7.2.2 Installation of the coaxial pipe

This subchapter is only relevant if the unit is to be operated with a coaxial probe�

The coaxial pipe and the rod must be of the same end length� The coaxial

pipe can be shortened (→ 7.3.2).

► Screw the rod to the unit and tighten it� Recommended tightening torque:

4 Nm�

► Slide the supplied flat seal (A) onto the thread� The elastomer seal may remain on the unit�

► Slide the coaxial pipe (B) onto the rod� Carefully centre it and carefully move the rod through the centring piece (C) (for lengths > 140 cm through both centring pieces) of the coaxial pipe� Do not damage the centring pieces�

► Screw onto the sensor thread and tighten�

A

B

34

32

C

7.3 Shortening of the probe, determination of the probe length

7.3.1 Shortening of the rod

The rod can be shortened to adapt the probe to different tank heights�

Ensure that the probe length is not below the minimum permissible probe length of 150 mm (L min

)� The unit does not support probe lengths below

150 mm� If shorter probes are used, malfunction can occur�

For probe lengths < 250 mm no tank adjustment is possible (→ 7.1.2 Notes on the tank adjustment)�

20

advertisement

Key Features

  • Guided wave radar
  • Tank adjustment
  • 2 Outputs: switching & analog
  • IO-Link function
  • High temp range
  • Adjustable damping

Related manuals

Frequently Answers and Questions

What type of media can be detected?
The LR2050 can detect aqueous media, oils, and oil-based media (for operations with coaxial probe).
What are the minimum installation distances?
For single probe operations, the minimum distances to tank walls, objects, and the tank bottom must be adhered to. Refer to the manual for specific distances.
How does tank adjustment work?
Tank adjustment helps suppress interfering reflections by entering an adjustment distance. This helps improve signal quality in challenging conditions.
How can I configure the analogue output?
You can configure the output function, start and end point for the analogue signal via the unit’s menu.
What are the switching functions available?
The device supports hysteresis and window functions for switching output, both in normally open and normally closed configurations.