Envoy-S Metered Multiphase Installation and Operation
Technical Data
Model Numbers
Enphase Envoy-S Metered™
ENV-S-WM-230
Enphase communications gateway with integrated single phase PV and consumption metering. PV production metering and optional consumption monitoring.
Accessories (order separately)
Current transformers (CTs)
CT-100-SPLIT
Enphase Mobile Connect™
CELLMODEM-02
WxHxD: 61 mm x 51 mm x 35 mm.
Lead length 4 m, extendable to 213 m depending on wire size.
Order extra CTs if monitoring multiple phases.
Plug and play industrial grade cellular modem with five-year data plan for systems up to 60 microinverters. (Available where there is adequate mobile service in the installation area.)
Wire / Power Requirements / Specifications
Power
230 VAC or 400Y/230 VAC, 50 Hz. Max 20 A overcurrent protection required.
When hard wired outdoors, the Envoy-S must be installed in an IP54 rated, or better, enclosure. (Use an appropriately rated enclosure if hard-wiring indoors.)
The supply wiring must be 2.5 mm protected by a max 20 A breaker
2
copper rated to 75º C or better, and it must be
Capacity
Number of Enphase
Microinverters polled
Number of Enphase AC
Batteries polled
Up to 600
Up to 39
Mechanical Data
Dimensions (WxHxD)
Weight
213 x 126 x 45 mm
0.5 kg
Environmental Data
Ambient temperature range
Relative humidity
Environmental rating
Altitude use
Cooling
-40° to 46° C when installed in an IP54-rated enclosure
95%
IP30. For installation indoors, or when hard wired outdoors, the Envoy-S must be installed in an IP54 rated, or better, enclosure. Use an appropriately rated enclosure if hard-wiring indoors.
To 2000 meters
Natural convection
Internet Connection Options
Integrated Wi-Fi
Ethernet
Mobile network
802.11b/g/n (2.4 GHz, 5 GHz)
Optional, 802.3, Cat5E (or Cat 6) UTP Ethernet cable (not included). If used, must be fitted with included ferrite bead.
Optional, CELLMODEM-02 (not included)
41
© 2016 Enphase Energy Inc. 141-00035 Rev 01
Envoy-S Metered Multiphase Installation and Operation
Measurement Circuit
Voltage
Current
Measurement circuit
Metering accuracy
Compliance
Compliance
230 VAC or 400Y/230 VAC at the power input terminal block
Up to 200 A via CT inputs
Per IEC/EN/CSA/UL 61010, CAT III
Production and consumption metering; Accuracy +/- 1.0%.
IEC/EN 61010-1:2010,
EN50065-1, EN61000-4-5, EN61000-6-1, EN61000-6-2
42
© 2016 Enphase Energy Inc. 141-00035 Rev 01