 Bairro Saude, São Paulo, SP04304-000, Brasil
Phone: 55-11-3585-1100 Fax: 55-11-5581-8795 http://www.yaskawa.com.br
YASKAWA ELECTRIC EUROPE GmbH
Hauptstraβe 185, 65760 Eschborn, Germany
Phone: 49-6196-569-300 Fax: 49-6196-569-398
YASKAWA ELECTRIC UK LTD.
1 Hunt Hill Orchardton Woods, Cumbernauld, G68 9LF, United Kingdom
Phone: 44-1236-735000 Fax: 44-1236-458182
YASKAWA ELECTRIC KOREA CORPORATION
7F, Doore Bldg. 24, Yeoido-dong, Youngdungpo-Ku, Seoul, 150-877, Korea
Phone: 82-2-784-7844 Fax: 82-2-784-8495
YASKAWA ELECTRIC (SINGAPORE) PTE. LTD.
151 Lorong Chuan, #04-02A, New Tech Park, 556741, Singapore
Phone: 65-6282-3003 Fax: 65-6289-3003
YASKAWA ELECTRIC (SHANGHAI) CO., LTD.
No. 18 Xizang Zhong Road, Room 1702-1707, Harbour Ring Plaza, Shanghai, 200001, China
Phone: 86-21-5385-2200 Fax: 86-21-5385-3299
YASKAWA ELECTRIC (SHANGHAI) CO., LTD. BEIJING OFFICE
Room 1011A, Tower W3 Oriental Plaza, No. 1 East Chang An Ave.,
Dong Cheng District, Beijing, 100738, China
Phone: 86-10-8518-4086 Fax: 86-10-8518-4082
YASKAWA ELECTRIC TAIWAN CORPORATION
9F, 16, Nanking E. Rd., Sec. 3, Taipei, Taiwan
Phone: 886-2-2502-5003 Fax: 886-2-2505-1280
YASKAWA ELECTRIC CORPORATION
YASKAWA
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture thereof, the export will fall under the relevant regulations as stipulated in the Foreign
Exchange and Foreign Trade Regulations. Therefore, be sure to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
©
2005-2010 YASKAWA ELECTRIC CORPORATION. All rights reserved.
MANUAL NO. TOBP C720600 00C