8.3 Functional features. Ascon tecnologic E30

Add to My manuals
12 Pages

advertisement

8.3  Functional features. Ascon tecnologic E30 | Manualzz

8.3 Functional features

Temperature Control: ON/OFF mode;

Defrost control: Interval cycles by stopping compressor;

Measurement range: NTC: -50 ÷ +109°C/-58 ÷ +228°F;

Display resolution: 1° or 0.1° (range -99.9 ÷ +99.9°);

Overall accuracy: ±(0.5% fs + 1 digit);

Sampling rate: 130 ms;

Display: 3 Digit Red (Blue optional), height 17.7 mm;

Software class and structure: Class A;

Compliance: Directive 2004/108/CE (EN55022: class B;

EN61000-4-2: 8kV air, 4kV cont.; EN61000-4-3: 10V/m;

EN61000-4-4: 2kV supply and relay outputs, 1kV inputs;

EN61000-4-5: supply 2kV com. mode, 1 kV\diff. mode;

EN61000-4-6: 3V),

Directive 2006/95/CE (EN 60730-1, EN 60730-2-9),

Control 37/2005/CE (EN13485 air, S, A, 2, -50°C +90°C with probe NTC 103AT11).

9. INSTRUMENT ORDERING CODE

MODEL

e30 - = Instrument with mechanical keyboard

a: POWER SUPPLY

D = 230 VAC

C = 115 VAC

b: OUTPUT 1 (OUT 1)

R = Out1 Relay SPST-NO 30A-AC1 (for resistive loads)

c: TERMINALS

V = Screw terminals (standard)

E = Complete removable screw terminals

N = R emovable screw terminals (fixed part only)

d: DISPLAY

I = Red (standard)

C = Blue

e30 a b c d e f g hh ii

e, f, g:

RESERVED CODES; hh, ii: SPECIAL CODES

Ascon Tecnologic - e30 - OPERATING INSTRUCTIONS - PAG. 11

Ascon Tecnologic - e30 - OPERATING INSTRUCTIONS - PAG. 12

advertisement